yokogawa dcs training

Upload: victor-biacolo

Post on 09-Oct-2015

2.050 views

Category:

Documents


361 download

DESCRIPTION

DCS training

TRANSCRIPT

  • Yokogawa Electric Corporation

    2-9-32 Nakacho, Musashino-shiTokyo, 180-8750JAPAN

    Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Distributed Control System

    TRAINING CENTRE

    YOKOGAWA INDIA LIMITED

    YOKOGAWA

    TRAINING CENTRE

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Basic Loop

    Controller

    I/P

    Transmitter

    I/P Convertor

    PV MVSV

    4-20 mA

    4-20 mA

    Pneumatic Signal(0.2 to 1 Kg/cm2 or 3 to 15 psi)

    Final Control Element

    Basic Control Loop

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Process Control Systems

    Process control systems are classified into

    Analog Control Systems

    Digital Control Systems

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Analog Control System

    Signal Conversion

    I/P4-20 mA DC

    1 to 5V DC

    Operational Amplifier

    Set Point

    Final Control Element

    Transmitter

    Analog Control System

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Digital Control System

    I/P4-20 mA DC

    A / D

    1 to 5V DC

    D / A

    DigitalOutput

    Unit

    Input Unit

    Memory Unit

    ControlUnit

    ArithmeticUnit

    Set Point

    Processor

    Digital Control System

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Digital Control System

    Digital Control Systems are further classified into

    Centralized Control Systems

    Distributed Control Systems

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Centralized Processing

    UnitCPU

    Centralized Control System

    Input Signals from Field

    Set Points

    OutputSignals to Field

    Centralized Control , Centralized Monitoring

    PV1

    PV2

    PVn

    PV3

    MV1

    MV2

    MVn

    MV3

    SV1 SV2 SV3 SVn

    Centralized Control System

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Centralized Control System

    Drawbacks Of CCS:

    If the CPU fails the entire plant gets affected.

    Redundancy concept was not available.

    Redundancy is having two controllers. One would be active and the other would be standby. If the active controller fails, the standby controller takes over.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Distributed Control System

    Input Signals from Field

    Distributed Control Centralized Monitoring

    Set Points

    Communication Bus

    Output Signals to Field

    MV1

    MV8FCS

    PV1

    PV8SV1 SV

    8 MV9

    MV16FCS

    PV9

    PV16

    SV9 SV16

    MV17

    MVnFCS

    PV17

    PVn

    SV17 SVn

    OPS

    OPS

    Distributed Control System

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Basic Components of DCS

    FCS (Field Control Station):Used to control the process. All the instruments and interlocks created by software reside in the memory of the FCS. All the field instruments like transmitters and control valves are wired to the FCS.

    OPS (Operator Station):Used to monitor the process and to operate various instruments.

    Communication Bus:Used to communicate between the FCS and the OPS

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Advantages of DCS

    9 Control function is distributed among multiple CPUs (Field Control Stations). Hence failure of one FCS does not affect the entire plant.

    9 Redundancy is available at various levels.

    9 Instruments and interlocks are created by software.

    9 Generation and modifications of the interlocks are very flexibleand simple.

    9 Information regarding the process is presented to the user in various formats.

    9 Field wiring is considerably less.

    9 Maintenance and trouble shooting becomes very easy.

    9 Cost effective in the long run.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    DCS Evolution

    CENTUM was released in 1975 as the world-first DCS (Distributed Control System), and has been progressed.CENTUM CS 3000 is the latest Yokogawa DCS.

    From 98 (1458 Systems)

    CENTUM/CENTUM V

    CENTUM-XL

    CENTUM CSFrom 93 (2113 Systems)

    From 88 to 00 (1703 Systems)

    From 75 to 93 (1983 Systems) As of March 03

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    CS3000 - System Configuration

    CS, CS 1000CENTUM-XL, -V

    MXL

    BCV

    CGW

    Remote Domain System

    V net

    HIS

    ooo

    PFCS

    LFCS

    Ethernet

    HIS / ENG

    FFCSKFCS

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    CENTUM CS 3000 - Major Components

    FCS (Field Control Station) Reliable controller. Cost-effective and capable I/O subsystem.

    HIS (Human Interface Station) The operator station based on Windows XP or Windows2000. (Both

    are selectable.) HIS provides easy & flexible operation.

