unigas m03953ca
TRANSCRIPT
-
8/18/2019 Unigas m03953ca
1/36
BURNER INSTRUCTION MANUAL
FOR GAS AND PRESSURE ATOMIZING OIL FUEL SYSTEMS
P-MODEL
FI FI 8 F OmF
-
8/18/2019 Unigas m03953ca
2/36
INTRODUCTION
q Starting a burner is an event which normally culminatesthe effort of severa1 different contractors, manufacturers,
utility and engineering concerns, Sales and factory
representatives, and others.
n In order for the burner to operate safely and meet its
design capabilities, the interfacing fuel, air, electrical,exhaust an.d plant heating contro1 systems must be
properly sized, selected, installed andtested.
Additionally,
all conditions must be such that the heat generated by
the burner can be safely used or wasted without
endangering personnel or equipment.
n It shall be the policy of CIB UNIGAS BURNERS that noresponsibility is assumed by the Company nor any of its
employees for any liability or damages caused by an
inoperable, inadequate or unsafe burner condition which
is the result, either directly or indirectly, of any of the
improper or inadequate conditions describedabove.
n TO insure that a safe and satisfactory installation has
been made, a pre-start inspection is necessary. This
inspection must be performed by an individua1 who is
thoroughly familiar with all aspects of proper boiler/
burner installation and how it interfaces with overall plant
operation.
n Part of this bulletin sets forth major inspection items thatmust be considered.
NOTE
This inspection should-be performed before the burner
start-up specialist is called in. An incomplete or inadequate
installation may require additional time and effort bystart-up personnel and cause an untimely and costly
delay.
n The result of this inspection will often times identify
corrections that must be made prior to start-up as well as
point out potential or long range problems in plant
operation if corrections are not made.
n Burner start-up is serious matter and should not be
viewed as a time for “crowd gathering” by unconcerned,
uninformed or unauthorized personnel. The number of
persons present should be held to an absolute minimum.
n Instruction of operating and other concerned personnel
should be done after the burner has been successfully
fired and adjusted by a qualified service agency or
Commissioning Engineer.
WARNING
Improper servicing of this equipment may create a potential hazard to equipment and operators.
SERVICING MUST BE DONE ONLY BY FULLY TRAINED AND QUALIFIED PERSONNEL.
Before disconnecting or opening up a fuel line and before cleaning or replacing patts of any kind.
W Turn OFF the main manual fuel shutoff valves including pilot gas cock, i f applicable li a multiple fuel burner,
shut OFF al l fuels.
n Turn OFF all electrical disconnects to the burner and any other equipment or systems electrically interlockedwith the burner.
2
-
8/18/2019 Unigas m03953ca
3/36
SPECIFICATION OF YOUR BURNER:
SERIAL No
BURNER MODEL
FUELS
2
ELECTRICS MOTOR
CONTROL
FUEL PRESSURES
2
IGNITION GAS
NOTES
3
-
8/18/2019 Unigas m03953ca
4/36
-
8/18/2019 Unigas m03953ca
5/36
-
8/18/2019 Unigas m03953ca
6/36
ADJUSTMENT PROCEDURE
1. Loosen positioning mechanism.
2. For initial start-up, position air cylinder midway of its stoke.
3. Start the burner and look for optimal cylinder position.
4. Arrange mechanical cam according to positions defined at point 3.
5. ock mechanism.
If positioned too far forward, the main flame may pulsate. If too far tothe rear, the surplus air may cause noisy operation.
Figure 3 1: Adjustment of manual proportioning primary secondary air control.
ITEM 2 ADJUSTMENT OF R INLET LOUVER BOX
DESCRIPTION HOW WORKS
The amount of air available for combustion is controlled by See figure 3-2. Louver opening and trave1 is controlled by
adjustable louvers located in the air box. The louvers are adjusting the linkage mechanism from the actuator to obtain
interconnected through a series of small linkage arms the desired opening and stroke. The actuator drives the
secured to a common drive rod. louvers open or closed as the combustion contro1 programs
the burner firing rate to meet the boiler load
R LOUVRE BOX IS Damper position indicator CT Positioning armRA Regulating boltVB Positioning arm clamp bolt
T Operating rod
ADJUSTMENT PROCEDURE
1. Use box end or socked wrench to loosen ball joint connector.
2. TO adjust low fire (minimum) air setting, loosen ball joint
connector holding drive rod and manually position louvers to
obtain the desired opening, then retighten connector.
