unigas m03953ca

Upload: maurice-lachaud

Post on 07-Jul-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/18/2019 Unigas m03953ca

    1/36

    BURNER INSTRUCTION MANUAL

    FOR GAS AND PRESSURE ATOMIZING OIL FUEL SYSTEMS

    P-MODEL

    FI FI 8 F OmF

  • 8/18/2019 Unigas m03953ca

    2/36

    INTRODUCTION

    q Starting a burner is an event which normally culminatesthe effort of severa1  different contractors, manufacturers,

    utility and engineering concerns,   Sales  and factory

    representatives, and others.

    n In order for the burner to operate safely and meet its

    design capabilities, the interfacing fuel, air, electrical,exhaust an.d plant heating contro1  systems must be

    properly sized, selected, installed andtested.

     Additionally,

    all conditions must be such that the heat generated by

    the burner can be safely used or wasted without

    endangering personnel or equipment.

    n It shall be the policy of CIB UNIGAS BURNERS that noresponsibility is assumed by the Company nor any of its

    employees for any liability or damages caused   by an

    inoperable, inadequate or unsafe burner condition which

    is the result, either directly or indirectly, of any of the

    improper or inadequate conditions describedabove.

    n TO  insure that a safe and satisfactory installation has

    been made, a pre-start inspection is necessary.   This

    inspection must be performed by an individua1 who is

    thoroughly familiar with all  aspects of proper  boiler/

    burner installation and how it interfaces with overall plant

    operation.

    n Part of this bulletin sets forth major inspection items thatmust be considered.

      NOTE

    This inspection should-be performed before the burner 

    start-up specialist is called in. An incomplete or inadequate

    installation may require additional time and effort bystart-up personnel and cause an untimely and costly

    delay.

    n The result of this inspection will often times identify

    corrections that must be made prior to start-up as well as

    point out potential or long range problems in plant

    operation if corrections are not made.

    n Burner start-up is serious matter and should not be

    viewed as a time for “crowd  gathering” by unconcerned,

    uninformed or unauthorized personnel. The number of 

    persons present should be held to an absolute minimum.

    n Instruction of operating and other concerned personnel

    should be done  after the burner has been successfully

    fired and adjusted by a qualified service  agency or 

    Commissioning Engineer.

    WARNING

    Improper servicing of this equipment may create a potential hazard to equipment and operators.

    SERVICING MUST BE DONE  ONLY BY FULLY TRAINED AND QUALIFIED PERSONNEL.

    Before disconnecting or opening up a fuel line and before cleaning or replacing patts of any kind.

    W Turn OFF the main  manual fuel shutoff valves including pilot gas cock, i f applicable li a multiple fuel burner,

    shut OFF al l fuels.

    n Turn OFF all  electrical disconnects to the burner and any other equipment or systems electrically interlockedwith the burner.

    2

  • 8/18/2019 Unigas m03953ca

    3/36

    SPECIFICATION OF YOUR BURNER:

    SERIAL No

    BURNER MODEL

    FUELS 

    2

    ELECTRICS   MOTOR

    CONTROL

    FUEL PRESSURES 

    2

    IGNITION GAS

    NOTES

    3

  • 8/18/2019 Unigas m03953ca

    4/36

  • 8/18/2019 Unigas m03953ca

    5/36

  • 8/18/2019 Unigas m03953ca

    6/36

     ADJUSTMENT PROCEDURE

    1. Loosen positioning mechanism.

    2. For initial start-up, position air cylinder midway of its stoke.

    3. Start the burner and look for optimal  cylinder position.

    4. Arrange mechanical cam according   to  positions defined at  point 3.

    5. ock mechanism.

    If positioned too far forward, the main  flame may pulsate. If too far tothe rear, the surplus air may cause noisy operation.

    Figure 3 1: Adjustment of manual proportioning primary secondary  air control.

