54 NFPA JOURNAL MARCH/APRIL 2014 Photograph: Shutterstock

SPRINKLERDIFFERENCE

A new study puts a dollar amount on the damage caused by sprinklered fires versus non-sprinklered fires—and in industrial occupancies, those dollar differences can get very large

BY FRED SANFORD

THE

Page 2: Sprinkler NFPA

MARCH/APRIL 2014 NFPA JOURNAL 55

FEATUREINDUSTRIAL + STORAGE OCCUPANCIES

ConfeRenCe SeSSIon

Do Sprinklers Really Make a Difference? Yes, They Do!fred Sanford and Ralph Tiede, Liberty Mutual InsuranceMonday, June 9, 9:30-10:30 a.m. for updated information on education sessions, visit nfpa.org/conference.

It’s been long recognized by property insurers and firefighting professionals that sprinklered properties generally suffer less damage in fires than non-sprin-klered properties. Nowhere is that more true than in

industrial occupancies; fires in these settings tend to be disproportionately more damaging than fires in other types of occupancies. It can be argued that without the automatic sprinkler, industry in the United States would not have developed as rapidly and to the extent that it has. From the early models of sprinklers in the mid-19th century, which kept the wooden floors of New England mills wet by spray-ing water in every direction, to the standard spray sprin-klers of the 1950s, which cooled light steel construction by setting up an umbrella pattern of finer droplets, sprinklers have fulfilled their promise. Nowadays, in response to ever-higher storages and modern exposures, early suppres-sion fast-response (ESFR) sprinklers and other specialized types of suppression are able to drive larger droplets down through the fire plume to control and suppress fires in their incipient stages.

A 14-year study of hundreds of fires by Liberty Mutual Insurance’s Property Risk Engineering Group underscores the importance of fire sprinklers in minimizing property damage, especially in industrial occupancies. The study

Page 3: Sprinkler NFPA

56 NFPA JOURNAL MARCH/APRIL 2014

THE SPRINKLER DIFFERENCE

damage involving sprinklered and non-sprinklered manufacturing occupancies was significant.

These categories bear a somewhat closer look, however. For rubber/plastics, the estimated fire damage in non-sprin-klered occupancies averaged $788,000, compared to $766,000 in sprinklered occupancies. We do not believe this is an aberration, but rather a function of a fire exposure unique to the industry. Plastic molding machines combine the extensive use of high-pressure hydraulic oils with ready ignition sources. When high-pressure combustible hydraulic oil sprays from a leak in the system, it frequently finds an ignition source and results in a fireball type of fire that may be one of the most severe expo-sures encountered by sprinklers in the manufacturing classes—it’s no wonder that large numbers of sprinklers operate almost instantly in these events. Even under the best of circumstances, damage at the ceiling and to adjacent equipment can be severe. Ten to 20 sprinklers can be expected to operate in a typical hydraulic oil fire, whereas fewer than five is typical for industrial fires overall. The average estimated fire damage of a sprinklered hydraulic oil fire in the plastics industry has been about $1.2 million. Exclu-sive of hydraulic oil fires, the average sprinklered fire damage has been about $500,000.

This illustrates a characteristic of industrial fires overall: Whereas dam-age resulting from non-sprinklered fires tends to be merely a function of the value of the property, as well as the combustibility of the construction and occupancy, the damage from sprin-klered fires is driven by the intensity of the hazard in the area of origin. The most damaging sprinklered fire, at slightly greater than $5 million, in-volved combustible oil where a carbon dioxide extinguishing system operated first but did not fully extinguish the fire.

In fact, it was a single large hydrau-lic oil fire in a sprinklered facility that

looks at 946 serious fires that occurred from 2000 to 2013 across 11 different occupancy types, with threshold dol-lar damage estimates of $100,000 and greater. The total estimated damage of those fires was $1.2 billion. Of the fires studied, 322 were industrial fires: 269 in manufacturing occupancies and 53 in warehouse occupancies. While those fires made up just over a third of all the fires included in the study, they were responsible for 49 percent of the total estimated damage.

