(alternative test) · 3 steam turbine testing variation in measured test data steady-state : -...
TRANSCRIPT
(Alternative Test)
STEAM TURBINE THERMAL PERFORMANCE TESTING
2008. 04. 10증기터빈설계1팀
1
Steam Turbine Testing
STEAM TURBINE PERFORMANCE TEST (ALTERNATIVE)
Raw Data Evaluation– Location and Type of Test Instrumentation– Variation in Measured Test Data– Permissible Variation of Variables– Effect of Measurement Error
Test Cycle CalculationContract Cycle CalculationVerification of Performance Test Results
2
Steam Turbine Testing
Location and Type of Test Instrumentation
3
Steam Turbine Testing
Variation in Measured Test DataSteady-state : - Average Value Over Short Intervals Does Not ChangeStable :
- Value Does Not Fluctuate Over TimeDifference From Reference : - Difference Between Average Value During Test and Value in Reference Case
300
400
500
600
700
800
900
1000
1100
0 1 2 3 4 5 6 7Time (hours)
Tem
pera
ture
(F)
Diffe
renc
e fro
m st
eady
-st
ate
Deviation from ReferenceInstability
Two-hour Performance Test
4
Steam Turbine Testing
Permissible Deviation of Variables
Temp +/- 30 O
F from design temp +/- 7 O
F from average value
Press +/- 3.0 % of the absolute press +/- 0.25% of the absolute press
RTH Steam Temp +/- 30 O F +/- 7 O F
+/- 0.05 psi +/- 0.02 psi
Not Specified +/- 1.0%
+/- 5.0%
+/- 10.0%
Exhaust Pressure
Power Factor
Voltage
Speed
Variable Permissible Deviationfrom Design Condition Permissible Fluctuation
Main Steam
5
Steam Turbine Testing
Effect of Measurement Error
1%
1ºF
1%
1ºF
1%
1ºF
1%
1ºF
-0.76%
+0.27%
+0.69%
-0.33%
-
-
-
-
-0.60%
+0.21%
+0.59%
-0.26%
Error HP Efficiency % IP Efficiency %
Throttle Pressure
Throttle Temperature
Cold Reheat Pressure
Cold Reheat Temperature
Hot Reheat Pressure
Hot Reheat Temperature
IPCrossover Pressure
IP Crossover Temperature
FOSSIL UNIT1% h HP = 0.16% HR & 0.30% KW 1% h IP = 0.12% HR & 0.12% KW1% h LP = 0.50% HR & 0.50% KW
NUCLEAR UNIT1% h HP = 0.26% ~ 0.41% HR & KW 1% h LP = 0.59% ~ 0.74% HR & KW
6
Steam Turbine Testing
STEAM TURBINE PERFORMANCE CALCULATION
Raw Data EvaluationTest Cycle Calculation
– Primary Flow & Secondary Flow– Test Cycle Heat Rate & kW Load
Contract Cycle CalculationVerification of Performance Test Results
7
Steam Turbine Testing
Primary Flow & Secondary Flows Calculation
Calculation of Flow Rate from Differential PressureThe average velocity(V) of the flow in the pipe can be calculated by the following formula:
V = sqrt ( 2g *Δ P / ρ )Where g : Gravitational constant
ΔP: Differential pressureρ : Density of fluid
However velocity is rarely calculated in practice, but volumetric and mass flow rate are.Volumetric flow rate(Q) is calculated by multiplying the average velocity by the cross-sectional area(A) of the pipe:
Q = A * sqrt( 2g *Δ P / ρ )And mass flow rate(m) is calculated by multiplying Q by the density of the fluid at the operatingpressure and temperature:
M = ρ Q = ρ A Cq * sqrt ( 2g * Δ P / ρ )Where Cq : Flow coefficient determined by calibration
8
Steam Turbine Testing
ASME PTC 6.0 Flow SectionQ = 1890.07 * d2 * Fa * Cq * ΔP/ v * [ 1 / 1-β4 ]
Where d : Nozzle Diameter (inches)D : Pipe Diameter (inches)β : d / Dv : Specific VolumeΔP: Differential Pressure Fa : Thermal Expansion FactorCq : Flow coefficient from calibration data
Cq = Cx - 0.185 * Rd-0.2 * (1 - 361239 / Rd) 0.8
Where Cx : Coefficient determined by calibrationRd : Reynolds Number
Rd = ρ * V * d / μ = 48 * Q / ( π * d * μ)
Where ρ : densityV : Velocity (ft/sec)μ : Dynamic viscocityQ : Flow (lb/hr)
9
Steam Turbine Testing
Primary Flow Calculation Method(1) Assume Reynolds Number(2) Determine Cq = Cx - 0.185 * Rd-0.2 * (1 - 361239 / Rd) 0.8 with assumed Rd (3) Determine Q = 1890.07 * d2 * Fa * Cq * ΔP / v * [ 1 / 1-β4 ] with predetermined Cq(4) Determine Rd = 48 * Q / ( π * d * μ) with predetermined Q (5) Iterate until Assumed Rd = Determined Rd
Cq = 1.0054 - 0.185 * Rd-0.2 * (1 - 361239 / Rd) 0.8
10
Steam Turbine Testing
Sample Calculation for Final Feedwater Flow
11
Steam Turbine Testing
Secondary Flow Elements
V-CONEORIFICE
PITOT TUBE Forward-Reverse Tube
12
Steam Turbine Testing
Sample Calculation for Secondary Flow
13
Steam Turbine Testing
Test Cycle Heat Rate and KW Load
KW Load = * K * WHMCF * CTRCF * PTR CF * CTR * PTR# Counts
Test Time(hrs)
Heat Rate = ( Heat Supplied – Heat Returned ) / KW Load
= Q throttle * (H throttle-H FFW) + Q HRT * ( H HRT – H CRH)
KW LoadWhere
K : Watt-hour meter constant, 0.003125WHMCF : Watt-hour meter correction factorCTRCF : Current tranformer ratio correction factorPTRCF : Potential tranformer ratio correction factorCTR : Current tranformer ratioPTR : Potential tranformer ratio
Q throttle: Turbine throttle steam flow, lbm/hrQ HRT : Turbine hot reheat steam flow, lbm/hrH throtle : Turbine throttle steam enthalpy , Btu/lbmH HRT : Turbien hot reheat steam enthalpy, Btu/lbmH CRH : Turbien cold reheat steam enthalpy, Btu/lbmH FFW : Final feedwater enthalpy, Btu/lbm
14
Steam Turbine Testing
Sample Calculation of Test kW Load (1) -Measurement
15
Steam Turbine Testing
Sample Calculation of Test kW Load (2) - Adjustment
16
Steam Turbine Testing
Sample Calculation of Test Heat Rate (1) - Unaccounted for Flow
17
Steam Turbine Testing
Sample Calculation of Test Heat Rate (2) - Throttle Flow and Heat Rate
18
Steam Turbine Testing
Raw Data EvaluationTest Cycle CalculationContract Cycle Calculation- Group 1 Correction for ASME PTC 6.0 Alternative Test - Group 2 Correction- Correction for Control Valves Throttling and MW Thermal Output
Verification of Performance Test Results
STEAM TURBINE PERFORMANCE CALCULATION
19
Steam Turbine Testing