    ITEM 2 ADJUSTMENT OF R   INLET LOUVER BOX

    DESCRIPTION HOW WORKS

    The amount of air available for combustion is controlled by   See  figure 3-2. Louver opening and trave1  is controlled by

    adjustable louvers located in the air box. The louvers are adjusting the linkage mechanism from the actuator to obtain

    interconnected through a series of small linkage arms the desired opening and stroke. The actuator drives the

    secured to a common drive rod. louvers open or closed as the combustion contro1  programs

    the burner firing rate to meet the boiler load

    R  LOUVRE BOX   IS   Damper position indicator CT Positioning armRA Regulating   boltVB   Positioning arm clamp bolt

    T   Operating rod

     ADJUSTMENT PROCEDURE

    1. Use box end or socked wrench  to   loosen ball joint connector.

    2. TO  adjust low fire (minimum) air setting, loosen ball joint

    connector holding drive rod and manually position louvers to

    obtain the desired opening, then retighten connector.

    3. TO adjust amount of trave1 (stroke), loosen base of ball-jointconnector located in slotted (louver) actuator arm and reposition

    to desired setting, then re-tighten connector.

    4. For initial start-up: Position air inlet louvers SO  they are

    approximately 1/4   inch open.

    Figure 3 2: Adjustment of air inlet louvre box

  • 8/18/2019 Unigas m03953ca

    7/36

  • 8/18/2019 Unigas m03953ca

    8/36

  • 8/18/2019 Unigas m03953ca

    9/36

    BURNERIR

     AND FUEL ADJUSTMENTS continued

    ITEM 6 ADJUSTMENT OF GAS PRESSURE SWlT H S

    DESCRIPTION   OW  IT WORKS

    Gas pressure switches are pressure-

     actuated electrical   See  figure 3-6. The pressure switch senses any change  in

    switching devices designed  for safety shutoff when gas gas pressure and, if properly adjusted, will  transmit an

    pressure are either too low or too high. electrical signal to the automatic shutoff valve andlor other 

    interlocking devices when an unsafe condition exists, The. burner will then re-eyele or completeiy shut down depending

    upon the flame  safeguard used. Gas pressure switches are

    designed  to operate over a specified pressure range;

    therefore, each  switch must be selected to be compatible

    with the burner operating gas pressure and also to obtain

    the desired electrical features.   .

    Gas Pressure Switch

    6AS

     

    =4

    20

    cr

    =3

    =

     40

     7

     5

    ADJUSTMENT PROCEDURE

    p ]

    See  gas pressure switch manufactures instructionsfor detailedprocedures.

    1) For initial Start-up

    a. Low Gas pressure Switch-

     Adjust to a lower pressurethan that to be experienced for norma1 operation to allowthe burner to be set up.

    b. High Gas Pressure  Switch-

     Adjust to a higher pressurethan that to be experienced for norma1 operation to allowthe burner to be set up.

    pi--NOTE]

    Final adjustment must be done after the burner has been

    test fired. See  burner start-up procedure

    Figure 3 - 6: Adjustment of gas pressure switches

    ITEM 7 ADJUSTMENT OF OlL  DRAWER ASSEMBLY

    DESCRIPTION  OW

     IT WORKS

     

    Oil

     bumers have  an assembly made up of vital oi l and air    See Figure 3-7. The oil  is forced  down the supply tube under 

    handling components known as the “Oil Drawer Assembly”. high pressure and is atomized into the combustion chamber 

    Basically, this assemblycontains theoil tube(s), the atomizing by the oil nozzle The air diff user distributes the combustion

    nozzle s),  the air diffuser with mounting bracket  and anoil air through the atomized oil  which is then ignited by the gas

    distnbutor block and backplate which secures the unit to the   pilot ignitor or by an electrical spark if burner has direct  spark

    burner housing. If the bumer has direct spark oi l  ignition, the ignition. On bypassing oil  nozzle systems, the excess oil is

    ignition electrodes are also a part of this assembly.   diverted  from the nozzle to the bypassreturn

     line.

  • 8/18/2019 Unigas m03953ca

    10/36

    ADJUSTMENT PROCEDURE

    1)  At back  of bumer use Allen key to loosen set screw VI.This will enable the diff userto be re-positioned in relationto the burner head.Generally the diffuser should be positioned as far to therear as possible without impinging the

    oil

     spray on theinner surface of the burner firing tube.

