Счетчики электроэнергии nik, счетчики воды, тепла, газа...

17

Upload: others

Post on 30-Sep-2020

11 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Счетчики электроэнергии NIK, счетчики воды, тепла, газа с ... · certified to comply with ISO 9001:2008 and ISO 14001:2004. We particularly
Page 2: Счетчики электроэнергии NIK, счетчики воды, тепла, газа с ... · certified to comply with ISO 9001:2008 and ISO 14001:2004. We particularly

2 3

!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!

!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!

NIK is one of the largest manufacturers of electricity metering devices, energy metering systems and other electrotechnical products in Eastern Europe. The Company is headquar-tered in Kyiv, Ukraine.

Established in 1995, the Company has gained the reputation as a producer of high-quality products under its own NIK and Nova-sys trademarks, well-known both in Ukraine and abroad.

Today our production facilities include 3 plants and several laboratories, employing over 600 people, including design engineers, programmers, production engineers and main-tenance engineers. Our company has been certified to comply with ISO 9001:2008 and ISO 14001:2004.

We particularly focus on preventing unau-thorized energy consumption. Unauthorized use of electricity remains a great problem for both developing and developed countries. Our solutions ensure that every single watt is me-tered and accounted for.

One of the main advantages of NIK meters is that they can be equipped with current con-trol relays (up to 120 amps) and load control relays.

NIK electricity meters have several lev-els of protection, including:- sealed casing;- protection against unauthorized replacement

of meters (laser engraving);- protection against magnetic field influence;- indication of magnetic field influence (sensor

ranging from 100 mT);- indication of radio frequency influence;- else.

About us

Page 3: Счетчики электроэнергии NIK, счетчики воды, тепла, газа с ... · certified to comply with ISO 9001:2008 and ISO 14001:2004. We particularly

4 5

AMI for the Residential Sector: NovaSyS® EnergySale®

The System is developed to provide solutions to existing and recurring problems in today’s power market environment, including:• Prevention of unauthorized electricity consumption in the residential sector;• Control of residential networks for the detection of unauthorized electricity consumption;• Monitoring of electricity consumption and timely payments made by residential electricity consumers;• Control over electricity consumption by disconnecting debtors from electricity networks;• Electricity supply and demand balance for districts, substations, and houses;• Forecasting electricity demand in the networks of the electricity owner;• Cost reduction and simplification of configurations of commercial power consumption data collection and storing

systems as well as systems for transmitting such data to a higher level.NovaSyS developed by NIK effectively solves these problems by implementing the following:• Metering data retrieval from electricity meters over such communication channels as Ethernet, PLC and radio channels;• Collection of metering data without loss of accuracy, no matter how many floors and consumers there are in a building;• Remote monitoring of electricity balance;• Non-volatile memory in the installed equipment, allowing the registration of all unauthorized interventions in the data

collection system;• Remote connection/disconnection of consumers to/from the network;• Unlimited expandability of the scanned network.

AMI FOR THE RESIDENTIAL SECTOR

Switching Controller Features

The switching controller is a functional device designed to operate within AMI. It enables commu-nication between any electricity meter equipped with a radio channel module and a data controller. Data transfer between meters and a switching controller is made through IEEE802.15.4 radio chan-nel (2.4 GHz), and the data controller – through one of the interfaces (chosen in advance) (depend-ing on device configuration). The controller has a sealed casing. It is powered from a single-phase alternating current network through mains leads connected to the device terminal block. The device is mounted using standard casing fasteners.

Technical PropertiesRated Voltage Urated 220 V

Operating voltage range from 143 V to 253 V

Power Consumption Max. 5 W

Rated mains frequency 50 Hz

Radio-module operating frequency 2.4 GHz

Max. radio-module output power + 19 dbm

Operating temperature range from - 40 °С to + 80 °С

Weight Max. 1 kg

Configurations of KK Controllers

Controller configura-

tions

Controller channel Data controller channelRadio module Radio module

RS-485 Ethernet PLCExternal antenna

Built-in antenna

External antenna

Built-in antenna

01 – + – + – – –02 – + – – + – –03 + – – + – – –04 – + + – – – –05 + – + – – – –06 + – – – + – –07 – + – – – + –08 – + – – + – +09 – + – – – – +10 – – – – + – +

Note: 02 – standard controller configuration

AMI COMpONENTS

Page 4: Счетчики электроэнергии NIK, счетчики воды, тепла, газа с ... · certified to comply with ISO 9001:2008 and ISO 14001:2004. We particularly

6 7

Configurations of KC-03-ХХ Data Controllers

Controller configurationsAvailability of modules and interfaces

RS-485 Module Radio module 2хUSB GSM Ethernet

01 - - + + + +

02 - 4 X RS-485 - + + +

04 - 2 X RS-232 - + + +

05 - 2 X RS-485 - + + +

06 - 2 X RS-485 1 X RS-232 - + + +

07 - radio module - + + +

08 - GpRS - + + +

09 - 4 X USB - + + +

10 -2xCL+1xхRS485++1xRS232

- + + +

Features

KC Data Controller

The controller is a stand-alone device designed to retrieve electricity consumption data remotely from single-phase and three-phase electricity meters equipped with relevant inter-faces and to accumulate and transmit such data to the server. As a part of AMI the controller receives data both from elec-tricity meters and switching controllers, which can function as intermediaries between meters and the data controller within the system. The device can be remotely controlled either via Ethernet or GpRS. The device can also be directly controlled from a computer equipped with the relevant console. The data are stored on an internal memory card (KC-02: 300 Мb; KC-03: up to 4 Gb). An external memory card can be con-nected to save the database.

