Technical information and Installation Servicing Instructions
Model
● KGW - 8NE , 8NF (13.9 kW)
● KGW - 10NE , 10NF (17.4 kW)
● KGW - 13NE , 13NF (22.6 kW)
● KGW - 15NE , 15NF (26.1 kW) Gas
wat
er h
eate
r …
……
…..…
……
....
1페이지
CONTENTS
1) overall view Specification ************************************** 3 Accessories ************************************** 3 2) Installation Standard installation ************************************** 4 Installing Hot water heater ************************************** 5 Connecting Flue ************************************** 6 Piping for upper floor ************************************** 17 Connecting Gas ************************************** 18 Piping Central heating water ************************************** 18 Piping Hot water ************************************** 18 Drain ************************************** 18 Electric works ************************************** 19 3) Functions of the convenient service Test working ************************************** 20 First ignition operation ************************************** 21 Water circuit Diagram ************************************** 22 Checking the CO2 ************************************** 22 Adjustment and gas conversion ************************************** 23 4) Direction for assembly Disassembly ************************************** 25 Part list ************************************** 26 5) Maintenance guide Main heat exchanger ************************************** 27 Burner unit ************************************** 28 Fan unit ************************************** 29 Temperature sensor ************************************** 30 Over heating sensor ************************************** 30 Gas valve ************************************** 30 Circulation pump ************************************** 31 3Way valve ************************************** 31 Others ************************************** 31 6) Function of the controller Main controller ************************************** 32 Function ************************************** 33 7) Function of the controller Room controller panel ************************************** 36 LED Panel ************************************** 37 8) Troubleshooting guide (error code) Finding failures ************************************** 38 9) Technical Data Table ************************************** 3910) Memo ************************************** 4011) Warranty ************************************** 41
2페이지
1. overall view
These instructions are suitable for KGW Series hot water heater;
Do not forget this instruction.
To ensure the correct installation, commissioning and servicing of domestic hot water heating system.
To the householder,Make sure you have a completed this book for your water heater. This book provides a record of the commissioning of your
hot water.
It contains very important information about your particular installation that may be required by service engineer.
This book will also provides contact details for the installer should you need guidance in the use of this unit or if there are
any problems. As with your car, your boiler will work more reliably and efficiently if it regularly is serviced. We recommend
an annual service check. The service history of the unit will be recorded on this book.
In the unlikely event of any problems with your boiler or system you should first contact your installer. If your installer cannot
resolve the problem he should calling to our service center.A charge
may beYou statutory rights are not affected.
To The InstallerAs part of the commissioning of this unit it is vital that this book is completed and given to the householder.
Please ensure that your customer is aware of the importance of keeping this book safe as a record of the installation and the
unit service history
Please ensure that your customer is aware of the correct operation of the system, water heater and controls. KITURAMI recommend
the use of protective clothing, when installing and working on the unit i.e. gloves.
GUARANTEEThe manufacturer’s guarantee is for 2 years(?) from the date of installed. The guarantee is invalidated if the unit is not installed
in accordance with the recommendations made herein or in a manner not approved by the manufacturer. To assist us in
providing you with an efficient after sales service, please return the guarantee registration card enclosed with the boiler without
delay.
1-1 General Information
3페이지
1. Product description
Model : KGW-8~15BE, BF
DIMENSION (Wx Dx H)
WEIGHT (kg)
FUEL TYPE
362 x 200 x 560
INSTALLATION TYPE
18
FF , FE
Δt 25℃ 10 ℓ
5 ℓ 8.1 ℓ
1-2 Speafication
13 ℓ
6.3 ℓ
MODEL
POWER SOURCE
Fixing bolt BendRoom controller
9.4 ℓ
220 - 240 V, 50Hz
KGW - 15PE , PFKGW - PE , PF KGW - 10PE , PF KGW - 13PE , PF
LNG, 13A, G20, G30
8 ℓ 15 ℓSpecific Domestic
Δt 25℃
Flue
Exhaust
Ignition bar
Gas valve
AL heat exchanger
Burner
Photo sensor
CU heat exchanger
ignition transformer
Fan
Controller
DHW innet sensor
Over heating
sensor
DHW Flow
Sensor
Mixing valve
Power transformer
Nozzle
4페이지
2. Installation
2-1 Standard installation
5페이지
ㅣ Installing Boiler ㅣ 1. The hot water heater has to be fixed horizontally to the wall with some space for cleaning and maintenance.
2. The wall should support enough to hang 25 ~ 35kg of hot water heater and be incombustible surface
3. Before installing the water heater, check the pipes and valves for domestic hot water in & out-let, and gas.
ㅣSelecting Location ㅣ 1. Please select the location and position, considering some space for cleaning and maintenance.
2. The wall should support enough to hang the water heater of 35 ~45kg. If need, reinforce the wall before installing.
3. Corrosive gas [ex. Ammonia gas, Chloric gas, Sulfur, Acids, etc] can destroy or rust the water heater, flues, and pipes by a
chemical reaction. And it may reduce the efficiency of heater or igniter. Please avoid this location or clean up the place
before installing water heater.
