1MAC050144-MB C Section 4Protection functions
615 series ANSI 235
Technical Manual
27 prevents sensitive equipment from running under conditions that could causeoverheating and thus shorten their life time expectancy. In many cases, 27 is a usefulfunction in circuits for local or remote automation processes in the power system.
4.2.2.7 SignalsTab le 231 : 27 1 /2 I nput signal s
Tab le 232 : 27 1 /2 Ou tput signal s
4.2.2.8 SettingsTable 233 : 27 1 /2 Group set ti ngs
Name Type Default Description
V_A_AB SIGNAL 0 Phase to ground voltage A or phase to phase voltage AB
V_B_BC SIGNAL 0 Phase to ground voltage B or phase to phase voltage BC
V_C_CA SIGNAL 0 Phase to ground voltage C or phase to phase voltage CA
BLOCK BOOLEAN 0=False Block signal for activating the blocking mode
Name Type Description
TRIP BOOLEAN Trip
PICKUP BOOLEAN Pickup
Parameter Values Range) Unit Step Default Description
Pickup value 0.05...1.20 xVn 0.01 0.90 Pickup value
Time multiplier 0.05...15.00 0.05 1.00 Time multiplier in IEC/ANSI IDMT curves
Trip delay time 60...300000 ms 10 60 Trip delay time
Operating curve type 5=ANSI DT15=IEC DT21=Inv. Curve A22=Inv. Curve B23=Programmable
5=ANSI DT Selection of time delay curve type
Type of reset curve 1=Immediate2=Def time reset-1=DT Lin decr rst
1=Immediate Selection of reset curve type
-