Electrical safety...always one step ahead
A-ISOMETERIRDH275, IRDH375, IRDH575
Electrical safety...always one step ahead
A-ISOMETERIRDH275, IRDH375, IRDH575
-
8/13/2019 Isometer - IRDH275-375-575_
2/6
IRDH... speak in plain language
All text messages are displayed as plain text on the illumi-
nated display and are emphasized by brightly lit LEDs.
IRDH... inform at the press of a button
Additional information such as system leakage capacitance,
parameter values etc.are immediately available at the pressof a button.
IRDH... simple to operate
The user-friendly menu structure and large keys makes thedevice simple to operate.
Variable installation
The panel-mounting enclosure is easy-to-install into the fascia of a switch-
board. In this way, the entire information is available to the user at aglance.Terminal cover and shock-hazard protected connection termi-nals provide additional protection.The IRDH275 series is designed for
installation into a switchgear cubicle (DIN rail).
T H E N E W D E V I C E F A M I LY A - I S O M E T E R I R D H 27 5 , I R D H 3 7 5 A N D I R D H 5 7 5
Whichever IT system you have,
the A-ISOMETERs IRDH275/375/575 will monitor them all
The use of unearthed power sup-plies (IT systems) is of the essence
in all electrical installations wherehigh operating safety and reliabi-
lity is paramount. IRDH275/375/575- the new family of innovative
A-ISOMETERs is exactly adaptedto the requirements of modern
power supply systems. The newAMPPlus measuring principle allows
exact measuring of the insulation
resistance,even in extended ITsystems and installations includingvariable-speed drives.
A solution that helps
to keep the costs lowComprehensive information and
clear indication via a plain textdisplay and yet simple-to-use
makes this device family standout where safety is important.
Time is gained and expensiveinterruptions can be avoided
thanks to advance information. Front view of the A-ISOMETER IRDH575, IRDH375 and IRDH275
-
8/13/2019 Isometer - IRDH275-375-575_
3/6
The modular system
Time gained thanks to flexibility
Basic functionThe A-ISOMETER IRDH275/375measure the insulation resistance
and indicate the measured value
on the display. If the measuredvalue falls below the preset value,
an alarm message is provided.
Monitoring several
interconnected
IT systems
Only one A-ISOMETER may beactive in each IT system.TheA-ISOMETERs IRDH275B/375B
can be configured accordingly sothat this requirement will always
be met when several IT systemsare interconnected.The RS485
interface (BMS protocol) providesthe necessary information exchan-
ge between the A-ISOMETERs.
Insulation monitoring
with automatic fault
location (EDS)If an insulation fault occurs, it mustbe localized and eliminated in order
to guarantee operating safety.Forfast, automatic localization of the
faulty circuit, the IRDH575 and theinsulation fault evaluator EDS47...-
12 with the appropriate measuringcurrent transformers are combined
to provide a complete insulationfault location system.
Basic function of the IRDH275
Monitoring of several interconnected IT systems
Insulation monitoring with automatic fault location (EDS)
-
8/13/2019 Isometer - IRDH275-375-575_
4/6
For various application fields
Techniques that convinces
IRDH275 / 375 / 575 series
Monitor the insulation resistance in all IT systems
the functional safety through automatic self monitoring
- System and earth connection - system functions
Signal
a drop in insulation resistance
- prewarning - main alarm
Inform
via plain LC text display- actual insulation resistance - system leakage capacitance
- faulty conductor (DC) - parameter values
IRDH275B / 375B / 575 seriesAdditional functions
Data memory
Historical memory to store alarm text messages with date and time
Communication
RS485 interface (BMS protocol)
Current output 0/4 .. . 20 mA
ISONET function For interconnection of several IT systems
Decoupling relays
IRDH575 seriesThe IRD575 series in combination with EDS47...-12 evaluators and
measuring current transformers can be extended to an automaticinsulation fault location system.
Location
Insulation faults in electrical installations with up to 708 subcircuits
No disconnection of the electrical installation
Information
Indication of the faulty subcircuit
Application fields
Industrial systems with variable-
speed drives
Power generation and distri-bution
Traffic engineering etc.
Technical features
Insulation monitoring with prewarning and
main alarm for universal use in all IT systems
Adjustable response value 1 k ...10 M
AMPPlus measuring principle for AC,DC and
AC/DC IT systems of up to 793 V,extendable via
coupling devices (not for IRDH575)
Monitoring of system functions,system and
earth connection
Automatic adaptation to system leakage
capacitances
Internal and external test and reset button
Illuminated plain text display:
2x 16 characters (IRDH275/375)
4x 16 characters (IRDH575)
Alarm LEDs
- prewarning
- main alarm
- system monitoring
additional features of IRDH575
- insulation fault location
- common alarm,fault located
Separately adjustable alarm relays in N/O and
N/C operation
RS485 interface (BMS protocol)
Panel mounting (optional) in IP 65 (IRDH375)
or in IP 42 (IRDH575)
DIN rail mounting (IRDH275)
Enclosure for installation into standard distri-bution panels
IRDH375 = 72 x 144 mm (H x B)
IRDH575 = 96 x 144 mm (H x B)
Industry Traffic engineering
-
8/13/2019 Isometer - IRDH275-375-575_
5/6
F U N C T I O N S A N D C H A R A C T E R I S T I C S A T A G L A N C E
Technical data
Right to modifications reserved!