3. TO adjust amount of trave1 (stroke), loosen base of ball-jointconnector located in slotted (louver) actuator arm and reposition
to desired setting, then re-tighten connector.
4. For initial start-up: Position air inlet louvers SO they are
approximately 1/4 inch open.
Figure 3 2: Adjustment of air inlet louvre box
-
8/18/2019 Unigas m03953ca
7/36
-
8/18/2019 Unigas m03953ca
8/36
-
8/18/2019 Unigas m03953ca
9/36
BURNERIR
AND FUEL ADJUSTMENTS continued
ITEM 6 ADJUSTMENT OF GAS PRESSURE SWlT H S
DESCRIPTION OW IT WORKS
Gas pressure switches are pressure-
actuated electrical See figure 3-6. The pressure switch senses any change in
switching devices designed for safety shutoff when gas gas pressure and, if properly adjusted, will transmit an
pressure are either too low or too high. electrical signal to the automatic shutoff valve andlor other
interlocking devices when an unsafe condition exists, The. burner will then re-eyele or completeiy shut down depending
upon the flame safeguard used. Gas pressure switches are
designed to operate over a specified pressure range;
therefore, each switch must be selected to be compatible
with the burner operating gas pressure and also to obtain
the desired electrical features. .
Gas Pressure Switch
6AS
=4
20
cr
=3
=
40
7
5
ADJUSTMENT PROCEDURE
p ]
See gas pressure switch manufactures instructionsfor detailedprocedures.
1) For initial Start-up
a. Low Gas pressure Switch-
Adjust to a lower pressurethan that to be experienced for norma1 operation to allowthe burner to be set up.
b. High Gas Pressure Switch-
Adjust to a higher pressurethan that to be experienced for norma1 operation to allowthe burner to be set up.
pi--NOTE]
Final adjustment must be done after the burner has been
test fired. See burner start-up procedure
Figure 3 - 6: Adjustment of gas pressure switches
ITEM 7 ADJUSTMENT OF OlL DRAWER ASSEMBLY
DESCRIPTION OW
IT WORKS
Oil
bumers have an assembly made up of vital oi l and air See Figure 3-7. The oil is forced down the supply tube under
handling components known as the “Oil Drawer Assembly”. high pressure and is atomized into the combustion chamber
Basically, this assemblycontains theoil tube(s), the atomizing by the oil nozzle The air diff user distributes the combustion
nozzle s), the air diffuser with mounting bracket and anoil air through the atomized oil which is then ignited by the gas
distnbutor block and backplate which secures the unit to the pilot ignitor or by an electrical spark if burner has direct spark
burner housing. If the bumer has direct spark oi l ignition, the ignition. On bypassing oil nozzle systems, the excess oil is
ignition electrodes are also a part of this assembly. diverted from the nozzle to the bypassreturn
line.
-
8/18/2019 Unigas m03953ca
10/36
ADJUSTMENT PROCEDURE
1) At back of bumer use Allen key to loosen set screw VI.This will enable the diff userto be re-positioned in relationto the burner head.Generally the diffuser should be positioned as far to therear as possible without impinging the
oil
spray on theinner surface of the burner firing tube.
2) TO adjust the nozzle in relation to the diffuser loosen setscrew V and position nozzle slightly behind diff user - thefinal position cannot be established unt the burner isfired.
Figure 3 - 7: Adjustment of oil drawer assembly
ITEM 8 ADJUSTMENT OF OIL M T RIN VALVE
ES RIPTION
HOW IT WORKS
Oil bumers whichhave
low fire startfuel
contro1 systemsmust deliver oil to the nott at reduced pressure for low fire.This is normally accomplished by diverting a
portion
of theoil
pump delivery thru a bypass return line
to the tank.
The amount ofoil
delivered to thenozzle
versus that
returned to the tank is controlled by a device which limits or meters flow, thus an oil metering valve is commonly used for this purpose.
Most oil metering devices work on the principle of limitingflow by constrictings the area thru which the oil must Pass.In order to vary the orifice area, mechanical movement musttake
place,
thus the oil metering valve requires an actuator to do its job.
By
interconnecting a common actuator to the
combustion contro1 and the oil metering valve, this allowsthe fuel oil to be proportioned in precise ratio to the amountof air available for combustion. This feature is essential onmodulating type fuel contro1 systems.