    ENG (Engineering Station) Engineering Station is used to do the engineering builder for all the

    stations like HIS, FCS, CGW, BCV etc. ENG is a PC loaded with Engineering software.

    The HIS can be loaded with engineering software so that it can be used as HIS as well as ENG.

    CGW: Communication Gateway Unit used to communicate with supervisory computers.

    BCV: Bus Converter is used to link two domains.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    CENTUM CS 3000 - Networks

    V-Net (Communication Bus) Real-time control bus. V-NET is a used for communication between HIS, FCS,

    BCV & CGW. Maximum 64 Stations can be connected on the V-net.

    ETHERNET (Communication Bus) Ethernet is a standard network in CS3000 to connect HIS,

    ENG and supervisory computers . Transmission speed: 10 MBPS

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    FFCS Hardware View

    Power supply unit

    CP401 CPU module

    Eight FIO slotsEight FIO slots

    EC401 ESB bus coupler(Note)

    Note: Two I/O slots are to be used for NIU extension.

    AIP504 Vnet coupler (10BASE2 Vnet cable is used.)

    Detachable bottom unit

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Hardware Configuration- Local Node

    FIO: Max. 8

    Local node Max. 3

    ESB busESB busUp to 6 Modules

    Up to 8Modules

    C

    P

    4

    0

    1

    C

    P

    4

    0

    1

    P

    W

    4

    8

    X

    P

    W

    4

    8

    X

    V netV net

    FFCSFFCS

    C

    P

    4

    0

    1

    C

    P

    4

    0

    1

    P

    W

    4

    8

    X

    P

    W

    4

    8

    X

    E

    C

    4

    0

    1

    E

    C

    4

    0

    1

    S

    B

    4

    0

    1

    P

    W

    4

    8

    X

    P

    W

    4

    8

    X

    S

    B

    4

    0

    1

    S

    B

    4

    0

    1

    P

    W

    4

    8

    X

    P

    W

    4

    8

    X

    S

    B

    4

    0

    1

    S

    B

    4

    0

    1

    P

    W

    4

    8

    X

    P

    W

    4

    8

    X

    S

    B

    4

    0

    1

    FFCSFFCS

    Minimum ConfigurationMinimum Configuration

    Maximum ConfigurationMaximum Configuration

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Hardware Configuration Remote Node

    V netV net

    FFCSFFCS

    Remote nodeRemote node

    Expanded Remote node up to 3

    ER busER bus

    E

    B

    4

    0

    1

    E

    B

    4

    0

    1

    E

    B

    4

    0

    1

    E

    B

    4

    0

    1

    E

    B

    4

    0

    1

    E

    B

    4

    0

    1

    E

    B

    4

    0

    1

    C

    P

    4

    0

    1

    C

    P

    4

    0

    1

    P

    W

    4

    8

    X

    P

    W

    4

    8

    X

    E

    B

    5

    0

    1

    P

    W

    4

    8

    X

    P

    W

    4

    8

    X

    E

    B

    5

    0

    1

    Remote nodeRemote node

    E

    B

    5

    0

    1

    P

    W

    4

    8

    X

    P

    W

    4

    8

    X

    E

    B

    5

    0

    1

    E

    B

    5

    0

    1

    P

    W

    4

    8

    X

    P

    W

    4

    8

    X

    E

    B

    5

    0

    1

    Remote nodeRemote node

    Optical Repeater can be usedOptical Repeater can be used

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    The Station for Real time Plant Monitoring/Operation

    Easy Operation by a mouse, a keyboard etc.

    Real time display of Plant Abnormalities.

    HIS (Human Interface Station)

    Plant Operation by thousands of Graphics

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Types of HIS

    DESKTOP HIS:A IBM PC/AT compatible machine is generally used. Apart from the general PC, the Yokogawa PC is also supported. Specifications of the PC HIS Desktop are as follows:CPU : Pentium IV ProcessorMain Memory : 256 MB (Minimum)Hard Disk : 20 GB or moreVideo Display : 1024 x 768 or more, 256 coloursCRT Monitor : Multi Scan 17 monitor or largerSerial Port : RS232C one port or moreParallel Port : One port or moreExtension Slot : PCI slot for V/VL net card, ISA slot for Ethernet cardPower Supply : 200-240V ACBasic Software : Windows NT with Service Pack ,Windows 2000 or

