DUALJET 20 DUALJET 30 DUALJET 40 DUALJET 50 IDJULJ 1207 - 6339500_00 VENTILCONVETTORI A MANDATA CONTROLLATA - Manuale installazione CONTROLLED OUTLET FAN COIL - Installation Manual VENTILO-CONVECTEURS À REFOULEMENT CONTRÔLÉ - Manuel d’installation GEBLÄSEKONVEKTOREN MIT KONTROLLIERTER ZULUFT - Installationsanleitung FAN COILS CON VENTILACIÓN CONTROLADA - Manual de instalación DUALJET

Upload: others

Post on 26-Apr-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: VENTILCONVETTORI A MANDATA CONTROLLATA - Manuale … · 2019-11-25 · AERMEC S.p.A. declines all responsibility for any damage whatsoever caused by improper use of the machine, and

DUALJET 20DUALJET 30DUALJET 40DUALJET 50

IDJULJ 1207 - 6339500_00

VENTILCONVETTORI A MANDATA CONTROLLATA - Manuale installazioneCONTROLLED OUTLET FAN COIL - Installation Manual

VENTILO-CONVECTEURS À REFOULEMENT CONTRÔLÉ - Manuel d’installationGEBLÄSEKONVEKTOREN MIT KONTROLLIERTER ZULUFT - InstallationsanleitungFAN COILS CON VENTILACIÓN CONTROLADA - Manual de instalación

DUALJET

Page 2: VENTILCONVETTORI A MANDATA CONTROLLATA - Manuale … · 2019-11-25 · AERMEC S.p.A. declines all responsibility for any damage whatsoever caused by improper use of the machine, and

2 IDJULJ 1207 - 6339500_00

Conservare i manuali in luogo asciutto, per evitare il deterio-ramento, per almeno 10 anni per eventuali riferimenti futuri.Leggere attentamente e completamente tutte le informa-zioni contenute in questo manuale. Prestare particolarmen-te attenzione alle norme d’uso accompagnate dalle scritte “PERICOLO” o “ATTENZIONE” in quanto, se non osservate, possono causare danno alla macchina e/o a persone e cose.Per anomalie non contemplate da questo manuale, interpellare tempestivamente il Servizio Assistenza di zona.L'apparecchio deve essere installato in maniera tale da rende-

re possibili operazioni di manutenzione e/o riparazione.La garanzia dell'apparecchio non copre in ogni caso i costi dovuti ad autoscale, ponteggi o altri sistemi di elevazione che si rendesero necessari per effettuare gli interventi in garanzia.AERMEC S.p.A. declina ogni responsabilità per qualsiasi danno dovuto ad un uso improprio della macchina, ad una lettura parziale o superficiale delle informazioni contenute in questo manuale.Il numero di pagine di questo manuale è: 80.

OSSERVAZIONI

Store the manuals in a dry location to avoid deterioration, as they must be kept for at least 10 years for any future reference.All the information in this manual must be carefully read and understood. Pay particular attention to the operating stan-dards with “DANGER” or “WARNING” signals as failure to comply with them can cause damage to the machine and/or persons or objects.If any malfunctions are not included in this manual, contact the local After-sales Service immediately.The apparatus must be installed in such a way that maintenan-

ce and/or repair operations are possible.The apparatus's warranty does not in any case cover costs due to automatic ladders, scaffolding or other lifting systems neces-sary for carrying out repairs under guarantee.AERMEC S.p.A. declines all responsibility for any damage whatsoever caused by improper use of the machine, and a par-tial or superficial acquaintance with the information contained in this manual.The number of pages in this manual is : 80.

REMARKS

Conserver les manuels dans un endroit sec, afin d’éviter leur détérioration, pendant au moins 10 ans, pour toutes éventuel-les consultations futures.Lire attentivement et entièrement toutes les informations con-tenues dans ce manuel. Prêter une attention particulière aux normes d’utilisation signalées par les inscriptions “DANGER” ou “ATTENTION”, car leur non observance pourrait causer un dommage à l’appareil et/ou aux personnes et objets.Pour toute anomalie non mentionnée dans ce manuel, contac-ter aussitôt le service après-vente de votre secteur.Lors de l'installation de l'appareil, il faut prévoir l'espace

nécessaire pour les opérations d'entretien et/ou de réparation.La garantie de l'appareil ne couvre pas les coûts dérivant de l'utilisation de voitures avec échelle mécanique, d'échafauda-ges ou d'autres systèmes de levée employés pour effectuer des interventions en garantie.AERMEC S.p.A. décline toute responsabilité pour tout domma-ge dû à une utilisation impropre de l’appareil et à une lecture partielle ou superficielle des informations contenues dans ce manuel.Ce manuel se compose de pages: 80.

REMARQUES

Guarde los manuales en un lugar seco para evitar su deterioro, al menos durante 10 años, por si fuera posible consultarlos en el futuro.Leer atenta y completamente todas las informaciones con-tenidas en este manual. Preste particular atención a las nor-mas de uso acompañadas de las indicaciones “PELIGRO” o “ATENCIÓN” puesto que, si no se cumplen, pueden causar el deterioro de la máquina y/o daños personales y materiales.En caso de anomalías no contempladas en este manual, con-tacte inmediatamente con el Servicio de Asistencia de su zona.El aparato debe ser instalado de manera que haga posibles las

operaciones de mantenimiento y/o reparación.En cualquier caso, la garantía del aparato no cubre los costes derivados del uso de escaleras automáticas, andamios u otros sistemas de elevación necesarios para efectuar las intervencio-nes en garantía.AERMEC S.p.A. declina cualquier responsabilidad por cual-quier daño debido a un uso impropio de la máquina, o bien a una lectura parcial o superficial de las informaciones conteni-das en este manual.Número de páginas de este manual: 80

OBSERVACIONES

Bewah ren S i e d i e Geb rauchsan l e i t ungen m in -d e s t e n s 1 0 J a h r e f ü r e v e n t u e l l e s z u k ü n f t i -ges Nachschlagen an e inem t rockenen Ort auf .Alle in diesem Handbuch enthaltenen Informationen aufmerksam und vollständig lesen. Insbesondere auf die Benutzungsanweisungen mit den Hinweisen "VORSICHT" oder "ACHTUNG" achten, da deren Nichtbeachtung Schäden am Gerät bzw. Sach- und Personenschäden zur Folge haben kann.Bei Betriebsstörungen, die in dieser Gebrauchsanweisung nicht aufgeführt sind, wenden Sie sich umgehend an die zuständige

