PowerChain Management PowerChain Management is a registered trademark of Eaton Corporation. All other trademarks are property of their respective owners. What’s the difference? HMCP High Interrupting Motor Circuit Protector MPCB Motor Protection Circuit Breaker The HMCP is designed to provide short circuit (magnetic) protection and a disconnect for a motor circuit. It is designed to be used with a contactor (to start/stop the motor) and an overload relay (to protect from over current) The MPCB is designed to provide short circuit (magnetic) protection, a disconnect and OVERLOAD RELAY protection all in one device. Series C GMCP Frame (3-63A) HMCP Frames (3-1200A) Series G HMCPE Frames (3-100A) HMCPJ Frame (250A) HMCPL Frame (600A) FDMP Frame (40-205A) JGMP Frame (50-250A) LGMP Frame (250-600A) Short Circuit Current Ratings with Eaton Motor Starters Combination Ratings up to 100KA (with Freedom Series) High Fault Ratings up to 65KA (with XT Series) High Fault Ratings up to 65KA(with XT Contactors) Standards and Certifications UL 489 Recognized device that requires further listing with a specific contactor and overload relay for proper application. (UL Listed with Eaton Motor Starters) • CSA C22.2 No. 5.1 IEC 157-7 UL 489 Listed Circuit Breaker that can be used with any controller without further testing or listings. • CSA C22.2 No. 14 IEC 60947-2, 60947-4 The Bottom Line Both are top-quality products ideally suited for their target applications! Eaton Corporation Electrical Sector 1000 Cherrington Parkway Moon Township, PA 15108 United States 877-ETN-CARE (877-386-2273) Eaton.com © 2009 Eaton Corporation All Rights Reserved Printed in USA June 2010, V1 • Adjustable Trip Settings ( in multiples of the continuous current rating) allows for customized motor protection • Maximum Setting of 13X FLA • Used with Starters Size 0-8 • Transient inrush trip suppression to sustain high inrush on very first cycle (included on units used with starters up to size 4) • Eliminates the need for an overload relay which reduces panel size and heat generation Selectable Trip Class: FD Frame – Class 5, 10, 20, 30 JG/LG Frames – Class 10, 15, 20, 30 Phase Unbalance and Phase Loss Protection Field Installable Accessories (JG, LG Frames) High Load Alarm Status Indicator (JG, LG) Pre-detection Relay (opens contactor instead of breaker on JG, LG) What is the major difference between the two products? Product Features and Benefits Product Offering

Upload: andres-perez

Post on 21-Apr-2015

42 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: What's the Difference - HMCP vs. MPCB

PowerChain ManagementPowerChain Management is a registeredtrademark of Eaton Corporation.

All other trademarks are property of theirrespective owners.

What’s the difference?

HMCPHigh Interrupting

Motor Circuit Protector

MPCBMotor Protection

Circuit Breaker

• The HMCP is designed to provide short circuit (magnetic)

protection and a disconnect for a motor circuit. It is

designed to be used with a contactor (to start/stop the motor)

and an overload relay (to protect from over current)

• The MPCB is designed to provide short circuit (magnetic)

protection, a disconnect and OVERLOAD RELAY

protection all in one device.

• Series C

GMCP Frame (3-63A)

HMCP Frames (3-1200A)

• Series G

HMCPE Frames (3-100A)

HMCPJ Frame (250A)

HMCPL Frame (600A)

• FDMP Frame (40-205A)

• JGMP Frame (50-250A)

• LGMP Frame (250-600A)

Short Circuit Current Ratings with Eaton Motor Starters

• Combination Ratings up to 100KA (with Freedom Series)

• High Fault Ratings up to 65KA (with XT Series)

• High Fault Ratings up to 65KA(with XT Contactors)

Standards and Certifications

• UL 489 Recognized device that requires further listing with

a specific contactor and overload relay for proper

application. (UL Listed with Eaton Motor Starters)

• CSA C22.2 No. 5.1

• IEC 157-7

• UL 489 Listed Circuit Breaker that can be used with any

controller without further testing or listings.

• CSA C22.2 No. 14

• IEC 60947-2, 60947-4

The Bottom Line

Both are top-quality products ideally suited for their target applications!

Eaton CorporationElectrical Sector1000 Cherrington ParkwayMoon Township, PA 15108United States877-ETN-CARE (877-386-2273)Eaton.com

© 2009 Eaton CorporationAll Rights ReservedPrinted in USA

June 2010, V1

• Adjustable Trip Settings ( in multiples of the continuous

current rating) allows for customized motor protection

• Maximum Setting of 13X FLA

• Used with Starters Size 0-8

• Transient inrush trip suppression to sustain high inrush on

very first cycle (included on units used with starters up to

size 4)

• Eliminates the need for an overload relay which reduces

panel size and heat generation

• Selectable Trip Class:

FD Frame – Class 5, 10, 20, 30

JG/LG Frames – Class 10, 15, 20, 30

• Phase Unbalance and Phase Loss Protection

• Field Installable Accessories (JG, LG Frames)

• High Load Alarm Status Indicator (JG, LG)

• Pre-detection Relay (opens contactor instead of breaker on JG, LG)

What is the major difference between the two products?

Product Features and Benefits

Product Offering