4. he water heater should be installed onto the incombustible surface.
5. Please avoid the wet place and hermetically sealed location.
The water heater can be installed on any suitable internal wall (suitable sound proofing may be required when installing onto a stud partition wall).
Provision must be made to allow for the correct routing of the flue and setting of the terminal to allow the safe and efficient removal of the flue
products.
Where a room sealed appliance is installed in a room containing a bath or shower, the appliance and any electrical switch or appliance control,
utilizing mains electricity should be situated specifically in accordance with current IEE Wiring Regulation.
[Installing water heater] 1. The water heater has to be installed horizontally to the wall with some space for cleaning and maintenance.
2. The water heater has to be fixed firmly with special bolt for its weight and tightly against any vibration.
It is recommended to stick the rubber against vibration.
2-2 Water heater Installation
6페이지
2-3-2 Installing flue (Connecting)
COXAIL FLUE Connecting
ASSEMBLING the socket of inlet and outlet flue.
1. Join the flue socket on flue outlet.
2. After sealing the top of boiler and socket with gasket,
fix the socket to the boiler body with screw.
JOINING FLUE WITH BOILER 1. Fix the socket, boiler adapter and flue elbow with sealing
tape after adjusting all.
2. After sealing well, join and screw the flue duct adapter.
3. Join and fix the flue elbow to main flue with careful check
of exhaust flue and inlet flue.
4. Seal the joint completely with tape and screw the Flue
duct adapter.
5. Slope down the flue outlet by 3 ~ 5˚ in order to drop the
condensation down.
2-3 Installing flue (Dimensions and Fixings)
Flue Air Duct
Flue Duct Adapter
Gasket
Flue Elbow
Flue Duct Adapter
Boiler Adapter
Gasket
Socket
Exhaust Flue
7페이지
2-3-1 FLUE
COXAIL FLUE
Forcible air inlet, outlet type (FF)Forcible air outlet type (FE)
Section Model 13.9 kW - 26.2 kW
Φ75 x Φ100Φ75
1 2 3 4 5 6 7
name air suction pipe exhaust pipe exhaust bend exhaust elbow air suction soket exhaust soket air suction bend
material SUS AL AL AL SUS SUS AL
remarks
8페이지
2-3-1 FLUE
The provision for satisfactory flue termination must be installed in accordance with local regulations.
The appliance must be installed so that the flue terminal is exposed to outdoor air.
The terminal must not discharge into another room or space such as an outhouse or lean-to. It is important that the
position of the terminal allows a free passage of air across it at all times. The terminal should be located with due
regard for the damage or discoloration that might occur on buildings in the vicinity,
it must also be located in a place not likely to cause nuisance. In cold or humidity weather water vapor may condense
on leaving the flue terminal The effect of such “steaming” must be considered. If the terminal is less than 1 meter
above a balcony, above ground or above a flat roof to which people has access, then a suitable stainless steel terminal
guard must be fitted. The minimum acceptable spacing from the terminal to obstructions and ventilation openings
are specified in Fig. X.
WarningThe exhaust gas duct must not be contact with or close to inflammable material and must not pass through building
structures or walls made of inflammable material. When replacing an old appliance, the flue system must be changed.
9페이지
2-3-7 Installing flue (Fitting The Flue (Cont) )
A Directly below an opening, air brick, opening widow, etc.
B Above an opening, air brick, opening window etc
C Horizontally to an opening, air brick, opening window etc
D Below gutters, soil pipes or drain pipes
E Below eaves
F Below balconies or car port roof
G From a vertical drain pipe or soil pipe
H From an internal or external corner
I Above ground, roof or balcony level
J From a surface or boundary line facing a terminal
K From a terminal facing a terminal (Horizontal flue).
From a terminal facing a terminal (Vertical flue).
L From an opening in carport (e.g. door, window) into the dwelling
M Vertically from a terminal on the same wall
N Horizontally from a terminal on the same wall
R From adjacent wall to flue (vertical only).
S From an adjacent opening window (vertical only).
T Adjacent to windows or openings on pitched and flat roofs
U Below windows or openings on pitched roofs
300mm
300mm
1200mm
1200mm
25mm
25mm
25mm
600mm
300mm
2000mm
600mm
300mm
25mm
25mm
300mm
300mm
1000mm
1500mm
10페이지
2-3-8 Installing flue (Flue Options - Horizontal Flue Systems)
Twin & Vertical Flue Systems 1. Maximum permissible equivalent flue lengths are:-
2. Any additional " in lin" bends in the flue system must be taken into consideration
Their equivalent lengths are:-
Concentric Pipes: Twin Flue Pipe 130 bend 0.5 metres 135 bend 0.25 metres 93 bend 1.0 metres 91.5 bend 0.50 metres
The elbow supplied with the standard horizintal telescopic flue kit is not included any equivalent length
calculations
Vertical Concentric
15 metres Vertical Twin Pipe
20 metres10 metres
11페이지
2-3-9 Flue options
The total equivalent length for this example is = 6.5 meters
AIR DUCT
sub totalEquivalent
Length ValueN of
fittings/pipes
1 m 5 5.0 m0.25 m
Equivalent N ofsub total
0.25 m 2 0.5 m
Equivalent Length Air Duct = 6.5 m
FLUE DUCT
0.5 m1.0 m
22
fittings/pipes
1 m 5 5.0 m
Length Value
0.5 m
2 1.0 mEquivalent Length Air Duct = 6.5 m
0.5 m
12페이지
2-4-1 Standard pipework
※ Caution on piping
This boiler is equipped with the pressure controller of water-inlet to protect
the body and each valves from the instantaneous high-water-pressure
when or closing the water valves.