Technical SpecificationsMaximum number of meters simultaneously connected to the same controller 1000 pcs

Non-volatile memory capacity 300 MB – 4 GB

Random-access memory capacity 60 MB

Central processing unit frequency 180 MHz

Radio-module operating frequency 2.4 GHz

Radio-module output power +17dbm

GSM/GpRS modem operating ranges 900/1800/1900 MHz

Compliance with the GSM classes Class 4 (2 W @ 900 MHz) Class 1 (1 W @ 800/1900MHz)

Rated supply voltage Urated (rated voltage of 12V DC) 220 V

Operating voltage range from 143 to 400 V

Power consumption max. 10 W

Rated supply frequency 50 Hz

Operating temperature range from -20 °С to +55 °С

Weight max. 2 kg

Configurations of KC-02-ХХ Data Controllers

Controller ConfigurationsAvailability of modules and interfaces

RS-485 USB 2.0 Ethernet GSM PLC Radio module

01 + – – + – –

02 + – + + – –

03 + – + – – –

04 – + + + – –

05 + + – + – –

06 + + + + – +

07 + + + – – –

08 + + + + + +

Note: 06 – standard controller configuration

AMI COMpONENTS

Note: 02 – standard controller configuration

Page 5: Счетчики электроэнергии NIK, счетчики воды, тепла, газа с ... · certified to comply with ISO 9001:2008 and ISO 14001:2004. We particularly

8 9

Р-485 Extender

РТ-01 Retransmitter

Features

Features

Extender Configurations

Technical Specifications

Technical Specifications

The extender is a portable device in a separate sealed casing. It is designed to transmit data from a device with an RS-485 interface to other devices equipped with a radio channel compliant with IEEE 802.15.4 (2.4 GHz). The device is mounted on a DIN- rail or other bearing surface. Flexible wires are connected to the extender terminals.

Rated supply voltage Urated 5 V

Operating supply voltage range from 4 V to 12 V

Power consumption Max. 1 W

Operating radio-module frequency (IEEE 2.4 GHz

802.15.4) +19 dbm

Max. radio-module output power 300-9600 bit/sec

Data transmission rate via RS-485 interface from - 40 °С to + 80 °С

Operating temperature range Max. 0.3 kg

Weight

Availability of an external antenna0 built-in antenna1 external antennaSoftware is compatible with0 KK-01 (extender mode)1 KC-02 (coordinator mode, firmware for connection with KK-01)2 KK-01 or KC-01 (coordinator mode, firmware for connection with meters)3 NIK meters (radio module emulation mode)Extender type

Р-485 Х Х

A portable device in a separate sealed casing (similar to the casing of Р-485). It is designed to expand the coverage area for stable wireless communication with devices equipped with radio modules compliant with IEEE802.15.4. The retransmitter is equipped with a NIK 002 radio module. The device is mounted on a DIN- rail or other bearing surface. Flexible wires are connected to the retransmitter terminals.

Technical SpecificationsRated supply voltage 220 V

Operating supply voltage range from 143 V to 264 V

Power consumption Max. 1 WOperating radio-module frequency (IEEE 802.15.4) 2.4 GHz

Max. radio-module output power +17 dbm

Operating temperature range from - 40 °С to + 80 °С

Weight Max. 0.3 kg

Features

Technical Specifications

The NIK optical probe is a double-sided interface for data exchange between a tariff device and a meter via infrared waves.The optical probe is designed and manufactured in compliance with IEC 62056-21 (MEK 1107) and can be synchronized with all meters that comply with these standards. It has a standard USB-connector, for connection to a desktop computer or laptop. The probe is compatible with Win98 / Win2000 / WinXp / Windows7.

FeaturesNIK TD-01 access point is designed to enable data exchange with electricity meters, equipped with radio modules, in the 2.4 GHz radio frequency range. The access point can be connected to a pC or laptop via USB (USB-A connection).It is equipped with a built-in chip antenna, with red and green LEDs indicating modes of operation.

Dimensions (Ø х Н) 32 х 29 mm

Material aluminium

Cable length 3 m

Weight about 150 g

Consumed current about 20 mA (transmission)

Data transmission rate 9600 bit/sec

Operating voltage 5 V (via USB)

Transmission mode Full Duplex

Wave length 940 nmOperating temperature range

from -30 °С to +55 °С

Optical Probe

NIK TD-01Access Point

Operating frequency 2.4 GHz

Supply voltage 4.75 – 5.25 V

Current consumption, max. 0.1 A

Transceiver sensitivity -96 dBm

Transceiver output power 2.5 dBm

Access point data transmission rates via USB interface 4800; 9600; 19200; 38400; 76800;115200 kbit/sec

Operating temperature range from 0 °С to +70 °С

Weight Max. 25 g

AMI COMpONENTS

Page 6: Счетчики электроэнергии NIK, счетчики воды, тепла, газа с ... · certified to comply with ISO 9001:2008 and ISO 14001:2004. We particularly

10 11

NIK 2102Overall and Mounting, mm Features

• Counter mechanism type - seven-segment LCD;• Number of tariffs – up to 4 tariffs and 12 time zones;• Automatic Summer/Winter time switch;• Daily recording of energy consumption per tariff at the mo-

ment of date change and data storage up to 63 days;• Monthly recording of energy consumption per tariff at

the moment of month change and data storage up to 48months;

• Recording and storage of a load profile up to 63 days withan integration period of 30 minutes;

• Storage of events and time of events (parameterization,correction of clock rate, internal failures, triggering ofclamp/casing cover opening sensors, influence of mag-netic field, attempts at entering an incorrect password,over-voltage and under-voltage);

• Optical port for programming.