Group 1 Correction for ASME PTC 6 Alternative Test Group 1 Correction Curves for The Alternative Procedure
Final Feed Water Temperature Correction - Top Heater Terminal Temperature Difference- Top Heater Drain Cooler Approach Temperature Difference- Top Heater Extraction Line Pressure Drop Correction for Auxiliary Extraction Steam Flow- Extraction Steam to Station Heating- Extraction Steam to Air Pre-heater (Fossil Only)- etc.Corrections for Main Steam De-superheating Flow (Fossil Only)Corrections for Reheat Steam De-superheating Flow (Fossil Only)Auxiliary Turbine Extraction CorrectionCondensate Sub-cooling CorrectionCondenser Make-up Correction
20
Steam Turbine Testing
Top Heater Terminal Temperature Difference Correction Curve for Load
Sample CalculationMeasured TTD : 3.64 ℉Design TTD : 5.00 ℉
From this curvekW % Correction @ 3.64 ℉ = 0.032%
kW = 1 + %Correction / 100= 1 + 0.032 / 100 = 1.0003
표준원전: -315kW @518,859kW
⎠
⎞⎜⎜⎝
⎛+=100
%Corr1kW ⎜
21
Steam Turbine Testing
Top Heater Terminal Temperature Difference Correction Curve for Heat Rate
Sample CalculationMeasured TTD : 3.64 ℉Design TTD : 5.00 ℉
From this curveHR % Correction @ 3.64 ℉= -0.032%
kW = 1 + %Correction / 100= 1 - 0.032 / 100 = 0.9997
표준원전: -0.7kCal @2,312kCal/kWh
⎠
⎞⎜⎜⎝
⎛+=100
%Corr1HR ⎜
22
Steam Turbine Testing
Top Heater Extraction Pressure Drop Correction
Sample CalculationMeasured ΔP (from TBN to HRT) = 10.13 psiDesign ΔP (from TBN to HRT) = 13.80 psi
Measured Pressure @ TBN = 478.80 psiaExpected Pressure @ HTR with Design ΔP = Pressure @ TBN - ΔP_Design = 478.8 - 13.8 = 465.0 psiaSaturation Temperature @ 465.0 psia = 459.59 ℉
Measured Pressure @ HTR = 468.67 psiaSaturation Temperature @ 468.67 psia = 460.39 ℉
Change of TTD caused by test ΔP = 460.39 - 459.59 = 0.8 ℉
From Top Heater Terminal Temperature Difference Correction CurveskW % correction @ 4.2 ℉= 0.019%HR % correction @ 4.2 ℉= - 0.019%
kW = 1 + %Correction / 100 = 1 + 0.019 / 100 = 1.0002HR = 1 + %Correction / 100 = 1 - 0.019 / 100 = 0.9998
23
Steam Turbine Testing
Top Heater Drain Cooler Approach Temperature Correction Curve
Sample CalculationMeasured DC : 12.26 ℉Design DC : 10.00 ℉
@ Test TFR of this curvekW % Correction = 0.018%HR % Correction = 0.022%
kW = 1-[ (0.018/100) x (12.26-10) / 10 ]= 1.0000
HR = 1+[ (0.022/100) x (12.26-10) /10 ]= 1.0000
⎟⎟⎠
⎞⎜⎜⎝
⎛
⎟⎟⎠
⎞⎜⎜⎝
⎛
−×−=
−×+=
F deg
F deg
10)DC(DC
100%Corr1kW
10)DC(DC
100%Corr1 HR
dt
dt
24
Steam Turbine Testing
Feedwater Pump Turbine Extraction Correction Curve
Sample CalculationMeasured % Throttle Flow : 1.29 %Design % Throttle Flow : 1.26 %
@ Test TFR of this curvekW % Correction = -1.015%HR % Correction = 1.019%
kW = 1 + [ (-1.019 / 100) x (1.29-1.26) ]= 0.9997
HR = 1 + [ (1.015 / 100) x (1.29-1.26) ]= 1.0003
⎟⎟⎠
⎞⎜⎜⎝
⎛
⎟⎟⎠
⎞⎜⎜⎝
⎛
−×+=
−×+=
1%)%TF(%TF
100%Corr1kW
1%)%TF(%TF
100%Corr1 HR
dt
dt
25
Steam Turbine Testing
