thermal fluid system design - dalatec...
TRANSCRIPT
Thermal Fluid System Design
Design #3
2
Table of Contents
Nomenclature Listing ……………………………………………………………………….3
Executive Summary ……………………………………………………………………….4
Introduction ……………………………………………………………………………….4
Analysis ……………………………………………………………………………….6
Results/Discussion ……………………………………………………………………...14
Conclusion ……………………………………………………………………………...24
References ……………………………………………………………………………...25
Appendix A: Detailed Calculations ……………………………………………………...26
Appendix B: Excel Data Tables ……………………………………………………...32
Appendix C: Shell and Tube Analysis ……………………………………………...44
3
Nomenclature Listing
T: refers to temperature of warmer fluid
t: refers to temperature of the cooler fluid
w: subscript refers to warmer fluid
h: subscript refers to hydraulic diameter
c: subscript refers to cooler fluid
a: subscript refers to the annular flow area / dimension
p: subscript refers to the tubular flow area / dimension
1: subscript refers to an inlet condition
2: subscript refers to an outlet condition
e: subscript refers to equivalent diameter
4
Executive Summary
This project entails the optimization of a heat exchanger. The system’s requirements are
oil coming from an engine at 4 lbm/s with an initial temperature of 300°F, being cooled by water
with an initial temperature of 55°F. The outlet requires oil to be within the range of 120°F and
165°F, with water not exceeding 180°F. Tubing is comprised of schedule 40 steel pipes and the
desired system is to implement a double pipe heat exchanger. Using Microsoft Excel to simplify
the calculations, the optimized system would be a double pipe heat exchanger of 2,930 feet, mass
flow rate of water of 2.34 lbm/s, and an outlet temperature of 165°F for the oil. If the customer
is interested in minimizing the length further, an 8 foot shell and tube heat exchanger could be
used, with a 171/4
” shell inner diameter, coupled with ¾” inner diameter tubing.
Introduction
Heat exchangers exist in many different configurations. Whether it is a double pipe, shell
and tube, cross flow, or a plate and frame heat exchanger, each system has specific uses.
Nevertheless, the analysis doesn’t differ greatly between each configuration. This project
examines a double pipe heat exchanger and the relationship between the placement of the given
fluids (such as in the annulus or tube) and the subsequent effect on length and pressure drop of
the system. As with any heat exchanger, a main objective for the system is to transfer as much
heat as possible, while minimizing the cost. To achieve this goal, it is necessary to keep the
system as small as possible. Figure 1 is an example of a double pipe heat exchanger.
Figure 1: Double Pipe Heat Exchanger
5
As Figure 1 suggests, the fluids have two separate inlets, which leads to the two concentric pipes.
For the project at hand, the heat exchanger is used to cool oil coming from an engine at 4 lbm/s
and 300°F to at least 165°F (but no less than 120°F). Water acts as the cooling fluid and is
available at 55°F and cannot exceed 180°F at the outlet. Schedule 40 piping will be used for the
heat exchanger and counterflow will be assumed as it is notably more effective, as compared to
parallel (unidirectional) flow. Figures 2 and 3 show the temperature graphs for both parallel
flow and counterflow.
Figure 2: Parallel Flow
Figure 3: Counterflow
These figures make it apparent as to why counterflow is a more logical choice when analyzing
the system. Note that counterflow could potentially allow the outlet of the hot fluid to be cooler
than the outlet for the cold fluid. This is not the case in parallel flow as the outlet of the cold will
never be above the outlet of the hot1.
6
To be able to optimize this system, careful consideration will be given to pipe size,
associated heat exchanger length, placement of the fluids, and the mass flow rate of water. With
this exposition for the project completed, it is appropriate to look at the mathematical model used
to solve this problem. While this model is applicable to solve the project by hand, the fact is that
many of the parameters aren’t specified, thus, Microsoft Excel is chosen to make the
computations simpler and iterative processes quicker.
Analysis
Like most thermal fluid applications, this project can be analyzed in two sections.
Firstly, with respect to heat transfer and secondly, with respect to fluid mechanics. To begin the
analysis it is necessary to determine the fluid properties at their average temperatures. This is
done for the oil over a range of 210°F to 233°F (as the oil outlet could vary) and at 118°F for the
water (as the water inlet and outlet were fixed). Next, it is appropriate to choose pipe sizes for
the flow. Figure 4 is a diagram showing the associated diameters of the heat exchanger.
Figure 4: Associated Diameters
While choosing the pipe sizes may seem random, it is necessary to ultimately look at the length
and pressure drop each pipe combination offers for the system, as will be discussed in the
Results section. Having these properties for the system, it is appropriate to start with Equation
(1).