-
8/18/2019 Unigas m03953ca
11/36
ADJUSTMENT PROCEDURE
The metering valve is adjusted by the position of the ratio
cam-
closing the valve increases the return pressure on the
gauge and increases the burner firing rate, opening the
valve lowers the return pressure and reduces the firing rate.
Normally high firereturn
pressure will be between 18-25 bar
and low fire 5-12 bar.
The return pressure can be adjusted with an Allen key as
shown in the diagram through the full modulating range of
the burner.
Figure 3 8: Adjustment of oil metering valve
BURNERR
AND FUEL ADJUSTMENTS continued
JUSTMIENT OF OIL SUPPLY PRESSURE REGULATOR VALVE (INTEGRAL TO OIL PUMP)
I
2
1
1 Suction2 Return3 Pressure nozzle
4 - Pressure regulator 5-
Gange port (suction)6 - Gange port (pressure)
HOW IT WORKS
Burner oi l pumps are generally identify by the rate at which
they can deliver (GPH), the pressure of the delivery (BAB)
and the speed of rotation (RPM). The pump is usually
capable of delivering more fuel than is required to meet firing
requirements; therefore, the amount of oil delivered to the
nozz must be controlled. This contro1 is accomplished thru
use of an adjustable pressure regulating valve which reduces
flow to the nozzle by causing more oil to be returned to the
tank. Like most regulators, flow is controlled by an adjustable
spring and each regulator has a pressure range over which
it will reliably operate.
ADJUSTMENT OF OIL SUPPLY PRESSURE
The pump is adjusted at the built in pressure regulator as
shown in the diagram.
Remove the cover with a spanner and with a gauge in the
pressure port as shown set the supply pressure between 20
and 25 bar. Replace cover and check supply pressure is
steady through modulating range.
Figure 3 9: Adjustment of oil supply pressure regulator valve
-
8/18/2019 Unigas m03953ca
12/36
-
8/18/2019 Unigas m03953ca
13/36
TART SEQUENCE
Check the electronic ftamesupervision
unit is not in the “lockout” position. In the affirmative,reset
it.
Be certain the temperature and pressure controls are in the “closed” position.
Whenoii
has reached the temperature for starting, blower motor starts and pre-purging begins.
pre-purgin is to to be carried out with maximum air delivery, the burner contro1 circuit turns the air damper to the
max. position, iva the air servocontrol is fully open position, a signal to the electronic contro1 unit starts the pre-purge cycle,
which lasts 30 seconds.
During that period hot oil is circulated as far as the nozzle to ensure good ignition. After pre-purging, the air servocontrol
returns to the fully closed position,SO
that ignition takes place at the minimum firing rate.
Simultaneously the ignition transformer receives voltage and after 3 seconds pre-ignition) the pilot burner ignites and
is proven following which the 3 port valve is energised. Theoil
flows to the atomizing nozzle and ignites, being controlled
by the pressure regulator.
Now the burner is operating at the minimum firing rate (about 30% of the max. firing rate). Afterwards, the air servocontrol
runs to the low flame position and, in case the temperaturecontro1
should be set for the max. firing rate, to the air damper ,
fully open position, while the atomizing nozzte is fed at the max. pressure. which is supplied by the regulator being fully
ctosed via the cam: maximum firing rate is thus reached.
Irrespective of heat required, the contro1 unit continues its programme to the end and retums to its start position for the
next cycle, which will be performed after the burner idle time caused by limit or response switches.
43
-
8/18/2019 Unigas m03953ca
14/36
iiiiii
-
8/18/2019 Unigas m03953ca
15/36
GAS IRING ,
1) Isolate the main gas train and operate the burner sequence and ensure that the pilot burner Iights reliably and is capable
of lighting the main flame under all conditions. At the appropriate time the flame safeguard will go to lockout when the
main
ftame does not ignite.
2) With the gas butterfly contro1 valve setto approx 15” open the main gas supply, run the burner sequence, and the burner will ignite on Iow fire.
3) As soon as pratica1 advance the burner to the high fire position and ensure that the gase contro1 valve is fully open - adjust
themain
gas governor to give the rated input by observing the gas meter.
By adjusting the ratio cam for the gas contro1 valve the bumer can now be set throughout its modulating range using
flue gas analysis instruments. Oxygen readings on high fire should be 3-4 and 5-6 % on low fire with zero CO. The
primary air adjustment can also be used for fine regulation of flame shape and excess air.
Adjustment of themain air damper is via the slotted lever.