Kundendienststelle.Das Gerät so aufstellen, dass Instandhaltungs- und/oder Reparaturarbeiten durchgeführt werden können.Die Garantie des Gerätes deckt in keinem Fall Kosten für Feuerwehrleitern, Gerüste oder andere Hebesysteme ab, die sich für die Garantiearbeiten als erforderlich erweisen sollten.Die AERMEC S.p.A. übernimmt keine Haftung für Schäden aus dem unsachgemäßen Gebrauch des Gerätes und der teilweisen oder oberflächlichen Lektüre der in diesem Handbuch enthal-tenen Informationen.Die Seitenanzahl diese Handbuches ist: Nr. 80 Seiten

HINWEISE

Page 3: VENTILCONVETTORI A MANDATA CONTROLLATA - Manuale … · 2019-11-25 · AERMEC S.p.A. declines all responsibility for any damage whatsoever caused by improper use of the machine, and

DUALJETAERMEC S.p.A.I-37040 Bevilacqua (VR) Italia – Via Roma, 996Tel. (+39) 0442 633111Telefax (+39) 0442 93730 – (+39) 0442 93566www.aermec.com - [email protected]

DICHIARAZIONE DI CONFORMITÀ Noi, firmatari della presente, dichiariamo sotto la nostra esclusiva responsabilità, che il prodotto:VENTILCONVETTORE serie DUALJET

al quale questa dichiarazione si riferisce è conforme alle seguenti norme armonizzate:

CONFORMITY DECLARATIONWe the undersigned declare, under our own exclusive responsibility, that the product:FAN COIL DUALJET seriesto which this declaration refers, complies with the following standardised regulations:

CERTIFICAT DE CONFORMITÉ Nous soussignés déclarons sous notre exclusive responsabilité que le produit:VENTILO-CONVECTEURS série DUALJETauquel cette déclaration fait référence, est conforme aux normes harmonisées suivantes:

KONFORMITÄTSERKLÄRUNG Wir, die hier Unterzeichnenden, erklären auf unsere ausschließlich Verantwortung, dass das Produkt:GEBLÄSEKONVEKTOR der Serie DUALJET

auf das sich diese Erklärung bezieht, den folgenden harmonisierten Normen entspricht:

DECLARACIÓN DE CONFORMIDAD Los que suscriben la presente declaran bajo la propia y exclusiva responsabilidad que el conjunto en objeto, definido como sigue:FAN COIL serie DUALJET

al que esta declaración se refiere, está en conformidad a las siguientes normas armonizadas:

Bevilacqua, 02/07/2012 La Direzione Commerciale – Sales and Marketing Director Luigi Zucchi

La persona autorizzata a costituire il fascicolo tecnico è: / The person authorized to compile the technical file is: / La personne autorisée à con-stituer le dossier technique est: / Die Person berechtigt, die technischen Unterlagen zusammenzustellen: Pierpaolo Cavallo

I-37040 Bevilacqua (VR) Italia - Via Roma, 996

soddisfando così i requisiti essenziali delle seguenti direttive:- Direttiva Bassa Tensione: LVD 2006/95/CE- Direttiva Compatibilità Elettromagnetica: EMC 2004/108/CE- Direttiva Macchine: 2006/42/CEDUALJET CON ACCESSORIE’ fatto divieto di mettere in servizio il prodotto dotato di accessori non di fornitura Aermec.

- CEI EN 60335-2-40- CEI EN 62233

- CEI EN 55014-1- CEI EN 55014-2- CEI EN 61000-6-1- CEI EN 61000-6-3

thus meeting the essential requisites of the following directives:- Low Voltage Directive: LVD 2006/95/EC- Electromagnetic Compatibility Directive: EMC 2004/108/EC- Machinery Directive: 2006/42/ECDUALJET WITH ACCESSORIESIt is not allowed to use the unit equipped with accessories not sup-plied by Aermec.

- EN 60335-2-40- EN 62233

- EN 55014-1- EN 55014-2- EN 61000-6-1- EN 61000-6-3

satisfaisant ainsi aux conditions essentielles des directives suivantes:- Directive Basse Tension: LVD 2006/95/CE- Directive compatibilité électromagnétique: EMC 2004/108/CE- Directive Machines: 2006/42/CEDUALJET PLUS ACCESSOIRESIl est interdit de faire fonctionner l'appareil avec des accessoires qui ne sont pas fournis de Aermec.

womit die grundlegenden Anforderungen folgender Richtlinien erfüllt werden:- Niederspannungsrichtlinie: LVD 2006/95/EG- Richtlinie zur elektromagnetischen Verträglichkeit: EMC 2004/108/EG- Maschinenrichtlinie: 2006/42/EGDUALJET + ZUBEHÖRFalls das Gerät mit Zubehörteilen ausgerüstet wird, die nicht von Aermec geliefert werden, ist dessen Inbetriebnahme solange untersagt.

- EN 60335-2-40- EN 62233

- EN 55014-1- EN 55014-2- EN 61000-6-1- EN 61000-6-3

- EN 60335-2-40- EN 62233

- EN 55014-1- EN 55014-2- EN 61000-6-1- EN 61000-6-3

al que esta declaración se refiere, está en conformidad a las siguientes normas armonizadas:- Directiva de Baja de Tensión: LVD 2006/95/CE- Directiva Compatibilidad Clectromagnétic: EMC 2004/108/CE- Directiva Máquinas: 2006/42/CEDUALJET CON ACCESORIOSEstá prohibido poner en marcha el producto con accesorios no suministrados por Aermec.

- EN 60335-2-40- EN 62233

- EN 55014-1- EN 55014-2- EN 61000-6-1- EN 61000-6-3

Page 4: VENTILCONVETTORI A MANDATA CONTROLLATA - Manuale … · 2019-11-25 · AERMEC S.p.A. declines all responsibility for any damage whatsoever caused by improper use of the machine, and

4 IDJULJ 1207 - 6339500_00

TRASPORTO • TRANSPORT • TRANSPORT • TRANSPORT • TRANSPORTE

NON bagnare. Tenere al riparo dalla pioggia.

KEEP DRY. Keep out of the rain.

NE PAS mouiller. Tenir à l’abri de la pluie.

NICHT nass machen. Vor Regen geschützt

anbringen

NO mojar. Conservar protegido

de la lluvia.

NON calpestare. DO NOT step on unit.NE PAS marcher sur

l’appareil. NICHT betreten . NO pisar.

NSovrapponibilità: con-trollare sull’imballo per conoscere il numero di macchine impilabili.

Stackability: check the package to know the number of stackable

machines.

Empilement : vérifier sur l’emballage le nombre d’appareils empilables.

Stapelbarkeit: Auf der Verpackung nachse-hen, wie die Anzahl

der stapelbaren Geräte lautet.

Superponibilidad: observar en el

embalaje la canti-dad de máquinas que pueden api-

larse.

>25Kg

NON trasportare la macchina da soli se il suo peso supera i

25Kg.

DO NOT carry the equipment alone if

weight exceeds 25Kg.

NE PAS faire transporter l’appareil par une seule personne si son poids est supérieur à 25kg.