IDa
ODp
IDp
7
(1)
Where is the area of the pipe in ft2 and is the inner diameter of the pipe in ft. Equation
(2) then allows the annulus area, , to be calculated using the outer pipe diameter, .
(2)
Having the areas associated with the pipe and annulus, the fluid velocities can then be computed,
as shown in Equations (3) and (4).
(3)
(4)
Where the pipe velocity in ft/s, the annulus velocity in ft/s, and is the mass flow rate of
the specified fluid in lbm/s.
8
Using the tubing sizes, it is appropriate to calculate the hydraulic and equivalent diameters of the
annulus. Equation (5) allows the hydraulic diameter to be computed, while Equation (6) allows
the equivalent diameter to be computed.
(5)
(6)
Where is the hydraulic diameter and is the equivalent diameter, both in feet.
With the associated diameters, it is feasible to compute the Reynolds Numbers for the pipe and
annulus. Equation (7) does so for the pipe while Equation (8) does so for the annulus.
(7)
(8)
With and being the Reynolds Numbers for the pipe and annulus, respectively. Note that
ν, the kinematic viscosity, is a fluid property and in ft2/s.
9
Having the Reynolds Numbers allows the Nusselt Numbers for the pipe and annulus to be
calculated. Equation (9) is appropriate if the flow is laminar (Re < 2200), while Equation (10) is
appropriate for turbulent flow (Re > 10000).
(9)
(10)
Where L is the length of the heat exchanger in feet, Pr is the Prandtl number (listed as a fluid
property), and n is .3 for a fluid being cooled, or .4 for a fluid being heated. Note that L is going
to require an iterative approach as it is an unknown. Coupling Equation (9) with Equation (20),
the length must be iterated until the results converge.
Using the Nusselt numbers, the convection coefficients for the pipe and annulus can be
computed. This is shown in Equations (11), (12), and (13).
(11)
(12)
10
(13)
With being the heat transfer coefficient of the inner pipe, being the coefficient of the entire
pipe, including the pipe wall, being the coefficient of the annulus, and is the fluid’s
thermal conductivity, a property of the fluid. Note that the convection coefficients are in Btu/(h-
ft2-°R). Having these coefficients it is possible to compute the exchanger coefficient, , as
shown in Equation (14).
(14)
Where is in Btu/(h-ft2-°R). Thus far this analysis has followed the Janna text
1, but due to the
project’s requirements, certain alterations are now necessary; primarily, obtaining mass flow rate
values. While economic velocities can be used to set limits on a mass flow rate, this project aims
to minimize the length of the system, thus the economic velocity range may not be met. This is
simply due to the fact that this system is trying to be economic elsewhere, more specifically with
respect to the length of the heat exchanger and pressure drop.
By knowing all of the temperatures for this project, it is possible to compute the log mean
temperature difference, as depicted in Equation (15). Also, by setting up a heat balance across
the system, it is appropriate to ultimately compute the mass flow rate of water, as displayed in
Equations (16) and (17).
11
(15)
Note that Equation (15) is applicable only for counterflow.
(16)
Where is the heat transfer due to the warm fluid in Btu/s, is the mass flow rate of the
warm fluid, and is the specific heat of the warm fluid in Btu/(lbm-°R). Using a heat balance,
Equation (17) is appropriate.
(17)
With being the specific heat of the cool fluid.
Recognizing that is an ideal exchanger coefficient, it is necessary to look at the fouling
factors the fluids have on the system. Equation (18) calculates the design coefficient, , also in
Btu/(hr-ft2-°R).
12
(18)
Where and are the fouling factors of the two fluids on the inner and outer pipe,
respectively. Having the actual exchanger coefficient, it is appropriate to calculate the area of
the heat exchanger. Equation (19) shows this computation.
(19)
With being the heat transfer area in ft2. Using , Equation (20) allows the length of the
system, L, to be computed. As previously stated, the fact both Equations (9) and (20) have
length in them, a separate input box in Microsoft Excel allows the lengths to be iterated until
convergence is achieved.
(20)
With L in feet. While Reynolds Numbers were computed in Equations (7) and (8), it is now
necessary to look at the Reynolds Numbers to be able to obtain friction factors, as shown in
Equations (21) and (22).