This pressure controller of water-inlet works under 2.5kgf/㎠ of inlet water
pipe pressure. Therefore, if over it, should install the pressure reducing
valve for inlet water pipe additionally.
If over pressure of inlet water, it may cause bursting pipes of house or
boiler inside and stopping hot water from boiler.
2-4 pipework
water heater Cool water INLET
reducing valve
(Sold separately)
Conneat direc
tly to water
pipe
Gas filter
DHW INLET Pipe
DHW OUTLET Pipe
Bathtub
DHW INLET Valve
Pressure redncing valve
Gas inlet pipe
DHW OUTLET Pipe
Bathtub
13페이지
2-4-2 Gas / Water connection
1. Gas connection 1). Make sure, using the labels on the packaging and the data plate on the appliance itself, that the boiler is in the correct
country and that the gas category for which the boiler was designed corresponds to one of the categories available in the
country where it will be used.
2). The gas supply piping must be created and measured out in compliance with specific legal requirements and in accordance
with the maximum power of the boiler; you should also make sure that the shut-off valve is the right size and that it is
connected correctly.
3). Check that the supplied gas corresponds to the type of gas for which the boiler was designed
(see the data plate located on the appliance itself).
It is also important to check that the pressure of the gas (methane or LPG) you will be using to feed the boiler is suitable,
because if it is insufficient the power may be reduced, causing inconvenience for the user.
2. Water connection 1). The illustration shows the connections for the water and gas attachments of the boiler. See valves configuration
2). Check that the maximum water mains pressure does not exceed 3bar; if it does, a pressure reducing valve must be
installed.
3). For measuring of the pipes and of the heating bodies in the heating system, the residual head value should be calculated
as a function of the requested flow rate, in accordance with the valves shown in the circulation pump graph
3. Drain connection 1). Extend the hose from the safety valve and connect the drain hole.
※ Caution ; Do not store any wettable things under the boiler or near the drain hole.
D Domestic Hot Water Inlet
C Domestic Hot Water inlet
B Domestic Hot Water Outlet
Name
others
mark
A Gas Inlet
D
C
BA
14페이지
2-5-1 Connecting Wires
※ This appliance is designed on AC 220V ~ 230V/ 50Hz. This work of connecting wires is required by a qualified electrician.
1. Make sure that the earth connection is required for safety uses from any electric leakage or short-circuit.
2. Make sure that the connecting electricity - for example, connecting power and cable, wiring, earthing, etc - should
comply with the regulation.
3. If this appliance is not earthed by power plug, ensure to earth separately, by minimum 30cm inserted in the
ground. Note not to connect gas pipe, telephone wire and lightning conductor(rod) in order to avoid any
accident from lightning, surge, or the gas accident.
4. Make sure that the socket outlet is apart by over 30 cm from the appliance.
5. The power outlet has to have at least the minimum clearance of 30Cm from the gas water heater
6. The grounding point need to be buried at least 30cm
2-5 Connecting Electricity
More than 30Cm
15페이지
3. TEST WORKING
1). Before switching-on, please check the followings after finishing the installation of boiler, flue, pipes, and electricity.
① □ Is the boiler installed horizontally on the wall?
② □ Does the installer work on the installation manual?
③ □ Are not there any inflammable material near the boiler, for example, gasoline, gas can and bottle, thinner, etc ?
④ □ Is the on-off valve installed between gas pipe and boiler?
⑤ □ Does check the gas leakage of each connecting points?
⑥ □ Does insulate each pipes properly to protect in winter season?
⑦ □ Does check the leakage of the exhaust gag from the flue ?
⑧ □ Does check the voltage and hertz - AC 220 ~ 230V 50Hz, before of plugging-on ?
⑨ □ Does locate the middle on-off valve for water inlet pipe?
⑩ □ Does check the classification of the supplied gas to the instruction of gas on the specification label in boiler?
3-1 Check list before switching-on
1 2 3 4 5
7 8 9 10
06
16페이지
Date : …….……………………………… Installer : ……………………………………
3-2 FIRST IGNITION OPERATION
15. Check the ionisation current
Compleat………………………….
12. Check the working in DHW mode
Compleat………………………….
9. Set the heating power. See section Compleat………………………….
6. Fill the installation. See section Compleat………………………….
3. Check the gas tightness
Compleat………………………….
2. Check the type of gas andchange the gas if necessary
Compleat………………………….
5. Check the exhaust fume. See section……
Compleat………………………….
8. Spin the pump.
Compleat………………………….