The findings supported the notion that the “heavier” the occupancy, such as industrial, the proportionately more damaging fires tend to be. In this study, for example, while residential fires ac-counted for 8 percent of the number of serious fires, they accounted for just 4 percent of the total estimated damage of those fires. Even within the manufactur-

ing occupancies themselves, such as a foundry compared to a watch manufac-turer, the heavier end tends to produce the more damaging and costly fires. Overall, in a comparison of estimated fire damage in non-sprinklered versus sprinklered industrial occupancies, fires in non-sprinklered facilities averaged an estimated $1.9 million in damage compared to $638,000 in sprinklered facilities, or a ratio of about 3:1.

While we are unable to share the ac-tual report with the public due to issues of confidentiality, we felt an overview here would lend valuable support in the cause of automatic sprinklers in industrial occupancies. The story told by the study isn’t that non-sprinklered fires get big—we knew that already. The critical point is that when sprinklers are installed in the area of origin and operate as designed, fires almost always

remain small. Now, we have the dollars-and-cents comparisons to prove it.

Running the numbersWe segmented our data in four ways: fires where sprinklers were installed in the area of origin and operated as de-signed; fires where sprinklers were not installed, but clearly could have been and would have operated; fires where sprinklers were not, and probably would not have been, a factor; and fires where sprinklers were impaired or oth-erwise adversely affected by physical conditions, as in instances where fire gained headway in a non-sprinklered concealed space or where water sup-plies were clearly deficient.

We also compiled comparative data for 11 different categories of manufac-turing operations: heavy metal classes, food, rubber/plastics, paper/printing,

textile/apparel, stone/glass, wood/furniture, chemical/petroleum, buildings only, light metal classes, and ag-ricultural. Again, fires at the heavier end of

the metal classes were disproportionate-ly more damaging on average; the heavy metal classes totaled 43 percent of the 269 manufacturing fires, but accounted for 60 percent of the $502 million of estimated damages caused by those fires.

Again, although not universal, the tendency was for a greater differential in estimated damage between non-sprin-klered and sprinklered fires among the heavier occupancies. In the heavy metal classes, the average non-sprinklered fire damage was nearly $3.1 million, compared to $819,000 for sprinklered occupancies, or a ratio approaching 4:1. Similarly, for textile/apparel, the average non-sprinklered fire damage was slight-ly more than $1.9 million, compared to $461,000 for sprinklered occupancies. In all categories except for two—rub-ber/plastics and wood/furniture—the difference between the average fire

THE STORY TOLD by the study is that when sprinklers are installed in the area of origin and operate as designed, fires almost always remain small.

Page 4: Sprinkler NFPA

MARCH/APRIL 2014 NFPA JOURNAL 57

The 2013 “U.S. experience wiTh SprinklerS” report, produced by NFPA’s Fire Analysis and Data Division, includes information on manufacturing and warehouse facilities, the types of occupancies that are termed “industrial” in the Lib-erty Mutual study. The data, taken from a survey by NFPA and the National Fire Incident Reporting System and excerpted here, supports the findings of the Liberty Mutual study: that sprinklers in these oc-cupancies are overwhelmingly successful at reducing the loss of life and property in the event of fire.

In the NFPA report, for manufactur-ing facilities (excluding buildings under construction) in 2007–2011, 48 percent of reported structure fires indicated some type of sprinkler was present: 85 percent were wet pipe, 12 percent were dry pipe, and 3 percent were other.

Wet pipe sprinklers operated in 91 percent of the fires and operated effectively in 86 percent of the fires. When failure occurred, leading reasons were system shutoff (62 percent) and manual intervention defeated system (20 percent). When operating equipment was ineffective, leading reasons were water did not reach fire (36 percent) and not enough water released (31 percent).

Only one or two sprinklers operated in 67 percent of reported fires where wet pipe sprinklers operated.

In manufacturing facilities, deaths per thousand reported fires were 88 percent lower when wet pipe sprinklers were present, when compared to fires with au-tomatic extinguishing equipment present.

In manufacturing facilities, di-rect property damage per reported fire was 38 percent lower when wet pipe sprinklers were present, when compared to fires with no automatic extinguishing equip-ment present.

For warehouses (excluding cold storage) in 2007–2011,

32 percent of structure fires reported that some type of sprin-kler was present: 79 percent wet pipe, 20 percent dry pipe, and 1 percent other.

Wet pipe sprinklers operated in 86 percent of fires and operated effectively in 84 percent of fires. Only one or two sprinklers operated in 73 percent of reported fires where wet

pipe sprinklers operated.In warehouses excluding cold storage,

deaths per thousand reported fires were 61 percent lower when wet pipe sprinklers were present, when compared to fires with no automatic extinguishing equipment present.

