SmartLineStartup

SmartLine

Initial wirings

Initial Wirings

SmartLine

Balance Zones with a 3.9kΩ resistance

Initial wirings

SmartLine

If Zones aren’t balanced panel displays “Zone open”

Fault 01/04Zone OpenZone 01<Zone 01>

Initial wirings

SmartLine

Balance Dialler with a 10 kΩ resistance(between terminals 19 and 23 )

Initial wirings

SmartLine

If Dialler isn’t balanced panel displays “Fault Dialler”

Fault 01/01FaultDialler

Initial wirings

SmartLine

Balance NAC with a 47kΩ resistance

Initial wirings

SmartLine

If NAC isn’t balanced panel displays “Open I/O Panel NAC”

Fault 01/01Open I/OPanel NAC

Initial wirings

SmartLine

Detectors wiring

3.9 kΩ End of Line resistance on the last detector

Balance other zones with a 3.9 kΩ resistance

Detectors Wiring

SmartLine

Callpoints wiring

3.9 kΩ End of Line resistance on the last callpoint

Balance other zones with a 3.9 kΩ resistance

Callpoints Wiring

SmartLine

NAC

47 kΩ End of Line resistance on the last device

NAC Wiring

NAC output activates on Alarm: it can activate alarm devices

SmartLine

NAC

47 kΩ End of Line resistance on the last device

If panel displays “Short I/O Panel NAC” it will need connect a diode in series (if devices haven’t it)

Fault 01/01Short I/OPanel NAC

SmartLine

Other wirings

17-18 FAULT Terminalsactivated on Fault.

Fault output can activate some devices

Other wirings

SmartLine

Dialer

19-20 DIALER Terminalsactivated on Alarm.

DIALER Output can activate an external dialler.

SmartLine

AUX R

25-26 AUX R Terminalsturn off 24V on Reset

They can reset latching linear beam smoke detector

SmartLine

Relay

27-28-29 RELAY Terminals activated on Alarm (at default)

They can activate some devices

SmartLine

Generic contact

Generic Contact Wiring

680Ω resistance

3.9kΩ resistance

NO Alarm Contact

Alarm contact only

SmartLine

Generic contact

680Ω resistance

NO Alarm Contact

NC Fault Contact

3.9kΩ resistance

Alarm Contact and

Fault Contact

SmartLine

Gas Detector Wiring

Gas Detector Wiring

3.9kΩ resistance

INE55/ING55 Detector

Detection-Line Zone Wiring

It have to program the Zone as “Gas (Relay Output)

SmartLine

Gas Detector Wiring

3.9kΩ zone balancing resistance

INE55/ING55Detector

I/O 4-20mA Input Wiring

150Ω resistance

INA55-101board

It have to program I/O Line as “Gas 4-20mA Input”

SmartLine

Gas Detector Wiring

Generic 4-20mA Gas Detector Wiring

4-20mAoutput

3.9kΩ zone balancing resistance

150Ω resistance

Generic4-20mA

gas detector

Detector have to supply current

It have to program I/O Line as “Gas 4-20mA Input”

SmartLine

To next expansion board

Expansion Boards Wiring

Expansion boards

SmartLine

Expansion boards

Expansion Zones are similar to panel ones

Balance Zones with a 3.9kΩ resistance

SmartLine

Espansions board

Expansion NAC output is programmable(at default output is activated on Alarm)

Balance NAC with a 47kΩ resistance

SmartLine

Expansion boards

It have to configure expansion boards

Enable panel programming phase

Control PanelIN PROGRAMMiING

Ver: 2.0301/01/12 17:45

SmartLine

Expansion boards

Control PanelIN PROGRAMMING

Ver: 2.0301/01/12 17:45

Control PanelIN PROGRAMMING

Ver: 2.0301/01/12 17:45

SettingsDisablementMaintenanceProgramming

ConfigurationProgr. ZoneProgr. OutputProgr. Timer

Acquire int.busAcquire ext.bus

Current DevicesExtin.module OExpansion OOk to execute

Current DevicesExtin.module OExpansion 1Ok to execute

SmartLine

RS485 Bus Wiring

RS485 Bus

Up to4 Repeater2 Power Station

SmartLetUSee/LCD-LiteRepeater

SmartLevelPower Station

SmartLine

RS485 Bus

It have to address RS485 Bus devices

SmartLetUSee/LCD-LiteRepeater

SmartLevelPower Station

Address

DIPSwitchPosition

SmartLine

RS485 Bus

It have to address RS485 Bus devices

SmartLetUSee/LCD-LiteRepeater

View logLED TestResetMaintenance

LED testResetMaintenanceProgramming

BoosterOptionsAddress RS485Default Data

SmartLevelPower Station

Address: 01

Address: 02

Prog

Enable SmartLevel programming phase

SmartLine

RS485 Bus

RipetitoreSmartLetUSee/LCD-Lite

SmartLevelPower Station

Set End of Line jumper in EOL position on the last device

SmartLevelRepeater

SmartLine

RS485 Bus

SmartLetUSee/LCD-LiteRepeater

SmartLevelPower Station

It have to address RS485 Bus devices

Enable panel programming phase

Control PanelIN PROGRAMMING

Ver: 2.0301/01/12 17:45

SmartLine

RS485 Bus

SmartLetUSee/LCD-LiteRepeater

SmartLevelPower Station

CentraleIN PROGRAMMAZ.!!

Ver: 2.0301/01/12 17:45

Control PanelIN PROGRAMMING

Ver: 2.0301/01/12 17:45

Control PanelIN PROGRAMMING

Ver: 2.0301/01/12 17:45

SettingsDisablementMaintenanceProgramming

ConfigurationProgr. ZoneProgr. OutputProgr. Timer

Acquire int.busAcquire ext.bus

Current DevicesRepeater OPower Station OOk to execute

Current DevicesRepeater 2Power Station 1Ok to execute