13
(21)
(22)
Note that Equation (22) requires the hydraulic diameter. Furthermore, coupling these equations
with the roughness factor of the piping, it is possible to obtain the friction factor from the moody
chart (if the flow is turbulent) or using 64/Re (if the flow is laminar). Having the friction factors
allows the pressure drop to be computed for both the pipe and the annulus, as depicted in
Equations (23) and (24)
(23)
(24)
Where and are the pressure drops, in lb/ft2, in the pipe and annulus, respectively. is
the friction factor for the pipe, is the friction factor in the annulus, is the density of the fluid
in the pipe, and is the density of the fluid in the annulus. Note that to get the pressure drop
into psi, simply divide and by 144.
With Equations (1) – (24), the mathematical analysis is completed. It is now appropriate
to look at the results that this analysis yields, for the case of water in the annulus and oil in the
annulus. Furthermore, Appendix A denotes detailed calculations for one case.
14
Results / Discussion
One of the first steps shown in the analysis is choosing pipe sizes. This process is a very
crucial one, as it is quite possible to have multiple tubing combinations that may appear to satisfy
the pressure drop requirement, yet doesn’t necessarily optimize the length of the system.
Similarly, the pressure drop is a function of the mass flow rate of water as well. This can be seen
in Table 1.
Tubing Size Pressure Drop
(psi) in Pipe and
Annulus
Mass Flow Rate
of Water (lbm/s)
Length of
System (ft)
8” x 5” 4.3 ; 1.3 3.06 17,450
10” x 8” .6 ; 2.8 2.90 14,710
10” x 8” .5 ; 2.1 2.75 12,550
8” x 6” 1.1 ; 3.0 2.65 10,930
8” x 6” .9 ; 2.3 2.49 9,300
8” x 6” .7 ; 1.7 2.39 7,910
Table 1: Tubing Sizes
As this table suggests, each tube combination satisfies the requirement of pressure drop being
less than 10 psi, for both the annulus and pipe, yet it is obvious that the 8” x 6” tubing
combination optimizes the length. While this data is for water in the annulus, comparative
results are applicable for oil in the annulus, with Table 1 simply displaying the iterative process
that must take place in order to optimize the system. Regarding this data, Appendix B contains
the entire workbook along with all the associated calculations. With this being said, it is
appropriate to look at the two cases presented in the Introduction and decide whether it is best to
place water or oil in the annulus. For the remainder of the report, Case 1 will pertain to water in
the annulus, while Case 2 will pertain to oil in the annulus.
Due to the fact that there are certain restrictions on the outlet temperatures of both the oil
and water, it is necessary to assume some parameters. Because economic flow velocity is not
going to be of interest, a heat balance was used to gain the mass flow rate of water (as shown in
15
Equation (17) ). Furthermore, because the outlet temperature of the oil can vary from 120°F to
165°F, six subsections are made for each case, that increases the oil outlet temperature 9°F per
section. This is done because water has very similar properties and by fixing its outlet
temperature at 180°F, the properties have an effect on the calculations. Oil on the other hand is
very much affected by temperature. For example: when temperature varies from 176°F to 212°,
Prandtl number varies from 490 to 276. Thus, this assumption is valid. By using Microsoft
Excel, a spread sheet is programmed to compute the characteristics for each case and the results
for the two best scenarios of each case will be compared. On the other hand, using the data for
the six subsections per case, certain trends will be apparent when comparing outlet temperature,
mass flow rate of water, pipe size, length, and pressure drop.
Starting with the case of water in the annulus of the heat exchanger, the system’s
characteristics are obtained. This is displayed in Table 2.
16
Table 2: Case 1: Water in the Annulus
Similarly, it is appropriate to look at the system’s characteristics for the case of oil in the
annulus. This is displayed in Table 3.
Dimensionsri (ft) 0.25
ro (ft) 0.28
Ri (ft) 0.33
L (ft) 7914.30
Temperatures UsedTc, in (°F) 55.00
Tc, out (°F) 180.00
Th, in (°F) 300.00
Th, out (°F) 165.00
Heat Transfer Coefficientshi (Btu/hr-ft2-°R) 0.67
ho (Btu/hr-ft2-°R) 121.30
Mass Flow Rate of Watermc (lbm/s) 2.34
Overall Heat Transfer CoefficientUi (Btu/hr-ft2-°R) 0.67
Pressure DropsWater (psi) 1.72
Oil (psi) 0.72
Heat Transfer AreaAi (ft2) 13727.14
Effectivenessε 0.55
Heat Exchanger Ratingq (Btu/s) 291.60
17
Table 3: Case 2: Oil in the Annulus
By simply looking at these two tables, it appears that placing oil in the annulus is the optimal
design, as the length is shorter by nearly 5000 ft. Nevertheless, it is of sound engineering
practice to perform a cost analysis for each of these systems since the necessary pipe size of
having oil in the annulus is larger than the case of water in the annulus. This is of importance as
the increase in diameter of the pipe size may contribute to a cost greater than the extra 5000 ft of
Dimensionsri (ft) 0.33
ro (ft) 0.36
Ri (ft) 0.42
L (ft) 2925.55
Temperatures UsedTc, in (°F) 55.00
Tc, out (°F) 180.00
Th, in (°F) 300.00
Th, out (°F) 165.00
Heat Transfer Coefficientshi (Btu/hr-ft2-°R) 36.22
ho (Btu/hr-ft2-°R) 1.44
Mass Flow Rate of Watermc (lbm/s) 2.34
Overall Heat Transfer CoefficientUi (Btu/hr-ft2-°R) 1.39
Pressure DropsWater (psi) 0.01
Oil (psi) 7.13
Heat Transfer AreaAi (ft2) 6606.41
Effectivenessε 0.55
Heat Exchanger Ratingq (Btu/s) 291.60
18
the smaller diameter pipe. Obtaining prices from Metals Depot2, Table 4 displays the cost
analysis for both cases.
