variable flow chiller plant design

28
VARIABLE FLOW CHILLER PLANT DESIGN Julian de Bullet Julian de Bullet ASHRAE Distinguished Lecturer julian@debullet com julian@debullet.com VARIABLE FLOW CHILLER PLANT DESIGN Please mute cell phones

Upload: kdpmansi

Post on 21-Jul-2016

82 views

Category:

Documents


18 download

DESCRIPTION

chiller design

TRANSCRIPT

Page 1: Variable Flow Chiller Plant Design

VARIABLE FLOW CHILLER PLANT DESIGN

Julian de BulletJulian de BulletASHRAE Distinguished Lecturer

julian@debullet [email protected] FLOW CHILLER PLANT

DESIGN

Please mute cell phones

Page 2: Variable Flow Chiller Plant Design

Standard 90.1

Code intended ANSI Code intended, ANSI approved, mandatory language, consensus document

Co-developed with IES

Under continuous maintenance and uses ISCs

On code cycle

Includes both Includes both prescriptive and performance paths

Page 3: Variable Flow Chiller Plant Design

Std 90.1 - Purpose

“ provide minimum requirements ...provide minimum requirements for the energy-efficient design of buildings except low-rise buildings except low rise residential buildings”

Std 90.2 Deals With Low Rise Residential Buildings

Guideline 18 Deals With Advanced Energy Efficient Designs

VARIABLE FLOW CHILLER PLANT DESIGN

Page 4: Variable Flow Chiller Plant Design

4

Page 5: Variable Flow Chiller Plant Design

Chiller Basics

Air, Water Or Evaporatively Cooled

Reciprocating, Scroll, Screw Or Centrifugal Compressors

DX or Flooded EvaporatorsEvaporators

VARIABLE FLOW CHILLER PLANT DESIGN

Page 6: Variable Flow Chiller Plant Design

Cooling Tower Basics

Induced Draft TowerForced Draft Tower

VARIABLE FLOW CHILLER PLANT DESIGN

Page 7: Variable Flow Chiller Plant Design

Load Basics

Chilled Water Coils Transfer Heat From Building Air To Chilled Water

Process Loads Cooling Jackets Cooling Jackets

VARIABLE FLOW CHILLER PLANT DESIGN

Page 8: Variable Flow Chiller Plant Design

HVAC Controls

BACnetAS

H R

E

A ™BACnetE

WebWeb based?based?

OPEN PROTOCOL IS A NORM!

WebWeb--based?based?

VARIABLE FLOW CHILLER PLANT DESIGN

OPEN PROTOCOL IS A NORM!

Page 9: Variable Flow Chiller Plant Design

Basic System

Building Load

Condenser Water Loop

Cooling TowerChill d W t PChilled Water Pump

Chilled Water LoopChillerCondenser Water PumpWater Pump

VARIABLE FLOW CHILLER PLANT DESIGN

Page 10: Variable Flow Chiller Plant Design

Full Load Vs. Annual Load

Chiller58% Chiller

33%Fans43%43%

Design Performance

Tower5%

Fans24%

Pumps13%

Annual Energy Usage

Pumps22%

Tower2%

g gy g

VARIABLE FLOW CHILLER PLANT DESIGN

Page 11: Variable Flow Chiller Plant Design

The Industry ARI Standard

Part Load Analysis (IPLV)Part Load Analysis (IPLV)% Load Old % Hrs New % Hrs

100 17 1100 17 175 39 4250 33 4525 11 12

Systems SolutionSystems Solution

VARIABLE FLOW CHILLER PLANT DESIGN

Page 12: Variable Flow Chiller Plant Design

HVAC HVAC -- Prescriptive Method (6.3) Prescriptive Method (6.3)

HydronicHydronic Systems (6.3.4)!!!!!Systems (6.3.4)!!!!!