NICHT das Gerät allein transportieren,

wenn sein Gewicht die 25kg übersteigt.

NO transportar la máquina solos si su peso es superior a

los 25Kg.

NON lasciare gli imballi sciolti durante

il trasporto.Non rovesciare.

DO NOT leave boxes unsecured during

transportation.Do not overturn.

NE PAS laisser les emballages sans

attaches durant le transport.

Ne pas renverser.

NICHT die Verpackungen wäh-rend des Transports

geöffnet lassen.Nicht stürzen.

NO dejar los embalajes sin

sujetar durante el transporte.No invertir.

Fragile, maneggiare con cura.

Fragile, handle with care.

Fragile, manipuler avec soin.

Zerbrechlich, sorgfältig handhaben.

Frágil, manipular con cuidado.

SIMBOLI DI SICUREZZA • SAFETY SYMBOL • SIMBOIES DE SECURITE SICHERHEITSSYMBOLEOLE • SÍMBOLOS DE SEGURIDAD

Pericolo:Tensione

Danger:Power supply

Danger:Tension

Gefahr !Spannung

Peligro:Tensión

Pericolo:Organi in movimento

Danger: Movings parts

Danger: Organes en mouvement

Gefahr !Rotierende Teile

Peligro:Elementos en movimiento

Pericolo!!! Danger!!! Danger!!! Gefahr!!! Peligro!!!

Imballo: indicazioni per trasporto e stoccaggio

Packing: indications for transport and storage

Emballage: signes pour le transport et le

stockage

Verpackung: Anzei-chen für Transport und

Lagerung

Embalajes: indicacio-nes para el transporte

y almacenamiento

Page 5: VENTILCONVETTORI A MANDATA CONTROLLATA - Manuale … · 2019-11-25 · AERMEC S.p.A. declines all responsibility for any damage whatsoever caused by improper use of the machine, and

Engl

ish

18 IDJULJ 1207 - 6339500_00

INDEX

Transport • Safety symbols 3

Declaration of conformity 4

Important information and maintenance • Operating limits • Packaging • Use 19

Description 20

Versions • Thermostat • Description of functions 21

Control of 2 pipe systems 22

TTL network settings • Installation information 23

Installation of the unit 24

Rotating the coil 26

Connections 27

Dip-Switch settings 28

Thermostat technical characteristics • Thermostat connection specification 29

Electrical connections 70

Dimensional data 72

Electrical schematic 73

PROBLEM SOLVING 75

Page 6: VENTILCONVETTORI A MANDATA CONTROLLATA - Manuale … · 2019-11-25 · AERMEC S.p.A. declines all responsibility for any damage whatsoever caused by improper use of the machine, and

Engl

ish

19IDJULJ 1207 - 6339500_00

The fan coil units are shipped in standard packaging which consists of expanded polystyrene foam and cardboard.

PACKAGING

WARNING: The fan coil unit is connect-ed to the power supply network and the hydraulic circuit. Any intervention by per-sonnel not technically qualified can result in injury to the operator and damage to the unit and the surrounding environment. WARNING: Do not allow the unit to be used by children or incapacitated people without suitable supervision. It is reminded that the unit must not be used as a toy by children. ONLY PROVIDE A POWER SUPPLY OF 230V ~ 50HZ TO THE FAN COIL UNITUsing other power supply ratings can cause irreparable damage to the fan coil unit. DO NOT USE THE FAN COIL UNIT IMPROPERLYDo not use the fan coil unit in animal hus-bandry applications. VENTILATING THE ROOMPeriodically air the room in which the fan coil unit has been installed; this is par-ticularly important if the room is occupied by many people, or if gas appliances or sources of odours are present.CORRECTLY CONTROLLING THE TEMPERA-TUREThe room temperature should be controlled in order to provide maximum comfort to the people in the room, especially if they are elderly, children or ill, avoiding sudden

changes in temperature between the out-side and inside above 7 °C in summer. A too low temperature will lead to increased electrical consumption in the summer.CORRECTLY ADJUSTING THE AIR JETThe air coming out of the fan coil unit must not strike people directly; in fact, even if at a temperature that is higher than the room temperature, it could cause a cold sensa-tion and resulting discomfort.DURING OPERATIONAlways leave the filter in the fan coil unit during operation otherwise dust in the air will dirty the surfaces of the coil. WHAT IS NORMALDuring cooling, water vapour may be pre-sent in the air discharge.During heating it might be possible to hear a slight hiss around the fan coil unit. Sometimes the fan coil unit might give off unpleasant smells due to the accumula-tion of substances from the air of the room (especially if the room is not ventilated regularly. Clean the filter more often).During operation, there could be noises and creaks inside the unit, due to the ther-mal expansion of the various components (plastic and metallic), but this does not indicate a malfunction and does not cause damage to the unit unless the maximum input water temperature is exceeded.

MAINTENANCEDO NOT USE TOO HOT WATER Use a soft cloth or sponge with water at a maximum of 40 °C to clean the fan coil unit. Do not use chemical products or sol-vents on any parts of the fan coil unit. Do not splash water on interior or exterior surfaces of the fan coil unit (it could cause short circuits).PERIODIC FILTER CLEANINGFrequent filter cleaning ensures a better operating efficiency. Check if the filter is very dirty: in this case increase the cleaning frequency. Clean frequently by removing the accumu-lated dust with a vacuum cleaner.When the filter is clean refit it to the fan coil unit reversing the removal procedure. SPECIAL CLEANINGThe possibility of removing the fan coil unit inspection panels (carried out only by per-sonnel suitably qualified) allows detailed cleaning of the internal parts, particularly for installations with high occupancy or requiring elevated hygiene standards.

IMPORTANT INFORMATION AND MAINTENANCE

Refer to the control panel manual for operating use and installation.

USE

If the fan coil unit operates continuously in cooling mode in a room with high relative humidity, condensate might form on the air discharge and unit casing. This condensate might be deposited on the floor and on any objects underneath. To prevent the formation of condensation on the exterior of the unit

while the fan is operating, the average water temperature should not drop below the operating limits shown in the table below, determined by the room ambient conditions. These limits refer to unit operation with fan at minimum speed.In the case of prolonged periods with the fan

switched off and cold water passing through the coil the formation of condensate on the unit casing is possible. In this case the installation of the 3 way valve accessory is recommended.

In order to avoid air stratification and therefore achieve better mixing it is advised not supply the fan coil unit with water hotter than 65°C. The use of very hot water could cause

creaking due to the thermal expansion of the different components (plastics and metals). This does not cause damage to the unit if the maximum operating temperature is not

exceeded.