Tubing
Sizes
Cost / ft Overall Cost
10” x 8” $207.26 $606,345.5
8” x 6” $150.99 $1,187,065.9
Table 4: Cost Analysis
With the cost analysis performed, it is clear that placing oil in the annulus is indeed the
optimal design for this system. Another point of interest is the fact that by having the oil (the
hotter fluid) in the annulus, the surrounding environment will also help with respect to heat
transfer. Lastly, it is of importance to note the fouling factors associated with the two fluids.
Due to the fact that water and oil have comparable fouling factors (both nearly .001 ft2-hr-
°R/Btu), the placement of the fluids won’t affect quality of the pipes. If the oil were to have a
fouling factor more than the water, it may be more appropriate to place it in the pipe, as only the
inner pipe would have to be replaced over time, versus the chance of replacing both pipes if the
greater fouling agent were placed in the annulus. With the optimal design for the system being
selected, by placing oil in the annulus, using 10” x 8” tubing, it is of interest to look at the heat
exchanger’s characteristics for the oil outlet temperature varying from 120°F to 165°F.
The first parameter to be altered when varying the outlet temperature is the mass flow
rate of water. Figure 4 displays this relationship.
19
Figure 4: Mass Flow Rate vs. Outlet Temperature
Note that regardless of placement of the fluids, whether it is oil in the annulus or water, the trend
is exactly the same, as this figure is predicated solely from the heat balance. Figure 4 is
affirming in the fact that it is congruous with the computation performed in Equation (17). By
increasing outlet temperature, the water mass flow rate must decrease in order to conserve
energy. Also interesting is the effect that the outlet temperature has on effectiveness. This is
shown in Figure 5.
Figure 5: Effectiveness vs. Outlet Temperature
110.0000
120.0000
130.0000
140.0000
150.0000
160.0000
170.0000
2.25 2.45 2.65 2.85 3.05 3.25
Ou
tle
t Te
mp
ear
ture
(°F
)
Mass Flow Rate of Water (lbm/s)
Mass Flow Rate of Water vs. Outlet Temperature
115.0000
125.0000
135.0000
145.0000
155.0000
165.0000
175.0000
0.50 0.60 0.70 0.80
Ou
tle
t Te
mp
era
ture
(°F
)
Effectiveness (ε)
Effectiveness vs. Outlet Temperature
20
The importance of Figure 5 is that for the system to operate with the highest efficiency, the oil
outlet temperature must be a minimum. This makes sense as the system must remove the most
heat to cool the outlet temperature to such a degree, thus increasing effectiveness. Nevertheless,
the system with the highest efficiency isn’t always the optimized design. Figure 6 displays this
fact, that length and effectiveness are directly related.
Figure 6: Effectiveness vs. Length
This figure demonstrates that by having more pipe, the effectiveness will increase as the fluids
will travel a longer length, allowing for more heat transfer. While it is appropriate to fit a linear
trendline to the data set, it is apparent the points don’t particularly fit a certain equation. This is
due to the fact that in order to keep pressure drop below 10 psi, while minimizing the heat
exchanger length, pipe sizes must change. The drastic drops in pipe length are indicative of this
fact.
A main factor in determining the length of the heat exchanger is the exchanger
coefficient, . Figure 7 shows this relationship.