Feedwater Pump Enthalpy Rise Correction Curve
Sample CalculationMeasured Enthalpy Rise : 2.69 Btu/lbDesign Enthalpy Rise : 3.36 Btu/lb
@ Test TFR of this curvekW % Correction = 0.079%HR % Correction = - 0.078%
kW = 1 + [ (0.079 / 100) x (2.69 - 3.36) ]= 0.9995
HR = 1 + [ (-0.078 / 100) x (2.69 - 3.36) ]= 1.0005
⎟⎟⎠
⎞⎜⎜⎝
⎛
⎟⎟⎠
⎞⎜⎜⎝
⎛
−×+=
−×+=
Btu/lb
Btu/lb
1)H_rise(H_rise
100%Corr1kW
1)H_rise (H_rise
100%Corr1HR
dt
dt
26
Steam Turbine Testing
Condenser Sub-cooling Correction Curve
Sample CalculationMeasured Sub-Cooled Temp : 0.24 ℉Design Sub-Cooled Temp : 0 ℉
@ Test TFR of this curvekW & HR % Correction = 0.027%
kW = 1 - [ (0.027 / 100) x (0.24 - 0.00) / 5 ]= 1.0000
HR = 1 + [ (0.027 / 100) x (0.24 - 0.00) / 5 ]= 1.0000
⎟⎟⎠
⎞⎜⎜⎝
⎛
⎟⎟⎠
⎞⎜⎜⎝
⎛
−×−=
−×+=
F deg
F deg
5)SCT(SCT
100%Corr1kW
5)SCT(SCT
100%Corr1HR
dt
dt
27
Steam Turbine Testing
Condenser Make-up Correction Curve
Sample CalculationMeasured % Make-up : 0.00 %Design % Make-up : 0.20 %
@ Test TFR of this curvekW % Correction = - 0.255%HR % Correction = 0.259%
kW = 1 + [ (-0.255 / 100) x (0.0-0.2) ]= 1.0005
HR = 1 + [ (0.259 / 100) x (0.0-0.2) ]= 0.9995
⎟⎟⎠
⎞⎜⎜⎝
⎛
⎟⎟⎠
⎞⎜⎜⎝
⎛
−×+=
−×+=
1%)%MU(%MU
100%Corr1kW
1%)%MU(%MU
100%Corr1HR
dt
dt
28
Steam Turbine Testing
Sample Calculation for Group1 Correction with Correction Curves
TTD – Top Feedwater HeaterELPD - Top Feedwater HeaterDC – Top Feedwater Heater Feedwater Pump Turbine ExtractionFeedwater Pump Enthalpy RiseCondensate Sub-cooling Condenser Make-up FlowCombined Factor
3.64 deg F2.12% (10.13 psi)12.26 deg F158391 lbm/h2.69 Btu/lm-0.24 deg F0 %
5.00 deg F3.0% (13.0 psi)10.00 deg F152482 lbm/h3.36 Btu/lm0.00 deg F0.2 %
1.00031.00021.00000.99970.99951.00001.00051.0001
0.99970.99981.00001.00031.00051.00000.99950.9999
Test Cycle Desing Cycle HR Factor kW Factor
Heat Rate after Group 1 Correction = Test Heat Rate / Combined HR Factor = 2308.87 / 0.9999 = 2308.23 kcal / kWh
KW Load after Group 1 Correction = Test kW Load / Combined KW Factor = 1,053,485 / 1.0001 = 1,053,385 KW
TEST HEAT RATE = 2,308.87 kcal/ kWhTEST kW LOAD = 1,053,485 kW
29
Steam Turbine Testing
Group 2 Correction
Turbine Initial Steam Pressure CorrectionTurbine Initial Steam Temperature CorrectionTurbine Hot Reheat Steam Temperature Correction (Fossil Only)Turbine Initial Steam Moisture (Nuclear only)Pressure Drop of Steam through the reheater systems (Fossil Only)Turbine Exhauster Pressure
Use of Group 2 Correction Curves requires correction of the test throttle flow to design conditions, as follows;
Pd x υt
Pt x υdQc = Q t x
Where Qc : Corrected Throttle FlowQt : Test Throttle FlowPd : Design Turbine Initial Steam PressureUd : Design Turbine Initial Steam Specific VolumePt : Test Turbine Initial Steam PressureUt : Test Turbine Initial Steam Specific VolumeFor nuclear unit, use Steam Quality
instead of Steam Specific Volume...