    Windows XP

    CONSOLE HISThe floor mounted console type HIS comes with 21 monitor which has a touch panel operation. It has an operation keyboard and an engineering keyboard.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Application Capacity of HIS

    Maximum number of tags that can be monitored from HIS : 1000000

    Maximum number of windows that can be created per HIS : 4000

    Maximum number of Trend Recording Points per HIS : 2304

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    V net Communication

    Protocol : IEEE 802.4Access Control : Token PassingTrans. Speed : 10 MbpsTrans. Distance : 500m to 20kmMedia : Coaxial/Optical FibreStd. max. length : 185 mMax. length : 20 Km (with optical repeater) 1.6 Km (with coax. repeater)

    V net

    HISHIS

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    V net : Extension Details

    HIS HISHIS

    OpticalFibre

    R

    R R

    RT

    T

    OpticalFibre

    R

    R R

    R T

    T

    Max. 500m Max. 500mMax. 500mMax.15 km

    Max.15 km

    Overall Max. 20 km

    Co-axial CableV net

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Domains are group of stations connected on the V-net. Bus Convertor is used to link two domains. BCV is used to connect CS, CS 1000, CENTUM-XL,CENTUM-V AND MXL to CS3000system

    Bus Convertor

    HF BUS

    EFCD FCS

    HIS

    ooo

    BCV

    ooo ooo

    Domain connection

    EOPS

    V-NET

    ETHERNET

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Operation Windows

    Information regarding the process is gathered as well as monitored by the following Standard Operation windows on the HIS.

    Tuning Window Control Group Window Trend Window Process Alarm Window Operator guide Message Window Graphic Window Overview Window Process Report Window Historical Report Window

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    System Message Window

    These buttons are provided for calling various functional windows on the HIS

    Type the TAGNAME to call the instrument faceplate window

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Various windows can be accessed by selecting

    the respective icons in theSystem Message Area

    These windows can also be accessed by the keys on the Operator Keyboard

    SYSTEM MESSAGE AREA ICONS

    System Message Area

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Operation Keyboard

    Operation KeyboardOPERATION KEYBOARD

    All the operations can be performed with the help of the Operation Keyboard. The same

    operations can also be performed by touch functions available

    on the System Message Area Icons.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    From this window, you can open the following windows.

    1. Overview Window 2. Control Window 3. Tuning Window 4. Trend Window 5. Graphic Window 6. Alerm Window7. Operator Guide message

    Window

    Operation Windows

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Instrument Faceplate Window

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Tuning Window

    Select this icon to display the Tool box

    Select this icon to display the Tuning Window

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Tuning Window

    TUNING WINDOW displays all the Tuning parameters of the instrument.

    The Tuning Window is used to set up the alarm setting as well as the loop tuning parameters.

    Only the items indicated with a = canbe changed.

    Displaying a Tuning Window1.Double click on a Tags name on a Control Window and a faceplate windowwill appear. Select the Tuning window icon from the toll box.

    2. Select NAME icon in the System Message Area then enter the TAGNAME.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Tuning Window

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Mode Status

    MAN (Manual)

    AUT (Auto)

    CAS (Cascade)

    PRD (Primary Direct)

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Manual Mode

    MANUAL MODE:In manual mode, the MV pointer appears in red colour and the SV pointer appears in yellow colour. MV of the i n s t r u m e n t c a n b e c h a n g e d b y increment/decrement keys or through d a t a e n t r y b o x . T h e S V o f t h e instrument can be changed either by set point change key or using ITEM and D A T A i n t h e d a t a e n t r y b o x .

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Auto Mode

    AUTO MODE:In auto mode, the SV pointer appears in red colour and the MV pointer appears in yellow colour. SV of the instrument c a n b e c h a n g e d b y increment/decrement keys or through d a t a e n t r y b o x . T h e M V o f t h e instrument cannot be changed by anymethod.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Cascade Mode

    CASCADE MODE:In a cascade loop the output of the primary controller (MV1) goes as set point of the secondary controller (SV2). The output of the secondary controller (MV2) goes to the final control element. For a cascade loop, the primary controller can be in AUT or MAN mode, but the secondary controller has to be in CAS mode. In cascade mode both the SV and MV pointers appear in yellow colour.