0.0000
5000.0000
10000.0000
15000.0000
20000.0000
25000.0000
0.50 0.55 0.60 0.65 0.70 0.75 0.80
Len
gth
(ft
)
Effectiveness (ε)
Effectiveness vs. Length
21
Figure 7: Exchanger Coefficient vs. Length
This relationship is important, as to minimize the area (and subsequently the length), must be
maximized. Because the oil has such a low Nusselt number, due to the laminar flow, the
controlling heat transfer coefficient is due to the oil. This in turn minimizes the exchanger
coefficient and thus makes the length exuberant. This effect is due to the 4 lbm/s flow rate of oil
coming from the engine. While I was the original person to question the 4 lbm/min flow rate, as
economic flow velocity yielded no valid pipe sizes, the fact economic flow velocity isn’t a goal
of this project, 4 lbm/min would have yielded much better results. To prove this, Tables 5 and 6
list the specifications of both cases with the original 4lbm/min mass flow rate, as given in the
problem statement.
0.3500
0.5500
0.7500
0.9500
1.1500
1.3500
1.5500
2000 7000 12000 17000 22000 27000
Exch
ange
r C
oe
ffic
ien
t (B
tu/h
r-ft
2 -°R
)
Length (ft)
Length vs. Exchanger Coefficient
22
Table 5: Case 1: 4 lbm/min Mass Flow Rate
Dimensionsri (ft) 0.04
ro (ft) 0.05
Ri (ft) 0.06
L (ft) 145.89
Temperatures UsedTc, in (°F) 55.00
Tc, out (°F) 180.00
Th, in (°F) 300.00
Th, out (°F) 165.00
Heat Transfer Coefficientshi (Btu/hr-ft2-°R) 3.27
ho (Btu/hr-ft2-°R) 42.75
Mass Flow Rate of Watermc (lbm/s) 0.04
Overall Heat Transfer CoefficientUi (Btu/hr-ft2-°R) 3.04
Pressure DropsWater (psi) 2.24
Oil (psi) 0.25
Heat Transfer AreaAi (ft2) 50.19
Effectivenessε 0.55
Heat Exchanger Ratingq (Btu/s) 4.86
23
Table 6: Case 2: 4 lbm/min Mass Flow Rate
While the lengths are still 145 ft and 85 ft, these lengths are significantly lower than when the oil
flow rate is 4 lbm/s. While some assume this is an engine in a car, and having a heat exchanger
of 85 ft is quite long, if this were an engine in a larger system (such as a ship), having a heat
exchanger that is 10’ x 9’ isn’t that unreasonable. The importance of Tables 5 and 6 is to depict
the effect oil flow rate has on the system. Another point to note is the amount of heat that must
Dimensionsri (ft) 0.03
ro (ft) 0.04
Ri (ft) 0.04
L (ft) 85.07
Temperatures UsedTc, in (°F) 55.00
Tc, out (°F) 180.00
Th, in (°F) 300.00
Th, out (°F) 165.00
Heat Transfer Coefficientshi (Btu/hr-ft2-°R) 108.29
ho (Btu/hr-ft2-°R) 9.00
Mass Flow Rate of Watermc (lbm/s) 0.04
Overall Heat Transfer CoefficientUi (Btu/hr-ft2-°R) 8.31
Pressure DropsWater (psi) 0.03
Oil (psi) 10.12
Heat Transfer AreaAi (ft2) 18.71
Effectivenessε 0.55
Heat Exchanger Ratingq (Btu/s) 4.86
24
be removed for the oil to be cooled to 165°F (or below for that matter). Having such a steep
temperature gradient requires a greater pipe length. Lastly, if 4 lbm/min were the required flow
rate, the cost of the optimal system (oil in the annulus) would be only $2,168, a considerable
savings.
Another consideration for this project is to analyze the system as a shell and tube heat
exchanger. The properties used to compute the shell and tube analysis are taken from the
optimal case of the double pipe heat exchanger, where engine outlet temperature is 165°F. This
is a valid assumption, as using the higher outlet temperature will lower the amount of heat
transfer, and thus minimize the length of the heat exchanger. Performing a shell and tube
analysis yielded the following results; a shell of 171/4
” ID, with ¾” ID 13 BWG tubes, on a 1”
square pitch. Appendix C contains the spreadsheet used to calculate the analysis. This data
indicates that a shell and tube heat exchanger would be a more reasonable heat exchanger design
for this system if the customer were willing to have this configuration.
Having this data and the presented evaluation complete, a conclusion of the knowledge
gained is appropriate.
Conclusion
This project displays the fact that designing a heat exchanger is very dependent on the
flow rates used, as well as the necessary temperature difference that the exchanger must supply.