    2) TO adjust the nozzle in relation to the diffuser loosen setscrew V and position nozzle slightly behind diff user - thefinal position cannot be established unt the burner isfired.

    Figure 3 - 7: Adjustment of oil drawer assembly

    ITEM 8 ADJUSTMENT OF OIL M T RIN VALVE

     ES RIPTION

    HOW IT  WORKS

    Oil bumers whichhave

     low fire startfuel

     contro1 systemsmust deliver oil to the nott at reduced  pressure  for low fire.This is normally accomplished by diverting a

    portion

     of theoil

     pump delivery thru a bypass return line

     to the tank.

    The amount ofoil

     delivered to thenozzle

     versus that

    returned to the tank is controlled by a device  which limits or meters flow, thus an oil metering  valve is commonly used for this purpose.

    Most oil metering  devices work on the principle of limitingflow by constrictings the area thru which the oil must Pass.In order to vary the orifice area, mechanical movement musttake

    place,

     thus the oil metering  valve requires an actuator to do its job.

    By

     interconnecting a common actuator to the

    combustion contro1  and the oil metering  valve, this allowsthe fuel   oil to be proportioned in precise ratio to the amountof air available for combustion. This feature is essential onmodulating type fuel contro1 systems.

  • 8/18/2019 Unigas m03953ca

    11/36

    ADJUSTMENT PROCEDURE

    The metering  valve is adjusted by the position of the ratio

    cam-

     closing the valve increases the return  pressure on the

    gauge and increases the burner firing rate, opening the

    valve lowers the return  pressure and reduces the firing rate.

    Normally high firereturn

     pressure will be between 18-25 bar 

    and low fire 5-12 bar.

    The return  pressure can be adjusted with an Allen key as

    shown in the diagram through the full modulating range of 

    the burner.

    Figure 3 8: Adjustment of oil metering  valve

    BURNERR

     AND FUEL ADJUSTMENTS continued

    JUSTMIENT  OF OIL SUPPLY PRESSURE REGULATOR VALVE (INTEGRAL TO OIL PUMP)

     

    I

     

    2

    1

    1 Suction2 Return3 Pressure nozzle

    4 - Pressure regulator 5-

     Gange port (suction)6 - Gange port (pressure)

     

    HOW  IT  WORKS

    Burner oi l pumps are generally identify by the rate at which

    they can deliver (GPH), the pressure of the delivery (BAB)

    and the speed of rotation   (RPM). The pump is usually

    capable of delivering more fuel than is required  to meet firing

    requirements; therefore, the amount of oil  delivered to the

    nozz must be controlled. This contro1  is accomplished thru

    use of an adjustable pressure regulating valve which reduces

    flow to the nozzle by causing  more oil  to be returned to the

    tank. Like most regulators, flow is controlled by an adjustable

    spring and each   regulator has a pressure range over which

    it will reliably operate.

    ADJUSTMENT OF OIL SUPPLY PRESSURE

    The pump is adjusted at the built in pressure regulator as

    shown in the diagram.

    Remove  the cover with a spanner and with a gauge in the

    pressure port as shown set the supply pressure between 20

    and 25 bar. Replace cover and check supply pressure is

    steady through modulating range.

    Figure 3 9: Adjustment of oil supply pressure regulator valve

  • 8/18/2019 Unigas m03953ca

    12/36

  • 8/18/2019 Unigas m03953ca

    13/36

    TART SEQUENCE

    Check the electronic ftamesupervision

     unit is not in the “lockout” position. In the affirmative,reset

     it.

    Be certain  the temperature and pressure controls are in the “closed” position.

    Whenoii

     has reached the temperature for starting, blower motor starts and pre-purging begins.

     pre-purgin is to to be carried  out with maximum air delivery, the burner contro1 circuit turns the air damper to the

    max. position, iva the air servocontrol is fully open position, a signal to the electronic contro1 unit starts the pre-purge cycle,

    which lasts 30 seconds. 

    During that period  hot oil is circulated as far as the nozzle to ensure good ignition. After pre-purging, the air servocontrol

    returns to the fully closed position,SO

     that ignition takes place  at the minimum firing rate.