    The SV and MV of the instrument cannot be changed.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Primary Direct Mode

    PRD: PRIMARY DIRECT MODEIn a normal cascade loop the output of the primary controller (MV1) goes as set point of the secondary controller (SV2). The output of the secondary controller (MV2) goes to the final control element.

    In PRD mode the output of the primary controller (MV1) directly goes to the final control element. The secondary controller is bypassed and cannot be operated.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Selecting/Deselecting PRD Mode

    To select PRD mode:Go to the tuning window of the Secondary controller.Select PRD Icon. Confirm.

    To select CASCADE mode:Change the mode status of the secondary controller to CAS.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Mode Sub Status

    IMAN (INITIALIZATION MANUAL MODE)In a cascade loop, if the cascade is broken by tak ing the secondary controller from CAS to either AUT or MAN mode, IMAN appears as the mode sub status of the primary controller. IMAN indicates that Cascade loop is broken Primary controller is bypassed Primary controller cannot be operated due

    to SV tracking.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    SV Tracking

    SV tracking:The output of the primary controller (MV1) automatically tracks the set point of the secondary controller (SV2) to have bumpless transfer to CAS mode.To bring the primary controller out of IMAN modeChange the mode s tatus o f the secondary controller to CAS. The primary controller will automatically c o m e o u t o f I M A Nmode.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Clamped Positive

    CLP+ (CLAMPED POSITIVE)In auto mode, if MV of the instrument is increased beyond MH value, MV gets clamped at the MH value and C appears on the instrument faceplate .

    MHI alarm also appears on the instrument as well as in the Process Alarm Window.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Clamped Negative

    CLP- (CLAMPED NEGATIVE)In auto mode, if MV of the instrument is decreased below ML value, MV gets clamped at the ML value and C appears on the instrument faceplate.

    MLO alarm also appears on the instrument as well as in the Process Alarm Window.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Process Alarm Status

    ----------REDREDLLPV < LLPV VERY LOW

    LL

    ----------REDREDPLPV < PLPV LOWLO

    REDREDOUTPUT LINE IS OPEN

    OUTPUT OPEN

    OOP

    RAW IS ACTUAL INPUT INTERMS OF %

    REDREDCHECK RAW VALUE IN TUNING WINDOW

    INPUT IS OUT OF RANGE

    INPUT OPEN

    IOP + / -

    YELLOWYELLOWVLVELOCITY LIMIT

    VEL = PV/ TVELOCITY ALARM

    VEL + / -

    YELLOWYELLOWDL DEVIATION LIMIT

    DV > DL DV = PV - SV

    DEVIATION ALARM

    DV+ / -

    ----------REDREDPHPV > PHPV HIGHHI

    ----------REDREDHHPV > HHPV VERY HIGH

    HH

    ----------GREEN GREEN--------------------PROCESS NORMAL

    NR

    REMARKSTAG MARK COLOUR

    PV BAR COLOUR

    ITEM TO BE SET IN THE TUNING

    PANEL

    ALARM

    SETTINGS

    PROCESS STATUS

    ALARM STATUS

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Process Alarm Status

    OCCURS ONLY IN CAS/ AUTO MODE

    YELLOWYELLOWMLMV < MLMV LOWMLO

    OCCURS ONLY IN CAS/ AUTO MODE

    YELLOWYELLOWMHMV > MHMV HIGHMHI

    REMARKSTAG MARK COLOUR

    PV BAR COLOUR

    ITEM TO BE SET IN THE TUNING

    PANEL

    ALARM

    SETTINGS

    PROCESS STATUS

    ALARM STATUS

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Alarm Sub Status

    AOF (Alarm Output Off)

    CAL (Calibration)

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Alarm Sub Status

    AOF (Alarm Output Off)Normally when an alarm occurs

    The tag mark changes colour depending on the typeof the alarm.

    Audible alarm is heard.

    The alarm status (HI/LO/HH/LL etc) is displayedon the process alarm window.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Alarm Sub Status

    AOF (Alarm Output Off)

    In AOF mode:

    The tag mark changes to dark blue colour irrespectiveof the alarm.

    Audible alarm is put off.

    The alarm status is displayed only on the instrument faceplate.