11. Balance the central heating circuit
Compleat ……………….………
14. Make a combustion rate with once pressing on RESET button during 5 secCompleat ……………….………
1. Check the electricalsupply.
Compleat……………………
4. Measure the gas inlet
Compleat………………………….
7. Check the hydraulic tightness
Compleat………………………….
10. Adapt the requlation atthe heating instation
Compleat………………………….
13. Adjust DHW flow rate onthe boiler(if necessary)
Compleat………………………….
16. Explain to the end uaerthe working of the boiler
Compleat………………………….
17페이지
3-4 Checking the CO2 ① The combustion may be checked after running the boiler for several minutes.
To do this it is necessary to set the boiler to Calibration Mode.
② Ensure that all external controls are calling for heating with maximum output.
③ The appliance should be check visually for obvious defects.
④ There are two test points in the flue, one for flue gas and the other for air.
⑤ Open the air and flue gas test points.
⑥ Insert the flue gas analyzer probe as far as the retainer.
⑦ Allow the boiler to reach thermal equilibrium (around 5~10min)
⑧ The CO and CO2 values should be check each below 200ppm and 5%.
3-3 Water Circuit Diagram
Air inlet test
point
Flue gas test
point
Exhaust flue
Flue gas
1
8 7 9
10
3
6
2
4
5
13
11
12 14
15
1. Heat Exchanger2. High Limit Switch3. Burner4. Flame Detector (Photo Sensor)5. Fan6. Igniter7. Water Inlet Temperature Probe8. Water Outlet temperature Probe9. Gas Valve10. Water Flow Sensor11. Water Supply Reducing Valve12. Cold Water Inlet Connection13. Hot Water Outlet Connection14. Gas Inlet Connection15. Safety Relief Valve
18페이지
1) Adjusting the pressure and gas flow rate to the main burner This boiler operates on the flame modulation principle. It has two fixed pressure values which are minimum and
maximum and must be shown in the following table, whichever type of gas is used.
Note – Because correct minimum and maximum pressure are critical to the efficient operation of the water heater it is
essential that the following adjustments are carried out by qualified personnel only.
2) Adjusting minimum and maximum pressure gas valve (TIME, UP33-06) ① Undo the screw “A”.
② Connect suitable pressure gauge (Analogue – Water columns, Digital – Digital manometer) to burner test point
with silicone tube “B” downstream of the gas valve.
③ Domestic hot water
④ After setting DIP S/W Nr 8 to the “ON” position, adjust potentiometer “C” on the main board at the minimum.
⑤ Adjust minimum pressure by rotating screw “D” clockwise to reduce pressure and anticlockwise to increase pressure.
⑥ After adjusting the minimum pressure, turn OFF position the DIP S/W Nr 8.
⑦ And then, After setting DIP S/W Nr 9 to the “ON” position, adjust potentiometer “D” on the main board at the maximum.
⑧ Adjust maximum pressure by rotating screw “E” clockwise to reduce pressure and anticlockwise to increase pressure.
3-5 Adjustment and gas Conversion
Water column
silicone tube
Screw for soundness
Burner 2nd pressure
test point
Water column
19페이지
2) Gas conversion
The following adjustment and conversion operations must be carried out by qualified personnel. KITURAMI
Limited accepts no liability for damage to property or personal injury resulting from tampering with the water heater by
unauthorized persons.
To convert the water heater from Natural Gas to LPG and vice versa, the main burner injectors must be replaced.
Minimum and maximum pressure must then be adjusted on the gas valve.
Table1, Gas valve 2nd pressure each Model Unit mmAq
MAX MIN MAX MIN MAX MIN MAX MIN
83 24 79 18 92 19 105 16
57 18 57 16 53 12 64 12
Table2, Nozzle diameter each model and gas Unit mm
UNIT 15
GAS
UNIT 10
UNIT 8 UNIT 10 UNIT 13
Ø1.1 x 17EA
UNIT 8 UNIT 13 UNIT 15
Model
3-6 Adjustment and gas Conversion
LPG
LNG
LPG
Model
Ø1.1 x 13EAØ1.1 x 10EA Ø1.1 x 15EA
Ø1.68 x 15EA Ø1.68 x 17EALNG Ø1.55 x 13EAØ1.55 x 10EA
Potential meter
maximum control
Potential meter
minimum control
DIP Switch
Water column
20페이지
4. Direction for assembly
4-1 Part exploded view
21페이지
4-1-1 Part name
8 NF 10 NF 13 NF 15 NF
1 Heat exchanger Ass'y ◎ ◎ □ □
2 Fan ◎ ◎ □ □
3 Ignition transformer ◎ ◎ □ □
4 Power transformer ◎ ◎ □ □
5 Gas valve ● ● ● ●
6 Nozzle adaptor ● ● ● ●
7 Fixing Clip ● ● ● ●
8 Side case ● ● ● ●
9 Main Controller ● ● ● ●
10 connector ● ● ● ●
11 Bath Controller ● ● ● ●
12 Power cord ● ● ● ●
13 Temperature control ● ● ● ●