    Simultaneously the ignition transformer receives voltage and after 3 seconds pre-ignition)  the pilot  burner ignites and

    is proven following which the 3 port valve is energised. Theoil

     flows to the atomizing nozzle and ignites, being controlled

    by the pressure regulator.

    Now the burner is operating at the minimum firing rate (about 30% of the max. firing rate). Afterwards, the air servocontrol

    runs to the low flame position and, in case the temperaturecontro1

     should be set for the max. firing rate, to the air damper    ,

    fully open position, while the atomizing nozzte is fed at the max. pressure. which is supplied by the regulator being fully

    ctosed via the cam: maximum firing rate is thus reached.

    Irrespective of heat required, the contro1 unit continues  its programme to the end and retums to its start position for the

    next cycle, which will be performed after the burner idle time caused  by limit or response switches.

    43

  • 8/18/2019 Unigas m03953ca

    14/36

     

    iiiiii

     

  • 8/18/2019 Unigas m03953ca

    15/36

    GAS IRING ,

    1) Isolate the main gas train  and operate the burner sequence and ensure that the pilot burner Iights reliably and is capable

    of lighting the main flame under all conditions. At the appropriate time the flame safeguard will go to lockout when the

    main

     ftame does not ignite.

    2) With the gas butterfly contro1 valve setto approx 15” open the main  gas supply, run the burner sequence, and the burner will ignite on Iow fire.

    3)  As soon as pratica1  advance  the burner to the high fire position and ensure that the gase  contro1 valve is fully open - adjust

    themain

     gas governor to give the rated input by observing the gas meter.

    By adjusting the ratio cam for the gas contro1 valve the bumer can now be set throughout its modulating range using

    flue gas analysis instruments. Oxygen readings on high fire should be 3-4 and 5-6 % on low fire with zero CO. The

    primary air adjustment can also be used for fine regulation of flame shape and excess air.

     Adjustment of themain air damper is via the slotted lever.

    AIR PRESSURE SWITCH S TTING

    Loosen the screw VB. The regulating ring nut is to be setat the bottom of its scale. While the burner is operating, s w y

    turn the regulating ring nut clockwise unti1 the burner stops. Then turn the ring back by two tums and re-start the burner.

    Should the bumer go to lockout again,  turn back  by one  more full turn.

    Tighten the screwVB.

    Figure 4.2

  • 8/18/2019 Unigas m03953ca

    16/36

    L

     DELIVERY ADJUSTMENT

    Theoil

     systemincludes:

    AFuel

     oil

     Pump

      By-passNozrle

     (Retum FlowNozzle

    C Oil  Metering  Valve

    The diagram illustrates  the fuel feeding system of these  types of burners, which incorpora a by-pass nozzle with oil flow

    regulation in its retum pipe.

    The oil supply is varied  by acting on the metering valve which determines the oil flow to the nozzle through the pressure

    on the return line.

    Max oli supply is therefore reached  when the pressure in the suction line is about (25 bar oule Type .W2 and the return

     is fully closed;  min.oil

     supply when the retumline

     is fully open. Relevant pressure reading in the retumline

     are as

    follows.

    TYPE  W2  

    max. oil supply: 25 bar 

    min. oil supply: 9 10  bar 

    Rate of adjustment: 1 to 4

    Figure 4.3

    46

  • 8/18/2019 Unigas m03953ca

    17/36

    R ARE TWO POSSIBILITIES

    - The burner has already been adjusted for gas firing.

    - The burner must be oil fired only.

    TART FL ME  S lTlN

    upposing the.bumer  has already been adjusted for gas firing:

    start flame size is to be proportioned to the nozzle size and oil pressure measured at the regulator. Therefore choose

    the most suitable nozzle fot the application, SO that during ignition the oil supply should be 113  of the max. one.

     When valves open, the pressure measured by the gauge fitted to the regulator must be of5 l

     2 bar toallow

     min. oil supply

    to thenoule.

     TO obtain that reading, act on the cam coupled  with the air servocontrol.