OPERATING LIMITSDUALJET 20 30 40 50

Maximum water inlet temperature 80°C

Maximum operating pressure 8 barAmbient temperature limits (Ta) 0°C < Ta < 40°CAmbient relative humidity limits (RH) RH < 85%Power supply 230V ( ±10% ) ~ 50Hz

MINIMUM AVERAGE WATER TEMPERATURE [°C]Ambient dry bulb temperature

21 23 25 27 29 31

Ambient wet bulb temperature

15 3 3 3 3 3 3

17 3 3 3 3 3 3

19 3 3 3 3 3 3

21 6 5 4 3 3 3

23 - 8 7 6 5 5

Minimum average water temperature

Water temperature

Page 7: VENTILCONVETTORI A MANDATA CONTROLLATA - Manuale … · 2019-11-25 · AERMEC S.p.A. declines all responsibility for any damage whatsoever caused by improper use of the machine, and

Engl

ish

20 IDJULJ 1207 - 6339500_00

• Fan coil unit with controlled discharge available in 4 sizes:

- Vertical installation: DUALJET: without control panel but

with VMF thermostat, ready for network installation as Slave unit, or as stand alone or Master unit if combined with cabled accessory panel VMF-E4 / VMF-E4D or unit mounted control panel VMF-E2DJ.

• All units compatible with the VMF system.

• Discharge air change-over, either frontal or upwards, by selector on the unit.

• Frontal discharge for operation in heating in the winter season.

• Upwards discharge for operation in cooling in the summer season.

• Version with 3 row coil (sizes 20, 30, 40, 50)

• 3 speed fan group• Full compliance with safety standards• Smooth lines•Metal protective casing with polyester

anti-corrosion paint• Feet in plastic material available as an

accessory•Low noise operation

• Low pressure drop in the heat exchanger coils

• Electric motors with fitted permanent capacitors

• Ease of installation and maintenance•Air filter easily extracted and cleaned• Removable panels for easy and effective

cleaning• Site reversible hydraulic connections.

Characteristics

White colour:casing: RAL 9002top and feet: RAL 7044

Fan coil unit with controlled discharge

Comfort everywhereOptimal distribution of the air in the space as a function of operating mode. In each season the temperature of the air in the room will be homogenous at all heights avoiding the unpleasant effect of stratification.In winter operation the flow of air is

directed towards the floor, in summer operation the flow of air is directed towards the ceiling.The user can decide at any moment where to direct the flow of air.

Low noise operationThe extremely low noise ventilation take the Aermec fan coil units to the pinnacle of acoustic comfort through the absence of noise peaks.

VMFAll the DUALJET fan coil units are equipped with VMF (Variable Multi Flow) thermostat; the control and management system of hydronic installations for the conditioning, heating and production of domestic hot water.The VMF system allows complete control of every component of a

hydronic installation both locally and in a centralised way and, using the communication between the various components of the installation, manages the performance without ever ignoring the required comfort of the final user, achieving this in the most efficient way with consequent energy savings.Adding the advantages of such an innovative controller to the flexibility of

a hydronic installation gives a more effective and efficient alternative to variable refrigerant flow installations (VRF).The VMF system is extremely flexible to the point of allowing various steps of control and management, expandible at any time.

DUALJET: Comfort everywhereOne of the main causes of discomfort is the perception of a non-homogenous vertical distribution of temperature in the

space. This is the situation that can happen in heating, during the winter season. The innovative DUALJET fan coil unit is capable of offering a pleasurable feeling of comfort directing the air in such a

way as to offer a uniform distribution of temperature throughout the space.In the winter season the warm air is directed towards the floor, in the summer the cool air is directed towards the

ceiling.

DESCRIPTION

HEATINGCOOLING

Page 8: VENTILCONVETTORI A MANDATA CONTROLLATA - Manuale … · 2019-11-25 · AERMEC S.p.A. declines all responsibility for any damage whatsoever caused by improper use of the machine, and

Engl

ish

21IDJULJ 1207 - 6339500_00

• Operation in TTL networkThe VMF-E0DJ thermostat is designed to

communicate with other thermostats through a dedicated serial network based on the logic standard TTL. Such serial communication is indispensable for the exchange of information within small networks of fan coil units (up to a maximum of 6) for a maximum network length of 30 metres. This has been conceived to satisfy small zones where there are several fan coil units which require control from a single point.

Specifically in this network there is always a master to which the user interface (VMF-E2, VMF-E4) is con-nected, which controls the operation of the slaves connected to it, based on the settings made on the user interface.

The slave fan coil units are without con-trol panel and can be Dualjet or fan coil units equipped with a VMF type electronic board.

All the fan coil units on the TTL network have to be of the same configuration type. For example: all standard or all with the additional water coil.

The electronic board on each slave fan coil unit, as a function of the set-tings received from the network and the ambient conditions read by the sensors, autonomously from the other fan coil units ensures the ventilation is switched on or off to meet the user's desired conditions in the space.

• Operation in coolingThe operation in cooling requires a

water circuit with chiller.

• Operation in heating The operation in heating requires a

water circuit with boiler, heat pump or solar installation.

• Change Over (Seasonal change)The change of season is determined by

the user, opening or closing the louvres determines the operating mode:- louvres open = cooling mode- louvres closed = heating mode

To optimise the operation of an installa-tion with units connected on a network it is recommended to duplicate on the Slave units the position of the louvres on the Master unit.

Installation with 4 pipes appropriately position the louvres on the Slave units which have a different operating mode to the Master unit.

The operation is permitted with the following settings if the water sensor reads the following temperatures:

Ventilation

Range CoolDead band

Heat

Normal 17° 22° - 35° 39°

Reduced 22° 25° - 31° 35°

Water temperature in °C

If the anti-freeze function is set the unit is forced to operate only in heating mode.

- Control on water temperature Ventilation enabling on water side is

active only with water tempera-ture sensor. The thermostat identifies the limit enabling the ventilation in Heating mode (Minimum Control) and

in Cooling mode (Maximum Control), through the dip-switch it is possible to select between two temperature rang-es.

- Control on temperature air sideWhenever the measured ambient tem-

perature is below the set point by a value equal to the Dead band the unit operates in Heating mode.

Whenever the measured ambient tem-perature is above the set point by a value equal to the Dead band the unit operates in Cooling mode.

In networked fan coil units the dead band values are those configured on the master fan coil unit.

• Stop by loss of powerAfter a stop from loss of power the unit

will restart with the settings active before stopping.

• Delayed startingThe unit can delay the start of the venti-

lation after switching on, normally up to 2’40” (pre-heat function).

• Anti-freeze protectionControl in switched off position (OFF).

The fan coil unit can restart in heating mode (set point 12°C) if the ambient temperature drops below 7°C and the temperature of the water systems is appropriate.

In networked fan coil units the slave fan coil units can activate the anti-freeze protection independently from the set-tings of the master fan coil unit.

