turbine mannual

Upload: nogeshwar

Post on 03-Apr-2018

243 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 Turbine Mannual

    1/154

    JHARSUGUDA 9135MW CAPTIVE POWER PLANT PROJECT

    Client: SEPCO ELECTRIC POWER CONSTRUCTION CORPORATION

    No. 26-W9-YX-01 TURBINE OPERATION RULES (A) Total 151 Pages

    Operation Instruction

    SEPCOIII

  • 7/28/2019 Turbine Mannual

    2/154

    JSG CPP TURBINE OPERATION RULES

    CONTENTS

    PART 1 Overview

    Chapter 1 Specification of Main Equipment 5

    Chapter 2 Specification of Auxiliary Equipment

    14

    PART 2 Unit Start-up

    Chapter 1 Cold Start of the Unit .26

    Chapter 2 Warm & Hot Start of the Unit ...38

    PART 3 Unit Operation

    Chapter 1 Operating Parameters of Steam Turbine

    42

    Chapter 2 Operating Modes of the Unit ....47

    Chapter 3 Regular Works and Requirements ..49

    PART 4 Unit Shutdown

  • 7/28/2019 Turbine Mannual

    3/154

    JSG CPP TURBINE OPERATION RULES

    Chapter 15 Generator parallels off, while turbine does not trip ...77

    Chapter 16 Generator parallels off, and turbine trips 77Chapter 17 Turbine trips, while the generator does not parallel off 78

    Chapter 18 Failure of Thermodynamic Power Supply 78

    Chapter 19 High Bearing Temperature of Turbine-generator Unit 79

    Chapter 20 Burning out of Turbine-generator Bearing Bush .79

    Chapter 21 Steam Turbine Shaft Bending 80Chapter 22 Steam turbine Overspeed ..82

    Chapter 23 Feed water pump set outlet check valve is untight and rotates

    reversely.83

    Chapter 24 Turbine-generator unit operates at abnormal frequency

    83

    Chapter 25 Boiler Fire Extinction 84

    Chapter 26 Treatment of Accidents & Abnormity of the Motor ..85

    PART 6 Auxiliary Equipment & Common Service System

    Chapter 1 General Operating Rules of Auxiliary Equipment..

    89

  • 7/28/2019 Turbine Mannual

    4/154

    JSG CPP TURBINE OPERATION RULES

    Appendix 2: Cold Start Curve at Sliding Parameters

    .148Appendix 3: Warm & Hot Start Curve

    ..........149

    Appendix 4: Normal Shutdown Curve ....150

    Appendix 5: Shutdown Curve at Sliding Parameters151

  • 7/28/2019 Turbine Mannual

    5/154

    JSG CPP TURBINE OPERATION RULES

    Chapter 1 Specification of Main Equipment

    1.1 Specification of steam turbine equipment

    Model: N135-13.73/537/537

    Type: super-high pressure, primary reheating, double cylinder, double-flow, single shaft,

    extraction and condensing steam.

    Rated power: 135MW

    Initial steam pressure: 13.73Mpa (a)

    Initial steam temperature: 537

  • 7/28/2019 Turbine Mannual

    6/154

    JSG CPP TURBINE OPERATION RULES

    Rated speed: 3,000 rpm

    Feed water temperature under rated condition: 244.4Max back pressure at which the unit is permitted to operate: 18.6kpa (a)

    Regeneration stages: 2 HP heaters, 4 LP heaters & 1 deaerator

    Length of the last blade of LP cylinder: 690mm

    Critical speed of shafting: 1,950r/min for HP & MP rotor

    2,450r/min for LP rotor

    1,260r/min for generator rotorStages of flow path: total 39 stages:

    HP cylinder: 1 governing stage + 13 pressure stages

    MP cylinder: 13 pressure stages

    LP cylinder: 26 pressure stages

    1.3 Description of turbine characteristics

    1.3.1 This unit can carry the base load of power network, as well as can be used as two-shift or

    peak regulation unit.

    1.3.2 This units operating time at no load when rejecting load must not exceed 15 mins.

    1.3.3 This units operating time without steam must not exceed 1 min.

    1.3.4 This units idle time with full vacuum after trip is about 45 mins and that without vacuum is

    b t 15 i

  • 7/28/2019 Turbine Mannual

    7/154

    JSG CPP TURBINE OPERATION RULES

    pressure is 20.3kPa (a).

    1.3.9 The unit is permitted to run for long when the exhaust temperature of steam turbine is lessthan 79 . The max temperature at which exhaust is permitted to operate is 120 .

    1.3.10 Permitted load variation rate of unit is:

    1.3.10.1 From 100% to 50% MCR 5%/min

    1.3.10.2 From 50% to 20% MCR and from 20% to 50% MCR 3%/min

    1.3.10.3 Below 20%MCR 2%/min

    1.3.11 The pressure after the governing stage must not exceed 10.34Mpa (a) at different workingconditions.

    1.4 General description of steam turbine

    1.4.1 Brief introduction of steam turbine proper

    1.4.1.1 Steam turbine type is: super-high pressure, primary reheating, double-flow and single

    shaft arrangement, reaction extraction and condensing type, which characteristics include:

    combination of HP and IP cylinder, reverse arrangement of through-flow parts, inlets of initial

    steam and reheat steam centered on the middle part of HP & MP cylinder and radial diffusion

    double-flow type of LP cylinder.

    This units shafting is supported by three points: HP & MP rotor connected with LP rotor by rigid

    coupling while the LP rotor connected with the generator rotor by semi-flexible coupling,

    t t d d t t f d d b k d ith th th ti b i i

  • 7/28/2019 Turbine Mannual

    8/154

    JSG CPP TURBINE OPERATION RULES

    The turbine unit is 13.5 meters long in total and arranged on the 9m operation floor, with a

    combination of HP initial steam stop valve and HP governing valve mounted on both sides in the

    front which is supported on the holder of main stop valve, 4 flexible HP steam inlet pipes

    connected with the 4 governing valves and the HP cylinders upper and lower steam inletsrespectively, and governing valve controlled by oil servo-motor.

    The high pressure nozzle section consists of four groups of nozzle segments, with each group

    containing 29 nozzle steam paths and steam inlet flow of each group controlled by the

    corresponding governing valve. The unit can reach rated power by 3 valves opening fully and the

    fourth group provides guarantee for the availability of rated power in summer and at low

    parameters.

    HP & MP cylinder is single-floor cylinder with 1 governing stage and 13 pressure stages in the HP

    part. There is a section of steam extraction led to HP heater #1 after stage 10, and steam

    exhausted by HP flows through lower cylinders exhaust port and HP exhaust check valve to the

    reheater, a portion of which is led to HP heater #2 as regenerative extraction.

    The reheated steam flows to MP part via MP combined valve through two rigid steam inlet pipes.

    Th 13 t i MP t ith thi d t t ti t d t ft t 7

  • 7/28/2019 Turbine Mannual

    9/154

    JSG CPP TURBINE OPERATION RULES

    protect all bearings from damage.

    LP cylinder is equipped with atomizing nozzle type low-load spray regulator inside that mayoperate to spray automatically in the case where the LP cylinder exhaust temperature is higher

    than 80 so as to ensure normal operation of the unit.

    1.4.1.2Dummy piston & thermal shroud

    Dummy piston: Because this units HP & MP rotor blade adopts reaction blade which reaction

    degree is higher and rotor thrust is also great correspondingly, the rotor is processed into several

    dummy clubs for the use of balancing the thrust on the blade. HP & MP cylinder has three dummypistons in all, including the dummy piston on HP exhaust side, on HP steam admission side and

    on MP steam admission side. There are two 1334 pipes connecting between the dummy

    piston outside chamber on HP exhaust side and MP exhaust chamber, which allows the pressure

    on the exhaust side dummy piston outside and that on the MP exhaust side to be equal. At the

    same time, there are two 764 pipes connecting between the HP exhaust chamber and

    chamber between HP steam admission side dummy piston & MP steam admission side dumpy

    piston, through which HP steam is led to the chamber between HP & MP outer cylinder and MP

    thermal shroud to cool HP & MP outer cylinder.