    All the alarms status except IOP & OOP on the Instrument are not displayed on the process alarm window.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Selecting / Deselecting AOF

    To put the instrument to AOF mode:Go to the tuning window of the instrument.Select AOF icon. Confirm.

    To bring the instrument back to normal mode:Go to the tuning window of the instrument.Select AOF icon once again. Confirm.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Alarm Sub Status

    CAL (Calibration)When an instrument is put in CAL mode

    CAL appears on the instrument faceplate.

    The PV bar changes to cyan colour.

    The Instrument automatically comes to MAN mode.

    The actual transmitter input is bypassed.

    PV of the instrument can be changed.

    All the alarms checking on the instrument arebypassed.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Selecting / Deselecting CAL

    To put an instrument in to CAL mode:Go to the tuning window of the instrument.Select CAL icon. Confirm.

    To bring the instrument back to normal mode:Go to the tuning window of the instrument.Select CAL icon once again. Confirm.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Importance Level

    Importance level is assigned to an instrument when it is created in the engineering builder. There are 8 importance levels.1 Important tag with confirmation 5 Important tag without confirmation 2 - General tag without confirmation 6 - General tag with confirmation3 - Auxillary tag I without Confirmation 7 - Auxillary tag I with Confirmation4 - Auxillary tag II without Confirmation 8 - Auxillary tag II with Confirmation

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Security Level

    Security level is assigned to an instrument when it is created in the engineering builder. There are 8 security levels.

    Tuning Parameters are displayed with = or : depending on the security level. Parameters displayed with = can be changed in the current key position.Parameters displayed with : cannot be changed in the current key position.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Security Level

    *1 : Only the PV alarm settings, SV, MV and block mode can be changed

    * 2 : Only the SV, MV and block mode can be changed

    O : Can be executed X : Cannot be executed

    XXXXXX8

    XXXOXX7

    OXXOOX6

    XXXOOO5

    OOXOOO4

    OO*2OOO3

    OO*1OOO2

    OOOOOO1

    ENGONOFFENGONOFF

    OPERATIONS

    PROCESS DATA INPUT

    FACEPLATE OPERATIONS,FACEPLATE DISPLAYACCESS LEVEL

    OPERATIONMONITORINGKEY POSITION/

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Control Drawing Display

    Select this icon to call the Control Drawing display

    Control drawing display

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Control Group Window

    Select this icon to display the Tool box

    Select this icon to display the Control Group Window

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Control Group Window 8 Instruments

    Control group windows are used to display multiple instrument faceplates.

    Maximum 8 or 16 instrument faceplatescan be displayed in one Control Group Window

    Normally the instruments are monitored and operated from this window.

    Double click on the instrument TAGNAME to display the Tuning Window of the instrument. Select the Upper Window Key to come back toControl Group Window

    .

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Control Group Window 16 Instruments

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Trend Window

    Select this icon to display the Tool box

    Select this icon to display the Trend Window

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Trend Window

    TREND WINDOW records the PV, SV and MV of various instruments.

    Trend can be displayed in Trend GroupFormat or in Trend Point Format.

    Maximum 8 pens can be assigned in one Trend Group Window

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Trend Group Window

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Trend Point Window

    Double click here to call the Trend Point Window

    Trend Point Window

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Calling Instrument from Trend Window

    Double click here to call the Instrument faceplate Window

    Instrument Faceplate Window. Instrument can be operated from this window.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Process Alarm Window

    PROCESS ALARM WINDOW displays the latest 200 process alarms.

    Alarms can be acknowledged either as a Group or as Individual alarm.

    Select this icon to call the Process Alarm Window

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Process Alarm Window

    PROCESS ALARM WINDOW displays the latest 200 process alarms.

    Alarms can be acknowledged either as a Group or as Individual alarm.

    This icon displays the current PV Values of the instruments that are in alarm

    This icon displays the important tags (High Priority Alarms) that are in alarm.

    This icon is used to acknowledge the process alarms.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Operator Guide Message Window

    Select this icon to call the Operator Guide Message Window

    OPERATOR GUIDE MESSAGE WINDOWdisplays the predefined messages to guide the operator regarding the current processstatus and /or the actions to be taken.

    OG messages can be acknowledged either as a Group or as Individual message.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Graphic Window

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Overview Window

    Select this icon to display the Tool box

    Select this icon to display the Overview Window

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Overview Window

    Overview Window displays the overview of the current process status.