If anti-freeze protection is active on the master fan coil unit then even the slave fan coil units will assume the set point

Description of functions

The evolved electronic thermostat type VMF-E0DJ installed on the unit requires an internal interface to the fan coil unit (VMF-E2) or wall mounted (VMF-E4).

The thermostat is composed of:

• Type VMF thermostat board fitted within a protective box, complete with fused protection, dip-switch for configuration and connectors for connection to:- power supply - earth connection- valve control- fan-motor control- space temperature sensor- water temperature sensor- control panel (user interface)- external contact

- micro-switch connected to the louvres of the fan coil unit- fan coil unit serial network (TTL).

The thermostat allows control of:

• Three speed manual fan speed control.• Automatic fan mode as a function of

load.• Continuous or thermostatic ventilation

through control of the valves.• Display of season.• Display of alarms and ventilation

demand.• Up to two valves of ON/OFF type as

two or three way.• One sensor for air temperature.• One sensor for water temperature with

minimum and maximum temperature function.

• The change of season is decided by the user; opening or closing the louvres determines the operating mode:- louvres open = cooling mode - louvres closed = heating mode.

• Input for "external contact". This is a digital input with the following logic: - open = on - closed = off.

• Anti-freeze protection.• Communication with other thermo-

stats through a dedicated serial network based on the logic standard TTL.

THERMOSTAT FOR DUALJET FAN COIL UNIT (VMF-E0DJ)

DUALJET20 - DUALJET30 - DUALJET40 - DUALJET50 Fan coil units with dual discharge for vertical wall installation in internal spaces. The DUALJET fan coil units are equipped with evolved electronic thermostat from the VMF series.

VERSIONS

Page 9: VENTILCONVETTORI A MANDATA CONTROLLATA - Manuale … · 2019-11-25 · AERMEC S.p.A. declines all responsibility for any damage whatsoever caused by improper use of the machine, and

Engl

ish

22 IDJULJ 1207 - 6339500_00

12°C, independent from their ambient conditions.

During the anti-freeze protection opera-tion the fan coil units are always forced to work in heating mode.

In the case that the water temperature sensor is absent or if continuous venti-lation, the fan is always enabled.

In the case that the valve is present with water sensor mounted upstream, the pre-heating of the heat exchanger is still carried out.

• Ambient temperature sensorThe ambient temperature sensor is not

required on the slave because they can use the sensor on the master, although the ambient temperature sensor can be used on the slave to avoid the creation of a micro-climate.

If the ambient temperature sensor on the slave fan coil unit is faulty then in its absence the temperature read by the master sensor is used.

If the ambient temperature sensor on the master fan coil unit is faulty then the slave fan coil units not fitted with sen-sor will operate in emergency mode, whilst the fan coil units fitted with ambient temperature sensor will con-tinue to operate normally.

• Water temperature sensorThe unit is equipped with a water tem-

perature sensor in the heat exchanger. The fan coil unit can operate without

water sensor, and if absent (or faulty) the ventilation is always enabled.

- Installation in TTL networkThe slave fan coil unit can operate

without water sensor, and if absent (or faulty) the temperature reading is taken from the sensor on the master, in which case the slave fan coil unit ven-tilation is always enabled.

- Installation with valveTo position the bulb of the water tem-

perature sensor on the outlet tube upstream of the valve, the standard water sensor must be substituted with the accessory sensor VMF-SW.

The water temperature sensor can be positioned downstream or upstream of the control valve, and as a conse-quence the dip-switch on the board must be set. The difference consists in the control of ventilation of the fan coil units with valve.

Setting the dip-switch as sensor down-stream of the valve the ventilation is started based on the ambient air tem-perature.

Sett ing the dip-switch as sensor upstream of the valve the ventilation is started based on the water temperature of the system. This setting activates the pre-heating function and delayed start-ing of the ventilation, variable between 0” and 2’40”.

• Ambient sensor correctionTo obtain the best ambient temperature

control the thermostat applies correc-

tive algorithms of the ambient sensor mounted on the fan coil unit, which is influenced by being mounted in con-tact with the casing.

The dynamic correction is a corrective algorithm of the ambient sensor which takes into account the operating status of the fan coil unit. There are two pos-sible dynamic corrections available:

- Dynamic Correction B: for systems wi thout valve (or wi th sensor d o w n s t r e a m ) t h e c o r r e c t i o n depends on the water and ambient temperatures.

- Dynamic Correction A: for systems with valve and sensor upstream the correction depends on the valve and the water and ambient temperatures. Wi th respec t to the prev ious correction, this uses different time constants in calculating the correction to be applied (because the casing is affected differently).

• VentilationThe three speed ventilation can be con-

trolled both manually and automati-cally.

- Manual, selecting the speed V1, V2 and V3. The fan is cycled on-off at the selected velocity.

- Automatic, with selector in AUTO position. The speed of the fan is con-trolled as a function of the ambient conditions and the configuration of the fan coil unit.

Thermostat settings:- 3 level thermostat. AUTO selection. The ventilation speed

is maintained between the 3 prede-termined settings as a function of the difference between the ambient tem-perature and the set point. Once the set point is reached the ventilation is switched off.

- Modulating capacity thermostat. AUTO selection. The ventilation car-

ries out alternating velocity cycles as a function of the difference between the ambient temperature and set point. Once the set point is reached the ven-tilation is switched off. This setting is not compatible with continuous venti-lation control.

• Ventilation ControlVentilation settings:- Continuous ventilation. The ventilation

is always enabled. Temperature control is through interruption of the water flow to the fan coil unit.

WARNING: This function requires the water valve (accessory) and can-not be activated at the same time as the Modulating capacity thermostat option.

- Thermostatic ventilation. The ventila-tion is switched off on reaching the set temperature (set point).

• Valve control logicWith the settings Thermostatic ventila-

tion or Modulating capacity thermo-

stat the valve is controlled with the following logic:

- Heating, the valve is controlled to exploit the stack effect of the fan coil unit and distribute heat even with the ventilation switched off. These settings reduce the number of valve openings and closings, circulating hot water in the fan coil unit, and at the demand of the thermostat, ventilation is immedi-ate.

- Cooling, to best exploit the cooling capacity of the unit and effect more accurate control of the ambient tem-perature, the opening of the valve is phase-shifted with respect to the ven-tilation.

• External contactAn external contact is available on the

board to connect to. With the external contact closed the unit is configured as in the OFF position of the thermostat (except in the case of the thermostat being in Anti-freeze protection or that the ambient thermostat is absent or faulty). This contact can be used to as an input from a remote ON-OFF sig-nal, occupancy sensor, window con-tact, circulating pump failure signal, etc.

In networked fan coil units only the external contact of the master is ena-bled. When the input to the master is closed all the slave fan coil units on the network are switched off.

• Emergency functionIn the case of an ambient sensor failure

the electronic board is capable of automatically detecting it and adopt and emergency function, in order to avoid discomfort to the user whilst signalling the fault (illumination of the LED).