    Thermal shroud: because high temperature steam flows into HP & MP cylinder directly, there is a

    thermal shroud mounted on the inner wall of MP part of HP & MP outer cylinder in order to

    prevent HP & MP outer cylinder from influence by high temperature steam. Reheat steam is led

    t th i id f th l h d d t i th h th d i t HP t

  • 7/28/2019 Turbine Mannual

    10/154

    JSG CPP TURBINE OPERATION RULES

    The sliding key system is the supporting and locating system of stator part, the steam turbine

    proper supporting and locating mode is: front frame, middle frame and rear frame and exhausthood frame are fastened on the foundation by means of foundation bolts and back grouting and

    are equipped with front bearing pedestal, middle bearing pedestal, rear bearing pedestal and LP

    outer cylinder thereon respectively. Longitudinal keys are arranged on the front frame along the

    center axis, the front bearing pedestal can move on its frame along the axis. HP & MP outer

    cylinder upper claws are supported on the front and middle bearing pedestal, the lower claws

    transverse keys connect with the front and middle bearing pedestal, besides longitudinal keys,there are also transverse keys on some position of the middle frame, and the cross point of

    longitudinal and transverse key is the dead point of HP & MP stator part, the front bearing

    pedestal HP and MP cylinder and middle bearing pedestal take this as the dead point to perform

    axial expansion and contraction. There is a vertical key mounted on both upside and downside of

    both ends of HP & MP outer cylinder with key way plate fixed on the neighboring bearing pedestal

    for the purpose of smooth expansion and contraction and keeping cylinder center aligning.

    1.4.1.5 Thrust bearing

    The unit adopts the Michell thrust bearing. The thrust collar integrates with steam turbine, and

    both its front and back sides are mounted with positive and negative thrust bearing pads with 12

    pieces laid on the whole circle of each. And each pad is equipped with a RTD temperature

    measuring device for measuring its metal temperature. The back of thrust bearing pad rests on

    ti l d ti l l i t th h i ti hi h i lf li t

  • 7/28/2019 Turbine Mannual

    11/154

    JSG CPP TURBINE OPERATION RULES

    The steam turbine proper shafting consists of HP & MP rotor and LP rotor. Connection between

    HP & MP rotor and LP rotor relies on the rigid coupling integrated with main shaft forging, and the

    shims in between two halves of coupling are connected with screws. As configured for the

    purpose of meeting the requirement of rotor center aligning in assembly, in such a case, the

    center on both ends of coupling must keep correct and concordant in assembly so as to allow the

    rotor center line to become smooth and continuous curve in operation. The rigid coupling is very

    sensitive to the bearing load distribution because of high rigidity, thus its requirements for the

    assembly technology and shafting aligning are much higher, but it has such advantages as highstrength, short rotor length, easy processing and reliable operation.

    Semiflexible coupling is used in between LP rotor and generator rotor, such coupling has a

    corrugated pipe joint on the end coupling connecting with generator rotor, which has certain

    flexibility, and connects with an minor axis on the other end coupling, and the minor axis covers

    the generator rotor to transmit the torque by means of interference and key, such semiflexible

    coupling may allow the unit safety operation not to be affected by slight change in the steam

    turbine and generator center in installation and operation.

    1.4.2 Technical specifications of governing system

    1.4.2.1 The governing system is able to keep idle running of steam turbine at rated steam inlet

    condition, rated vacuum and full open main stop valve, with speed oscillation value 6r/min.

    1.4.2.2 The governing system is able to guarantee stable parallel operation of steam turbine and

    th it

  • 7/28/2019 Turbine Mannual

    12/154

    JSG CPP TURBINE OPERATION RULES

    d. LP cylinder differential expansion reaches +7.5mm;

    e. Lubricating oil pressure is lower than 0.06Mpa;

    f. Back pressure of the condenser is lower than 20.3kPa;

    g. Peak to peak vibration amplitude of the rotor is 0.254mm;

    h. Metal temperature of # bearing 1-3 reaches 112, the metal temperature of bearing #4 and #5

    reaches 80 or the temperature of thrust bearing reaches 107;

    i. EH oil pressure decreases to 9.31Mpa;

    j. Power failure to DEH system;k. Exhaust temperature of LP cylinder reaches 121 ;

    l. The oil level of the main oil tank is lower than 1245mm;

    m. MFT of the boiler;

    n. Main protection of the generator operates.

    1.4.3.2.2 Oil injection test function

    1.4.3.2.3 Emergency governor test function

    1.4.3.2.4 Steam turbine reset function

    1.5 Heat calculation data of the steam turbine

    Name UnitRated

    conditions THATMCR VWO

    Cutting off all

    HP Heaters

    Generator end power kW 135,029 135,101 145,005 135,043

    T t l t i l t fl f t/h 407 502 410 107 440 000 368 560

  • 7/28/2019 Turbine Mannual

    13/154

    JSG CPP TURBINE OPERATION RULES

    Name UnitRated

    conditions THATMCR VWO

    Cutting off all

    HP Heaters

    No.3 extraction flow t/h 8.066 8.47 9.124 9.863

    No.4 extraction steam condition MPa/ 0.451/315.8 0.45/315.4 0.484/315.3 0.475/315

    No.4 extraction flow t/h 13.064 13.57 14.335 14.003

    No.5 extraction steam condition MPa/ 0.251/248.4 0.25/247.8 0.269/247.8 0.264/247.5

    No.5 extraction flow t/h 22.097 22.912 24.148 23.568

    No.6 extraction steam condition MPa 0.067 0.0665 0.0718 0.0705

    No.6 extraction flow t/h 15.801 16.335 17.153 16.775

    No.7 extraction steam condition MPa 0.0143 0.0142 0.0152 0.015

    No.7 extraction flow t/h 2.905 2.95 3.977 3.621

    Note: Turbine Heat Acceptance condition (THA): means the condition in which the unit can

    operate safely and continuously with generators net output power of 135MW when the turbine is

    under rated initial steam and reheat steam conditions, back pressure is 8.83kP, make-up water

    percentage is 0%, and regenerative system is put into operation all normally and generators

    efficiency is 98.35, which heat rate is not more than the acceptance value of 8,402.9kJ/kWh.

    Turbine maximum continue rate (TMCR): means the condition in which the unit can operate

    safely and output maximum power when the turbine is under rated initial steam and reheat steam

    conditions, back pressure is 8.83kP, make-up water percentage is 3%, and regenerative system

    is put into operation all normally and generators efficiency is 98.35.

  • 7/28/2019 Turbine Mannual

    14/154

    JSG CPP TURBINE OPERATION RULES

    Chapter 2 Specification of Auxiliary Equipment

    2.1 Specification of heater2.1.1 Specification of HP heater

    Item Unit HP heater #2 HP heater #1

    Model JG-530-2-00CK JG-530-1-00CK

    Design pressure of shell side Mpa 3.0 4.5

    D i t t f h ll id 350/250 390/260

  • 7/28/2019 Turbine Mannual

    15/154

    JSG CPP TURBINE OPERATION RULES

    Design temperature of tube

    side

    100 100 260 350

    Working pressure of tube side Mpa 1.724 1.724 1.724 1.724

    Working pressure of shell side Mpa 0.0152 0.07257 0.2693 0.454

    Working temperature of tube

    side 55 69.45 109.05 138.25

    Working temperature of shell

    side 55 90.63 129.9 150.6

    Manufacturer Shanghai Power Equipment Co., Ltd.

    2.1.3 Specification of deaerator and deaerated water tank

    2.1.3.1 Specification of deaerator

    Class Class I Test pressure 1.374MPa

    Model GC-514 Pressure drop of nozzle 0.0588MPa

    Design pressure 0.88Mpa (g) Opening pressure of safety valve 0.85MPa

    Design temperature 380 Operating modeSliding pressure

    operation

    Max working pressure 0.78Mpa (a)Corrosion allowance (tank

    /deaerator)1.6/2.5mm

    R t d t t 514t/h O t t f tl t t 7PPb

  • 7/28/2019 Turbine Mannual

    16/154

    JSG CPP TURBINE OPERATION RULES

    Inlet water pressure MPa 1.48 0.6837

    Outlet water pressure MPa 19.18 1.48

    Shaft power kW 2733.9 128.7

    Rotating speed r/min 4686 2982

    Working temperature 166.7 166.7

    Medium density kg/m3 900.59 900.59

    Intermediate bleed-off pressure (stage 2) MPa 8

    Intermediate bleed-off flow m3/h 35.5

    Guarantee efficiency % 81.32 80.84

    ManufacturerShanghai Power Equipment

    Maintenance Works Co., Ltd.