AIR PRESSURE SWITCH S TTING
Loosen the screw VB. The regulating ring nut is to be setat the bottom of its scale. While the burner is operating, s w y
turn the regulating ring nut clockwise unti1 the burner stops. Then turn the ring back by two tums and re-start the burner.
Should the bumer go to lockout again, turn back by one more full turn.
Tighten the screwVB.
Figure 4.2
-
8/18/2019 Unigas m03953ca
16/36
L
DELIVERY ADJUSTMENT
Theoil
systemincludes:
AFuel
oil
Pump
By-passNozrle
(Retum FlowNozzle
C Oil Metering Valve
The diagram illustrates the fuel feeding system of these types of burners, which incorpora a by-pass nozzle with oil flow
regulation in its retum pipe.
The oil supply is varied by acting on the metering valve which determines the oil flow to the nozzle through the pressure
on the return line.
Max oli supply is therefore reached when the pressure in the suction line is about (25 bar oule Type .W2 and the return
is fully closed; min.oil
supply when the retumline
is fully open. Relevant pressure reading in the retumline
are as
follows.
TYPE W2
max. oil supply: 25 bar
min. oil supply: 9 10 bar
Rate of adjustment: 1 to 4
Figure 4.3
46
-
8/18/2019 Unigas m03953ca
17/36
R ARE TWO POSSIBILITIES
- The burner has already been adjusted for gas firing.
- The burner must be oil fired only.
TART FL ME S lTlN
upposing the.bumer has already been adjusted for gas firing:
start flame size is to be proportioned to the nozzle size and oil pressure measured at the regulator. Therefore choose
the most suitable nozzle fot the application, SO that during ignition the oil supply should be 113 of the max. one.
‘
When valves open, the pressure measured by the gauge fitted to the regulator must be of5 l
2 bar toallow
min. oil supply
to thenoule.
TO obtain that reading, act on the cam coupled with the air servocontrol.
Ouring start flame setting, it is advisable to interrupt the working cycle.
Air delivery has already been adjusted when burner has been set for gas firing.
Oil and air might not be mixed in the correct proportion, but a futther adjustment of air delivery is negligible as ignitiontime is limited by the interval of the servocontrol between ignition sequence and futther steps.
Before cartying out more operations, trip switch to resume the working cycle.
HIGH FLAME ADJUSTMENT
The servontrol tums the air damper (previously adjusted for gas firing only) to max. delivery. Simultaneously the pressure
egulator controlled by the sector cam is fully closed
and casues an increases in the pressure of the nozzlereturn
flow,
which
evelops max. firing rate.
As air is delivered at a fixed rate during gas firing, it might be necessary to correct max. oil supply. That can be obtained
by acting on the cam which controls the regulator, resulting in a variation of the oil firing rate, unti1 combustion readings
are found to be satisfactory.
-
8/18/2019 Unigas m03953ca
18/36
-
8/18/2019 Unigas m03953ca
19/36
MO UL TING DRIVE MOTOR:
1) The SQM 10 is always set to 90” operation via Cam ‘A’ which is preset at the factory.
2) The low fire position of the burner can be set on Cams ‘C’ or ‘E’ for gas and oil the small indicator arrow shows the position
of the motor in degrees.
3) Cam ‘l3’ is the setting for gas ignition flame.
4) Cam ‘D’ is the setting for oil ignition flame.
Figure 4.5
- HIGH FLAMEIl - IGNITION GAS
Ill - LOW FLAME
IV - IGNITION 01L
V - LOW FLAME OIL
VI - NOT USED
-
8/18/2019 Unigas m03953ca
20/36
BY PASSING NOZZLES TYPE FLUIDICS “W2”
Inlet
pressure 25 bar
Turn-down ratio 1: 4
Viscosity 5 cSt
R
500 790” Spray angle
5
Supply 25 bar supp y
357 ps
2
eturn
pressure
I
t ll 1 0 0 kg h
over
bar e
2 0 4 0 6 0 8 0
3 0 0 psi
Return pressure
2 0 0 psi
1 0 0 psi
100 % Output
Figure 4 - 6
-
8/18/2019 Unigas m03953ca
21/36
100
90
80
70
60
5 0
40
30
20
10
9
8
7
6
5
4
3
2
1
BURNER GAS THROUGPUT VERSUS HEAD PRESSURE
i
Ill
r I I
I
”
t 1
6 7 8 9 1 0 0 2 3 4 5 6 7 8 9 1 0 0 0 2
THROUGPUT Nm3/ h
Figure 4 - 7
24
-
8/18/2019 Unigas m03953ca
22/36
BURNERGASTHROUGPUTVERSUSHEADPRESSURE
MO L F22
I
THROUGPUT Nm3 h
Figure 4 9
3
-
8/18/2019 Unigas m03953ca
23/36
HEAVY OIL IRIN ONLY
l L N FILLING
Oi l
in the pre-heater is to be kept at 50” C approx.