    Ouring start flame setting, it is advisable to interrupt the working cycle.

     Air delivery has already been adjusted when burner has been set for gas firing.

    Oil and air might not be mixed in the correct proportion, but a futther adjustment of air delivery is negligible as ignitiontime is limited by the interval of the servocontrol between ignition sequence  and futther steps.

    Before cartying out more operations, trip switch to resume  the working cycle.

    HIGH FLAME ADJUSTMENT

    The servontrol  tums the air damper (previously adjusted for gas firing only) to max. delivery. Simultaneously the pressure

    egulator controlled  by the sector cam is fully closed

     and casues  an increases in the pressure of the nozzlereturn

     flow,

     which

    evelops max. firing rate.

     As air is delivered  at a fixed rate during gas firing, it might be necessary  to correct max. oil supply. That can be obtained

    by acting on the cam which controls the regulator, resulting  in a variation of the oil firing rate, unti1 combustion readings

    are found to be satisfactory.

  • 8/18/2019 Unigas m03953ca

    18/36

  • 8/18/2019 Unigas m03953ca

    19/36

    MO UL TING DRIVE MOTOR:

    1) The SQM 10  is always set to 90” operation via Cam ‘A’ which is preset at the factory.

    2) The low  fire position of the burner can be set on Cams ‘C’ or ‘E’ for gas and oil the small  indicator arrow shows the position

    of the motor in degrees.

    3) Cam ‘l3’ is the setting for gas ignition flame.

    4) Cam ‘D’ is the setting for oil  ignition flame.

    Figure 4.5

     

    -  HIGH FLAMEIl -  IGNITION GAS

    Ill - LOW FLAME

    IV - IGNITION 01L

    V - LOW FLAME OIL

    VI - NOT USED

  • 8/18/2019 Unigas m03953ca

    20/36

    BY PASSING NOZZLES TYPE FLUIDICS  “W2”

    Inlet

     pressure 25 bar 

    Turn-down ratio 1: 4

    Viscosity  5 cSt

    500  790”  Spray angle

     5

    Supply 25 bar  supp y  

    357 ps

    2

    eturn

     pressure

    I

    t ll 1 0 0 kg h

    over

    bar   e

    2 0 4 0 6 0 8 0

    3 0 0 psi

    Return pressure

     

    2 0 0 psi

    1 0 0 psi

    100 % Output

    Figure 4 - 6

  • 8/18/2019 Unigas m03953ca

    21/36

    100

    90

    80

    70

    60

    5 0

    40

    30

    20

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    BURNER GAS THROUGPUT VERSUS HEAD PRESSURE

     

    i

    Ill

    r I I

     

    I

     

    t 1

    6 7 8 9 1 0 0 2 3 4 5 6   7 8 9 1 0 0 0 2

    THROUGPUT Nm3/  h

    Figure 4 - 7

    24

  • 8/18/2019 Unigas m03953ca

    22/36

    BURNERGASTHROUGPUTVERSUSHEADPRESSURE

    MO L F22

    I

     

    THROUGPUT Nm3 h

    Figure 4 9

      3

  • 8/18/2019 Unigas m03953ca

    23/36

    HEAVY OIL IRIN ONLY

      l L N FILLING 

    Oi l

     in the pre-heater is to be kept at 50” C approx.

    Before starting the burner, set the regulating and oil temperature contro1  thermostats at 130” C and 1 IO  “C  respectively.

    These  values apply to fuel oil

     with viscosity ranging from 25” to 50” E at 50°C.

    TO fill the oil line  (pre-heater, oil  suction, feed to and return  from the nozzle) proceed as follows:

    1-

     Cut offoil

     electric heaters via theline

     switch (off the contro1 panel).

    2-

     Link oil, interlock thermostat.

    3-

     Turn on the cock on the vent pipe of the pre-heater.

    4-

     Turnfuel

     selector to the position “OIL”.

     At this point the burner performs a complete start-up cycle. As soon as oil flows out of the vent pipe, throw the line switch

    to the “ON” position and turn the cock  off. If at the end of the first cycle, when burner goes to lockout and stops, oil has not

    filled theline

     yet, push reset contro1  button to repeat the cycle.