Place for the seal

• Measurement of active energy in single-phase two-wirealternating-current circuits;

• Compatible with AMI for residential sector, using radio chan-nel (ZigBee module);

• Data transmission rate: 38400 baud over the radio channel;• Protection against unauthorized energy consumption (in-

dication of inappropriate connections, reverse current di-rection, clamp cover opening sensors, and housing coveropening sensors);

• Improved connector block, which ensures reliable wire fas-tening;

• Enhanced level of protection against constant and variablemagnetic fields in accordance with the requirements ofSOU-N MpE 40.1.35.110:2005;

• Indication of magnetic field influence (sensor ranging from100 mT);

• Indication of influence of electromagnetic field from 10 V/m;• Accuracy class margin is at least 50%;• Low internal energy consumption;• Optional connection of external power source with voltage

from 6 to 12 V to take the readings in the event of a mainspower failure;

• Optional installation of consumer load disconnecting relayin the event power exceeds threshold values;

• Housing made of UV stabilized polycarbonate;• Mountable on a DIN-rail;• Durable operation at U = 380 V (up to 24 hours).

Accuracy Class for active energy mea-suring

1.0 under GOST 30207

DSTU IEC 61036Rated current intensity 5 А

Maximum current intensity50 А or 60 А

(depending on me-ter configurations)

Rated voltage 220 V

Maximum voltage 253 V

Minimum voltage 143 V

Gear-ratio 6400 imp/(kW•h)

Rated frequency 50 Hz

Sensitivity 12.5 mА

Recalibration interval 16 years

Counter mechanism type Seven-segment LCDThe number of events and last 20 dates when sensors detected magnetic and electromagnetic fields are stored in the memory

Operating temperature range from -40 ºСto +70 ºС

Weight Max. 1.0 kg

Technical Specifications NIK 2102 – Multi-Tariff Meter

NIK 2102 ХХ Х Х М С Т Р 1

Availability of a load control relay 60 А Availability of a radio channel (ZigBee module)Т added to reference designation of multi-tariff meters only

Availability of a radio frequency sensorMagnetic field sensorNumber of measuring elements in the current circuit1 one measuring element2 two measuring elements

Type of counter mechanismЕ Electronic Display

Rated voltage; rated and maximum current intensity:01 220 V; 5(60)А03 220 V; 5(50)А

Meter Type

Meter Configurations

ELECTRONIC ELECTRICITY METERS

SINGLE-pHASE METER

Page 7: Счетчики электроэнергии NIK, счетчики воды, тепла, газа с ... · certified to comply with ISO 9001:2008 and ISO 14001:2004. We particularly

12 13

NIK 2104Overall and Mounting, mm

Accuracy Class for active energy measuring

1.0 under GOST 30207

DSTU IEC 61036

Rated current intensity 5 А

Maximum current intensity50 А or 60 А

(depending on me-ter configurations)

Rated voltage 220 V

Maximum voltage 253 V

Minimum voltage 143 V

Gear-ratio 6400 imp/(kW•h)

Rated frequency 50 Hz

Sensitivity 12.5 mА

Recalibration interval 16 years

Counter mechanism type Seven-segment LCD

The number of events and last 20 dates when sensors detected magnetic and electromagnetic fields are stored in the memory

Operating temperature range from -40 ºСto +70 ºС

Weight Max. 1.0 kg

• Counter mechanism type - seven-segment LCD withoptional installation of the backlight module;

• Number of tariffs – up to 4 tariffs and 12 time zones;• Automatic Summer/Winter time switch;• Daily recording of energy consumption per tariff at the

moment of date change and data storage up to 63 days;• Monthly recording of energy consumption per tariff at

the moment of month change and data storage up to 48months;

• Recording and storage of a load profile up to 63 days withan integration period of 30 minutes;

• Storage of events and time of events (parameterization,correction of clock rate, internal failures, triggeringof clamp/casing cover opening sensors, influenceof magnetic field, attempts at entering an incorrectpassword, over-voltage and under-voltage).

• Measurement of active energy in single-phase two-wirealternating-current circuits;

• Protection against unauthorized energy consumption (in-dication of inappropriate connections, reverse current di-rection, clamp cover opening sensors, and housing coveropening sensors);

• Improved connector block, which ensures reliable wire fas-tening;

• Enhanced level of protection against constant and variablemagnetic fields in accordance with the requirements ofSOU-N MpE 40.1.35.110:2005;

• Accuracy class margin is at least 50%;

• Low internal energy consumption;• Indication of magnetic field influence (sensor ranging from

100 mT);• Indication of influence of electromagnetic field from 10 V/m;• Optional installation of the electrical RS-485 interface, radio

channel (ZigBee module) or pLC modem for data reading,programming meters, and their adoption in AMI;

• Optional installation of a relay output and consumer loaddisconnecting relay in the event power exceeds thresholdvalues;

• Housing made of UV stabilized polycarbonate;• Mountable on a DIN-rail.