Before starting the burner, set the regulating and oil temperature contro1 thermostats at 130” C and 1 IO “C respectively.
These values apply to fuel oil
with viscosity ranging from 25” to 50” E at 50°C.
TO fill the oil line (pre-heater, oil suction, feed to and return from the nozzle) proceed as follows:
1-
Cut offoil
electric heaters via theline
switch (off the contro1 panel).
2-
Link oil, interlock thermostat.
3-
Turn on the cock on the vent pipe of the pre-heater.
4-
Turnfuel
selector to the position “OIL”.
At this point the burner performs a complete start-up cycle. As soon as oil flows out of the vent pipe, throw the line switch
to the “ON” position and turn the cock off. If at the end of the first cycle, when burner goes to lockout and stops, oil has not
filled theline
yet, push reset contro1 button to repeat the cycle.
The line is full up when pressure gauge on the pump indicates about 25 bar., which is the pressure required for proper burner
operation.
TO obtain that reading, loosen or tighten the screw “4”.
A few minutes’ time is admitted to fill the oil line, but a longer time might damage the pump seals.
If the line is not full up, it is necessary to check the suction pipe.
Upon completion of filling, disconnect link and connect start-up thermostat there.
24
-
8/18/2019 Unigas m03953ca
24/36
UEL OIL THERMOSTATS
Figure 4.11
ADJUSTMENT PROCEDURE
140 80
130
@’
I
9 0
0 Q
120 100
110
\
140 8
130
90
{@’
0
120
110
J J
m
TR TCN
Remove the cover which encloses the thermostat and interlock switch (thermostat).
The pointer (2) controls the thermostat setting while the pointer (1) controls the interlock switch (thermostat).
The thermostat pointer (2) should be set at 190” C and then raised or lowered as required.
The coldoil
interlock switch-thermostat is controlled by the pointer (1).
This is setto prevent the burner from starting unti1 a minimum oil temperature is reached and should be set 20 - 25” below
the oil temperature setting on the Heater Contro1 Thermostat.
CAUTION: Do not set the cold oil interlock higher than the oil temperature.
Replace the cover which encloses the thermostat and interlock switch-thermostat.
HEATER CONTROL THERMOSTATHEATER CONTROL THERMOSTAT
TO regulate the thermostat use a screwdriver as shown. The temperature to be set can be determined from viscosityTO regulate the thermostat use a screwdriver as shown. The temperature to be set can be determined from viscosity
iagram. We suggest the actualoil
temperature be set precisely with the burner working using a mercury thermometer iniagram. We suggest the actual oil temperature be set precisely with the burner working using a mercury thermometer in
he pocket.he pocket.
Figure 4.12
-
8/18/2019 Unigas m03953ca
25/36
SUNTEC TA
Figure 13
SUCTION HEIGHT : Max. 0 5 bar Vacum 0 4 bar
advised to prevent air separation from oil.
RATEDSPEED : Max. 3600 rpm.
OPERATING VISCOSITY RANGE : 2 8 to 800 cSt.
INLET AND RETURN PRESSURE : Max 5 bar.
5 6
LEGEND:
1 Pump Suction2 Return
3
Nozzle4 Pressure Regulator
5 Vacuum Port
6 Pressure Gauge
7 Electric Heater
OIL LANCE SCHEMATIC
FLOW RETURN NEEDLE
OPERATING
2
3 PORT
AUXILIARY BLOCK HEATER
Figure
-
8/18/2019 Unigas m03953ca
26/36
OIL LANCE
NOZZL
E
PRE-PURG
Figure 4 15
N T ON
FI
Figure 4 16
-
8/18/2019 Unigas m03953ca
27/36
-
8/18/2019 Unigas m03953ca
28/36
OIL PRESSURE REGULATOR
f gaseous fuel was not available initiaily, the directions given to set the burnerfor gas firing also apply to oil firing, p rti ul rly
as far as combustion air adjustment is concerned
OIL SUPPLY PRESSURE SETTING
t is to be carried out during pre-purge time by tightening or loosening the socket headed screw RP on the oil pump. For
proper burner operation, the pressure reading indicated by the pressure gauge M must be 25 bar appox.