- Operation with water temperature sensor failure

The ventilation is always enabled.The enabling of operating mode is as a

function of the difference between the set temperature and the ambient tem-perature.

If the ambient temperature exceeds an interval equal to the dead band set in heating then it goes to cooling mode.

If the ambient temperature drops an interval equal to the dead band set in cooling then it goes to heating mode.

- Operation with ambient temperature sensor failure

Selector in OFF/Aux position:- ventilation is switched off- valve is closedSelector in AUTO, V1, V2, V3 position:- valve is always open- ventilation carries out On/Off cycles

of variable durations as a function of temperature setting position. The maximum duration of the cycle is 5'20".

Page 10: VENTILCONVETTORI A MANDATA CONTROLLATA - Manuale … · 2019-11-25 · AERMEC S.p.A. declines all responsibility for any damage whatsoever caused by improper use of the machine, and

Engl

ish

23IDJULJ 1207 - 6339500_00

- Operation with ambient temperature sensor failure of a slave fan coil unit.

The board automatically assumes the value read by the ambient sensor of the master fan coil unit.

Control of 2 pipe systemsWater Sensor Upstream Water Sensor Downstream

Water Sensor Present Water Sensor Absent Water Sensor Present Water Sensor Absent

With Valve

Pre-heating delayed Pre-heating delayed No Ventilation delay Pre-heating delayed

Minimum and maximum controls active

No minimum or maximum control

Minimum and maximum controls active

No minimum or maximum control

Dynamic Correction A Fixed Correction Dynamic Correction B Fixed Correction

Without Valve Configuration not used

No Ventilation delay No Ventilation delay

Minimum and maximum controls active

No minimum or maximum control

Dynamic Correction B Fixed Correction

Page 11: VENTILCONVETTORI A MANDATA CONTROLLATA - Manuale … · 2019-11-25 · AERMEC S.p.A. declines all responsibility for any damage whatsoever caused by improper use of the machine, and

Engl

ish

24 IDJULJ 1207 - 6339500_00

NETWORK SETTINGS

TTL NETWORK- Composed of a maximum of 6 fan

coil units (one Master and 5 Slaves) - Maximum TTL line length 30m.The Master fan coil units are

equipped with a control panel and an electronic board with microprocessor, equipped with outputs to be inserted in a TTL network.

The Slave fan coil units are only equipped with an electronic board with microprocessor (VMF series), equipped with outputs to be inserted in a TTL network.

All the fan coil units of the TTL network must have the same type of accessories.

The settings (set point) of the control

panel on the fan coil unit (master) are received by the other fan coil units (slave).

The units connected to the TTL ne twork a r e au toma t i ca l l y recognised; no configuration procedure is required.

Instructions essential for the proper installation of the equipment are shown here.

The final touches to all the operations are however left to the experience of the installation engineer in accordance with the specific needs.

Before proceeding with the installation please read carefully the following information:

• WARNING: Disconnect the power supply before carrying out any intervention.

• WARNING: Provide appropriate personal protective equipment before carrying out any intervention.

• WARNING: The unit must be installed in accordance with the applicable national regulations.

• WARNING: Keep separated electrical connections from hydraulic connec-tions. The hydraulic connections and condensate discharge must be on the opposite side to the electrical connec-tions.

• WARNING: wiring connections, installation of the fan coil units and relevant accessories must be performed by a technician who has the necessary technical and professional expertise to install, modify, extend and maintain systems and who is able to check the system for the purposes of safety and correct operation.

In particular to electrical connections the

following checks must be made:- Measure the insulation resistance of the

electrical installation.- Continuity check of the electrical

protective conductors.• WARNING: Install an electrical isolator

or plug that allows the electrical power to be completely isolated from the unit.

• WARNING: The unit is connected to the power supply network. Any intervention by personnel not technically qualified can cause injury to the operator, or damage to the unit and surrounding environment.

• Check that the power supply voltage matches that of the unit being installed.

• The sizing of electrical cabling must be carried out in accordance with relevant standards, taking into account the system load.

• For the electrical power use continuous cables with cross section suitable for the load. It is recommended to make connection with a single cable for each connection. Do not make joints in the cable but use a longer cable. Joints can cause overheating or fires.

• Only use the appropriate equipment for making electrical connections.

• Use twisted cables for connecting the wired panel.

• Do not attempt to repair the unit alone. An incorrect intervention can cause electrical shock or fires.

It is recommended to contact the local Assistance Service. For any technical intervention, or installation, it is recommended to contact the local Assistance Service.

• All the cables must be enclosed inside a tube or conduit until they are within the fan coil unit. The cables at the outlet of the tube or conduit must not be subjected to stress or twisting and must be protected from external forces.

• Stranded cables can only be used with cable lugs. Ensure the strands are correctly inserted.

• In the case the three way valve is installed the minimum water temperature sensor can be moved from its location in the coil the outlet tube upstream of the valve.

WARNING: Moving the water sensor requires its replacement with the accessory sensor VMF-SW, equipped with a cable of adequate length.

• The connections have to be made to the connectors of the electronic board.

• The electronic board is protected by a plastic box and a cover easily removed with the use of a tool

• Electrical schematics are subject to continuous updates. Refer to those supplied loose with the accessory.

• WARNING: The wiring schematic for the terminal connections to the electronic board is stamped on the

INSTALLATION INFORMATION

INSTALLATION

TTL LineMax 30m

+-

DUALJETDUALJET

+VMF-E2D / VMF-E4/-E4D

MASTER SLAVE

VMF-E2D

E4VMF-E4VMF-E4D

Page 12: VENTILCONVETTORI A MANDATA CONTROLLATA - Manuale … · 2019-11-25 · AERMEC S.p.A. declines all responsibility for any damage whatsoever caused by improper use of the machine, and

Engl

ish

25IDJULJ 1207 - 6339500_00

inside of the cover of the box.• WARNING: Earth the installation. • It is obligatory to connect the casing of

the fan coil unit to the earthing.• It is mandatory to tighten the screw

that fixes the thermostat box to the side of the fan coil unit as this provides the earthing of the whole installation.

• The fan coil unit is a product that can only be installed internally.

• The fan coil unit must be installed in such a position that the air can be

distributed throughout the room and that there are no obstacles (curtains or objects) to the passage of the air from the intake and discharge.

• The fan coil unit must be installed in such a way as to make easy ordinary maintenance (filter cleaning) and spe-cial maintenance, as well as the access to the air vent valve on the side of the frame (connections side).

• To install the unit proceed as follows:• Remove the casing by unscrewing the

screw.• For wall mounting use expansion plugs

(not provided) as shown in the diagram.• Carry out the hydraulic connections. The position and diameters of the

hydraulic connections are shown in the dimensional data.

