CamHosp

1

Camfil Farr- clean air solutions

2009-07-01

CamHosp-R – MF

Camfil Farr

CamHosp-R Features in Detail

CamHosp

2

Principle of a ceiling system without recirculation

CamHosp2

CLEAN AIR CLEAN AIR CLEAN AIR

Ceiling

Exhaust air

Fresh air

AHU

CamHosp

3

Principle of a ceiling system incl. recirculation function

CamHosp-R

CLEAN AIR CLEAN AIR CLEAN AIR

Ceiling

Exhaust air

Fresh air

AHU

CamHosp

4

General Function

• Recirculating (UCV) systems provide exactly what the name suggests:

– Generally a 3m x 3m ultra clean zone in an operating theatre

– This zone is used primarily when orthopaedic surgery is to be carried out

– Also used for open heart and ophthalmic surgery

– UCV systems assure a laminar flow clean zone by recirculating air from side areas

of the operating theatre [70%] mixed with AHU-conditioned supply air [30%]

• The air entering the clean zone is supplied through generally 12 x H14 HEPA filters

• The recirculated air is firstly filtered by 6 x F7 pre-filters

• The air is circulated by 6 x three phase fans through a control system

CamHosp

5

CamHosp-R Features

CamHosp

6

No sealing with silicone needed

Special gasket and clamping system

CamHosp

7

Divided Screentek Laminator

CamHosp

8

CamHosp-R Installation

Adaption to the wall Filter section around surgical lamp

CamHosp

9

CamHosp-R Installation

Soundabsorber

Prefilter Opakfil F7

CamHosp

10

Even surfaces for easy cleaning / desinfection

Pressure plenum with filter installation

CamHosp

11

OP Light installation

a) Standard

blending

b) NEW !!!

Filtersection H14 around

surgical lamp

CamHosp

12

Lighting system

Standard lighting system (eg. Zumtobel / Trilux) can be integrated

around the clean zone on request

CamHosp

13

HEPA-Filter with Gel–gaskets

Knife Edge

CamHosp

14

Filterheight 130 mm

CamHosp

15

Pressure drop

in the ceiling

below

40 Pa

Pressure drop measurement with H14 filter Basis: 8.000 m³/h with MG media pack

CamHosp

16

Filter performance

CamHosp

17

Integrated prefilter F7 in standard depth 292mm

(Possibility to alternatively install AMC prefilters)

CamHosp

18

Exclusive use of standard components

for ventilators und electronic control

CamHosp

19

Media Bridges

Media bridges (eg. Dräger) can be integrated on request

Integration to the

CamHosp-R done !

CamHosp

20

All validation tests performed

acc. to the new DIN 1946-4 Dec. 2008

CamHosp

21