14 Front Door ● ● ● ●
15 DHW Inlet apparatus ● ● ● ●
16 DHW Inlet Temp. Sensor ◎ ◎ □ □
17 DHW Outlet Temp. Sensor ● ● ● ●
18 Mixsing valve ● ● ● ●
19 Gas pipe ◎ ◎ □ □
20 Gas Valve Inlet Connection ● ● ● ●
21 DHW Flow Sensor ● ● ● ●
22 DHW Inlet Pipe ● ● ● ●
23 DHW Outlet Pipe ● ● ● ●
24 Photo sensor ● ● ● ●
25 Ignition rod ● ● ● ●
26 Ignition rod BKT ● ● ● ●
27 Ignition rod Gasket ● ● ● ●
28 Temperature sensor ● ● ● ●
29 Mica ● ● ● ●
30 Nozzle ● ● ● ●
31 Air INLET ● ● ● ●
32 Air OUTLET ● ● ● ●
33 Air OUTLET Packing ● ● ● ●
34 Wall bracket ● ● ● ●
35 Gas Valve Outlet Connection ● ● ● ●
온수파이프
가스밸브 출구니쁠
배기구 패킹
온도조절기(A1)
가버너 입구니쁠
온도센서
운모
노즐 아답타
전면문짝
급수장치
벽걸이브라켓
점화봉 가스켓
유량센서
급기구
배기구
포토센서
점화봉
급수센서
점화봉 브라켓
가버너 출구니쁠
출수센서
믹싱밸브
가스배관
Part Name(English)Capacity
ERP Code
점화트랜스
주열교환기
No Korean
송풍기
파워트랜스
가스밸브
노즐 아답타
고정클립
케 이 싱
메인 콘트롤
콘넥터
욕실 온도조절기(A2)
파워코드
22페이지
5. MAINTENCE GUIDE
Assembly Instructions for Ignition transformer and Ignition rod
1. Plug off the power cord 4. After disassemble screws on ignition rod bracket fixed on
2. Plug off igniter plug(①) from ignition rod(⑤) heat exchanger, separate ignition rod
3. After disassemble screws on Ignition transformer, 5. In reverse order, assemble ignition rod and transformer.
separate it. And then check the ignition rod gasket
Assembly Instructions for Photo Sensor
1. Plug off the power cord 3. After disassemble screws fixed on Photo sensor bracket,
2. Separate Electrode lead for Flame Detect and sensor separate the bracket.
from Photo Sensor. 4. In reverse order, assemble Photo Sensor. And check
whether to insert mica on assembling.
※ On reverse order, assemble the parts and boiler.
Warning ! : Carefully assemble the cover and nuts to seal the parts. If fail to seal, there may occur the accident of gas leakage.
1
5-1 Main heat exchangeur
2
Ignition transformer
Igniter Plug
Electrode Lead
Ignition bar1
2
3
4
5
Photo Sensor Bracket
Photo Sensor
Electrode Lead for Flame1
2
3
23페이지
Assembly Instructions for Fan
1. Plug off the power cord. 4. After disassemble screws joining Fan and Heat exchanger,
2. Separate the plug from Fan. separate Fan by pulling forward.
3. After disassemble screws fixed on ignition transformer, 5. In reverse order, assemble Fan.
separate ignition transformer.
Assembly Instructions for Heat exchanger and Burner
1. Plug off the power cord. 4. Separate screws fixed on the cover of Heat exchanger
2. Separate gas pipe from Burner. and the cover.
3. After disassemble screws fixed on Heat exchanger 5. After separate Burner Assembly by pulling forward,
Assembly, separate ignition transformer. disassemble screws fixed on Nozzle adaptor and it.
6. In reverse order, assemble Heat exchanger and Burner.
And check the air-permeability of the cover
※ On reverse order, assemble the burner ass'y, nozzle adapter, and heat exchanger.
4
5-2 Burner unit
3
1
2 Fan
Ignition Transformer
Burn
Heat Exchanger Assembly
Front of Combustion Chamber
Mani-folder Gas Pipe
Burner
2
4
3
5 1
24페이지
Assembly Instructions for the Temparuture Sensor of Cold Water Inlet and Hot Water Outlet
1. Plug off the power cord. 3. Separate hot water outlet temperature Probe by rotating
2. Separate cold water inlet temperature Probe, fixed on counterclockwise.
the pipe, by rotating counterclockwise. 4. In reverse order, assemble them.
Assembly Instructions for Flow sensor and Reducing valve.
1. Plug off the power cord. 3. After disjoin the clip from water flow sensor, dismantle it.
2. After disassemble screws fixed on the water inlet 4. In reverse order, assemble them. And check the insertion
connection, separate Reducing valve. of O-ring.
5
5-3 Fan unit
6
Hot Water Outlet Temp. Probe
Cold Water Inlet Temp. Probe1
2
Water Flow Sensor
Reducing Valve
Water Inlet Connection1
2
3
25페이지
Assembly Instructions for Gas Valve
1. Plug off the power cord. 4. After disassemble screws fixed on Gas valve adapter,
2. After pull the plug off from Gas Valve, separate separate Gas Valve.
Gas Valve. 5. In reverse order, assemble them. And check the insertion
3. Disassemble screws fixed on Gas inlet connection. of O-ring in pipes and Adapter.
Assembly Instructions for Overheating Sensor
1. Plug off the power cord. 4. In reverse order, assemble it. And check the insertion of
2. Pull the plug off from Overheating Sensor. the airtight sealing material.
3. After disassemble screws fixed on Overheating Sensor,
separate it.