In both manufacturing and warehouse facilities, estimates of reliability and effectiveness are based only on fires and installations where the fire should have acti-vated and been controlled by an operational sprinkler system, therefore excluding buildings under construction, fires with sprinklers not in the fire area reported as the reason for failure or ineffectiveness, fires reported as being too small to activate equipment, and fires reported as being confined to cooking ves-sel, chimney or flue, fuel burner or boiler, commercial compac-tor, incinerator, or trash.

Manufacturing and warehouse sprinkler data from NFPA’s 2013 “U.S. Experience with Sprinklers” report

nfpa.org/researchTo see the complete “U.S. Experience with Sprinklers” report, visit nfpa.org/research.

Photograph: AP/Wide World

A firefighter pulls a hose past a pile of burning molded fiber apple and egg crates at a manufactur-ing facility in washington state. nFpA data found that, in manufacturing facilities where sprinklers were present, 85 percent were wet pipe, which operated effectively in 86 percent of the fires.

Page 5: Sprinkler NFPA

58 NFPA JOURNAL MARCH/APRIL 2014

THE SPRINKLER DIFFERENCE

The LiberTy MuTuaL sTudy documented fires in indus-trial occupancies where sprinklers were present and should have operated, or perhaps even did operate, but were shut off either before the fire event or prematurely during the fire. These actions, known as impairments, are almost always the result of human error.

In one instance, an impairment occurred at a warehouse where, ironically, sprinkler contractors were making improve-ments to the system. At closing time, they lacked a necessary part to recharge the system. Instead of getting the part and completing the recharging process, they left the system off without notifying anyone and went home. A fire occurred that night. What may have been damage around $250,000 to $500,000 amounted to many multiples of that.

Another example involved a fire in a typical New England textile mill. The fire seemed to exceed what would normally be expected in a sprinklered building. After the fire, a fire protection engineer visited the location and found several sprinkler control valves in the closed position, including the one controlling sprinklers in the fire area. It turns out they were shut off during the fire to conserve water escaping through some damaged pipe. Although the consequences of this action were not fully investi-gated, it has to be at least assumed that sprinklers in the fire area were shut off during the fire as well. Again, what may have been fire damage of around $300,000 was many multiples of that.

Finally, one of the most unusual and well-documented cases of sprinkler impairment occurred in Roseville, Califor-nia, in 2010. Although it was in a retail location, this scenario could just as easily have happened in a large, complex indus-trial facility. The details were taken from the official City of Roseville loss report.

As the 1.4 million-square-foot Westfield Galleria at Roseville Mall, an important local employer, geared up for holiday shop-ping, a person believed to be carrying a gun barricaded himself in the storage room of a video game store on the second floor and started a fire. A standoff ensued, the mall was evacuated, and a suspect was apprehended. Emergency responders deter-mined that sprinklers in that area of the mall were operating. But the fire continued to grow in intensity and spread to adja-cent stores until a partial roof collapse led to the withdrawal of all emergency personnel. The fire entered a phase of drastic escalation and fighting it became an external effort.

In the aftermath, the central question was how the fire could have grown so large when sprinklers should have contained it.

An investigation revealed that, unbeknownst to authorities at the time, the sprinklers had actually been shut off shortly after responders arrived at the scene. They did not discover this for well over an hour, when fire department personnel overheard a Westfield maintenance employee talking about having been told by police to shut off one of the sprinkler valves. Upon hearing this, the fire department ordered him to reopen the valve, which was done at about 71 minutes after it had been shut—plenty of time for the fire to intensify and spread. In the final investiga-tion it appeared that a delivery service driver relayed a “shut the valve” message from police to the maintenance employee.

The fire was extinguished by the next day, but the Bureau of Alcohol, Tobacco and Firearms (ATF) did not allow the mall to reopen until days later. According to ATF, the fire destroyed 20 stores and resulted in an estimated $55 million in damage. The four anchor stores had been able to shut themselves off from the mall, which somewhat limited their damages. The man who started the fire pled guilty to two counts of arson and was sen-tenced to 15 years in federal prison.

—F.S.

a former mill building used for storage burned out of control in Massachusetts in 2010. a local fire official was alleged to have ordered the building’s sprinkler system turned off weeks before the fire.