Furthermore, in selecting a certain type of heat exchanger, it is important to look at the given
parameters, as well as the requirements, and choose the most suitable system. The fact that a
shell and tube can handle these requirements, with a length of 8 feet is a lot more realistic than a
double pipe heat exchanger that is nearly 3,000 feet. Nevertheless, whether the calculated results
and the expected results differ or are synonymous, it is important to note the relationships
between the parameters. Such as; that mass flow rate and outlet temperature are inversely
related. That effectiveness and outlet temperature are inversely related. Effectiveness and length
are directly related and lastly, that length and exchanger coefficient have an inverse relationship
as well. Being able to obtain these relationships is the important part of any project and while
the resulted values, such as length of the system, are exuberant, the knowledge gained regarding
heat exchangers is immeasurable.
25
References
1) Design of Fluid Thermal Systems. 3rd ed. Stamford, CT: Cengage Learning, 2010. Print.
2) Metals Depot® - Buy Small Quantity Metal Online! Steel, Aluminum, Stainless, Brass.
Web. 03 May 2010. <http://www.metalsdepot.com/index.phtml?aident=>.
26
Appendix A: Detailed Calculations
(See Attached)
27
28
29
30
31
32
Appendix B: Excel Data Tables
Case 1:
Table B-1: Oil Outlet Temperature of 120°F
Dimensionsri (ft) 0.21
ro (ft) 0.23
Ri (ft) 0.33
L (ft) 17449.04
Temperatures UsedTc, in (°F) 55.00
Tc, out (°F) 180.00
Th, in (°F) 300.00
Th, out (°F) 120.00
Heat Transfer Coefficientshi (Btu/hr-ft2-°R) 0.61
ho (Btu/hr-ft2-°R) 87.85
Mass Flow Rate of Watermc (lbm/s) 3.06
Overall Heat Transfer CoefficientUi (Btu/hr-ft2-°R) 0.60
Pressure DropsWater (psi) 1.33
Oil (psi) 4.29
Heat Transfer AreaAi (ft2) 25413.52
Effectivenessε 0.73
Heat Exchanger Ratingq (Btu/s) 381.60
33
Table B-2: Oil Outlet Temperature of 129°F
Dimensionsri (ft) 0.33
ro (ft) 0.36
Ri (ft) 0.42
L (ft) 14712.92
Temperatures UsedTc, in (°F) 55.00
Tc, out (°F) 180.00
Th, in (°F) 300.00
Th, out (°F) 129.00
Heat Transfer Coefficientshi (Btu/hr-ft2-°R) 0.41
ho (Btu/hr-ft2-°R) 115.94
Mass Flow Rate of Watermc (lbm/s) 2.90
Overall Heat Transfer CoefficientUi (Btu/hr-ft2-°R) 0.41
Pressure DropsWater (psi) 2.78
Oil (psi) 0.58
Heat Transfer AreaAi (ft2) 33224.38
Effectivenessε 0.70
Heat Exchanger Ratingq (Btu/s) 362.52
34
Table B-3: Oil Outlet Temperature of 138°F
Dimensionsri (ft) 0.33
ro (ft) 0.36
Ri (ft) 0.42
L (ft) 12519.72
Temperatures UsedTc, in (°F) 55.00
Tc, out (°F) 180.00
Th, in (°F) 300.00
Th, out (°F) 138.00
Heat Transfer Coefficientshi (Btu/hr-ft2-°R) 0.44
ho (Btu/hr-ft2-°R) 111.04
Mass Flow Rate of Watermc (lbm/s) 2.75
Overall Heat Transfer CoefficientUi (Btu/hr-ft2-°R) 0.44
Pressure DropsWater (psi) 2.13
Oil (psi) 0.46
Heat Transfer AreaAi (ft2) 28271.74
Effectivenessε 0.66
Heat Exchanger Ratingq (Btu/s) 343.44
35
Table B-4: Oil Outlet Temperature of 147°F
Dimensionsri (ft) 0.25