    2.2.2 Specification of feed-water pump motor

    2.2.2.1 Specification of feed-water pump motor

    Item Unit Specification

    Model YKOS3700-2

    Rated power kW 3,700

    Rated voltage V 6,600

    Rated current A 370

    Rated speed r/min 2,982

  • 7/28/2019 Turbine Mannual

    17/154

    JSG CPP TURBINE OPERATION RULES

    2.2.3.1 Parameters of hydraulic coupling

    Item Unit SpecificationModel R17K.2-E

    Motor speed r/min 2,986

    Output speed r/min 4,783

    Max output power kW 3,000

    Slip % 3

    Scope of speed governing % 25-100

    Efficiency % 94.7

    Capacity of oil tank m3 0.85

    Manufacturer Germany VOITH

    2.2.3.2 Auxiliary equipment of coupling

    Item Unit Auxiliary oil pumpWorking oil

    cooler

    Lubricating oil

    cooler

    Model CB-B125 LY54 LY16

    Oil flow m3/h 7.5 30 17

    Pressure MPa 0.25

    Cooling surface area m2 54 16

  • 7/28/2019 Turbine Mannual

    18/154

    JSG CPP TURBINE OPERATION RULES

    Inlet & outlet diameter mm 300

    Manufactured by Shanghai Power Equipment Research Institute

    2.3.3 Circulating water booster pump

    Specification of circulating water booster pumpSpecification of circulating water

    booster pump motor

    Model 10Sh-9A Model Y250M-4

    Shaft power 40 kW Voltage 415 V

    Lift 30 m Current A

    Rotating speed 1,480r/min Power 55 kW

    Flow 420 t/h Power factor

    Efficiency 80% Rotating speed 1,480 r/min

    Manufactured byShijiazhuang Kingda Pump

    Co, Ltd.Manufactured by Xian Motor Works

    2.3.4 Indoor circulating sump pit blowdown pump

    Specification of indoor circulating sump pit

    blowdown pump

    Specification of indoor circulating

    sump pit blowdown pump motor

    Model 40PV-SP Model Y112M-2

    Shaft power 3.1kW Voltage 415V

    Lift 15m Current A

    Rotating speed 1,800 rpm Power 4 kW

    Fl 25t/h P f t

  • 7/28/2019 Turbine Mannual

    19/154

    JSG CPP TURBINE OPERATION RULES

    diaphragm with fillet; the seal ring of LP diaphragm seal is mounted in the septalium and fixed

    with spring leaf.

    2.4.2 Shaft seal heater

    Item Unit Specification

    Model JQ-50-1

    Heating surface area m2 50

    Design flow of main

    condensate flowm3/h Total flow, 300 minimum

    Design pressure MPa Tube side 3.1, shell side 0.1

    Working pressure MPa Tube side 2.00

    Test pressure MPa Tube side 3.9, shell side 0.125

    Design temperature Tube side 100, shell side 100

    Working temperature Tube side 60, shell side 100

    Net weight t 2.23

    2.4.3 Shaft seal fan:

    Specification of shaft seal fan Specification of the motor

    Model AZY-09.32-020.0-01 Model 132S

    Full pressure 9.32kPa Power 7.5kW

    Speed 2,900r/min Speed 2,900r/min

    Fl 20 3/ i V lt 415V

  • 7/28/2019 Turbine Mannual

    20/154

    JSG CPP TURBINE OPERATION RULES

    Co., Ltd.

    2.5.2 Specification of condensate pump

    Specification of condensate pump Specification of the motor

    Model 7LDTNB-6PJS Model YLKK400-4

    Flow 350m3/h Power 280kW

    Lift 190m Voltage 6,600V

    Npsh 2.2m Current 31AShaft power 223kW Rotating speed 1,487r/min

    Rotating speed 1,487r/min Insulation class F

    Manufactured byShenyang Pump Co.,

    Ltd.Manufactured by

    Shenyang Electric

    Machine Works

    2.5.3Vacuum pump

    Specification of vacuum pumpSpecification of the

    motor

    Specification of

    vacuum pump cooler

    Model: 2BW4 253-0EK4 Model: Y315M-8 Model: M16

    Min. suction pressure (min. vacuum degree):

    3.3kpa (a)Voltage: 415V

    Heat exchange surface

    area: 9m2

    P i it 44k /h ( i l t C li t i l t

  • 7/28/2019 Turbine Mannual

    21/154

    JSG CPP TURBINE OPERATION RULES

    Efficiency: 61 Insulation class: F

    Manufactured by: Shanghai Hualian Pump Co.,Ltd.

    Manufactured by: Jiamusi Electric MachineWorks

    2.6 Specification of steam turbine lubricating oil system

    2.6.1 Main oil tank

    Dimension (lengthdiameter) 5,8103,020 mm

    Maximum volume 40 m3

    Working volume 24 m3

    Operating oil level 1,808mm

    Maximum oil level 2,616mm

    Minimum oil level 1,245mm

    Suction level of oil injector 1,045mm

    2.6.2 Oil coolerModel GX-64P

    Cooling surface area 240m2

    Working temperature Above 0

    Flow 80l/min

    Test pressure 21bar

    E t i ht 1 803k

  • 7/28/2019 Turbine Mannual

    22/154

    JSG CPP TURBINE OPERATION RULES

    Manufactured by: Shanghai HP Oil Pump WorksManufactured by: Shanghai WUYI Electric

    Company

    2.6.5 AC lubricating oil pump

    Specification of AC lubricating oil pump Specification of the motor

    Model: YS150-50B Model: YB180M-2

    Water head: 36m Power: 22kW

    Flow: 133m3/h Voltage: 415V

    Rotating speed: 2950r/min Current: 42.2A

    NPSH: 4.5m Insulation class: F

    Manufactured by: Shanghai Pump WorksManufactured by Shanghai Wuyi Electric

    Machine Works

    2.6.6 Starting-up oil pump

    Specification of starting oil pump Specification of the motor

    Model: 150Y-150A Model: Y315S-2

    Outlet oil temperature: 1.1 MPa Power: 110 kW

    Flow: 186m3/min Rotating speed: 2,982r/min

    Lif 130 V l 415V

  • 7/28/2019 Turbine Mannual

    23/154

    JSG CPP TURBINE OPERATION RULES

    Matched power: 3kW Current: 6.4A

    Rotating speed: 2,960 r/min Insulation class: B

    Manufactured by: Mudanjiang Aidi Electric Power

    Technology Co., Ltd.

    Manufactured by: Hebei Chengde

    Electric Machine Works

    2.6.9 Specification of the oil purifying equipment

    Model: HCP100 380 50 AS-SD

    Power: 3.0kW

    Voltage: 415V

    Max current: 8.2A

    Flow: 100l/min

    System working pressure:

  • 7/28/2019 Turbine Mannual

    24/154

    JSG CPP TURBINE OPERATION RULES

    Specification of EH oil pump Specification of the motor Specification of oil cooler

    Code: 029-09941-5 Model: Y200L-4 B35 Model: GL02

    Model: PV29 2R50 COO Power: 30kW Working pressure: 1.6MPa

    Outlet pressure: 13.7MPa Voltage: 415V Working temperature:

    100

    Setting value of overflow

    valve:16.2MPa

    Current: 56.8A Cooling surface area: 2.1m2

    Rotating speed: 1,470r/min Manufactured by: Shanghai

    Lubricating Equipment Plant

    Manufactured by Shanghai Wuyi

    Electric Machine Works

    2.9 Specification of rapid cooling device

    Item Unit Specification

    Model YQL- 150

    Rated air flow m3/min 40

    Voltage V 415

    Power kW 150

    Outlet temperature 400

  • 7/28/2019 Turbine Mannual

    25/154

    JSG CPP TURBINE OPERATION RULES

    The two-stage series connection bypass system is adopted, in which, the flow capacity of HP

    pass is considered as 70% of steam flow under VWO condition and the flow capacity of LP

    bypass is considered as the sum of HP bypass flow plus HP bypass attemperating water flow.

    2.11 Specification of air cylinder:

    Design pressure: 1.0 MPa

    Design temperature: 100

    Maximum working pressure: 0.98 MPaWorking temperature: normal temperature

    Working medium : air

    Test pressure: 1.25 MPa

    Volume: 1.0 m3

  • 7/28/2019 Turbine Mannual

    26/154

    JSG CPP TURBINE OPERATION RULES

    Chapter 1 Cold Start of the Unit1.1 General rules of start-up

    1.1.1 Division of the start-up state

    According to the inner wall temperature in lower half where HP inner cylinder governing stage is

    located, the start-up state of steam turbine is divided into:

  • 7/28/2019 Turbine Mannual

    27/154

    JSG CPP TURBINE OPERATION RULES

    pressure, bearing metal temperature, bearing return oil temperature, thrust bearing pad

    temperature, pressure and temperature of initial steam and reheat steam, vacuum of condenser,pressure switch of control system, metal temperature of main cylinders and etc.).