    The line  is full up when pressure gauge on the pump indicates about 25 bar., which is the pressure required for proper burner 

    operation.

    TO obtain that reading, loosen or tighten the screw “4”.

     A few minutes’ time is admitted to fill the oil line, but a longer time might damage the pump seals.

    If the line  is not full up, it is necessary  to check the suction pipe.

    Upon completion of filling, disconnect link and connect start-up thermostat there.

    24

  • 8/18/2019 Unigas m03953ca

    24/36

    UEL OIL THERMOSTATS

    Figure 4.11

    ADJUSTMENT PROCEDURE

    140 80

    130

     @’

    I

    9 0

      0 Q

    120 100

    110

    \

     

    140  8

    130

     

    90

    {@’

      0

    120 

    110

    J J

     m

    TR TCN

    Remove  the cover which encloses the thermostat and interlock switch (thermostat).

    The pointer (2) controls the thermostat setting while the pointer (1) controls the interlock switch (thermostat).

    The thermostat pointer (2) should be set at 190” C and then raised or lowered as required.

    The coldoil

     interlock switch-thermostat is controlled by the pointer (1).

    This is setto prevent the burner from starting unti1 a minimum oil temperature is reached and should be set 20 - 25” below

    the oil  temperature setting on the Heater Contro1 Thermostat.

    CAUTION:  Do not set the cold oil  interlock higher than the oil temperature.

    Replace the cover which encloses the thermostat and interlock switch-thermostat.

    HEATER CONTROL THERMOSTATHEATER CONTROL THERMOSTAT

    TO regulate the thermostat use a screwdriver as shown. The temperature to be set can be determined from viscosityTO regulate the thermostat use a screwdriver as shown. The temperature to be set can be determined from viscosity

    iagram. We suggest the actualoil

     temperature be set precisely with the burner working using a mercury thermometer iniagram. We suggest the actual oil  temperature be set precisely with the burner working using a mercury thermometer in

    he pocket.he pocket.

    Figure 4.12

  • 8/18/2019 Unigas m03953ca

    25/36

    SUNTEC TA

    Figure 13

    SUCTION HEIGHT : Max. 0 5 bar Vacum  0 4  bar 

    advised to prevent air separation from oil.

    RATEDSPEED : Max. 3600 rpm.

    OPERATING VISCOSITY RANGE : 2 8 to 800 cSt.

    INLET AND RETURN  PRESSURE : Max 5 bar.

    5   6

    LEGEND:

    1   Pump Suction2   Return

    Nozzle4  Pressure Regulator 

    5   Vacuum Port

    6   Pressure Gauge

    7  Electric Heater 

    OIL LANCE SCHEMATIC

    FLOW RETURN NEEDLE

     OPERATING

     

    2

    3  PORT 

    AUXILIARY  BLOCK  HEATER

    Figure

  • 8/18/2019 Unigas m03953ca

    26/36

    OIL LANCE

    NOZZL

     E

     PRE-PURG

    Figure 4 15

      N T ON

     FI

    Figure 4 16

  • 8/18/2019 Unigas m03953ca

    27/36

  • 8/18/2019 Unigas m03953ca

    28/36

    OIL PRESSURE REGULATOR

     f gaseous fuel was not available initiaily, the directions given to set the burnerfor gas firing also apply to oil firing, p rti ul rly

    as far as combustion air adjustment is concerned

    OIL SUPPLY PRESSURE SETTING

     t is to be carried  out during pre-purge time by tightening or loosening the socket  headed screw RP on the oil pump. For 

    proper  burner operation, the pressure reading indicated  by the pressure gauge M must be 25 bar appox.

    Figure 4 18

    OIL PRESSURE REGULATORS lTIN

    The shape given to the blade in the oil  sector  determines the oil supply to the nozzle.