Variable Flow Required For Systems Over 10 HP (6.4.3.1)10 HP (6.4.3.1)– Modulate Down To 50%

Exceptions– Where Minimum Flow Is Less Than Flow

Required By Equipment And < 75HP Individual Variable Flow Pumps p

> 100 Feet And 50 hp Motor– 30% Design Wattage At 50% Flow– Controlled As A Function Of Flow Or Pressure

VARIABLE FLOW CHILLER PLANT DESIGN

– Controlled As A Function Of Flow Or Pressure Differential

Page 13: Variable Flow Chiller Plant Design

Why Variable Chilled Water Flow?

Pi i A d P B d O D i Piping And Pumps Based On Design Load Rather Than Connected Load

Lower First Cost

Lower Operating Cost

VARIABLE FLOW CHILLER PLANT DESIGN

Page 14: Variable Flow Chiller Plant Design

Primary/Secondary Design

Primary PumpTyp One Per Chiller

DecouplerBuilding Load2 Way Valves

Condenser Water PumpTyp One Per Chiller

Cooling Tower

Chilled Water Loop

Secondary PumpVariable Flow

Flow Varies With Load

VARIABLE FLOW CHILLER PLANT DESIGN

Page 15: Variable Flow Chiller Plant Design

Primary/Secondary Design

ProsPros Variable Flow Through Secondary Loop Stable Constant Flow through Chillers Stable Constant Flow through Chillers

ConsCons C l it Complexity Low Delta T Syndrome Stepped Primary Flow

(More Pump Work Than Variable Primary Flow)

VARIABLE FLOW CHILLER PLANT DESIGN

Page 16: Variable Flow Chiller Plant Design

Low Delta T-Definition

A Condition Whereby a Low Chilled Water Return Temperature Causes an Temperature Causes an Excessive Amount of Chilled Water to Circulate to Meet System Cooling Loads and System Cooling Loads and Chillers Receiving the Low Temperature CHR CANNOT be pLoaded to Their Design Capacity

VARIABLE FLOW CHILLER PLANT DESIGN

Page 17: Variable Flow Chiller Plant Design

Low Delta T Syndrome

Low Delta T Symptoms And SolutionsLow Delta T Symptoms And Solutions 3 Way Valves

Don’t Use Them

Supply Air Setpoints Lowered Beyond Design Valves Go Wide Open - No Control Ensure Valves Are Tracking

Valves Not Closed When Not Required Ensure Valves Close When AHU Not In Use

All System Components Not Designed For Same Delta T

VARIABLE FLOW CHILLER PLANT DESIGN

Page 18: Variable Flow Chiller Plant Design

Low Delta T Syndrome

Low Delta T Symptoms And Low Delta T Symptoms And Solutions Cont’dSolutions Cont’d

Coils And Valves Not Properly Selected Select Correctly

Coils Piped “Backwards” Coils Must Be Piped So Water Is Counterflow To Air

Improper Tertiary Piping Ensure Tertiary Setpoint Is Above Chilled Water

SetpointSetpoint

Dirty Coils- Clean the Coils

VARIABLE FLOW CHILLER PLANT DESIGN

Page 19: Variable Flow Chiller Plant Design

Low Delta T Syndrome

Low Delta T Retrofit Solutions Cont’dLow Delta T Retrofit Solutions Cont’d

VFD Or Dual Compressor Chillers Excellent Part Load Performance Allows Two Chillers To

Operate More Efficiently Even With Parasitic Losses

Oversize Primary Pumps Oversized Primary Pumps With VFDs Can Over Pump Oversized Primary Pumps With VFDs Can Over Pump

Chillers And Avoid Starting Additional Machines

Variable Primary Flow Variable Primary Flow Easily Accommodates Over Pumping Chillers

VARIABLE FLOW CHILLER PLANT DESIGN

Page 20: Variable Flow Chiller Plant Design

Low Delta T Syndrome

Low Delta T Retrofit Solutions Cont’dLow Delta T Retrofit Solutions Cont’d

Reduce Delta T On Primary Side Larger Pumps And Piping Will Increase Capital Cost Penalty At Full Load

Add Flow Control Valves At Each Coil Ensures Terminal Device Doesn’t Exceed Design Flow Ensures Terminal Device Doesn t Exceed Design Flow Space Cooling Not Satisfied Increase System Pressure Drop Adds Cost Adds Cost

Any More Fixes???yVARIABLE FLOW CHILLER PLANT

DESIGN

Page 21: Variable Flow Chiller Plant Design

Low Delta T SyndromeLow Delta T Retrofit Solutions ?Low Delta T Retrofit Solutions ?