To avoid condensate drips during cool-ing operation it is recommended to properly insulate the water piping or to install the appropriate auxiliary con-densate tray, available as an accessory.

The condensate drain system must be appropriately sized and the piping positioned in such a way to maintain a slope (min. 1%). To avoid unpleasant smells a trap is recommended if the condensate is connected to the sewage system.

• Carry out the electrical connections as detailed in the wiring schematics and the chapter dedicated to the electronic thermostat connections.

• Replace the casing, not forgetting to connect the ambient sensor and micro-switch.

INSTALLATION OF THE UNIT

Page 13: VENTILCONVETTORI A MANDATA CONTROLLATA - Manuale … · 2019-11-25 · AERMEC S.p.A. declines all responsibility for any damage whatsoever caused by improper use of the machine, and

Engl

ish

26 IDJULJ 1207 - 6339500_00

If the hydraulic connections require the rotation of the coil, then after removal of the casing proceed as follows:– remove the fixing screw to the con-trol panel (if fitted) on the right side and remove it, disconnecting the electrical connections– remove the thermostat from the right side– remove the coil enclosure cover by unscrewing the screws– remove the screws that fix the coil and remove the coil– remove the knock-outs (6) from the right side– rotate the coil and fix with the screws previously removed– refit the cover and fix with the screws, mount the plastic caps supplied loose into the holes left empty by the hydraulic connections– all the drain pans are provided with condensate discharges on both sides. To move the condensate discharge to the right side it is necessary to move the dis-charge connection to the right.– remove the electrical connections from the right side, remove the knock-out and move the grommet from right to left– move the electrical connections to the left side passing through the grommet– move the thermostat and the earth connection to the left side.

ROTATING THE COIL

Page 14: VENTILCONVETTORI A MANDATA CONTROLLATA - Manuale … · 2019-11-25 · AERMEC S.p.A. declines all responsibility for any damage whatsoever caused by improper use of the machine, and

Ital

iano

27IDJULJ 1207 - 6339500_00

WARNING: Keep separated electrical connections from hydraulic connections. The hydraulic connections and condensate discharge must be on the opposite side to the electrical connections.

ELECTRICAL CONNECTIONS

• Connect the TTL network cables (if networked). • Connect the cables of the control panel. • Ensure that all connections and their cables are correctly

fixed. • Run cables so that they cannot suffer cuts, crushing, jerking,

abrasion and damage in general.• Ensure that the board's fuse is intact and of the prescribed

characteristics.• Close the box with the cover.• Fix with the cable blocker the power cables and valve

cables.

DANGER: It is mandatory to tighten the screw that fixes the thermostat box to the side of the fan coil unit as this pro-vides the earthing of the whole installation.

Page 15: VENTILCONVETTORI A MANDATA CONTROLLATA - Manuale … · 2019-11-25 · AERMEC S.p.A. declines all responsibility for any damage whatsoever caused by improper use of the machine, and

Ital

iano

28 IDJULJ 1207 - 6339500_00

Remove power to the unit.Operation to be carried out during installation by specialised personnel only. Dip-Switch are found on the electronic board.

*The settings Continuous ventilation (Dip3 ON) and Modulating capacity thermostat (Dip8 ON) are not compatible.

**The settings Continuous ventilation (Dip3 ON) and Control valve absent (Dip1 OFF) are not compatible.

DIP-SWITCH SETTINGS

Function dependent on the combination of 2 Dip-SwitchesDip 6 Dip 5 ** Type of installationOFF OFF 2 pipe system

OFF ON 4 pipe system

Position FunctionDip 1 (Default OFF) Water valve control:

OFF ** Control valve absent

ON Control valve present

Dip 2 (Default OFF) Water temperature sensor position:

OFF Water temperature sensor downstream of control valve

ON Water temperature sensor upstream of control valve

Dip 3 (Default OFF) Ventilation control:

OFF Thermostatic ventilation

ON */** Continuous ventilation

Dip 4 (Default OFF) Ventilation enabling:

OFF Enabling normal range

ON Enabling reduced range

Dip 5 (Default OFF) Selection of the type of installation (See table)

OFFCombination between Dip 5 and Dip 6

ON

Dip 6 (Default OFF) Selection of the type of installation (See table)

OFFCombination between Dip 5 and Dip 6

ON

Dip 7 (Default OFF) Dead band:

OFF Cooling set limit = 17°C - 33°C

ON Cooling set limit = 14°C - 30°C

Dip 8 (Default OFF) Thermostat settings:

OFF 3 level thermostat

ON * Modulating capacity thermostat

Dip-Switch settings functions:

ONOFF

1 2 3 4 5 6 7 8

ONOFF

1 2 3 4 5 6 7 8

ONOFF

1 2 3 4 5 6 7 8

ONOFF

1 2 3 4 5 6 7 8SW

SW

SW

SW

ON ON

ON ON

ONOFF

1 2 3 4 5 6 7 8

ONOFF

1 2 3 4 5 6 7 8

SW

SW

ON

ON

SOME EXAMPLES:

VMF_E0 (default) Continuous ventilationWater sensor upstream of valve

Dead band Cooling set limit = 14°C - 30°CReduced range Control valve present

Page 16: VENTILCONVETTORI A MANDATA CONTROLLATA - Manuale … · 2019-11-25 · AERMEC S.p.A. declines all responsibility for any damage whatsoever caused by improper use of the machine, and

Ital

iano

29IDJULJ 1207 - 6339500_00

THERMOSTAT TECHNICAL CHARACTERISTICS (E0)

Power 230Vac +/-10%, 50-60 Hz

Max Absorbed Power (excluding TRIAC controlled loads)

2.5VA

Digital Inputs N°2 dry contacts

Analogue Inputs N°2 for sensors NTC 10K

Digital Outputs N°5, 230Vac Triac

Mounting Unit mounted

Protective Rating IP20 (referring to plastic containment)

Storage conditions -20 to 80°C, relative humidity 80% non condensing

Operating conditions 0 to 50°C, relative humidity 80% non condensing

Software class Class A

Outputs: Fan control

Voltage 230Vac

Maximum current 0.7A

THERMOSTAT CONNECTIONS SPECIFICATIONS (E0)

Power Screw terminals sized 5mm

Cable section min=0.5mm2 max=2.0mm2

Accessory control outputs (Valves-Plasmacluster germi-cide lamp, etc…)

Screw terminals sized 5 mm

Cable section min=0.5mm2 max=1.3mm2

Max cable length = 30m

Digital Input CE Screw terminals sized 3.81mm

Cable section min=0.2mm2 max=1.0mm2

Max cable length = 100m

Digital Input MS Sweeping contact Max cable length = 3m

Analogue Inputs (SA-SW) Quick insertion connection

Max cable length = 3m

Local serial TTL Screw terminals sized 3.81mm

Cable section min=0.2mm2 max=1.0mm2

Max cable length = 30m

Page 17: VENTILCONVETTORI A MANDATA CONTROLLATA - Manuale … · 2019-11-25 · AERMEC S.p.A. declines all responsibility for any damage whatsoever caused by improper use of the machine, and

75IDJULJ 1207 - 6339500_00

PROBLEMA • PROBLEMPROBLEME • PROBLEMPROBLEMAPoca aria in uscita.Feeble air discharge.Il y a peu d’air en sortie.Schwacher Luftstrom am Austritt.Poco aire en salida.