Features

Technical Specifications NIK 2104 – Multi-Tariff Meter

NIK 2104 Х Х Х Х Х Т М СAvailability of a radio frequency sensor Availability of a magnetic field sensor Multi-tariff meterAvailability of a relay Р Load control relay 80 АР1 Relay outputР2 Load control relay and relay outputAvailability of a radio channel0 No radio channel1 Radio channel in meter configurations with a built-in antenna without a power amplifier2 Radio channel in meter configurations with a built-in antenna and a power amplifier Availability of interfaces 0 No electrical interfaces 1 Four-wire electrical RS-485 interface 2 Four-wire electrical RS-485 interface and optical port interface3 Optical port interface4 Electrical PLC interface and optical port interface 5 Electrical pLC and RS-485 interfaces, optical port interface 6 Four-wire electrical RS-485 and IRDA interfaces Rated and maximum current intensities 1 5(80) А 2 5(60) А 3 5(40) А 4 5(50) А Rated voltage 0 220 V1 230 V2 240 VMeter type

Meter Configurations

ELECTRONIC ELECTRICITY METERS

SINGLE-pHASE METER

Place for the seal put by verifica-

tion officer

Page 8: Счетчики электроэнергии NIK, счетчики воды, тепла, газа с ... · certified to comply with ISO 9001:2008 and ISO 14001:2004. We particularly

14 15

NIK 2303Features

• Enhanced level of protection against constant and alternatemagnetic fields in accordance with the requirements ofSOU-N MpE 40.1.35.110:2005;

• 2 independent interfaces: current loop, RS-485 (RS-232,ZigBee) for data reading and application in AMI;

• Accuracy class margin is at least 50%;• Radio frequency radiation sensor (10 V/m in the frequency

range 80-500 MHz);

• Magnetic field sensor ranging from 100 mT;• Mountable on a DIN-rail;• Sealable optical port for reading data and programming;• Optional connection of an external power source (12 V) to

take readings in the event of a mains power failure;• Housing made of UV stabilized polycarbonate.

Overall and Mounting, mm

Accuracy Class for active energy measuring 1.0 under GOST 30207 and DSTU IEC 61036

Accuracy Class for reactive energy measuring 2.0 under DSTU IEC 61268Counter mechanism type LCDNumber of tariffs 4Number of time zones 12Recalibration interval 16 yearsOperating temperature range from -35 °С to +70 °СData transmission rate 9600 bit/sec

Supplementary indication via LCD

• current time;• current date;• current active power;• current reactive power (positive/negative value, direct - reverse);• current voltage;• effective current intensity;• power-factor;• voltage underrating or voltage overrating;• current reverse;• influence of magnetic field and radio frequency radiation.

Technical Specifications

Availability of a radio frequency sensorAvailability of a magnetic field sensor*Availability of relay outputs0 No relay outputs1 One relay output of telemetry commandAvailability of a complementary interface module0 No complementary interface module1 Equipped with complementary RS-232 interface module2 Equipped with complementary RS-485 interface module3 Equipped with complementary wireless channel

interface module in configuration with external antenna4 Equipped with complementary wireless channel

interface module in configuration with built-in antenna5 Equipped with complementary current loop

interface moduleAvailability of main interface0 No main interface module1 With installed main current loop interface module2 With installed main RS-485 interface moduleAvailability of optical port interface0 No optical port interface1 With installed optical port interfaceT A multi-tariff meter Network ConnectionsП1 Direct connection 5 (100) АП2 Direct connection 5 (60) А П3 Direct connection 5 (120) А П6 Direct connection 5 (80) А К1 Combined connection

(direct connection and transformer connection) 5 (10) А Т1 Transformer connection 5(10) А Т2 Transformer connection 5(10) А Measured energyА Active energy А+АР Active and reactive energy А+, А-**, R+, R-Meter type

NIK 2303 Х Х T Х Х Х Х M С

Meter Configurations

*Reference designations of meters equipped with magnetic field sensors may lack M, but meter plates should bear the inscription«Protected against magnetic and radio interferences».**А – only reference designations with Т2

ELECTRONIC ELECTRICITY METERS

THREE-pHASE METER

Page 9: Счетчики электроэнергии NIK, счетчики воды, тепла, газа с ... · certified to comply with ISO 9001:2008 and ISO 14001:2004. We particularly

16 17

Availability of a radio frequency sensor Availability of a magnetic field sensor Availability of relay outputs0 No relay outputs2 Load control relayAvailability of a complementary interface module0 No complementary interface module2 Equipped with complementary RS-485 interface module4 Equipped with complementary wireless channel

interface module in configuration with built-in antenna5 Equipped with complementary current loop

interface module8 Equipped with the main electrical PLC interface Availability of main interface0 No main interface moduleAvailability of optical port interface0 No optical port interface1 With installed optical port interfaceT A multi-tariff meter Network Connections П1 Direct connection 5 (100) АП2 Direct connection 5 (60) А П3 Direct connection 5 (120) А П6 Direct connection 5 (80) А К1 Combined connection

(direct connection and transformer connection) 5 (10) А Т1 Transformer connection 5 (10) А Т2 Transformer connection 5 (10) А Measured energyА Active energy А+АР Active and reactive energy А+, А-*, R+, R- Meter design and softwarefeaturesMeter type

NIK 2303 L Х Х T Х Х Х Х M C

Meter Configurations

NIK 2303L NIK 2303i

• Enhanced level of protection against constant and alternatemagnetic fields in accordance with the requirements of SOU-N MpE40.1.35.110:2005;