7
9
Gas Pipe
Gas Inlet
Connection
Gas Valve
Gas Valve Outlet connection
Electrode Lead
3
2
4
1
5
Heat Exchanger Safety Thermostat1 2
26페이지
Assembly Instructions for Main controller
1. Plug off the power cord. 3. After disassemble screws fixed on Main controller,
2. Separate the connector from Main controller. separate it by pulling forward.
4. In reverse order, assemble it. Before assemble it, check
the fixing on exact location and missing of connector.
10
1
27페이지
6. Functions of the controller
Model : GTH-7000
6.1 Main Controller part name
No Name
1. Gas sensor
2. Dip S/W (RPM control)
3. Hot water outlet sensor
4. DHW Flow Sensor
5. Cold water inlet sensor
6. Overheat / Burning(infrared rays) / Room
No Name
7. Gas valve
8. Ignition transformer
9. Reset switch
10. 10P Connecter
11. proportion control
12. Fan output
678
10
11
12
5
4
3
21
9
28페이지
6-2-1 Controller model name
◎ GTH-7000 : 13,000Kcal ~ 20,000Kcal (normal , open type, FF/FE, LNG/LPG)
* Normal Functions
NO
1
2
3
capacity and Mode
6-2-2 Function
◎ Operation start when plug-on
① During first 60 seconds, the controller will not sense the gas due to requirement of pre heating time for gas sensor heater.
② And then for 5 seconds, in order to initialize the system, the controller will not operate P/T.
1) Function while the Temperature controller Power is OFF
NO
2) Room controller start on function - Function only with Bath Temp. controller
Control Custom Temperature by hot water outlet
Temp., cold water inlet Temp. and Flow value
FORCED CLEAR
Powers ON/OFF
70℃Operating conditions
water heater's
DISPLAY
Select Switch for
OPERATIONFUNCTION SENSING
Reactivating SWITCH
Automatically recognize Operating condition(YES) of Bath Temp. controller
※ Functions without Temp. controller [BATH 300A1]
Controller [BATH 300A1, A2] When GTH-7000 sensing FlowRemark
Automatically set up Custom Temp. as 42℃
Fan starts to work
YES
NO
ON
OFF
OFF
OFF
60℃
Gas leakage
detect
Power LED
flickers
Power/Alarm LED
NAME
Manual SWICH for reactivating when safety blocked
Specifications
6-2 Function
MAIN and Temp. coltrollerSensing by Gas sensor
Remark
[LNG/LPG, Domestic/Export, FF/FE, General/Condensing]
□ Select Mode
Flickers at the alarm
Min. Combustion
Functions for□ Select Water heater capacity
Lights when Power is on
Forcible Max. Combustion or
29페이지
3). Burner control time chart
① PRE-PURGE TIME : for 2 sec ± 1sec → In order to operate safely, fan emit the exhaust gas from burner before starting ignition transformer.
② PRE IGNITION TIME : 0 sec → To ignite and burn well, start the ignition before supplying gas. ③ POST IGNITION TIME : 3 sec ± 1sec → After the initial burning, the igniter operates for 2 ~ 4 seconds in order to protect the burn from the initial failure due to incomplete combustion. [Ignition is OFF in 3 seconds after sensing flame] ④ POST PURGE TIME : 6 sec ± 1sec
Ⅰ. Normal operation time chart
⑤ Safety cut-off time chart : 3sec ± 1sec
Function cutting off supply of GAS for safety, when not sensing flame in spite of PRE PURGE by fan,
PRE IGNITION and supply of GAS.
[Safety cut-off time is the duration between Gas feeder is ON and OFF]
Ⅱ . Failure of initial ignition (signal after 3 times failure)
→ After the burner stops, the fan will operate for 5 ~ 7 seconds to emit the exhausted gas from boiler.
RPM Sensing
Time(sec)
Flaimessensing
Flaimes sensing
Time(sec)
30페이지
Custom Temperature control : Control Gas pressure and RPM of Fan, comparing custom temperature, inlet cold water
temperature and flow
[that is, combust with high gas pressure in case of large temperature difference and with low gas pressure,
in case of small temperature difference.]
▶ LNG [for EXPORT]
⑥ Re-ignition after failure of burning during operation :15sec ± 1sec When sensing the failure of burning, cut off supply of gas and repeat Re-ignition according to routine [PRE PURGE, PRE IGNITION, Supply of Gas, Sensing flame].
4). Combustion Specifications
UNIT 15 [26.2kW]UNIT 13 [22.7kW]
FAN keep value for working
50
130
FAN value 60 70
When flame sensor detects flame during PRE PURGE, proceeding progress is halted,
Re-ignition after performing POST PURGE for 15±1 sec.