30
Steam Turbine Testing
Initial Pressure Correction Curve for Load
Sample CalculationMeasured Pressure : 1076.82 psiaDesign Pressure : 1025 psia
%Change in pressure = (1076.82-1035) / 1035 = 4.04%
From of this curve @ 4.04%kW % Correction = 0.30%
kW = 1 + % Correction= 1 + ( 0.30 / 100) = 1.0030
⎟⎟⎠
⎞⎜⎜⎝
⎛+= 100%Corr1kW
31
Steam Turbine Testing
Initial Pressure Correction Curve for Heat rate
⎟⎟⎠
⎞⎜⎜⎝
⎛+= 100%Corr1HR
Sample CalculationMeasured Pressure : 1076.82 psiaDesign Pressure : 1035 psia
%Change in pressure = (1076.82-1035) / 1035 = 4.04%
From of this curve @ 4.04%HR % Correction = - 0.30%
HR = 1 + % Correction= 1 + ( - 0.30 / 100) = 0.9970
32
Steam Turbine Testing
Initial Moisture Correction Curve for LoadSample Calculation@ Steam Generator Outlet Pressure : 1109.98 psiaMoisture : 0.003%Enthalpy : 1188.64 Btu/lb from steam table
@ Turbine inletPressure : 1076.82 psiaMoisture : 0. 21% from steam tableEnthalpy : 1188.64 Btu/lb = H @ SG outlet
Design Moisture : 0.45%
From of this curve @ 0.21%kW % Correction = 0.06%
kW = 1 + % Correction= 1 + ( 0.06 / 100 ) = 1.0006
⎟⎟⎠
⎞⎜⎜⎝
⎛+= 100%Corr1kW
33
Steam Turbine Testing
Initial Moisture Correction Curve for Heat RateSample Calculation@ Steam Generator Outlet Pressure : 1109.98 psiaMoisture : 0.003%Enthalpy : 1188.64 Btu/lb from steam table
@ Turbine inletPressure : 1076.82 psiaMoisture : 0. 21% from steam tableEnthalpy : 1188.64 Btu/lb = H @ SG outlet
Design Moisture : 0.45%
From of this curve @ 0.21%HR % Correction = - 0.06%
HR = 1 + % Correction= 1 + ( - 0.06 / 100 ) = 0.9994
⎟⎟⎠
⎞⎜⎜⎝
⎛+= 100%Corr1HR
34
Steam Turbine Testing
Exhaust Pressure Correction
Sample CalculationMeasured Exhaust Pressure : 32.1 psiaDesign Exhaust Pressure : 38.0 psia
From of this curve @ 33.1 psiakW & HR % Correction = 0.12%
kW = 1 + % Correction= 1 + ( 0.12 / 100) = 1.0012
HR = 1 - % Correction= 1 - ( 0.12 / 100 ) = 0.9988
⎟⎟⎠
⎞⎜⎜⎝
⎛
⎟⎟⎠
⎞⎜⎜⎝
⎛
−=
+=
100%Corr1HR
100%Corr1kW
35
Steam Turbine Testing
Sample Calculation for Group2 Correction with Correction Curves
Initial Pressure, psiaInitial Moisture, %Exhaust Pressure, mm HgCombined Factor
1076.8 psia0.21%33.1 mm Hg
1035 psia0.45%38.0 mm Hg
1.00301.00061.00121.0048
0.99700.99940.99880.9952
Test Cycle Design Cycle HR Factor kW Factor
Contract Cycle Heat Rate = Heat Rate after Group1 Correction / Combined HR Factor = 2,308.23 / 0.9952 = 2,311.27 kcal / kWh
Contract Cycle KW Load = kW Load after Group1 Correction / Combined kW Factor = 1,053,385 / 1.0048 = 1,050,996 kW
HEAT RATE after Group1 Correction = 2,308.23 kcal / kWh kW LOAD after Group1 Correction = 1,053,385 kW
36
Steam Turbine Testing
Correction for Control Valves Throttling and MW Thermal OutputCorrection for Control Valves Throttling
% HR Correction = x x 100 x KW mo P tW n ΔP mo - ΔP vwo
where subscript mo indicates highest load test, and