    9) Any safety protection or system fails or unit protection operating values are not in accordance

    with stipulation.

    10) Any one of the following equipment has fault or the corresponding interlock protection test is

    unqualified: starting oil pump, AC (DC) lubricating oil pump, jacking oil pump, turning gear, EH oil

    pump.

    11) The oil level of main oil tank and EH oil tank is lower than the limit value or the oil quality and

    cleanliness are unqualified. Lubricating oil inlet temperature is abnormal and return oil

    temperature is overhigh.

    12) Water seeps through the turbine.

    13) Quality of water and steam are not in accordance with requirements.

    14) Heat preservation of the unit is imperfect.

    15) Other auxiliary equipment or system fails in operation.

    1.2 Preparations for start-up

  • 7/28/2019 Turbine Mannual

    28/154

    JSG CPP TURBINE OPERATION RULES

    through test;

    14) Instrument and tools used in operation are to be prepared and checked;1.2.2 Tests prior to turbine start-up (after overhaul and minor repair of unit)

    1) Static test of turbine governing system;

    2) ETS test of turbine;

    3) Major interlock test of the unit;

    4) Interlock test of starting oil pump, AC lubricating oil pump and DC lubricating oil pump of

    turbine, and interlock test of jacking oil pump and exhaust fan of main oil tank;

    5) Interlock test of feed water pump;

    6) Interlock test of circulating water pump;

    7) Interlock test of vacuum pump;

    8) Interlock test of condensate water pump;

    9) Interlock test of EH oil pump;

    10) Protection test of HP& LP heater and deaerator;

    11) ON/OFF tests of all motor-operated valves, and pneumatical valves and hydraulic valves;

    12) Interlock test of HP & LP bypass devices;

    13) Interlock test of circulating water booster pump;

  • 7/28/2019 Turbine Mannual

    29/154

    JSG CPP TURBINE OPERATION RULES

    test. Maintain the oil temperature inside the system within the range of 43~54 .

    1.3.9 Put the jacking oil system into operation and put continuous turning of unit into operationafter the jacking oil pressure of all bearings is normal through checking. The unit shall be put into

    continuous turning operation for at least more than 4 hours prior to the turbine start-up.

    1.3.10 Put the inner cooling water system into operation and adjust the water inlet pressure of

    rotor and stator to be < 0.3Mpa.

    1.3.11 Put the generators air cooling system into operation.

    1.3.12 Start the vacuum pump to build up vacuum of condenser to 30kPa.

    1.3.13 After warming up of shaft seal pipe by water drain is normal, start the shaft seal fan to put

    the shaft seal system of turbine into operation. The LP cylinder shaft seal steam temperature

    shall be within the range of 121~177 . Inform the boiler staff to ignite the boiler when the

    vacuum of condenser reaches 70kPa.

    1.3.14 Ignite the boiler to increase temperature and pressure.

    1.3.15 Put the bypass system (first the LP bypass and then HP bypass) into operation after

    warming up the piping. Put the bypass automatic control into operation.

    1.3.16 Start the feed water pump according to the water level of steam drum. The water goes via

    bypass valve of the HP heaters. Adjust the water flow with feed water bypass (or conduct water

  • 7/28/2019 Turbine Mannual

    30/154

    JSG CPP TURBINE OPERATION RULES

    1.4.2 Check if the display of DEH panel is normal.

    1.4.3 Condition and preparation for unit impulsing1.4.3.1 Steam conditions of turbine cold impulsing:

    Initial steam pressure: 1.5~1.6Mpa;

    Initial steam temperature: 360 ;

    Reheat steam temperature: 300 (the temperature of the initial steam and reheat steam

    shall have the superheat degree of 50 at corresponding pressure);

    Temperature difference between initial steam side and reheat steam side

  • 7/28/2019 Turbine Mannual

    31/154

    JSG CPP TURBINE OPERATION RULES

    1.4.4.1 Put the Operator Auto on IN in Control Mode. Click the button MODE on the upper

    left side of the DEN OVERVIEW picture, then the sub-picture CONTROL MODE will appear.Click the button OA and click button IN within 3 seconds to put in the Operator Auto Mode.

    1.4.4.2 Reset the low pressure safety oil emergency governor on the head of turbine and check if

    the low pressure safety oil is normal;

    1.4.4.3 Click LATCH button of hand-controlled panel on control panel DEH MAN PANNEL to

    reset the unit. After turbine reset, check the indicator of governor TRIPPED that shall change

    into LATCHED reset indicator.

    1.4.4.4 Open the Limit Value picture to input valve limit value 120% and click button GO, check

    if the valve limit value is set normally and locally check if safety oil pressure is normal. Click the

    main stop valve opening button TVOPN on the control panel DEH MAN PANNEL, and locally

    check if HP & MP main stop valves are wide open and check if the HP & MP governing valves are

    closed after the picture displays that HP & MP main stop valve are wide open.

    1.4.4.5 Set the target speed at 500rpm and speed up rate at 50rpm/min on the set value sub-

    picture CTRL SP, press button GO, here the turbine starts to impulse and speed up, check the

    turbine speed that shall rise step by step.

    1.4.4.6 Check the turning gear that shall trip automatically to stop turning motor when the speed

  • 7/28/2019 Turbine Mannual

    32/154

    JSG CPP TURBINE OPERATION RULES

    Superheat degree of initial steam is 50.

    1.4.4.9 Continue to set the target speed at 2,500 r/min and speed up rate at 40rpm/min. Jackingoil pump A and B shall stop automatically when the speed reaches 1,500r/min, otherwise stop

    them manually;

    1.4.4.10 Time of turbine speed up and warming is distributed as follows:

    Rotating speed

    r/min

    Time (min) Temperature of HP

    stator lower carrier

    ( )

    Overall expansion

    of cylinder

    mm

    Vacuum of

    condenser

    Mpa (a)

    Speed up Stay

    Hold 300~500 10 4 60 1 0.0347

    From 500 to 2,500 50 4 130 3.5 0.0213

    From 2,500 to 2,96010

    2 Above 150 5~6Full

    vacuum

    Up to 3,000 to

    incorporate into

    network

    10

    / Above 150 5~6Full

    vacuum

    It requires about 90 min from impulsing to full speed.

    1.4.4.11 Make speed up to 2,500 r/min by the operating procedure above-mentioned and warm

    up the turbine for 4 min:

    a. Reinforce the checking and adjustment of all parts of the turbine during the whole speed-up

  • 7/28/2019 Turbine Mannual

    33/154

    JSG CPP TURBINE OPERATION RULES

    1.4.4.16 Check the main oil pump locally if its outlet oil pressure of is 1.18Mpa, inlet oil pressure

    is 0.098~0.3Mpa and operation is normal.1.4.4.17 Check if AC and DC lubricating oil pump interlock are on Auto position, after main oil

    pump operates normally through check, stop the starting oil pump and confirm the starting oil

    pump interlock is on Auto position.

    1.4.4.18 Check if lubricating oil pressure, EH oil pressure and temperature are normal.

    1.5 Unit incorporation into power network & initial load on

    1.5.1 Generator synchronous paralleling

    Hold the speed of unit at 3000rpm and perform an overall check, if everything is normal, advise

    the electric personnel to parallel in the generator. After the electric test ends and the automatic

    synchronization conditions are fulfilled (with speed at 2950~3050rpm) and upon receiving the

    signal ASPERM from electric personnel, press the button MODE on the upper left of DEH

    control picture, then MODE sub-picture will appear, press the button and click button IN within 3

    seconds to put AUTOSYNCHRONIZATION control mode into operation, the main picture will

    display enter the mode AS at the same time.

    1.5.2 Checking after generator paralleling in and precautions in load on

    1) After paralleling in, the generator is to have 5% active load and to a certain amount of inactive

  • 7/28/2019 Turbine Mannual

    34/154

    JSG CPP TURBINE OPERATION RULES

    1.6.1 After warming up with initial load ends, check if the turbine cylinder expansion is normal

    without jamming;1.6.2 Put the governing stage pressure circuit into operation as the case may require in the

    process of load up;

    1.6.3 Make the load up to 13.5MW (10% of rated load) by means of valve position at a load up

    rate of 0.6MW/min.