    Information regarding the process is distributed among the various display blocks.

    32 Display Block s per Overview Window.

    Each block gives dynamic information regarding the process.

    Double click on the display block to more details.

    3 Types of Display Blocks

    Single Tag BlockWindow Display BlockComment Block

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Overview Window

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Process Report Window

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Historical Message Report Window

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Sequence Tables

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Sequence Tables

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Logic Charts

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Logic Charts

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    System Status Window

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    System Alarm Window

    SYSTEM ALARM WINDOW displays the latest 100 system alarms.

    Alarms can be acknowledged either as a Group or as Individual alarm.

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Navigator Window

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    System Code : %ZnnusccSddss

    %Z - Process Input/Output S - Station

    nn - node number dd - Domain number

    u - I/O unit number ss - Station number

    s - Slot number

    cc - Channel number

    Digital Inputs are contact inputs from field to CS3000.

    Digital Inputs are used to indicate the

    i) ON / OFF status of pumps, motors, heaters, etc.

    ii) OPEN / CLOSE status of on-off valves. Digital Inputs are used only as a condition signal in the Sequence Table. They cannot be used as an action signal in Sequence Table.

    Digital Inputs

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Digital Inputs Syntax

    YTAGNO.PV.ON DI = OFFPV = 0

    PV=1DI=ON

    N

    VALVE

    PV=1DI=1

    PV = 0DI = 0

    OPEN

    CLOSE

    Contact is closed in field

    Contact is open in field

    Conditions

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    System Code : %ZnnusccSddss

    %Z - Process Input/Output S - Station

    nn - node number dd - Domain number

    u - I/O unit number ss - Station number

    s - Slot number

    cc - Channel number

    Digital Outputs are contact outputs from CS3000 to field.Digital Outputs are used to i) Switch ON / OFF pumps, motors, heaters etcii) OPEN / CLOSE on-off Valves.

    Digital Outputs can be used as condition signals or as action signals in sequence table. If Digital Output is specified as Latched i.e. H, it has to be made ON on a particular condition and has to be made OFF on another condition

    Digital Outputs

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Output relay is energised

    PV=1DO=1

    PUMP

    PV=0DO=0

    Output relay is deenergised OFF

    ON

    Y

    Y

    Y

    TAGNO.PV.ON

    CO1

    ON

    N

    PV = 1

    TAGNO.PV.LTAGNO.PV.HTAGNO.PV.P

    YYY

    N

    Condition

    Action

    N

    Y

    Y

    PV = 0 OFF

    OFF PV=0 ON PV=1

    Digital Outputs Syntax

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Whenever Digital Outputs, Switches and Annunciators are used in sequence table as an action signal, they have to be specified as L (or) H

    Input

    OutputUnlatched (L)(level triggered)

    Output Latched (H)(edge triggered)

    Output pulse (P) The O/P is turned ON only once, for approx..1sec. When condition is true. If the condition goes false and then true again,output is turned ON again for a second.

    R-1Stop

    Start

    Start

    Stop

    R - 1 - 1 (Latching or hold on contact)

    Latch & Unlatch

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Switches are classified into Global switches and Common Switches.

    Global Switches are common to all FCS. The status of global switches

    are transmitted to other FCS through link transmission. Hence they can

    be set and referred in any FCS.

    Common Switches are used to within the FCS. They are specific to each

    FCS.

    Switches

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Max.256 GS/FCS

    System Code: %GSxxxxSddss%GSxxxx - Switch number (0001 - 0256)dd - Domain numberss - Station number

    Global Switches

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Max.4000 SW/FCS

    System Code: %SWxxxxSddss%SWxxxx - Switch number (0001 - 4000)dd - Domain numberss - Station number

    Switches are used to store intermediate variables in the interlocks. Switches are internal flags that can be set and reset whenever required.

    Switches are used for auto / man selection, pump selection, speed selection, bypass selection etc..

    Switches No. 1 - 200 are used by the system. Hence the user can use switches from 201 - 4000.

    Common Switches

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Y

    Y

    Y

    Y

    Y

    N - PV=0, SW=OFFPV=1, SW=0N

    N

    N- PV=0PV=1

    TAGNO.PV.ON

    TAGNO.PV. L

    TAGNO.PV.H

    TAGNO.PV.P

    BYPASS

    NORMAL

    PV=1, SW=ON

    PV=0, SW=OFF

    Condition

    Action

    CO1

    Switches Syntax

    BYPASSSW

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Timers are used to introduce time delays in Sequence Table.