⑦ Initial flame sensing [02 ERROR]
KGW identify it consecutively for 3±1 sec, print out [02 ERROR] on Temp. controller and Fan works.
7070
At the moment flame is no more detected, previous function operates.
[On derequisition of initial flame sensing, Fan halts for 1 sec and combustion progresses for 1 minute.]
UNIT 10 [17.4kW]UNIT 8 [13.9kW]capacity
60
70
Max. of Ignition
current(electric)
Standard Max. RPM
Output
60
60
10
155
FAN working value durationMax. of combustion
current(electric)Min. of combustion
current(electric)
Min. of Ignition
current(electric)Max. of Fan output
Min. of Fan output
Fan output on ignition
120
95
50
78
55
65
60
100
70
10
147
53
60
130
80
50
120
65
130
118
10
178
55
10
194
65
100
55
75
78
120
60
125
65
75
70
65
98
130
120
78
95
55
78Standard Min. RPM
RPMSensing
Time(sec)
Flaimes sensing
31페이지
▶ LPG [for EXPORT]
5). Specifications by DIP SWITCH
Method of Capacity setting and Mode setting by DIP SWITCH position
Method of Capacity setting and Mode setting by DIP SWITCH position
OFFUNIT 15 [22,500Kcal]
OFF
OFF
UNIT 13 [19,500Kcal]
UNIT 10 [15,000Kcal]
UNIT 8 [12,000Kcal]
96
FAN value 60 60 70
capacity UNIT 8 [13.9 kW] UNIT 10 [17.4 kW] UNIT 13 [22.7 kW]
FAN working value duration 10 10 10
FAN keep value for working 60 60 70
Max. of Ignition
current(electric)
Min. of combustion
current(electric)50 50
150 150
Max. of combustion
current(electric)165 200 200
Min. of Fan output 50 50 50
Max. of Fan output 80 85 100
Output 60 60 70
Fan output on ignition 65 65 75
Standard Max. RPM 95 100 98
55 55 65
78
SWITCH OFF ON SWITCH
Standard Min. RPM 78 78 78
FE
1
2
3
4
5
6
Condensing
MIN. Combustion
LNG LPG
Export
Capacity setting
Capacity setting
Capacity setting
LNG / LPG
FF
General
Noraml Combustion
Noraml Combustion
Domestic / Export
FF / FE
General / Condensing
Forcible Min. Combustion
50
115
ON
SWITCH NO
7
8
9MAX DUSTH
OFF
75
ON ON
CAPACITY
OFF
OFF
ON
2 3Remark
65
70
1
OFF
OFF
Forcible Max. Combustion
Domestic
223
10
119
70
UNIT 15 [26.2 kW]
Min. of Ignition
current(electric)119 119 119
70
50
160 160
50
32페이지
5) Hot water outlet function 5-1. The function works when Flow sensor detects a flow while Temp. controller[BATH-300A1/A2] is ON.
5-2. Custom Temperature is set on Temp. controller[BATH-300A1/A2] [ can be set from 35℃ to 60℃]
◎ 35℃ ~ 50℃: can be set by 1℃
◎ 50℃ ~ 60℃: can be set by 5℃
6) Manual-Return function [Function works on BATH-300A1/A2] 6-1. Push Manual Return SWITCH on Main Controller for Manual Return Mode.
6-2. For 2nd consecutive time, if detecting gas, Gas sensor detects gas automatically again. At 3rd time, if detecting
gas, Manual Return Mode is activated.
[Manual-Return Mode is converted to Auto-Return Mode if not detecting gas for 5 minutes]
However, The alarm code [97] is printed in case of Manual-Return[detecting gas for 3rd consecutive time]
6-3. The countdown for Auto-return is cleared if not detecting gas continuously more than 1 hour
6-4. [97] is printed promptly if detecting gas continuously more than 10 minutes.
7) Re-ignition function In case of not detecting flame for a limited period of time during normal operation, P/T[Fan and GasValve] stop and
try to reignite for keeping fire alive.
8) Initial Gas Shut-off function Function to shut off Gas for safety in case of no ignition within a limited period of time at initial gas supply
[Safety shut-off after 3 attempts]
9) Ignition Cut-off function Function not to ignite for safety when Photo sensor detects flame before the ignition.
[However, if Gas valve is closed by temperature of hot water outlet, Photo sensor doesn't detect flame for 10 seconds.]
10) Forcible Max. and Min. Combustion function When Switch is set on Forcible Max. or Forcible Min. Combustion takes place to the Maximum capacity or
Minimum capacity after normal ignition.
11) for Domestic / Export [DIP SWITCH No.5] ▶ for Domestic : There is not Forced Off function after normal combustion.
▶ for Export : Burner is forced off when meeting the conditions of continuous operation for 20 minutes after normal
combustion. [Conditions for operating again : Power Off and On]
33페이지
7. Functions of the Room controller
7-1 Room Control panel (CTR-5700)
◎ LEGEND
1. ON/OFF Button and In-Use Indicator
2. Thermostat Adjustment Button (Decreases the temperature setting)
3. Thermostat Adjustment Button (Increases the temperature setting)
4. Combustion status Indicator
5. Temperature setting Display
34페이지
8. Troubleshooting guide (error code)
Error code
The error codes display when errors occur
The last ten errors are saved in the appliance error memory
→ Press the “Timer” button for 5 seconds
→ Automatically the last errors history display 2 times by step on LCD panel.