    1.6.4 Check if the auto operation of bypass system is normal, bypass valves close gradually with

    rise of unit parameters.

    1.6.5 When the load is up to 13.5MW (10% of rated load), steam pressure to 2.0~3.5 Mpa, initial

    steam temperature to 450, reheat steam temperature to 400 and the temperature of HP

    stator lower carrier to 390, check if the drain valve at upstream of MP combined valve closed

    automatically, if not, close it manually.

    1.6.6 When the load reaches 27MW (20% of rated load), check if the water spray device closed

    automatically according to LP cylinder exhaust temperature, if not, close it manually. It may put

    the unit power control circuit into operation at this time.

    1.6.7 When the load reaches 27MW (20% rated load):

    A. Check if the initial steam pressure is 4~5 Mpa, temperature is 470 and reheat steam

  • 7/28/2019 Turbine Mannual

    35/154

    JSG CPP TURBINE OPERATION RULES

    according to the water level of LP heater, close water drain of LP heater to drain valve of

    condenser, and put the auto control of drain into operation when the water level is adjusted to benormal.

    1.6.13 When the load reaches 121.5MW (90% of rated load), steam conditions shall be up to

    nominal parameters in which initial steam pressure is 13.73Mpa, initial and reheat steam

    temperature are 537 :

    1.6.13.1 From warming up with initial load to 90% of rated load, the time of steam conditions

    reaching the ratings shall be controlled at 120 min;

    1.6.13.2 Put the Initial Steam Pressure Control into operation on the DEH panel as the case

    may require after initial steam pressure reaches the rating;

    1.6.14 Change the control mode of valves from Single Valve Control to Sequence Valve

    Control after the unit load reaches over 50MW, and pay attention to the change in load in

    changeover.

    1.6.15 Continue to make load up until 135MW, perform an overall check and report the check

    results to the unit supervisor.

    1.7 Precautions in unit start-up

  • 7/28/2019 Turbine Mannual

    36/154

  • 7/28/2019 Turbine Mannual

    37/154

    JSG CPP TURBINE OPERATION RULES

    unit speed up so as not to affect the rotating speed. After the unit paralleling in, check if the

    automatic control of bypass is normal and pay attention to that the tracking of attemperating

    water shall be normal; the adjustment of the opening extent of HP & LP bypass shall be based on

    the need of boiler to prevent too acute oscillation of MP governing valve as a result of too high

    steam pressure of boil side and too large opening of bypass, at the same time pay attention to

    the pressure difference before and after HP exhaust steam check valve to prevent it from being

    closed and causing chocking.

    1.7.17 Strictly monitor the water level of HP & LP heater, deaerator and condenser in the process

    of start-up.

    1.7.18 Temperature rise & decrease rate

    Name Temperature rise rateTemperature

    decrease rate

    Temperature of initial steam

  • 7/28/2019 Turbine Mannual

    38/154

    JSG CPP TURBINE OPERATION RULES

    Chapter 2 Warm & Hot Start of the Unit

  • 7/28/2019 Turbine Mannual

    39/154

    JSG CPP TURBINE OPERATION RULES

    down, so it is inappropriate to maintain the vacuum of condenser and initial steam pressure too

    high.

    4) In the case where there is excess pressure in boiler, the extraction system must be put into

    operation to set up the vacuum of condenser prior to boiler ignition so as to prevent the exhaust

    rupture disk of LP cylinder from operating.

    2.2 Boiler ignition

    2.2.1 The start-up procedure of boiler follows that of Cold start and temperature & pressure rise

    follows the Hot Start Curve of turbine.

    2.2.2 For hot start, pay attention to maintaining the parameters stable as up to impulsing

    parameters.

    2.3 Impulsing speed up of turbine

    2.3.1 Preparations prior to turbine impulsing

    2.3.1.1 Keep continuous turning time more than 4 hours prior to impulsing with the shaft

    eccentricity of less than 0.076mm.

    2.3.1.2 Feed water pump shall be in good standby condition.

    2.3.1.3 Drain water to warm up pipe sufficiently prior to supplying steam to shaft seal, it is strictly

  • 7/28/2019 Turbine Mannual

    40/154

    JSG CPP TURBINE OPERATION RULES

    Max speed in

    speed up (r/min)

    100

    450

    Must not be more

    than 500

    2.3.3 Impulsing speed up of turbine:

    2.3.3.1 Checking and tripping operation of DEH panel are the same with that of Cold Start;

    2.3.3.2 Fix the impulsing time and speed up rate according to cylinder temperature;

    2.3.3.3 Other operations and checking in the process of turbine speed up are the same with that

    of Cold Start.

    2.3.3.4 Because HP automatic main stop valve, speed governing valve, MP combined valve and

    steam lead pipe, etc. parts can cool quickly after shutdown, pay attention to the temperature rise

    rate of them in start-up to prevent excessive heating and pay attention to the vibration of unit.

    2.4 Unit paralleling in & load on

    2.4.1 Operator Auto mode:

    2.4.1.1 Make load up to the rated value according to the load variation rate looked up in the Hot

    Start Curve;

    2.4.1.2 Other operations in the process of unit load up are the same with that of Cold Start.

  • 7/28/2019 Turbine Mannual

    41/154

    JSG CPP TURBINE OPERATION RULES

    2.5.6 Make the unit have initial load according to cylinder temperature as soon as possible after

    paralleling in;

    2.5.7 Reinforce water drain of the initial steam pipe and turbine proper in hot start to prevent cold

    water or steam from flowing into the cylinder in impulsing.

    2.5.8 In hot start, prevent overhigh HP cylinder exhaust temperature to parallel in quickly as up to

    the rated speed. If necessary, open wider the low pressure bypass to lower the reheat steam

    pressure and control the HP cylinder exhaust temperature to be lower than 360 .

  • 7/28/2019 Turbine Mannual

    42/154

    JSG CPP TURBINE OPERATION RULES

  • 7/28/2019 Turbine Mannual

    43/154

    JSG CPP TURBINE OPERATION RULES

    between two sides of initial

    steam and reheat steam

    HP cylinder exhaust

    pressureMPa 2.531 3.0

    HP cylinder exhaust

    temperature 312.1 321.6

    LP cylinder exhaust

    pressure

    kPa 8.83 20.3

    LP cylinder exhaust

    temperature

  • 7/28/2019 Turbine Mannual

    44/154

    JSG CPP TURBINE OPERATION RULES

    Note: motor vibration of all auxiliary equipment

    It is qualified if bearing pad vibration is < 0.085mm for rotating speed at below 1,500r/min;

    It is qualified if bearing pad vibration is < 0.05mm for rotating speed at below 3,000r/min.

    1.6 Operating parameters of deaerator

    Name Unit ItemOperating

    valueOperating result

    Water level

    of deaeratormm

    Normal value 2,550

    High value I 2,750 Alarm

    High value II 2,850Interlock open the motor-operated overflow

    valve of deaerator

    High value III 2,950

    Interlock close the steam extraction No.3

    motor-operated valve and check valve

    interlocking, interlock close the motor-

    operated overflow valve of the deaerator

    when the water level decreases to below

    2,750mm;