ro (ft) 0.28
Ri (ft) 0.33
L (ft) 10927.17
Temperatures UsedTc, in (°F) 55.00
Tc, out (°F) 180.00
Th, in (°F) 300.00
Th, out (°F) 147.00
Heat Transfer Coefficientshi (Btu/hr-ft2-°R) 0.60
ho (Btu/hr-ft2-°R) 134.07
Mass Flow Rate of Watermc (lbm/s) 2.65
Overall Heat Transfer CoefficientUi (Btu/hr-ft2-°R) 0.60
Pressure DropsWater (psi) 3.05
Oil (psi) 1.12
Heat Transfer AreaAi (ft2) 18952.88
Effectivenessε 0.62
Heat Exchanger Ratingq (Btu/s) 330.48
36
Table B-5: Oil Outlet Temperature of 156°F
Dimensionsri (ft) 0.25
ro (ft) 0.28
Ri (ft) 0.33
L (ft) 9309.36
Temperatures UsedTc, in (°F) 55.00
Tc, out (°F) 180.00
Th, in (°F) 300.00
Th, out (°F) 156.00
Heat Transfer Coefficientshi (Btu/hr-ft2-°R) 0.63
ho (Btu/hr-ft2-°R) 127.72
Mass Flow Rate of Watermc (lbm/s) 2.49
Overall Heat Transfer CoefficientUi (Btu/hr-ft2-°R) 0.63
Pressure DropsWater (psi) 2.30
Oil (psi) 0.91
Heat Transfer AreaAi (ft2) 16146.83
Effectivenessε 0.59
Heat Exchanger Ratingq (Btu/s) 311.04
37
Table B-6: Oil Outlet Temperature of 165°F
Dimensionsri (ft) 0.25
ro (ft) 0.28
Ri (ft) 0.33
L (ft) 7914.30
Temperatures UsedTc, in (°F) 55.00
Tc, out (°F) 180.00
Th, in (°F) 300.00
Th, out (°F) 165.00
Heat Transfer Coefficientshi (Btu/hr-ft2-°R) 0.67
ho (Btu/hr-ft2-°R) 121.30
Mass Flow Rate of Watermc (lbm/s) 2.34
Overall Heat Transfer CoefficientUi (Btu/hr-ft2-°R) 0.67
Pressure DropsWater (psi) 1.72
Oil (psi) 0.72
Heat Transfer AreaAi (ft2) 13727.14
Effectivenessε 0.55
Heat Exchanger Ratingq (Btu/s) 291.60
38
Case 2:
Table B-7: Oil Outlet Temperature of 120°F
Dimensionsri (ft) 0.25
ro (ft) 0.28
Ri (ft) 0.42
L (ft) 22439.73
Temperatures UsedTc, in (°F) 55.00
Tc, out (°F) 180.00
Th, in (°F) 300.00
Th, out (°F) 120.00
Heat Transfer Coefficientshi (Btu/hr-ft2-°R) 72.85
ho (Btu/hr-ft2-°R) 0.40
Mass Flow Rate of Watermc (lbm/s) 3.06
Overall Heat Transfer CoefficientUi (Btu/hr-ft2-°R) 0.39
Pressure DropsWater (psi) 0.56
Oil (psi) 5.50
Heat Transfer AreaAi (ft2) 38921.11
Effectivenessε 0.73
Heat Exchanger Ratingq (Btu/s) 381.60
39
Table B-8: Oil Outlet Temperature of 129°F
Dimensionsri (ft) 0.25
ro (ft) 0.28
Ri (ft) 0.42
L (ft) 19041.11
Temperatures UsedTc, in (°F) 55.00
Tc, out (°F) 180.00
Th, in (°F) 300.00
Th, out (°F) 129.00
Heat Transfer Coefficientshi (Btu/hr-ft2-°R) 69.92
ho (Btu/hr-ft2-°R) 0.42
Mass Flow Rate of Watermc (lbm/s) 2.90
Overall Heat Transfer CoefficientUi (Btu/hr-ft2-°R) 0.42
Pressure DropsWater (psi) 0.43
Oil (psi) 4.67
Heat Transfer AreaAi (ft2) 33026.29
Effectivenessε 0.70
Heat Exchanger Ratingq (Btu/s) 362.52
40
Table B-9: Oil Outlet Temperature 138°F
Dimensionsri (ft) 0.25
ro (ft) 0.28
Ri (ft) 0.42
L (ft) 16190.07
Temperatures UsedTc, in (°F) 55.00
Tc, out (°F) 180.00
Th, in (°F) 300.00
Th, out (°F) 138.00
Heat Transfer Coefficientshi (Btu/hr-ft2-°R) 66.96
ho (Btu/hr-ft2-°R) 0.44
Mass Flow Rate of Watermc (lbm/s) 2.75
Overall Heat Transfer CoefficientUi (Btu/hr-ft2-°R) 0.44
Pressure DropsWater (psi) 0.33
Oil (psi) 3.71
Heat Transfer AreaAi (ft2) 28081.24
Effectivenessε 0.66