• 1 modular interface for data reading and application in AMI (currentloop, RS-485, ZigBee, pLC, GSM);

• Accuracy class margin is at least 50%;• Consumer load disconnecting relay;• Snap-on case cover;• Magnetic field sensor ranging from 100 mT;• Radio frequency radiation sensor (10 V/m in the frequency range 80-

500 MHz).

Features

• Enhanced level of protection againstconstant and alternate magnetic fieldsin accordance with the requirementsof SOU-N MpE 40.1.35.110:2005;

• 2 independent interfaces: currentloop, RS-485, RS-232, ZigBee, pLC,GSM, Ethernet for data reading andapplication in AMI;

• Accuracy class margin is at least 50%;

• Consumer load disconnecting relay;• Snap-on case cover;• Magnetic field sensor ranging from

100 mT;• Radio frequency radiation sensor (10

V/m in the frequency range 80-500MHz);

• Single-phase metering, 2 batteries,DLMS.

Overall and Mounting, mm

Overall and Mounting, mm

Availability of a radio frequency sensor Availability of a magnetic field sensor Availability of relay outputs0 No relay outputs1 One relay output of telemetry command2 Load control relay3 Two relaysAvailability of a complementary interface module0 No complementary interface module1 Equipped with complementary RS-232 interface module2 Equipped with complementary RS-485 interface module3 Equipped with complementary wireless channel interface module in configuration with external antenna4 Equipped with complementary wireless channel interface module in configuration with built-in antenna5 Equipped with complementary current loop interface module7 Equipped with complementary Ethernet interface module 8 Equipped with the main electrical PLC interfaceAvailability of main interface0 No main interface module1 Equipped with main RS-232 interface module 2 Equipped with main RS-485 interface module3 Equipped with main wireless channel i nterface module in configuration with built-in antenna4 Equipped with main wireless channel interface module in configuration with external antenna5 Equipped with main current loop interface module 6 Equipped with GSM radio module7 Equipped with main Ethernet interface module8 Equipped with main electrical PLC interfaceAvailability of optical port interface1 With installed optical port interfaceT A multi-tariff meterNetwork ConnectionsП1 Direct connection 5 (100) A П2 Direct connection 5 (60) A П3 Direct connection 5 (120) A П6 Direct connection 5 (80) AК1 Combined connection (direct connection and transformer connection) 5 (10) AТ2 Transformer connection 5 (10) AMeasured energyА Active energyАР Active and reactive energyMeter design and software featuresMeter type

NIK 2303 I Х Х T Х Х Х Х M C

Meter Configurations

Features

ELECTRONIC ELECTRICITY METERS

THREE-pHASE METER

Page 10: Счетчики электроэнергии NIK, счетчики воды, тепла, газа с ... · certified to comply with ISO 9001:2008 and ISO 14001:2004. We particularly

18 1918

NIK 2102Overall and Mounting, mm

Overall and Mounting, mm

Technical SpecificationsFeatures

Meter Configurations

Accuracy class 1.0 (GOST 30207 DSTU IEC 61036)

Rated (max.) current intensity:— 02— 04— 05

5(60) А5(50) А10(60) А

Sensitivity 12.5 mА

Recalibration interval 16 years

Operating temperature range from -40 °С to +70 °С

Total wattage of metervoltage circuit Max. 8 W·А

Total wattage of metercurrent circuit Max. 0.2 W·А

Weight Max. 1.0 kg

Meter type Meter configuration

Rated (maximum) current intensity, A

Rated voltage,V

Meter constant, impulses/kWh

Casing type

Number of measuring elements in the current circuit

NIK 2102 02.М1 5 (60) 220 6400 flat 1

NIK 2102 02.М2 5 (60) 220 6400 flat 2

NIK 2102 04.М1 5 (50) 220 6400 flat 1

NIK 2102 04.М2 5 (50) 220 6400 flat 2

NIK 2102 05.М1 10 (60) 220 6400 flat 1

NIK 2102 05.М2 10 (60) 220 6400 flat 2

NIK 2102 02.М1В 5 (60) 220 6400 convex 1

NIK 2102 02.М2В 5 (60) 220 6400 convex 2

NIK 2102 04.М1В 5 (50) 220 6400 convex 1

NIK 2102 04.М2В 5 (50) 220 6400 convex 2

NIK 2102 05.М1В 10 (60) 220 6400 convex 1

NIK 2102 05.М2В 10 (60) 220 6400 convex 2

• Measurement of active energy in single-phase two-wire alternat-ing-current circuits;

• Extended operating voltage range (from – 35 % to +15 % of thebasic value);

• Two-element meter (shunt and transformer used as current sen-sors);

• Enhanced level of protection against constant and variable mag-netic fields in accordance with the requirements of SOU-N MpE 40.1.35.110:2005;

• Protection against unauthorized energy consumption, indicationof reverse current direction, current inequality in the phase and neutral wire;

• Quick and easy installation (mounting dimensions and clamp lay-out allow installation without any modifications of the connected cable lines when replacing induction meters);

• Accuracy class margin is at least 50%;• Low internal energy consumption;• Housing made of UV stabilized polycarbonate;• Mountable on a DIN-rail;• Durable operation at U=380 V (up to 24 hours);• Operable in boxes for outdoor installation.