Wn / W mo = the ratio of flow through the final valve(s) to total flow during the highest load test (decimal fraction of total flow being subject to extra throttling)
(ΔP mo - ΔP vwo) / P t = the ratio of (1) the difference between pressure drop across the final valve(s) during the highest load test and the pressure drop across the same valve(s) atVWO conditions to (2) throttle pressure (extra pressure drop due to final valvesnot being wide open)
P t = absolute throttle pressure
K = 0.15 for turbines with nuclear steam supply operating predominantly in the moisture region= 0.10 for turbines operating predominantly in the superheated region
37
Steam Turbine Testing
Sample CalculationMeasured Initial Steam Pressure : 1076.82 psiaMeasured Steam Chest Pressure : 1073.73 psiaMeasured CV#4 Discharge Pressure : 906.79 psiaMeasured CV#4 Position : 28.97%
1) By interpolation between 23.43% and 30.08% in the %Lift column of this table Total Flow (W mo) = 12,185,173 lbm/hrCV#4 Flow (W m ) = 2,152,956 lbm/hr
∴ W m / W mo = 0.1767
2) Assuming 1% pressure drop at Main Stop ValvesΔP vwo @ Design = P initial @ Design x 0.99 - P CV#4 @ Design= 1035 x 0.99 - 1014.97 = 9.68 psia
∴ ΔP vwo = P initial @ Measured x (ΔP vwo @ Design / P initial @ Design ) = 1076.82 x (9.68 / 1035) = 10.07 psia
3) ΔP mo = P steam chest @ Measured - P CV#4 Discharge @ Measured = 1073.73 - 906.79 = 166.94 psia
% kW & HR Correction = 0.1767 x [ (166.94-10.07) / 1076.82 ] x 100 x 1.5 = 0.386
kW = 1 + % Correction = 1 - ( 0.386 / 100) = 1.0039HR = 1 - % Correction = 1 + ( 0.386 / 100 ) = 0.9961 ⎟⎟
⎠
⎞⎜⎜⎝
⎛
⎟⎟⎠
⎞⎜⎜⎝
⎛
−=
+=
100%Corr1 HR
100%Corr1kW
38
Steam Turbine Testing
Correction for MW Thermal Output
MW Thermal Output = Net heat to the cycle x 3,412.14= Q SG Outlet x ( H SG Outlet - H SG inlet ) / 3,412.14
Where Q SG Outlet : Steam Generator Outlet Flow (lbm/hr)H SG Outlet : Steam Generator Outlet Enthalpy (Btu/lbm) H SG Inlet : Steam Generator Inlet Enthalpy (Btu/lbm)3412. 14 : Conversion factor from BTU to kW
Sample Calculation1) Measured final feedwater flow : 12,879,666 lbm/hr
Measured unaccounted for flow : 20,222 lbm/hr∴ Q SG Outlet = 12,879,666 - 20,222 = 12, 859,444 lbm/hr
2) Calculate H SG Outlet and H SG Inlet using Steam Table H SG Outlet = STMPTH (1,204.10 psia, 456.6 ℉) = 438.03 Btu/lb H SG Intlet = STMPMH (1,109.98 psia, 0.003%) = 1,188.64 Btu/lb
3) MW Thermal Output = 12,859,444 x ( 1188.64 - 438.03) / 3,412.14 = 2828.84 MW
From Design MW Thermal Output of 2825 MW
% kW Correction = (2828.84 / 2825) - 1 = 0.136 kW = 1 + % Correction = 1 + ( 0.136 / 100) = 1.0014 ⎟⎟
⎠
⎞⎜⎜⎝
⎛+= 100%Corr1kW
39
Steam Turbine Testing
Raw Data EvaluationTest Cycle CalculationContract Cycle Calculation
Verification of Performance Test Results– Test Result Calculation – Contract Cycle Heat Rate
STEAM TURBINE PERFORMANCE CALCULATION
40
Steam Turbine Testing
Test Result Calculation
41
Steam Turbine Testing
Contract Cycle Heat Rate
42
END OF DOCUMENT