Check Valve InDecoupler

Check Valve Puts Pumps In Series Potentially Over-pump Chiller Can Starve Building Doesn’t Fix Real Problem

VARIABLE FLOW CHILLER PLANT DESIGN

Page 22: Variable Flow Chiller Plant Design

Is it this Simple?

Eliminate De-coupling Lines:

Modern Chillers and Boilers can work with variable flowModern Chillers and Boilers can work with variable flow

Employ Pumps in Series:

Modern DDC controls can Coordinate Series Pumping

Load Flow Control:

Avoid any Overflow by using local Temperature Sensors on the Return Line and Limit the Valve

VARIABLE FLOW CHILLER PLANT DESIGNThe Hartman Company

Page 23: Variable Flow Chiller Plant Design

Variable Primary Flow Design

GeneralGeneral Primary Pump Operates When Chilled Water

Required

Condenser Pump And Tower Operate When Chiller Operates

2 Way Valves 2 Way Valves Diversity To Flow

Works With Single, Series And Parallel Chillers Works With Single, Series And Parallel Chillers

VARIABLE FLOW CHILLER PLANT DESIGN

Page 24: Variable Flow Chiller Plant Design

Variable Primary Flow Design

Bypass LineUsed to Ensure Minimum

Flow Through Chillers

Apply Diversity to FlowUse 2 Way ValvesVFD Primary Pump

Flow Meter

Automatic Isolating Valves

VARIABLE FLOW CHILLER PLANT DESIGN

Page 25: Variable Flow Chiller Plant Design

Variable Primary Flow Design

Design Flowrate Determined by Tube Velocity Minimum 1 5 FPS ( Based On A Reynolds # Of 7500) Minimum 1.5 FPS ( Based On A Reynolds # Of 7500)

Maximum 12 FPS

At Typical Conditions, 6-7 FPS At Typical Conditions, 6 7 FPS

Select Evaporator With More Passes & Higher Pressure Drop

Minimum Flow Typically 50% Or Less Of Design

Bypass Must Be Sized To Maintain Minimum Flow Rate Bypass Must Be Sized To Maintain Minimum Flow Rate Of Largest Chiller

VARIABLE FLOW CHILLER PLANT DESIGN

Page 26: Variable Flow Chiller Plant Design

When to consider VPF ?

When:

•System flow can be reduced by at least 30% of design•System flow can be reduced by at least 30% of design.

•Design affords greater cost savings than a “de-coupled” system.

•Operators will understand how the system works and will run it properly.

•The system can tolerate a modest variation in supply water temperature.y pp y p

•A single chiller is being replaced and the primary flow can be varied.

•Variable Flow can be applied to Parallel as well as Series Flow.

VARIABLE FLOW CHILLER PLANT DESIGN

Page 27: Variable Flow Chiller Plant Design

VPF vs. P/S

450000

500000

300000

350000

400000

200000

250000

300000

kWh

100000

150000

00000

0

50000

Chillers Pumps Towers FansC e s u ps o e s a s

Variable Primary Flow 2 Chiller Primary/Secondary Flow 2 Chiller Parallel FlowVARIABLE FLOW CHILLER PLANT

DESIGN

Page 28: Variable Flow Chiller Plant Design

Evaluations - Your Feedback Is important!

Before you leave Before you leave this session please complete evaluation form.

VARIABLE FLOW CHILLER PLANT DESIGN