92

35

138

205

178

115

80

ELECTROMECHANICAL ELECTRICITY METERS

SINGLE-pHASE METER

Page 11: Счетчики электроэнергии NIK, счетчики воды, тепла, газа с ... · certified to comply with ISO 9001:2008 and ISO 14001:2004. We particularly

20 21

ELECTROMECHANICAL ELECTRICITY METERS

THREE-pHASE METERNIK 2301Overall and Mounting, mm Features

Overall and Mounting, mm

Технические характеристики

• Measurement of active electrical energy;• Protection against unauthorized energy consumption

(indication of inappropriate connections,reverse current direction, phase under/over voltage);

• Improved connector block,which ensures reliable wire fastening;

• Enhanced level of protection against constantand variable magnetic fields in accordance withthe requirements of SOU-N MpE 40.1.35.110:2005;

• Accuracy class margin is at least 50%;• Low internal energy consumption;

• Extended temperature range (from -40 °С to +70 °С);• Housing made of UV stabilized polycarbonate;• Quick and easy installation

(mounting dimensions and clamplayout allow installation withoutany modifications of the connectedcable lines when replacing induction meters);

• Mountable on a DIN-rail;• Registration of magnetic field influence

(in new casing design).

Technical Specifications

314

213

84170

150

14316

7191

208

Accuracy class 1.0 under GOST 30207 and DSTU IEC 61036Rated Voltage Un- Ap1, Ap2, Ap3, AK1- АТ1- Аp1-127, Аp2-127, Аp3-127, АK1-127- АТ1-127

3х220/380 V3х100 V

3х127/220 V3х220 V

Permissible mains voltage deviation from -20 % to +15 %

Rated current intensity, In 5 АMaximum current intensity, Imax- Аp1, Аp1-127- Аp2, Аp2-127- Аp3, Аp3-127- АK1, АK1-127, АТ1, АТ1-127

100 А60 А120 А10 А

Rated frequency 50 Hz

Sensitivity 12.5 mА

Recalibration interval 16 yearspower consumption:- In voltage circuits- In the current circuits (I – In)

Max. 10 (≤2) V·А (W)Max. 0.05 V·А (W)

Number of counter mechanism digits 6+1

Meter constant: duration of additional output impulses 8000 imp/kW·h

Operating temperature range from -40 °С to +70 °С

Weight Max. 2.3 kg

Page 12: Счетчики электроэнергии NIK, счетчики воды, тепла, газа с ... · certified to comply with ISO 9001:2008 and ISO 14001:2004. We particularly

22 23

Mounting PadsTechnical Specifications

Features

Type Kp 25 Kp 125Operating voltage Urated 3×220/380 VMaximum current intensity, Imax 25 А 125 АRated mains frequency 50, 60 HzOperating temperature range from - 40 °C to + 55 °Cprotection level under GOST 14254 IP30Average lifespan 30 yearsWeight Max. 0.5 kg Max.1 kg

Dimensions, max. 170×112×36 mm

218×126×48 mm

• Mounting pads are designed for the mounting and dismantlingof three-phase electricity meters (combined and transformerconnection) in the metering spot without load disconnection.They allow measurement of current intensity and loadvoltage without load disconnection and interruption of energymetering due to meter connection to the mounting pad;

• Mounting pads are suitable for any industry;• Climatic and mechanical features of mounting pads

comply with GOST 22266 for the indoor use of mounting

pads in buildings free from aggressive fumes, dust, and gases;

• Insulation between the conductive parts of different mountingpad phases with disengaged jumpers can withstand sinusoidalalternating-current voltage of 2000 V at a frequency of 50 Hzwithin one minute;

• Mounting pad clamps can withstand tenfold current overloadfor 0.5 sec;

• Cover made of UV stabilized polycarbonate.

Features• Low-voltage distribution boards are designed for outdoor installation of

single- and three-phase alternating-current electricity meters operating atvoltages up to 380 V in order to protect devices from mechanical damage,prevent unauthorized energy consumption, and protect meters from dustand precipitation. The casing is made of a flameproof material. The casingdesign allows the taking of meter readings through a viewing window,without removing the cover. Viewing windows are made of UV stabilizedplastic, which remains completely transparent over the course of time;

• The distribution board has universal fasteners for mounting the meterson a DIN rail, as well as for installing and fastening other equipmentinside a switching board (circuit breakers, corrugated pipes, andcables). The board casing can be sealed;

• The protection level of the board is ІР 54 under GOST 14254.

Technical SpecificationsCasing wall thickness Min. 2.5 mm

Viewing window glass thickness Min. 3 mm

Operating temperature range from -50 °Сto +70 °С

Electrical insulation density Min. 4 kV

Average lifespan Min. 25 years

Warranty period 3 years

Weight Max. 6 kg

Dimensions 615х580х114 mm

SCHRN BoardsSCHRN-01

Configuration SCHRN 01-4

SCHRN 03-2

Number of phases in meters installed in boards 1 3

Max. number of meters installed in one board 4 2

Max. board weight, kg 6 6Max. number of holes for fastening a corrugated pipe 22 22

Max. number of automatic switches

Single-pole 8 2

Three-pole - 2Note: boards are also available in other configurations to satisfy customer's needs, taking into account number of available seats in the board.