You can exit the error memory display as follow;
→ Do not press any button return to the former times display
CodeE 01 Appliance does not start Faults in the gas supply such as
Attempts to ignite during start failed Gas meter or gas pressure detector defective
Air in gas
Gas flow pressure too low
Faults in the gas fitting, wrong gas setting, igniter (ignition
transformer, ignition cable, ignition plug) defective, photo r
sensor defective (cable, electrode), faulty earth in appliance,
electronics defective.
E 02 Flame detect before supplied gas Electronics defective, Photo sensor defective
E 03 Flame goes off during the appliance Gas supply pressure too low, flame detect device defective,
operating until less than 1 minute for PCB defective
5 times repeat
E 14 Interruption in DHW outlet temperature sensor Sensor connection defective, sensor faulty
E 34 Interruption in DHW inlet temperature sensor Sensor connection defective, sensor faulty
E 06 Fan RPM signal doesn’t detect Fan detective, RPM signal connection faulty, PCB defective,
plug not inserted correctly on fan, hall sensor defective
E 07 Fan RPM signal in the wrong range Check the flue condition, PCB defective, electronic defective
E 08 No communication with the PCB Communication faulty between the room controller and the
PCB. PCB faulty, Room controller faulty
E 96 High temperature limiter actuated Flow probe not connected thermally correct of defective,
appliance does not shut down
E 97 Gas leakage detect Change of air in boiler installing site, electronics defective
Meaning Cause
8-1 Finding fault
35페이지
9. Technical Data Table
* Specifications are subject to change without prior notice to improve design and performance
kW
(kcal/h)
%
star
kW (Btu)
(kcal/h)
bar(psi)
bar(psi)
Adjustable Domestic Hot Water Temperature ℃(℉)
△t=25℃ ℓ/min(gpm)
△t=30℃ ℓ/min(gpm)
△t=40℃ ℓ/min(gpm)
V/Hz
A
W
mm
mm
mm(A)
mm(A)
WxDxH (mm)
kg
class
mm
mA
mbar
mbar
(mmH2O)
%
ppm
ppm
℃(℉)
℃(℉)
17.4 (59,371)(15,000)
22.7 (77,455)(19,500)
26.2 (89,398)(22,500)
6.7
10
8.3 10.8
30.8(26,470)
91.5
★ ★ ★ ★ ★ ★ ★ ★
119.2 120.8 116.3
16.4(14,120)
91.3
20.5(17,650)
91.6
26.7(22,940)
92.1
13.9 (47,428)(12,000)
CO2 at Max Output 6.7
70
116.9
NOx (0%O2) at Max Output
Exhaust Temperature at Max Output
CO(0%O2) at Max Output
118.6 118.8
Exhaust Temperature at Min Output
Gas Type LNG
Gas Supply Pressure
LPG
Φ1.1 x10
9.1~2.2
362 x 200 x 560
Nozzle Diameter Φ1.5x13
6.2~2.0
Gas Type
18
3 3 3 3
Gas Connection
Physical dimensions
Weight
Nox
Connecting
Diameter
Intake/Exhaust Flue System Type
Installation Type
Intake/Exhaust Flue Diameter
Domestic Hot Water Connection
19.6 (200)
LPG
Φ1.68 x15
5.5~1.2
2.75 (280)
LPG
Φ1.1 x15
LNGLNG
Φ1.5x10
Other Comestic Hot Water Rate
Electrical Supply
Nominal Absorption
Power consumption
Electrical Protection
75×100
1/2 (15)
1/2 (15)
Other Comestic Hot Water Rate
15
12.5
9.45 6.3 8.1
Max Domestic Hot Water Pressure
Specific Domestic
35 - 60 (113~140)
8 13
121.2
7.4
98
27
122.6
Energy Perfomance
28
60
Purpose
17.5 (253.8)
Min working Pressure for DHW
LNG
0.2 (2.9)
Domestic Hot Water Output
2.75
(280)
KGW - 13BE , BF KGW - 15BE , BF
Natural Gas supply (gas control valve)
M odel Technical Spec ification
Domestic Hot Water Input (Max-Min)
KGW - 8BE , BF KGW - 10BE , BF
Useful Efficiency Output
62
DHW Production
B33-C13-C33-C43-C53-C63-C83
7.5
LNG
7.5
LNG
19.6 (200)2.75
(280)
6.0~2.0
19.6 (200)
LPG
230V / 50Hz
0.6
IPX4D
Wall Mounting Type
6458
132
28
152
29
167~81 216~93 173~81 209~93 170~73 237~64 243~87
Φ1.1 x17
LPGLNG
2.75
(280)
2.75
(280)
8.4~1.9 10.5~1.99.2~1.9
223~89
Φ1.68 x17
6.2~1.1
Φ1.1 x10
36페이지
10. Memo
37페이지