The Impairment ProblemWhat can happen when sprinklers meet human error

Page 6: Sprinkler NFPA

MARCH/APRIL 2014 NFPA JOURNAL 59

as impairments, sprinklers were present and should have operated, or perhaps even did operate, but were shut off either before the fire event or prematurely dur-ing the fire. In almost every instance, the result of shutting off sprinklers before

the fire is fully controlled is roughly the same as if sprinklers had not been pres-ent. It can also be highly embarrassing for those responsible, which is why it’s often difficult to establish exactly how the impairment occurred. (For examples, see “The Impairment Problem,” page 58.)

These are the exceptions, however. The study illustrates clearly that when sprinklers are installed in the area of origin, and when they operate as designed—which occurs in the vast majority of instances—fires almost always remain small, as reflected by the cost of the damage associated with those fires. This is a key reason why the value of automatic sprinklers for all occupancies, from residential to heavy industrial, continues to be more widely recognized, not just in the United States but around the world.

It is our hope that that momentum will continue, aided by the work of NFPA, major insurers, firefighting organizations, and other stakeholders to constantly investigate improvements in hardware and to upgrade sprinkler installation codes and standards. That collective effort will ensure that automatic sprinklers continue to fulfill their promise of reduced loss of life and property damage well into the 21st century and beyond.

Fred SanFord has been a P.E. for more than 55 years, and is director of special projects with Liberty Mutual Insurance’s Property Risk Engineering Group.

with great effectiveness in spite of design deficiencies.

However, they do not compensate well for failures in the post-design human activities intended to keep sprin-klers in service. Those activities include regular inspections to make sure valves are open, using an “impairment” system that assures sprinkler systems are restored promptly after repairs, and, perhaps most important, posting a person dur-ing emergency situations to make sure sprinkler valves stay open until ordered shut by an authorized person.

An example of a design/review fail-ure is where sprinklers are omitted in concealed spaces, in enclosed process equipment such as ovens and printers, from beneath mezzanines, or from other enclosures. In these cases, fire is able to gain headway before encounter-ing sprinklers. On average, fires in this category tend to be as damaging as if there were no sprinklers. However, the balance between fire and water damage leans toward less fire and more water damage when sprinklers are delayed.

Another example of a design/review failure is a fire in an occupancy that simply overwhelms the ability of sprin-klers to control it. Usually these types of fires involve a deficiency in water supplies and are fortunately few and far between. The study includes fires in three warehouses—which stored rub-ber tires, non-woven textiles, and baled cotton—where deficient water supplies were believed to be the critical factor in the failure to control the fire. All three fires resulted in the total destruction of the buildings and contents.

Saddest of all are those post-design/review cases where the capital expense of sprinklers has been incurred but the benefit of sprinkler protection is not re-alized at the time it is most needed, dur-ing the fire. In these situations, known

skewed the comparison in a relatively small sample in the wood/furniture category. This was the only category where the estimated average damage caused by a sprinklered fire was actually higher than that of a non-sprinklered fire—$582,000 to $438,000, respective-ly. Without the single large hydraulic oil fire, however, the estimated average damage caused by sprinklered fires would have been $391,000—a relatively small differential due to the fortunate lack of serious non-sprinklered fires.

While the study included warehousing as an industrial occupancy, there are so many variables of commodity, storage height, arrangement, sprinkler design, and other factors that an enormous amount of loss data would be needed to drill into it very deeply. From a loss point of view, there was not a large number of fires to generate the data. The study did find that fires in facilities without sprin-klers typically did three times more dam-age than those in sprinklered properties, which was in line with the 3:1 ratio generally found across all occupancies.

The human elementThe study also revealed cases where sprinklers were present but were impeded or impaired. Most of these cases—where sprinklers were pres-ent but failed to control the fire within expected limits—could be traced to failures in what we termed the “human element,” which are those activi-ties, conducted by people, that either support or defeat the effectiveness of sprinkler protection.

The human element begins with proper design and review of sprinkler system placement and hardware, as well as competent evaluation of the water supply to meet the intensity of the fire anticipated by the occupancy. For best results, system design should anticipate the most challenging condi-tions, not necessarily the least costly solution. That said, sprinklers are amazingly resilient and often perform

Photograph: Dave Roback, Springfield-Republican

in design/review failures, sprinklers are omitted in concealed spaces and other enclosures. Fires in this category tend to be as damaging as if there were no sprinklers.