Board Configurations

Features

DOT BoxesDOT.3-1

Configuration DOT.3-1 DOT.3-1В*Number of phases in meters installed in boxes 1, 3 1, 3

Max. number of meters installed in one box 1 1

Max. box weight 6 kg 6 kg* - convex

• The Box is designed for outdoor installation of a single phasealternating current electricity meter operating at a voltage up to380 V to protect the device from mechanical damage, preventunauthorized energy consumption, and protect the meter fromdust and precipitation;

• The box is designed for meters with electric damage protectionclass ІІ;

• protection level of the box is ІР 54 under GOST 14254;• Its casing is made of a flameproof material;• The casing design allows taking meter readings through a viewing

window, without removing the cover. Viewing windows are madeof UV stabilized plastic, which remains completely transparentover the course of time;

• The box has universal fasteners for mounting a meter with the helpof 3 self-threading screws, on a DIN-rail, as well as for installingand fastening other equipment inside the box (circuit breakers,corrugated pipes and cables);

• The box casing can be sealed.

Casing wall thickness Min. 2.5 mm

Viewing window material thickness Min. 3 mm

Operating temperature range from -35 °С to +85 °С

Electrical insulation density Min. 4 kV

Average lifespan Min. 25 years

Warranty period 3 years

Dimensions: DOT.3-1 DOT.3-1В

280х305х117 mm280х305х167 mm

Technical Specifications

Box Configurations

Page 13: Счетчики электроэнергии NIK, счетчики воды, тепла, газа с ... · certified to comply with ISO 9001:2008 and ISO 14001:2004. We particularly

24 25

• Amorphous alloys are used to manufacturethe transformer;

• Calibration interval - 4 years;• IEC 60044-1;• Accuracy class 0.5S;• Laser marking;• Secondary winding under a transparent

sealable cover;• Operating temperature range: from -45 °С

to +70 °С;• Climate versions and usage categories under

GOST 15150: U2; U3.

CURRENT TRANSFORMERSTOLN-10

FeaturesOverall and Mounting, mm

Support Type Compound-Filled Transformer

The TOLN-10 Current Transformer is designed to transmit measuring data signals to metering devices of AC installations.

Technical Specifications

Short time thermal and dynamic current values

Rated primary current Ipn, А 10 15 20 30 50 75 100 150 200 300 400 500 600 800 1000

Short time thermal currentIth, max., kА 1.1 2.2 3.3 3.3 5.4 8.8 11 17 22 32 44 55 66 88 110

Short time dynamic current Idyn, max., kА 2.75 5.5 8.25 8.25 13.5 22 27.5 42.5 55 80 110 137.5 165 220 275

No. Parameter Values

1 Rated voltage 10 kV

2 Maximum operating voltage 12 kV

3 Rated isolation level 28/75 kV

4 Rated primary current 10, 15, 20, 30, 50, 75, 100, 150, 200, 300, 400, 500, 600, 800, 1000 А

5 Rated secondary current 5 А

6 Rated line frequency 50 Hz

7 Number of secondary windings 2

8Rated power of secondary winding (cos φ = 0.8, VА)- measuring winding- protecting winding

1015

9 Accuracy class of measuring secondary winding 0.5S

10 Accuracy class of protecting secondary winding 10Р

11Rated Instrument Security Factor (FS), no more than:- for transformers with Ipn<800 А- for transformers with Ipn≥800 А

35

12 Accuracy limit factor of the protecting winding 10

Page 14: Счетчики электроэнергии NIK, счетчики воды, тепла, газа с ... · certified to comply with ISO 9001:2008 and ISO 14001:2004. We particularly

26 27

CURRENT TRANSFORMERSTPLN-10

• Amorphous alloys are used tomanufacture the transformer;

• Calibration interval - 4 years;• IEC 60044-1;• Accuracy class 0.5S;• Laser marking;• Secondary winding under a

transparent sealable cover.• Operating temperature range: from

-45 °С to +70 °С;• Climate versions and usage

categories under GOST 15150: U2;U3.

transformerswith rated current > 150А

Bushing-Type Compound-Filled Transformer

The TPLN-10 Current Transformer is designed to transmit measuring data signals to metering devices of AC installations.

FeaturesOverall and Mounting, mm

No. Parameter Value

1 Rated voltage 10 kV

2 Maximum operating voltage 12 kV

3 Rated isolation level 28/75 kV

4 Rated primary current10, 15, 20, 30, 50, 75, 100,

150, 200, 300, 400, 500, 600, 800, 1000 А

5 Rated secondary current 5 А

6 Rated line frequency 50 Hz

7 Number of secondary windings 2

8Rated power of secondary winding (cos φ = 0.8, VA)- measuring winding- protecting winding

1015

9 Accuracy class of measuring secondary winding 0.5S

10 Accuracy class of protecting secondary winding 10Р

11Rated Instrument Security Factor (FS), no more than:- for transformers with Ipn<800 А- for transformers with Ipn≥800 А

35

12 Accuracy limit factor of the protecting winding 10

Technical Specifications

Rated primary current Ipn, А 10 15 20 30 50 75 100 150 200 300 400 500 600 800 1000

Short time thermal currentIth, max., kА 1.1 2.2 3.3 3.3 5.4 8.8 11 17 22 32 44 55 66 88 110

Short time dynamic current Idyn, max., kА 2.75 5.5 8.25 8.25 13.5 22 27.5 42.5 55 80 110 137.5 165 220 275

Short time thermal and dynamic current values

Page 15: Счетчики электроэнергии NIK, счетчики воды, тепла, газа с ... · certified to comply with ISO 9001:2008 and ISO 14001:2004. We particularly

28 29

• Amorphous alloys areused to manufacture thetransformer;

• Calibration interval - 4years;

• IEC 60044-1;• Accuracy class 0.5S;• Laser marking;• Secondary winding under

a transparent sealablecover;

• Operating temperaturerange: from -45 °Сto +70 °С;

• Climate versions andusage categories underGOST 15150: U2; U3.