Non fa caldo.It does not heat.Pas de chaleur.Keine Heizung.No hace calor.

Non fa freddo.It does not cool.Pas de froid.Keine Kühlung.No hace frío.

Il ventilatore non gira.The fan does not turn.Le ventilateur ne tourne pas.Ventilator Arbeitet nicht.El ventilador no gira.

Fenomeni di condensazione sulla struttura esterna dell’ap-parecchio.Condensation on the unit cabinet.

Phénomènes de condensa-tion sur la structure exterieu-re de l’appareil.Kondenswasserbildung am Gerät.

Fenómenos de condensación en la estructura externa del aparato.

PROBABILE CAUSA • PROBABLE CAUSECAUSE PROBABLE • MÖGLICHE URSACHECAUSA PROBABLEErrata impostazione della velocità sul pannello comandi.Wrong speed setting on the control panel.Mauvaise préselection de la vitesse sur le panneau de commandes.Falsche Geschwindigkeitseinstel lung am Bedien paneel.Programación errada de la velocidad en el tablero de mandos.

Filtro intasato.Blocked filter.Filtre encrassé.Filter verstopft.Filtro atascado.

Ostruzione del flusso d’aria (entrata e/o uscita).Obstruction of the air flow (inlet and/or outlet).Obstruction du flux d’air (entrée/sortie).Luftstrom behindert (Eintritt bzw. Austritt).Obstrucción del chorro del aire (entrada y/o salida).Mancanza di acqua calda.Poor hot water supply.Il n’y a pas d’eau chaude.Kein Warmwasser.Falta de agua caliente.

Impostazione errata del pannello comandi.Wrong setting on control panel.Mauvaise présélection sur le panneau de commandes.Falsche Einstellung am Bedien paneel.Programación errada del tablero de mandos.Mancanza di acqua fredda.Poor chilled water supply.Il n’y a pas d’eau froide.Kein Kaltwasser.Falta de agua fría.

Impostazione errata del pannello comandi.Wrong setting on control panel.Mauvaise présélection sur le panneau de commandes.Falsche Einstellung am Bedien paneel.Programación errada del tablero de mandos.Mancanza di corrente.No current.l n’y a pas de courant.Kein Strom.Falta de corriente.L’acqua non ha raggiunto la temperatura d’esercizio.

The water has not reached operating temperature.

L'eau n'a pas atteint la température de service.

Das Wasser hat die Betriebstemperatur nicht erreicht.

El agua no ha alcanzado la temperatura de ejercicio.

Sono state raggiunte le condizioni limite di temperatura e umidità descritte in “MINIMA TEMPERATURA MEDIA DELL’ACQUA”.The limit conditions of temperature and humidity indicated in “MINIMUM AVERAGE WATER TEMPERATURE” have been reached.On a atteint les conditions limite de température et d’humi-dité indiquées dans “TEMPERATURE MINIMALE MOYENNE DE L'EAU”.Erreichen der maximalen Temperatur- und Feuchtigkeitswerte (siehe Abschnitt “DURCHSCHNITTLICHE MINDEST - WASSERTEMPERATUR”).Se han alcanzado las condiciones límites de temperatura y humedad descritas en “MÍNIMA TEMPERATURA MEDIA DEL AGUA".

SOLUZIONE • REMEDYSOLUTION • ABHILFESOLUCIÓNScegliere la velocità corretta sul pannello comandi.Select the speed on the control panel.Choisir la vitesse sur la panneau de commandes.Die Geschwindigkeit am Bedien paneel wählen.Elegir la velocidad correcta en el tablero de mandos.

Pulire il filtro.Clean the filter.Nettoyer le filtre.Filter reinigen.Limpiar el filtro.

Rimuovere l’ostruzione.Remove the obstruction.Enlever l’objet faisant obstruction.Verstopfung beseitigen.Quitar la obstrucción.Controllare la caldaia.Control the boiler.Verifier la chaudière.Kaltwasserseitigen Wärmeaus tau scher kontrollieren.Comprobar el calentador.

Impostare il pannello comandi.See control panel settings.Présélectionner au panneau de commandes.Richtige Einstellung am Bedien paneel vornehmen.Programar el tablero de mandos.Controllare il refrigeratore.Control the chiller.Vérifier le réfrigerateur.Kaltwasserseitigen Wärmeaus tau scher kontrollieren.Comprobar el refrigerador.

Impostare il pannello comandi.See control panel settings.Présélectionner au panneau de commandes.Richtige Einstellung am Bedien paneel vornehmen.Programar el tablero de mandos.Controllare la presenza di tensione elettrica.Control the power supply.Contrôler l’alimentation électrique.Kontrollieren, ob Spannung anliegt.Comprobar la presencia de tensión eléctrica.Controllare la caldaia o il refrigeratore.Controllare il settaggio del termostato.Please check up the boiler or the chiller.Check up the thermostat settings.Contrôler la chaudière ou le refroidisseur.Contrôler le réglage du thermostat.Das Heiz- oder Kühlaggregat überprüfen.Die Einstellungen des Temperaturreglers überprü-fen.Comprobar el calentador o el refrigerador.Comprobar la programación del termostato.Innalzare la temperatura dell’acqua oltre i limi-ti minimi descritti in “MINIMA TEMPERATURA MEDIA DELL’ACQUA”.Increase the water temperature beyond the mini-mum limits indicated in “MINIMUM AVERAGE WATER TEMPERATURE”.Elever la température de l’eau audelà des limites minimales indiquées dans “TEMPERATURE MINI-MALE MOYENNE DE L'EAU”.Wassertemperatur über die um Abschnitt “DURCH-SCHNITTLICHE MINDEST - WASSERTEMPERATUR” angegebenen min. Werte erhöhen.Aumentar la temperatura del agua por encima de los límites descritos en “Mínima temperatura media del agua”.

Per anomalie non contemplate, interpellare tempestivamente il Servizio Assistenza.For anomalies don’t hesitate, contact the aftersales service immediately.Pour toute anomalie non répertoriée, consulter le service après-vente.Sich bei hier nicht aufgeführten Störungen umgehend an den Kundendienst wenden.En el caso de anomalías no contempladas, ponerse en contacto de inmediato con el Servicio de Asistencia.