    Low value I 2,350 Alarm

    Low value II 680 Feed water pump trip

    Pressure of

    deaeratorMPa

    Normal 0.68 Operate at sliding pressure

    Low pressure 0.3 Alarm for low pressure

    High pressure 0.85 Safety valve operate

  • 7/28/2019 Turbine Mannual

    45/154

    JSG CPP TURBINE OPERATION RULES

    Name Unit Normal Max Mini Remarks

    journal bearing #4-5

    Metal temperature of

    thrust bearing

  • 7/28/2019 Turbine Mannual

    46/154

  • 7/28/2019 Turbine Mannual

    47/154

  • 7/28/2019 Turbine Mannual

    48/154

  • 7/28/2019 Turbine Mannual

    49/154

  • 7/28/2019 Turbine Mannual

    50/154

  • 7/28/2019 Turbine Mannual

    51/154

    JSG CPP TURBINE OPERATION RULES

    Att. List of Equipment Regular Works

    No. Work contents Time requirement Operator Supervisor

    1Test of emergency sound &

    thermodynamic signalPer shift

    Vice operator

    on duty

    Operator

    on duty

    2 Check of the oil level gauge of oil tankDaytime shift per

    day

    Vice operator

    on duty

    3Moving test of HP & MP main stop

    valve

    Daytime shift on

    Monday

    Operator on

    duty

    Unit

    supervisor

    4 Moving test of extraction check valves Daytime shift on

    Monday

    Operator on

    duty

    Unit

    supervisor

    5Water drain of main oil tank and feed

    water pump oil tank

    Daytime shift on

    Thursday

    Routine

    inspector

    6 Vacuum leak testDaytime shift on the

    5th per month

    Operator on

    duty

    Unit

    supervisor

    7 Switching of vacuum pump Daytime shift on the10th per month

    Vice operatoron duty

    Operatoron duty

    8Switching of LP heater drain water

    pump

    Daytime shift on the

    10th of per month

    Vice operator

    on duty

    Operator

    on duty

    9 Switching of industrial water pumpDaytime shift on the

    10th per month

    Routine

    inspector

    Operator

    on duty

    Daytime shift on the Vice operator Operator

  • 7/28/2019 Turbine Mannual

    52/154

    JSG CPP TURBINE OPERATION RULES

    PART 4 Unit Shutdown

  • 7/28/2019 Turbine Mannual

    53/154

    JSG CPP TURBINE OPERATION RULES

    1.1 Preparations prior to unit shutdown

    1.1.1 After receiving shutdown command from the unit supervisor, contact all posts to make

    preparations for shutdown;

    1.1.2 Do starting test of AC and DC lubricating oil pump, jacking oil pump and starting oil pump of

    turbine and they are normal through test, and do starting test of the steam turbine turning gear

    motor and it is normal through test;

    1.1.3 Switch the auxiliary steam supply to be supplied by neighboring turbine (or supplied by

    starting boiler);

    1.1.4 Check the unit thoroughly and count detects of equipment.

    1.2 Normal shutdown

    1.2.1 Confirm DEH is in Operator Auto mode; confirm lower limit of initial steam pressure is

    released.

    1.2.2 Open the sub-picture of set value control on the main control picture of DEH to set the

    target load at 110MW, and set the load down rate at 1.25MW//min by turning down the governing

    valve in the condition of holding steam temperature and pressure, then press the button GO to

    make the unit load start to decrease. At the same time, the main operator shall decrease the

    temperature and pressure according to normal shutdown curve.

  • 7/28/2019 Turbine Mannual

    54/154

    JSG CPP TURBINE OPERATION RULES

    GO button, the unit load continues to decrease.

    1.2.7 When the differential pressure between HP heater #2 steam side and deaerator is 0.06Mpa, switch it to the cleaning side. The lubricating oil shall

    keep on circulating until the strainer of filter is clean;

    8.2.2.6 Check if the water level of the deaerator is normal, the temperature is > 50C, the feed

    water pump has a temperature difference between its upper and bottom pump body is lower than

    20C;

    8.2.2.7 The sealing water system works normally and loop is smooth; Check if the pressure after

    the sealing water governing valve is the ring is 0.05~0.1Mpa higher than the unloading water

    pressure;

    8.2.2.8 Check if all transmission contacts of hydraulic coupling speed governing mechanism are

    firm transmitting reliably, and the handle is flexible, after it is normal through hand operation, set

    the scoop tube at 0 position;

    8.2.2.9 Power on the feed water pump motor after it is qualified through insulation test and it is

    permitted to close the switch;

    8 2 2 10 Cl th t di h l f th f d t b d

    JSG CPP TURBINE OPERATION RULES

  • 7/28/2019 Turbine Mannual

    122/154

    8.3 Start-up of feed water pump set

    8.3.1 All equipment of t feed water pump set and valves of pipe are checked and verified as

    normal;

    8.3.2 Confirm the inlet valve of booster pump is fully opened and the water discharge valve has

    been closed;

    8.3.3 Verify the feed water pump motor-operated outlet valve and the center tap valve is closed,

    the recirculation valve of feed water pump is opened;

    8.3.4 Verify the scoop tube of the hydraulic coupling is in the maximum position;

    8.3.5 Verify when the auxiliary oil pump is working, the lubricating oil pressure is more than

    017Mpa;

    8.3.6 Click the Start button of feed water pump and record the constant speeds time; if no-load

    current is normal, then start the feed water outlet electric value;

    8.3.7 After feed water pump starting, check the sound and vibration, etc. of the feed water pump

    and booster pump that are normal;

    8.3.8 When the lubricating oil header pressure is > 0.22MPa, the auxiliary oil pump shall stop

    automatically;

    8.3.9 Put the oil-cooler of motor into operation;

    8 3 10 P t th il l d l b i ti il l i t ti di t th il t t

  • 7/28/2019 Turbine Mannual

    123/154

    JSG CPP TURBINE OPERATION RULES

  • 7/28/2019 Turbine Mannual

    124/154

    8.5.1 Put the HP protective water source into operation;

    8.5.2 Verify the inlet and outlet four-way value of HP heater are closed, feed water runs along the

    bypass, the water filler valve is closed tightly and open the steam discharge valve on the water

    side of HP heater;

    8.5.3 Open the primary and secondary oil filler valve of HP heater to fill HP heater with water,

    after there is water overflowing the air valve, close the air release valve on the water side of HP

    heater, after the internal pressure of HP heater becomes equal to the feed water pressure, check

    the HP heater four-way valve that shall open automatically, close the water filler valve, check that

    there is no water level on the steam side of HP heater and verify no leak in HP heater;

    8.5.5 Open the drain valves before and after the steam extraction section 1 and 2 check valve to

    warm up the pipe;

    8.5.6 Open the water discharge valve at the bottom of HP heater1 & 2 HP heater, as well as the

    air release valve on the top;

    8.5.7 Open the check valves of steam extraction section 1 and 2;

    8.5.8 Open the air inlet motor-operated valves of HP heater 1 & 2, maintain the HP heater

    pressure within 0.05~0.1Mpa for warming, after there is steam coming from the air valve of HP

    heater, close the air release valve of HP heater, and close the drain valves before and after the

    t t ti ti 1 d 2 h k l

  • 7/28/2019 Turbine Mannual

    125/154

  • 7/28/2019 Turbine Mannual

    126/154

    JSG CPP TURBINE OPERATION RULES

  • 7/28/2019 Turbine Mannual

    127/154

    deaerator. It may open the heating & steam inlet at the bottom if necessary to adjust the oxygen

    content to qualified;

    d. Check the indication of the pressure gauge, thermometer and water level gauge of deaerator

    on schedule, if any abnormality, it shall report for treatment in time;

    e. If the water level decreases because of improper adjustment of water level or the condensate

    pumps insufficient output, it shall take some measures to make up water timely. But pay attention

    to that: Dont hurry, it may affect the pressure of deaerator and cause vibration. It may lower the

    unit load if necessary;

    f. If the water level still keeps on decreasing measures, it report to the unit supervisor. If

    emergency water level occurs to affect normal operation of feed water pump and cause fault

    hereof, it shall lower the load to shut down the unit;

    g. Check the running condition of the safety valve of deaerator in operation regularly, when

    deaerator is overpressed, pop the safety valve in order to ensure normal operation of deaerator.

    8.10.2 Check & maintenance of feed water pump

    a. Check if the feed water pump set has any friction and leak, vibration is normal and no

    abnormal sound.

    b. The oil level of oil tank and bearing is normal and the auxiliary oil pump is in good and standby

    t t

    JSG CPP TURBINE OPERATION RULES

  • 7/28/2019 Turbine Mannual

    128/154

    safety;

    b. Water lever of HP heater rises, treatment takes no effect and water level gauge is on the

    utmost;

    c. When water level gauge burst and can not keep on working;

    d. The HP heater proper leaks seriously and cannot keep on working.

    8.11.1.2 Treatment of t HP heater overfeed with water

    Phenomenon:

    a. Alarm for high water level of HP heater;

    b. Protection may operate;

    c. The HP heater outlet water temperature is low, and the heater vibrates.

    Treatment:

    a. When HP heater water level is high, check if the HP heater drain system operates normally,

    when the drain governing valve is jammed, it shall open the emergency drain valve to lower the

    water level, and contact with the maintenance personnel for treatment;

    b. The running HP heater leaks and the water level rises to 850mm/1,125mm (HP heater1/ HP

    heater2) sharply, the water level high value I alarm is raised;

    c. If the HP heater water level rises to 1,000mm /1,275mm (HP heater1/ HP heater2), the

    t l l hi h l II l i i d t d i l t ti ll

  • 7/28/2019 Turbine Mannual

    129/154

  • 7/28/2019 Turbine Mannual

    130/154

    JSG CPP TURBINE OPERATION RULES

  • 7/28/2019 Turbine Mannual

    131/154

    e. Record the idle time and vibration value of the faulted pump;

    f. Complete other operations of pump stop, and take necessary safety measures as the fault may

    be;

    g. Report to the unit supervisor if there is no standby pump to shut down the unit for emergency.