Figure 4 18
OIL PRESSURE REGULATORS lTIN
The shape given to the blade in the oil sector determines the oil supply to the nozzle.
The figure shows two possible shapes:
: blade shape before start flame setting
L2 : final shape after setting
v
LP
LP
Figure 4 19
RAB-DISTRIBUTOR BLOCK
AUXILIARY HEATER
Figure 4 20
-
8/18/2019 Unigas m03953ca
29/36
OIL PIPE CONNECTIONS
CARTRIDGEBELT TYPE HEATER
Figure 42
LEGEND
1 Flow2 Return
3 Needle operating port CARTRIDGE P P HEATER
BELT TYPE HEATER
HASBESTOS HOS Figure 4 22
-
8/18/2019 Unigas m03953ca
30/36
THERE ARE TWO POSSIBILITIES:
1 The burner has already been adjusted for gas firing.
2 The burner must beoil
fired only.
START FLAME S TTIN
Supposing the burner has already been adjusted for gas firing:
Start flame size is to be proportioned to the nozzle size and oil pressure measured at the regulator. Therefore choose
the most suitable nozzle for the application, SO that during ignition the oil supply should be one third of the max. one.
When valve opens, the pressure measured by the gauge fitted to the regulator must be of 5-l 2 bar to allow min.oil
supply
to the nozzle.
TO obtain that reading, act on the cam oupled with the air servocontrol.
During start flame setting, it is advisable to interrupt the working cycle.
Air delivery has already been adjusted when has been set for gas firing.Oil and air might not be mixed in the correct proportion but a further adjustment of air delivery is negligible as ignition
time is limited by the intetval of the servocontrol between ignition sequen e and further steps.
HIGH FLAME ADJUSTMENT
The servocontrol turns the air damper (previously adjusted for gas firing only) to max. delivery. Simultaneously the
pressure regulator controlled by the se tor is fully closed and uses an increase in the pressure of the nozzle return
flow, which develops max. firing rate.
As air is delivered at a fixed rate during gas firing, it maight be ne ess ry to correct max. oil supply. That can be obtained
by acting on the cam which controls the regulator resulting in a variation of the oil firing rate, unti1 combustion readings
are found to be satisfactory.
LOW FLAME ADJUSTMENT
Please, refer to gas firing as well.
Oil
supply regulation is carried out by rotating the cam that controls the oil return pressure regualtor unti1 the pressure
reading corresponds to the correct quantity of oil required to burn the air delivered at low flame rating (already adjusted
during gas firing).
3A
-
8/18/2019 Unigas m03953ca
31/36
MINIMUM SUPPLY TEMPERATURE TO THE BURNER ACCORDING TO GRADE OF FUEL OIL
100908 0
I I I I I Il
l t MT”
10
98
7
6
i i i i i
1 0 2 0 3 0 4 0 5 0 6 0 8 0
TEMPERATURE “C
Figure 4 23
The burners must be supplied with oil having a min. temperature at the pump inlet according to the above diagram with
relation to the grade of oil being used.
For example: oil being used 7” E, 15” E, 50” E at 50” C the inlet temperature to the pump must be respectively 35” C,
50” C, and 77” C as indicated by the diagram.
32
-
8/18/2019 Unigas m03953ca
32/36
GAS TRAINS
The gas train will be supplied in a straight line arrangement and a special DWG and schematic will be provided with each
contract.
There will effectively be a main gas tr in and a pilot train the pilot can be either natura1 gas or L.P.G.
All components will comply with loca1 standards.
CONTROL PANEL
This is normally supplied as a remote oòr standing unit c/w following
1) Flame safeguard
2) Motor starters fuses
3) Necessary lamps switches
4) Necessary relays timers
5) Modulating ontroller
6) All components wired to a terminal strip7) Pane1 vol tor
A spe ifi schematic and wiring diagram will be provided for each contract.
For any further information please contact our
as shown at the front of this manual.
engineering department at the following address quoting the full specification
-
8/18/2019 Unigas m03953ca
33/36
-
8/18/2019 Unigas m03953ca
34/36
-
8/18/2019 Unigas m03953ca
35/36
-
8/18/2019 Unigas m03953ca
36/36