No. Parameter Value1 Rated voltage 10 kV

2 Maximum operating voltage 12 kV

3 Rated isolation level 28/75 kV

4 Rated primary current 10, 15, 20, 30, 50, 75, 100, 150, 200, 300, 400, 500, 600, 800, 1000, 1500, 2000 А

5 Rated secondary current 5 А

6 Rated line frequency 50 Hz

7 Number of secondary windings 2

8 Rated power of secondary winding (cos φ = 0.8, VA)- measuring winding- protecting winding

1015

9 Accuracy class of measuring secondary winding 0.5S

10 Accuracy class of protecting secondary winding 10Р

11 Rated Instrument Security Factor (FS), no more than:- for transformers with Ipn<800 А- for transformers with Ipn≥800 А

35

12 Accuracy limit factor of the protecting winding 10

Rated primary current Ipn, А 10 15 20 30 50 75 100 150 200 300 400 500 600 800 1000 1500 2000

Short time thermal current Ith, max., kА 1.1 2.2 3.3 3.3 5.4 8.8 11 17 22 32 44 55 66 88 110 165 210

Short time dynamic current Idyn, max., kА 2.75 5.5 8.25 8.25 13.5 22 27.5 42.5 55 80 110 137.5 165 220 275 412.5 525

CURRENT TRANSFORMERSTPOLN-10

The TPOLN-10 Current Transformer is designed to transmit measuring data signals to metering devices of AC installations.

Bushing-Type Compound-Filled Round Transformer

OUTLINE DRAWINGS OF TpOLN-10 TRANSFORMERS WITH RATED CURRENT FROM 10 TO 300 A

OUTLINE DRAWINGS OF TpOLN-10 TRANSFORMERS WITH RATED CURRENT FROM 400 TO 2,000 A

primary transformer bus bar with rated cur-rent from 1,000 to 2,000 A; bus bar width

– 60 mm, bus bar thickness – 16mm

FeaturesTechnical Specifications

Overall and Mounting, mm

Short time thermal and dynamic current values

Page 16: Счетчики электроэнергии NIK, счетчики воды, тепла, газа с ... · certified to comply with ISO 9001:2008 and ISO 14001:2004. We particularly

30 31

CURRENT TRANSFORMERSTOPN-0.66

The TOPN-0.66 Current Transformer is designed to transmit measuring data signals to metering devices of AC installations.

Support Type Transformer in a Plastic Casing

• Amorphous alloys are used to manufacture thetransformer;

• Calibration interval - 16 years;• IEC 60044-1;• Accuracy class 0.5, 0.5S;• Laser marking;• Mountable on a DIN-rail;• Secondary winding under a transparent sealable cover;• Operating temperature range: from -45 °С to 40 °С;• Available configurations with a vertical or horizontal bas

bar or without a bus bar.

Transformer with a horizontal bus bar (TOPN-0.66-1…)

Transformer bus bar with rated current 800 A and 1,000 A

Transformer without a bus bar (TOPN-0.66-2…)

Features

Technical Specifications

Dimensions and Weight of TOPN-0.66 Transformers

No. Parameter Value1 Rated voltage 0.66 kV2 Maximum operating voltage 0.72 kV3 Rated isolation level 3 kV

4 Rated primary current 150, 200, 300, 400, 500, 600, 800, 1000 А

5 Rated secondary current 5 А6 Rated line frequency 50 Hz7 Rated power of secondary winding (cos φ = 0.8, VA) 58 Accuracy class 0.5S; 0.5

9Rated Instrument Security Factor (FS), no more than:- for transformers with accuracy class 0.5- for transformers with accuracy class 0.5S

53

Overall and Mounting, mm

Rated primary current Ipn, А 150 200 300 400 500 600 800 1000Short time thermal current Ith, max., kА 9.6 9.6 19.2 19.2 24 24 28.8 36Short time dynamic current Idyn, max., kА 24 24 48 48 60 60 72 90

Short time thermal and dynamic current values

Parameterprimary current, А

150 - 200 300 - 400 500 - 600 800 1000Size А, mm 128 128 160 180 180Size В, mm 117.5 117.5 135.5 135.5 135.5Size С, mm 95 95 105 105 105Size D, mm 108 108 128 - -Size E, mm 92 92 112 - -Size F, mm Ø 8.5 Ø 8.5 Ø 8.5 Ø 11 Ø 11Size G, mm 48 48 54 54 54Size H, mm 2 4 6 8 10Size I, mm - - - 100 100Size J, mm - - - 150 150Size K, mm 6.6 6.6 12.5 12.5 12.5Size L, mm 16.6 16.6 22.5 22.5 22.5Size M, mm 26.6 26.6 32.5 32.5 32.5Weight, kg, max. 0.8 0.8 1.1 1.1 1.1Weight without a bus bar, kg, max. 0.75 0.75 1.0 1.0 1.0

Page 17: Счетчики электроэнергии NIK, счетчики воды, тепла, газа с ... · certified to comply with ISO 9001:2008 and ISO 14001:2004. We particularly

InternationalSales Department:

+38 (044) 248-74-71 [email protected]

www.nik-energy.com

Regional Representative:

NIK, NovaSyS, EnergySale are registered trademarks and cannot be used without the prior written consent of the Trademark Owner.