l1 rtu96x_f2

Upload: tomuta-stefan

Post on 03-Jun-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/12/2019 L1 RTU96x_f2

    1/2

    Energy Automation & Information

    T&D

    MiCOM C 9 64C / C 9 64Modular Remote Terminal Unit - RTU

    Sophistic ated Remote Terminal Unit for substation co ntrol ,monitoring, transducerless measurement, power quality monitoring,automation and gateway communications.

    Key features Transducerless RTU New standard communication

    protocols: UCA2, IEC 61850 Large LCD graphical display for

    user-friendly local control,monitoring

    Multi-bays management Power quality analysis and

    waveform recording Modular and expandable design

    Appl ic ation prof il e Stand-alone RTU Local or remote data acquisition

    and processes for control andsupervision

    Substation Gateway Integrated into the ALSTOM

    SCADA solutions

    General functions Data acquisition and processes

    digital and analog (I/O) values Control and monitoring of switching

    devices Designed for use without

    interposing relays and transducers Integrated and configurable

    indications / alarms panel Interlocking and automatic

    functions IEC 61131-3 compliant Metering functions Standardised and proprietary

    communication protocols Load profiling Storage of events, counters and

    measured values Download on site or via remote

    access of the configuration IEDs Gateway

    Field of Application

    The MiCOM C 9 64 modular RTUprovides a powerful solution for SCADA, automation, and digitalsubstation control systems. It isdesigned for a wide range of applications:

    Electrical utility Transmission and distribution

    substations

    Power substations Industry

    Process control, includingmanufacturing, transit,telecommunications, testing,etc.

    Oil and gas, includingpipelines

    Water and wastewater

    Transportation control Railways Airport

    High-performance with modular and expandable archit ecture for every applic ation

    The MiCOM C 9 64 combines thefeatures of several digital-discreetdevices and functions into one unit.Its high-performance is further expanded through the modular I/O.This design allows the user to simplifytheir design and installation, improve

    precision and quality as well asincrease efficiency through space andcost reductions in wiring, testing,maintenance and management.The MiCOM C 9 64 offers on-boardcommunication modules for everyapplication with multiple standardprotocols and interfaces. Each port isable to communicate with a dedicatedprotocol including IEC 60870-5-101,MODBUS, DNP3.0, etc and can beused as a master or slave device.

  • 8/12/2019 L1 RTU96x_f2

    2/2

    2 0 0 2 A L S T O M

    O u r p o l

    i c y

    i s o n e o f c o n t

    i n u o u s

    d e v e

    l o p m e n

    t a n d

    t h e r i g

    h t i s r e s e r v e d

    t o s u p p

    l y e q u i p m e n

    t w h i c h m a y v a r y

    f r o m

    t h a t

    d e s c r i

    b e d .

    P r i n t e d i n

    - h o u s e

    P u

    b l i c a

    t i o n :

    C 9 6 4 / E N

    D S / A a

    T&D Energy Automation & Information, Le Sextant, 3, avenue Andr Malraux, 92300 Levallois-Perret. France. www.tde.alstom.comTel: +33 (0) 141 49 20 00 - FAX: +33 (0) 141 49 24 85 - Contact Centre on line 24 hours a day : +44 (0) 1785 25 00 70

    Technical data

    Hardware

    CaseMiCOM C 9 64CWxHxD 40T(206 mm) x

    4U(177 mm) x 168 mm

    Slots 4 or 5 free assignmentMiCOM C 9 64WxHxD 80T(405 mm) x

    4U(177 mm) x 168 mmSlots 14 or 15 free

    assignment

    Control panelLarge graphical LCD (optional)Display 72 x 72 mm (optional)LEDs 17, 12 free configurableButtons 12 : 7 for operations

    5 for control (optional)

    Power supply boardUN 24, 48/60, 110/125,

    220/250 V DC100 - 250 V AC 50/60 Hz

    2 Relays Alarm, Watchdog

    Processor board32-bit Power PC-based processor Internal WatchdogClock 80 MhzRAM 16 MbytesFlash 2 MbytesSRAM 256 KbytesEthernet-Based 10/100Base-FXor 10/100Base-TX2 insulated serial interfacesRS232/422/485 or 4 insulatedserial interfaces RS232/422/485(optional)IRIG-B interface

    Digital Input Board (16 DI)16 optically insulated inputs withone common for 2 DI.UN 24, 48/60, 110/125,

    220/250 V DC

    Digital Output Board (10 DO)8 outputs NO + 2 outputs NO/NCUN 250 V DC / 230 V ACMaking 70 VA / WBreaking 30 VA / W

    CommunicationsLANUCA2, IEC 61850 LAN node asEthernet-Based 10/100Base-FXor 10/100Base-TX

    Standard SCADA protocol sIEC 60870-5-101, DNP3,

    MODBUS

    InterfacesOptical / RS232 / RS422 / RS485

    Standard IEDs protoc olsIEC 60870-5-103, DNP3.0,MODBUS, IEC 60870-5-101

    SynchronisationExternal synchronisation usingIRIG-B

    PLC functionsBuilt in applications Circuit Breaker monitoring Interlocking Transformer monitoring Voltage regulation Auto-recloser Synchrocheck (with coupling)

    User application sISaGRAF PLC software toolcompliant IEC 61131-3: Sequential function chart (SFC) Function Block Diagram (FBD) Ladder Diagram (LD) Structured Text (ST) Instruction List (IL)

    Available for Load shedding application Busbar transfer Etc.

    Standard complianceSuperior construction and

    isolations in accordance with IEC

    Mixed b oard (8 DI / 4DO)8 optically insulated inputs withone common for 2 DI.UN 24, 48/60, 110/125,

    and 220/250 V DC4 power outputs relay (2 NOcontacts)

    UN 250 V DC / 230 V ACSwitching 1000VA/WBreaking 5A at 230 V AC

    cos =0.40.5 A at 220 V DC andL/R=40 ms

    Continu. 5 A

    Analo gu e Input Bo ard4 isolated analogue inputs for measuring transducer connection.Range:

    Current: 1 / 2 / 5 / 10 / 20 mAVoltage: 1 / 2.5 / 5 / 10 V

    Transducerless AI BoardTMS320C6713, DSP integrated 32/64-Bit data word 150 MHz clock rate 6.7 ns Instruction cycle time 1200 MIPS / 900 MFLOPSCurrent transfo rmers (4CT)Features: 1A or 5A (I N)

    0.1 VA at 1 A ,