    Second timer

    Timer Types

    Minute timerMax time - 9999 secs (or) 9999 Mins.

    PH = Maximum time the timer should count

    PV = Actual time the timer has counted

    DV = PH-PV i.e.the time left to finish counting

    DL = Deviation limit

    Timer

  • 90

    Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    1. When the timer is started, PV starts incrementing automatically Alarm status is NR2. When the timer has finished timing, i.e. when PV = PH

    Alarm status is CTUP3. When the timer is stopped while timing Alarm status is STOP4. When the timer is paused while timing Status is PAUS5. When the DV < DL alarm status is PALMAny of the alarm status can be referred in sequence table as a condition signal.

    Timer Operation

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Used to count internal events or external pulses. Counter PV updates by one every time the counter is started

    INT - Internal counter

    Counter types

    P - Pulse counter

    Max.9999 Counts

    Counter operation is same as timer except that pause option is not available.

    Counter

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Operator Guide Messages are used to guide the operator regarding the current process status and/or the actions to be taken. Operator Guide messages are also activated through sequence table on a specific condition. Operator Guide messages appear on operator guide message panel.

    System Code: %OGXXXX

    CO1

    %OGXXXX.PV.NON

    Action

    Y

    Y

    Condition

    Operator Guide Messages

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Annunciator messages are user defined alarms. Annunciator messages are also activated through sequence table on a specific condition. Annunciator messages appear on Alarm Summary Panel.

    System Code: %ANxxxxSddssaa

    CO1

    C02

    %ANXXXX.PV.L

    %ANXXXX.PV.H

    Action

    Y

    Y

    Y

    N

    N

    Condition

    Message

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Sequence instruments (or) status input output instruments are used to

    i) Switch ON/OFF motors, pumps, heater etc..

    ii) OPEN / CLOSE on-off valves

    iii) Indicate the ON/OFF status of motors, pumps, heaters etc.

    iv) Indicate the OPEN/CLOSE status of on-off valves.

    Sequence Instruments

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    One DO is linked with the instrument.

    OPEN MV = 2DO = ON

    CLOSE MV = 0DO = OFF

    OUT

    Loop Connection

    Tag No.

    SO - 1

    DOTAGNO.PV

    Wiring

    SI0 Model

    (OR) %ZnnusccPIO

    C01

    C02

    Y

    Y

    TAGNO.CSV.2

    TAGNO.CSV.0

    Action Y

    Y

    Condition

    Model SO-1

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Two DOs are linked with the instrument.

    OPEN MV = 2DO1 = ON

    CLOSE MV = 0DO2 = ON

    OUT

    Loop Connection

    Tag No.

    SO - 2

    DOTAGNO.PV

    Wiring

    SI0 Model

    (OR) %ZnnusccPIO

    C01 Y

    TAGNO.CSV.0

    TAGNO.CSV.1

    TAGNO.CSV.2

    MV = 1DO1 = OFFD02 = OFF

    Y

    Y

    Y

    This DO number and the next consecutive DO number will be taken as the 2 output signals automatically.

    Action

    Condition

    Model SO-2

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    One DI is linked to the instrument.

    OPEN PV = 2DI = ON

    CLOSE PV = 0DI = OFF

    IN

    Tag No.

    SI - 1

    DITAGNO.PV

    TAGNO.PV.2

    TAGNO.PV.0

    Condition

    Y

    Y

    Action

    Model SI-1

    PIO

    (OR) %Znnuscc

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Two DIs are linked to the instrument.

    OPEN PV = 2DI1 = ON

    CLOSE PV = 0DI2 = ON

    IN

    Tag No.

    SI - 2

    DITAGNO.PV PIO

    TAGNO.PV.0

    TAGNO.PV.1

    TAGNO.PV.2

    PV = 1DI1 = OFFDI2 = OFF

    Y

    This DI number and the next DI number

    will be taken as the 2 answerback inputs.

    Y

    Y

    Condition

    ActionTRAVERSE

    Model SI-2

    (OR) %Znnuscc

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    1 DI and 1 DO is linked to the instrument.