Series
Type
Application field
Nominal voltage range UnFrequency range fn
System leakage capacitance Ce
Nominal voltage range Un (extendable)
Application
Main circuits AC,3(N) AC/DC
Control circuits AC/DC
Diode-decoupled systems
Interconnected IT systems
Response values/contacts
Number of response valuesResponse value
Contact main alarm
Contact prewarning
Contact (1 changeover contact)
Communication
Measured value display/parameter
Alarm LEDs
Function keys
RS485 interface
Current outputGeneral features
Measuring principle
Test/reset button
Fault memory
Indication faulty conductors L+/L-
Connection monitoring
Historical memory
Isometer disconnecting relays
Insulation fault location
Test current adjustableIndication
Evaluators
IRDH575
3(N)AC/DC 20 ...575 V/340 ...760 VDC 50 ...400 Hz
< 150 (500) F
--
x
x
x
x
21 k ...10 M
1 changeover contact
1 changeover contact
system fault/EDS alarm
four-line LC display
5
4
BMS protocol
0/4 ...20 mA
AMPPLUS
internal/external
x
x
system/PE
x
x
1 ...50 mAfaulty conductors
EDS470/473-12
IRDH375
3(N)AC 0 .. . 793 V, DC 0 ... 650 VDC 0.2 ... 400 Hz
< 150 (500) F
x
x
x
x
x
21 k ...10 M
1 changeover contact
1 changeover contact
system fault
two-line LC display
3
4
BMS protocol (B version)
0 ...400 A(0/4 ...20 mA B version)
AMPPLUS
internal/external
x
x
system/PE
B version
B version
----
--
IRDH275
3(N)AC 0 .. . 793 V, DC 0 ... 650 VDC 0.2 ... 400 Hz
< 150 (500) F
x
x
x
x
x
21 k . . . 10 M
1 changeover contact (or system fault)
1 changeover contact
--
two-line LC display
3
4
BMS protocol (B version)
0 ...400 A(0/4 ...20 mA B version)
AMPPLUS
internal/external
x
x
system/PE
B version
B version
----
--
-
8/13/2019 Isometer - IRDH275-375-575_
6/6
A SUMMARYIRDH 375 series
I RD H 3 75 B s eri es
IRDH 575 series
MONITORING insulation resistance in all ungrounded (IT) systems system and earth connection system functions functional safety due to automatic self monitoring
SIGNALLING A drop in insulation resistanceprewarning main alarm
INFORMATION
via LC text displaycurrent insulation resistance faulty conductor (DC polarity)system leakage capacitance parameter settings
DETECTING insulation fault location in electrical installations
with up to 708 sub circuits without disconnection of circuits
INFORMATION indication of the faulty sub circuit
DATA MEMORY historical memory to store alarm text messages with date and time
COMMUNICATION
RS485 interface (BMS protocol) current output 0/420mA
IT SYSTEM MANAGER automatic decoupling of Isometers in interconnected systems
The IRDH575 series in combination with EDS47..-12 evaluators andmeasuring current transformers can be extended to provide an
automatic insulation fault location system.
Additional functions:
OF THE FUNCTIONS
BENDER INC.700 Fox Chase Coatesville, PA 19320- USA
Toll-free:1-800-356-4266 Fax: 610-383-7100
E-Mail: [email protected] : www.bender r e lay .com
TECHNICALCHARACTERISTICStwo-step insulation monitoring for
universal use in all IT systems
adjustable response value1kOhm10 MOhm
AMPplus measuring principle forAC,DC and AC/DC IT systems up to690 V, extendable via couplingdevices
continuous monitoring of systemfunctions and system and earthconnection
automatic adaptation to systemleakage capacitances
internal and external test andreset button
illuminated LC text display: 2x16 characters (IRDH375)
4x16 characters (IRDH575)
alarm LEDs - IRDH 375- prewarning
main alarm
system monitoring
supplementary functions-IRDH575- insulation fault location
common alarm fault located
separately adjustable alarm relaysin N/O / N/C operation
RS485 interface
shock hazard protected terminalsfront plate mounting optional
cover for IP65
enclosure for installation intostandard distribution panels IRDH 375 =72x144 mm (HxW)
IRDH 575 = 96x144 mm (HxW)
Rights to modification reserved