Heat Exchanger Ratingq (Btu/s) 343.44
41
Table B-10: Oil Outlet Temperature of 147°F
Dimensionsri (ft) 0.25
ro (ft) 0.28
Ri (ft) 0.42
L (ft) 14139.64
Temperatures UsedTc, in (°F) 55.00
Tc, out (°F) 180.00
Th, in (°F) 300.00
Th, out (°F) 147.00
Heat Transfer Coefficientshi (Btu/hr-ft2-°R) 64.93
ho (Btu/hr-ft2-°R) 0.46
Mass Flow Rate of Watermc (lbm/s) 2.65
Overall Heat Transfer CoefficientUi (Btu/hr-ft2-°R) 0.46
Pressure DropsWater (psi) 0.26
Oil (psi) 3.01
Heat Transfer AreaAi (ft2) 24524.83
Effectivenessε 0.62
Heat Exchanger Ratingq (Btu/s) 330.48
42
Table B-11: Oil Outlet Temperature of 156°F
Dimensionsri (ft) 0.33
ro (ft) 0.36
Ri (ft) 0.42
L (ft) 3422.72
Temperatures UsedTc, in (°F) 55.00
Tc, out (°F) 180.00
Th, in (°F) 300.00
Th, out (°F) 156.00
Heat Transfer Coefficientshi (Btu/hr-ft2-°R) 38.14
ho (Btu/hr-ft2-°R) 1.37
Mass Flow Rate of Watermc (lbm/s) 2.49
Overall Heat Transfer CoefficientUi (Btu/hr-ft2-°R) 1.32
Pressure DropsWater (psi) 0.01
Oil (psi) 8.93
Heat Transfer AreaAi (ft2) 7729.11
Effectivenessε 0.59
Heat Exchanger Ratingq (Btu/s) 311.04
43
Table B-12: Oil Outlet Temperature of 165°F
Dimensionsri (ft) 0.33
ro (ft) 0.36
Ri (ft) 0.42
L (ft) 2925.55
Temperatures UsedTc, in (°F) 55.00
Tc, out (°F) 180.00
Th, in (°F) 300.00
Th, out (°F) 165.00
Heat Transfer Coefficientshi (Btu/hr-ft2-°R) 36.22
ho (Btu/hr-ft2-°R) 1.44
Mass Flow Rate of Watermc (lbm/s) 2.34
Overall Heat Transfer CoefficientUi (Btu/hr-ft2-°R) 1.39
Pressure DropsWater (psi) 0.01
Oil (psi) 7.13
Heat Transfer AreaAi (ft2) 6606.41
Effectivenessε 0.55
Heat Exchanger Ratingq (Btu/s) 291.60
44
Appendix C: Shell and Tube Analysis
L 8
A. Fluid Properties
Oil: Evaluated at 233°F
mw (lb/s) 4.00 T1 (°F) 300
ρ (lbm/ft3) 52
Cp (Btu/lbm-
°R) 0.54
kf (Btu/hr-
ft-°R) 0.079 α (ft2/hr) 0.0028
nu (ft2/s) 0.000169 Pr 217
Water: Evaluated at 118°F
mc (lb/s) 2.34 t1 (°F) 55
ρ (lbm/ft3) 61.7
Cp (Btu/lbm-
°R) 0.9987
kf (Btu/hr-
ft-°R) 0.37 α (ft2/hr) 0.0059
4
nu (ft2/s) 6.11E-06 Pr 3.68
B. Tubing Sizes
IDt(ft) 0.0467 ODt (ft) 0.0625
Nt 124.0000 Np 2
C. Shell Data
Ds 1.4375
B 0.1450
Nb 7.0000
Pt 0.1667
C 0.1042
D. Flow Areas
At 0.1060
As 0.1303
45
E. Fluid Velocities
Vt 0.3570
Vs 0.5905
F. Shell Equivalent Diameter
De 0.5034
G. Reynolds Numbers
Ret 2726.639
6
Res 1758.788
8
H. Nusselt Numbers
Nut 21.7055
Nus 131.8226
I. Convection
46
Coefficients
hi 172.0934 ht 128.49636
87
ho 20.6879
J. Exchanger Coefficient
Uo 17.8191
K. Outlet Temperature
R 1.2500 Ao 194.77874
45
UoAo/mcC
pc 0.4133 S 0.46
t2 167.7000
T2 159.1250
L. Log Mean Temperature Difference
Counterflow:
LMTD 117.6508
M. Heat Balance
qw 304.2900
47
qc 262.9066
N. Overall Heat Balance for Exchanger
F 0.9300
q 105.4877
O. Fouling Factors and Design Coefficient
Rdi 0.0002 Rdo 0.001
U 17.46125
78
P. Area Required to Transfer Heat
Ao 198.7701
L 8.1639 (Ideal length as contaminates will
build up)
Q. Friction Factors
ft 0.0235
fs 0.4301
R. Pressure Drop Calculations
Δpt 0.0136
Δps 0.019206
Table C-1: Shell and Tube Analysis
48