    OUT

    Tag No.

    SI0 - 11

    DOTAGNO.PV

    TAGNO.PV.0TAGNO.PV.2

    TAGNO.ALRM.ANS+ TAGNO.ALRM.ANS-

    Answerback Signal

    START

    PV = 2DI = ON

    MV = 2DO = ON

    Output Signal

    STOP

    PV = 0DI = OFF

    MV = 0DO = OFF DITAGNO.PV

    INY YY Y

    TAGNO.MODE.AUTTAGNO.MODE.MAN

    TAGNO.CSV.2TAGNO.CSV.0

    Y YY Y

    Action

    Condition

    Model SIO-11

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    2 DIs and 1 DO are linked to the instrument.

    MV = 0DO = OFF

    TAGNO.PV.2TAGNO.PV.1TAGNO.PV.0

    OPEN

    PV = 2DI1 = ON

    MV = 2DO = ON

    CLOSE

    PV = 0DI2 = ON

    OUT

    Tag No.

    SI0 - 21

    DITAGNO.PV

    Y YY

    TAGNO.MODE.AUTTAGNO.MODE.MAN

    TAGNO.CSV.0TAGNO.CSV.2

    Y YY Y

    PV =10DI1 = OFFDI2=OFF

    IN

    DOTAGNO.PV

    First DI No. will be taken as the first answerback signal.

    Next DI No. will be taken as the second answerback signal.

    TRAVERSE

    Action

    Condition

    Model SIO-21

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    1 DI and 2 DOs

    MV = 0DO2 = ON

    TAGNO.PV.0TAGNO.PV.2

    PV = 2DI = ON

    MV = 2DO1 = 0N

    PV = 0DI = OFF

    OUT

    Tag No.

    SI0 - 12

    DITAGNO.PV

    Y Y

    TAGNO.MODE.AUTTAGNO.MODE.AUT

    TAGNO.CSV.0 TAGNO.CSV.1TAGNO.CSV.2

    Y YY YY

    MV =1D01 = OFFD02=OFF

    IN

    DOTAGNO.PV

    FORWARD

    STOP

    REVERSE

    First DO No. will be taken as the first output signal.

    Next DO No. will be taken as the second output signal.

    Action

    Condition

    Model SIO-12

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    2 DIs and 2 DOs

    MV = 0DO2 = ON

    TAGNO.PV.2TAGNO.PV.1TAGNO.PV.0

    PV = 2DI1 = ON

    MV = 2DOI = ON

    PV = 0DI2 = ON

    OUT

    Tag No.

    SI0 - 22

    DITAGNO.PV

    Y YY

    TAGNO.MODE.AUTTAGNO.MODE.MAN

    TAGNO.CSV.0 TAGNO.CSV.1TAGNO.CSV.2

    Y YY YY

    MV =1DO1 = OFFDO2=OFF

    IN

    DOTAGNO.PV

    First DO No.

    PV = 1DI1 = OFFDI2 = OFF

    First DI No.

    PUMP 1

    STOP

    PUMP 2

    Action

    Condition

    Model SIO-22

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Interlocks are written in the form of sequence table.

    Each S.T. has 32 conditions, 32 actions and 32 rules.

    General Rules:

    Actions will be performed only if all the conditions in the rule are satisfied. Even if one condition is not satisfied, actions will not be performed.

    Condition Signal: Y/N

    Colour:

    Red: Condition is true (satisfied)

    Cyan: Condition is false (not satisfied)

    Sequence Tables

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    C01

    C02

    |

    |

    C32

    A01

    A02

    |

    |

    A32

    1 2 3 4 32Conditions

    Actions

    Band Colour :Red : All the conditions in therule are satisfied.

    Green : All the conditions in therule are not satisfied.

    Sequence Tables

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    SYSTEM GENERATION

    FUNCTION

    OPERATION

    &

    MONITORING

    FUNCTION

    CONTROL FUNCTION

    FUNCTION

    TEST

    FUNCTION

    HUMAN INTERFACE STATIONHUMAN INTERFACE STATION

    Virtual test Function

    SFCS

  • Proprietary info goes here Yokogawa Electric CorporationCopyright by Yokogawa Electric Corporation

    Thank you very much for your attention.

    YOKOGAWA INDIA LIMITED