    8.11.3.4 Tripping off of feed water pump

    Phenomenon:

    a. The service pumps current reaches 0, the pump stops, emergency alarm is raised and feed

    water pressure swings or decreases;

    b. The standby pump interlock starts.

    Cause:

    a. Fault in the 6.6 KV busbar;

    b. Protections of feed water pump and motor operate or are operated by mistake;

    c. Misoperation made by man;

    d. The emergency button is pressed by mistake.

    Treatment:

    a. Check and close the outlet motor-operated valve and center tap valve of the tripped-off pump,

    check the auxiliary oil pump of the tripped-off pump that shall interlock to stop automatically;

    b If th t db d t t t t t it i di t l if t db th t db

    JSG CPP TURBINE OPERATION RULES

  • 7/28/2019 Turbine Mannual

    132/154

    operating, for which the operation and treatment are not timely;

    d. The inlet valve of booster pump is closed by mistake in operation.

    Treatment:

    a. Treat as per the requirements of emergency stop of pump;

    b. Find out the causes for vaporization in feed water pump, and eliminate the abnormity;

    c. If the vaporization is caused by inlet strainers of booster pump and feed water pump being

    blocked, it shall start the standby pump immediately;

    d. Only when the inlet pressure and deaerator pressure and water level become normal can it

    restart the pump or put the standby into operation.

    8.11.3.6 Feed water pressure decrease

    Cause:

    a. Fault in the hydraulic coupling or the scoop tube is jammed;

    b. Water quantity used by the boiler increases greatly suddenly;

    c. Water pipe breaks or HP heater leaks seriously;

    d. The outlet check valve of standby pump is not closed tightly and the pump reverses;

    e. The system valve is operated by mistake;

    f. The service feed water pump is vaporized;

    Wh th f d t fl i 280t/h th i l ti l f i f d t i t

    JSG CPP TURBINE OPERATION RULES

  • 7/28/2019 Turbine Mannual

    133/154

    b. The feed water pump operates at a certain speed, which cant satisfy the requirement of the

    boiler or the rotating speed decreases.

    Treatment:

    a. Move the scoop tube locally to make it return to normal;

    b. If moving the scoop tube locally is useless, it shall stop the faulted pump and start the standby

    pump in time;

    c. Contact the maintenance personnel, it must not restart or put the standby into operation until

    eliminating the defect.

    Chapter 9 DEH System

    9.1 General statement of DEH system

    DEH-steam turbine digital electric hydraulic control system adopts the I/A hardware manufactured

    by FOXBORO company and uses HP fire resistant oil as its hydraulic pressure part, and the

    governing valve is directly controlled by DEC with electro-hydraulic converter.

    9.2 Structure of DEH System

    With the operation of OPC solenoid valve and OPC oil way, HP oil system can realize overspeed

    t ti d ith th ti f di h l d f t il i t f it li l

    JSG CPP TURBINE OPERATION RULES

  • 7/28/2019 Turbine Mannual

    134/154

    Steam turbine in the state of tripping;

    Starting oil pump and EH oil pump operate normally and oil pressure is normal;

    Manual shutdown is on the Reset position;

    9.5 DEH Control and Operation

    9.5.1 Automatic control mode (OA)

    Operator can perform reset by clicking the button Reset on manual operation panel, and after

    steam turbine is reset, main control panel will display Latched.

    Click button control mode on top left of main control panel, and then sub picture of control mode

    will pop up, here can select a control mode for application. Click the button OPERATOR AUTO,

    afterwards click button Put-in within 3S, then auto control mode (OA) is put in, meanwhile, main

    panel displays equipment being in OPERATOR AUTO mode.

    Operator click the button Limit Value on lower left of main control panel to pop up the sub

    window, then input valve position limit value, thereupon valve position limit will rising ceaselessly

    up to valve position limit value.

    Click button Control Set Value to pop up sub picture, input the target speed (0~3,000rpm/min)

    into target value bar and the speed (0~500rpm/min) in Speed bar, afterwards click buttons

    ENTER d GO th th t l ill i t t t t ti d di t th t

  • 7/28/2019 Turbine Mannual

    135/154

    JSG CPP TURBINE OPERATION RULES

  • 7/28/2019 Turbine Mannual

    136/154

    limit, afterwards click button Put-in within 3S, and then control will enter to TPL mode,

    meanwhile the main panel will display the main steam pressure limit is IN

    In the case of TPL mode, as initial steam pressure being lower than 90% rated pressure, load set

    value will decrease at a fixed rate. Shut down the control valve hydraulic servomotor can

    compensate the decrease of main steam, thus avoid initial steam pressure decrease being to

    large.

    TPL mode also can be cleared on limit at sub picture: click the button initial steam pressure

    restriction, afterwards click button Clear within 3S, and then control will disengage from TPL

    mode.

    9.5.6 Remote control initial steam pressure limit (RTPL)

    In OA operation, and the initial steam pressure is larger than 90% rated pressure, operator can

    select the RTPL (Remote control initial steam pressure limit) mode: operator shall press the limit

    value on lower left of the main control panel to pop up the sub picture, then click button Remote

    control initial steam pressure limit, afterwards click button Put-in within 3S, and then control will

    enter the RTPL mode, meanwhile, the main panel will display the Remote control initial steam

    pressure limit being IN

    In RTPL mode, and the initial steam pressure is lower than 90% rated pressure, load set value

    ill d t fi d t Sh t d th t l l h d li t t

    JSG CPP TURBINE OPERATION RULES

  • 7/28/2019 Turbine Mannual

    137/154

    click button GO, here valve limit value will enter the DEH control logic. In case of valve position

    limit mode, valve command will not exceed the valve position limit value.

    9.5.9 Single valve/ sequence valve (SIG/SEQ) mode

    In case of OA operation, operator also can select SIGLE (single valve) or SEQ (sequence valve)

    operation mode: click the button valve mode on milled lower part of main control panel to pop

    up he side picture, click single valve (or sequence valve) and the two switching buttons (press

    switching button within 3S after clicking single valve button, and it will be effective if the two

    buttons being red synchronously.

    In SIGLE mode, command of all the control valves is the same and all the control valves take part

    in control synchronously; in SEQ mode, four control valves will operate one after another

    according to a certain sequence. The switching time between two modes is about 3S so as to

    guarantee no disturbance of load in the whole switching process.

    9.5.10 OPC mode (OPC MODE)

    Moreover, there is OPC (overspeed protection control) function set in DEH, in case load of steam

    turbine is over 30%, and main oil switch of motor trips, at that time, with the function of solenoid

    valve, all the hydraulic servomotors of control valve will control oil pressure to unload, thereby

    closing all hydraulic servomotors of governing steams. With the quick close of hydraulic

    t t ti d l ti ill b t i d d if t t bi t ti d i

    JSG CPP TURBINE OPERATION RULES

  • 7/28/2019 Turbine Mannual

    138/154

    In TM mode, OPC function remains, once OPC operate, it still will close all steam governing

    valves.

    9.6 Stimulation Test of DEH

    DEH has a built-in simulator that can perform closed-loop simulation test to DEH when the

    turbine is in the state of rest.

    It can stimulate control signals such as latching, synchronization, paralleling in and remote control

    signal, etc. to carry static test to verify the signals or functions and ensure the smoothness of

    impulsing.

    Attention: this test can only be done by related personnel during outage and is forbidden in

    normal operation of turbine. After the test is finished, all the original parameter must be restored,

    otherwise a serious result may be caused; it is recommended to do this test in the engineer

    station.