    The figure shows two possible shapes:

     

    : blade shape before start flame setting

    L2 : final shape after setting

    v

    LP

    LP

    Figure 4 19

    RAB-DISTRIBUTOR BLOCK

    AUXILIARY HEATER

    Figure 4 20

  • 8/18/2019 Unigas m03953ca

    29/36

    OIL PIPE CONNECTIONS

    CARTRIDGEBELT TYPE HEATER

    Figure 42

    LEGEND

    1 Flow2 Return

    3 Needle operating port CARTRIDGE P P HEATER

    BELT TYPE HEATER

    HASBESTOS HOS Figure 4 22

  • 8/18/2019 Unigas m03953ca

    30/36

    THERE  ARE TWO POSSIBILITIES:

    1 The burner has already been adjusted for gas firing.

    2 The burner must beoil

     fired only.

    START FLAME S TTIN

    Supposing the burner has already been adjusted for gas firing:

      Start flame size is to be proportioned to the nozzle size and oil pressure measured at the regulator. Therefore choose

    the most suitable nozzle for the application, SO that during ignition the oil  supply should be one  third of the max. one.

      When valve opens, the pressure measured by the gauge fitted to the regulator must be of 5-l 2 bar to allow  min.oil

     supply

    to the nozzle.

    TO obtain that reading, act on the cam oupled with the air servocontrol.

    During start flame setting, it is advisable to interrupt the working cycle.

     

     Air delivery has already been adjusted when has been set for gas firing.Oil and air might not be mixed in the correct proportion but a further adjustment of air delivery is negligible as ignition

    time is limited by the intetval of the servocontrol between ignition sequen e and further steps.

    HIGH FLAME ADJUSTMENT

      The servocontrol turns the air damper (previously adjusted for gas firing only) to max. delivery. Simultaneously the

    pressure regulator controlled by the se tor is fully closed  and uses an increase in the pressure of the nozzle return

    flow, which develops max. firing rate.

       As air is delivered at a fixed rate during gas firing, it maight be ne ess ry to correct max. oil supply. That can be obtained

    by acting on the cam which controls the regulator resulting in a variation of the oil firing rate, unti1 combustion readings

    are found to be satisfactory.

    LOW FLAME ADJUSTMENT

      Please, refer  to gas firing as well.

     

    Oil

     supply regulation is carried  out by rotating the cam that controls the oil  return  pressure regualtor unti1 the pressure

    reading corresponds to the correct quantity of oil  required to burn the air delivered at low flame rating (already adjusted

    during gas firing).

    3A

  • 8/18/2019 Unigas m03953ca

    31/36

    MINIMUM SUPPLY TEMPERATURE TO THE BURNER ACCORDING TO GRADE OF FUEL OIL

    100908 0

      I   I  I I  I   Il

    l t MT”

    10

    98

    7

    6

      i i i i   i

      1 0 2 0 3 0 4 0 5 0 6 0   8 0

    TEMPERATURE “C

    Figure 4 23

    The burners must be supplied with oil having a min. temperature at the pump inlet according  to the above  diagram with

    relation to the grade of oil  being used.

    For example: oil being used 7” E, 15” E, 50” E at 50” C the inlet temperature to the pump must  be respectively 35” C,

    50” C, and 77” C as indicated  by the diagram.

    32

  • 8/18/2019 Unigas m03953ca

    32/36

    GAS TRAINS

    The gas train will be supplied in a straight line arrangement and a special DWG and schematic will be provided with each

    contract.

    There will effectively be a main  gas tr in and a pilot train the pilot can be either natura1  gas or L.P.G.

    All components will comply with loca1 standards.

    CONTROL PANEL

    This is normally supplied as a remote oòr standing unit c/w   following

     

    1) Flame safeguard

    2) Motor starters fuses

    3) Necessary lamps switches

    4) Necessary relays timers

    5) Modulating ontroller

    6) All components wired to a terminal strip7) Pane1 vol tor

     A spe ifi schematic and wiring diagram will be provided for each  contract.

    For any further information please contact our 

    as shown at the front of this manual.

    engineering department at the following address quoting the full specification

  • 8/18/2019 Unigas m03953ca

    33/36 

  • 8/18/2019 Unigas m03953ca

    34/36

  • 8/18/2019 Unigas m03953ca

    35/36

  • 8/18/2019 Unigas m03953ca

    36/36