    Chapter 10 Bypass System

    10.1 Function of bypass system

    10.1.1 Because of improving cold, warm and hot start conditions of unit that greatly reduces the

    unit start-up time and makes unit operate with full load in advance, the bypass system is suitable

    f th it HP li d i l i HP & MP &LP li d bi d t t

  • 7/28/2019 Turbine Mannual

    139/154

    JSG CPP TURBINE OPERATION RULES

  • 7/28/2019 Turbine Mannual

    140/154

    Chapter 11 Turbine Proper Water Drain System

    11.1 In order not to let the drain flow inversely, all drains are connected and arranged on the drain

    JSG CPP TURBINE OPERATION RULES

  • 7/28/2019 Turbine Mannual

    141/154

    11.3 The turbine proper part includes the following drains:

    11.3.1 Drain of cold and hot section of the initial and reheat steam pipes;

    11.3.2 Drain of HP air duct;

    11.3.3 Drain of MP air duct;

    11.3.4 Drain of HP cylinder jacket;

    11.3.5 Drain of valve level steam leakage;

    11.3.6 Drain before and after HP exhaust check valve and extraction check valve.

    Chapter 12 Quick Cooling System of Steam Turbine

    12 1 P ti i t ti

    JSG CPP TURBINE OPERATION RULES

  • 7/28/2019 Turbine Mannual

    142/154

    12.1.9 Verify the air compressor and service air system are put into operation and operating

    normally.

    12.1.10 The manhole on the steam side of condenser steam side is opened. Check if the drain

    valve before HP exhaust check valve is opened.

    12.1.11 Only when the cylinder temperature decreases to below 350, it can put the quick

    cooling equipment into operation.

    12.2 Monitoring of parameters in quick cooling process:

    In order to ensure the mental temperature inside the turbine can decrease evenly in the processof quick-cooling after turbine shutdown so as to prevent overstress due to excessive cooling,

    rotor from bending and cylinder and welded junction from deforming, it must strictly monitor the

    changes in each point temperature, temperature difference between cylinder inner and outer wall,

    temperature difference between upper and lower cylinder, absolute expansion, differential

    expansion, axial deflection, rotor eccentricity, turning gear current, compressed air temperature

    and flow and electric heater current in the process of putting the quick cooling equipment of

    turbine into operation. The monitor control index of main parameters includes:

    12.2.1 First stage metal temperature decreasing rate of HP cylinder is

  • 7/28/2019 Turbine Mannual

    143/154

    rise again obviously, it may end the forced ventilation. Close the air inlet valve and keep on

    turning for 30min to see if the temperature of all points rises again, if not, it may stop turning to

    start servicing.

    12.3 Put-in of quick cooling equipment of turbine:

    12.3.1 Put the LP cylinder spray of main machine into operation normally.

    12.3.2 Slightly open the blowdown valve of oil-water separator and the drain valve of the gas

    collection tank.

    12.3.3 Open the total valve of compressed air.12.3.4 Put the heater into operation.

    12.3.5 Open wide the primary valve and adjust the air inlet flow of secondary valve as putting the

    quick cooling equipment into operation. Slowly open the hand-operated air inlet valve of

    compressed air to HP & LP drain pipe.

    12.3.6 Open gradually the air inlet valve wider and set the outlet temperature of air heater

    according to the decreasing of cylinders temperature, and control the temperature decreasing

    rate not exceed 5 /h.

    12.3.7 Check if the exhaust temperature that shall not exceed 80 .

    12.3.8 In the process of put-in, check if the temperature difference between upper and lower

    li d th t h ll t b th 41

  • 7/28/2019 Turbine Mannual

    144/154

    JSG CPP TURBINE OPERATION RULES

  • 7/28/2019 Turbine Mannual

    145/154

    than 130 .

    12.4.12 When air temperature exceeds the deviation or the electric heater loses power, it shall

    raise the alarm and interlock close the inlet valve to prevent cold air from entering and cooling the

    cylinder excessively, meanwhile cut off the power supply of heater to prevent the heater from dry

    heating.

    12.5 Stop of quick cooling system

    After finishing quick cooling, adjust the potentiometer to 0 point manually, stop the heater, open

    the power supply switch and continue to ventilate for 5~10 minutes, then close all valves. Slightlyopen of the blowdown valve to prevent air leak of air inlet valve from resulting in water entering

    the equipment.

    Chapter 13 Inner Cooling Water System

    JSG CPP TURBINE OPERATION RULES

  • 7/28/2019 Turbine Mannual

    146/154

    Model: DFB100-80-230 Model: Y200L1-2

    Flow: 70 m3/h Power: 30 kW

    Pump lift: 70m Voltage: 415 V

    Rotating speed: 2,900 r/min Current: A

    Rotating speed: 2,900 r/min

    Insulation grade: F

    13.2 Start of inner cooling water pump

    13.2.1 Check if the oil level of bearing is normal, if turning coupling is flexible, if the water in the

    cooling water tank is qualified and water level is normal.

    13.2.2Check if all parts of the inner cooling water pump are normal, each valve is on right

    position, inlet and outlet are opened and the air release valve is opened and close it after

    discharging air thoroughly.13.2.3 Release the interlock of inner water cooling pump.

    13.2.4 Start the inner cooling water pump and check if the vibration, current, pressure and sound

    are normal, Glan throw no water and water discharge is smooth.

    13.2.5 Put the interlocking switch into operation.

    JSG CPP TURBINE OPERATION RULES

  • 7/28/2019 Turbine Mannual

    147/154

    13.4.1.6 Slowly open the cooling water outlet valve of water cooler, pay attention to the change in

    water inlet and outlet temperature and pressure of inner cooling water, adjust the opening extent

    of cooling water outlet valve to keep the temperature of inner cooling water normal. In normal

    condition, two water coolers are in operation, one is for standby.

    13.4.2 Stop of water cooler

    13.4.2.1 In operation, pay attention to that water level of cooling water tank shall be normal, each

    water inlet pressure and temperature of the generator shall be normal.

    13.4.2.2 Slowly close the inner cooling water outlet valve of water cooler and pay attention to thateach water inlet pressure and temperature of the generator shall be normal.

    13.4.2.3 When it is to stop isolation, first close the cooling water inlet & outlet valve of the water

    cooler, then close the inlet valve of inner cooling water to reduce the pressure and discharge

    water.

    JSG CPP TURBINE OPERATION RULES

  • 7/28/2019 Turbine Mannual

    148/154

    water of winding

    Differential pressure of

    the filter is high

    actual

    measure

    ment

    20kPa higher than

    normal value

    Air inlet temperature of generator: normal 20~40 , 45 max;

    Air outlet temperature of generator:

  • 7/28/2019 Turbine Mannual

    149/154

    Appendix Part

    JSG CPP TURBINE OPERATION RULES

  • 7/28/2019 Turbine Mannual

    150/154

    0.008 41.534 0.17 115.17 0.41 144.52 2.4 221.78 9.0 303.21

    0.009 43.787 0.18 116.93 0.42 145.39 2.5 223.94 9.5 307.21

    0.01 45.833 0.19 118.62 0.43 146.25 2.6 226.04 10.0 310.96

    0.011 47.71 0.20 120.23 0.44 147.09 2.7 228.07 11 318.05

    0.012 49.446 0.21 121.78 0.45 147.84 2.8 230.05 12 324.65

    0.013 51.062 0.22 123.27 0.5 151.84 2.9 231.97 13 330.83

    0.014 52.574 0.23 124.71 0.6 158.84 3.0 233.84 14 336.64

    0.015 53.997 0.24 126.09 0.7 164.96 3.2 237.45 15 342.13

    0.02 60.86 0.25 127.43 0.8 170.41 3.4 240.88 16 347.33

    0.025 64.992 0.26 128.73 0.9 175.36 3.6 244.16 17 352.26

    0.03 69.124 0.27 129.98 1.0 179.88 3.8 247.31 18 356.96

    0.04 75.886 0.28 131.20 1.1 184.07 4.0 250.33 19 361.43

    0.05 81.345 0.29 132.39 1.2 187.96 4.2 253.24 20 365.70

    0 06 85 945 0 30 133 54 1 3 191 61 4 4 256 05

    JSG CPP TURBINE OPERATION RULES

    Appendix 2: Cold Start Curve

  • 7/28/2019 Turbine Mannual

    151/154

    - 151 -

    Fig.14 Cold Start Curve of 135MW Unit (D151)

  • 7/28/2019 Turbine Mannual

    152/154

    JSG CPP TURBINE OPERATION RULES

    Appendix 4: Normal Shutdown Curve

  • 7/28/2019 Turbine Mannual

    153/154

    - 153 -

    JSG CPP TURBINE OPERATION RULES

    Appendix 5: Shutdown Curve at Sliding Parameters

  • 7/28/2019 Turbine Mannual

    154/154

    Fig.16 Shut Curve at Sliding Parameters of 135MW Unit (D151)

    Speed

    Initialsteamtemp.

    Lower carriersteam temp.

    Reheatsteam temp.