1 DAVYSUKAMTA & PARTNERS Structural Engineers DAVYSUKAMTA & PARTNERS Structural Engineers ISEMS, 7 – 8 Nov 2013 Suryani Mettawana, Suryani Mettawana, Suryani Mettawana, Suryani Mettawana, Structure Engineer, DS&P TINJAUAN BALOK PERANGKAI KHUSUS (RC LINKED BEAM) TINJAUAN BALOK PERANGKAI KHUSUS (RC LINKED BEAM) TINJAUAN BALOK PERANGKAI KHUSUS (RC LINKED BEAM) TINJAUAN BALOK PERANGKAI KHUSUS (RC LINKED BEAM) DENGAN GAYA GESER TINGGI PADA DINDING OUTRIGGER DENGAN GAYA GESER TINGGI PADA DINDING OUTRIGGER DENGAN GAYA GESER TINGGI PADA DINDING OUTRIGGER DENGAN GAYA GESER TINGGI PADA DINDING OUTRIGGER GEDUNG 50 LANTAI GEDUNG 50 LANTAI GEDUNG 50 LANTAI GEDUNG 50 LANTAI DAVYSUKAMTA & PARTNERS Structural Engineers DAVYSUKAMTA & PARTNERS Structural Engineers ISEMS, 7 – 8 Nov 2013 Latar Belakang Prinsip kerja outrigger & linked beam Composite Shear Plate Coupling Beam Photo pelaksanaan di lapangan DAVYSUKAMTA & PARTNERS Structural Engineers DAVYSUKAMTA & PARTNERS Structural Engineers ISEMS, 7 – 8 Nov 2013 Latar Belakang Vu < Ø Vn Vn = Vc + Vs Linked beam pada gedung tinggi biasanya menghasilkan gaya geser yang sangat besar. Apakah bisa dikerjakan dengan cara memperbesar penampang jika Vu > Ø Vn ? Bagaimana jika dimensi yang diperoleh menjadi tidak layak/feasible untuk dibangun? DAVYSUKAMTA & PARTNERS Structural Engineers DAVYSUKAMTA & PARTNERS Structural Engineers ISEMS, 7 – 8 Nov 2013 Apartemen 50 lantai di atas 3 lapis basement Luas lantai tipikal = 1600 m2 (27x61) Tebal core 65cm Periode getar 6.5 s Sepasang Outrigger setinggi 3 lantai di level 22,23,24

Upload: nguyenanh

Post on 04-Feb-2018

230 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: Latar Belakang Composite Shear Plate Coupling Beamdavysukamta.com/media/5090/presentasi_isems_suryani.pdf · Composite Shear Plate Coupling Beam ... terhadap roof deflection ... Nilai

1

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

Suryani Mettawana, Suryani Mettawana, Suryani Mettawana, Suryani Mettawana, Structure Engineer, DS&P

TINJAUAN BALOK PERANGKAI KHUSUS (RC LINKED BEAM) TINJAUAN BALOK PERANGKAI KHUSUS (RC LINKED BEAM) TINJAUAN BALOK PERANGKAI KHUSUS (RC LINKED BEAM) TINJAUAN BALOK PERANGKAI KHUSUS (RC LINKED BEAM) DENGAN GAYA GESER TINGGI PADA DINDING OUTRIGGER DENGAN GAYA GESER TINGGI PADA DINDING OUTRIGGER DENGAN GAYA GESER TINGGI PADA DINDING OUTRIGGER DENGAN GAYA GESER TINGGI PADA DINDING OUTRIGGER

GEDUNG 50 LANTAIGEDUNG 50 LANTAIGEDUNG 50 LANTAIGEDUNG 50 LANTAI

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

� Latar Belakang

� Prinsip kerja outrigger & linked beam

� Composite Shear Plate Coupling Beam

� Photo pelaksanaan di lapangan

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

Latar Belakang

� Vu < Ø Vn Vn = Vc + Vs

� Linked beam pada gedung tinggi biasanya menghasilkan gaya geser yang sangat besar.

� Apakah bisa dikerjakan dengan cara memperbesar penampang jika Vu > Ø Vn ?

� Bagaimana jika dimensi yang diperoleh menjadi tidak layak/feasible untuk dibangun?

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

� Apartemen 50 lantai di atas 3 lapis basement

� Luas lantai tipikal = 1600 m2 (27x61)

� Tebal core 65cm

� Periode getar 6.5 s

� Sepasang Outrigger setinggi 3 lantai di

level 22,23,24

Page 2: Latar Belakang Composite Shear Plate Coupling Beamdavysukamta.com/media/5090/presentasi_isems_suryani.pdf · Composite Shear Plate Coupling Beam ... terhadap roof deflection ... Nilai

2

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

Outrigger� Definisi: A support that extends out from the base of a tall item to

add stability.� Outrigger system performance is affected by:

1. outrigger locations through the height of a building, 2. the number of levels of outriggers provided, 3. their plan locations, 4. the presence of belt trusses to engage adjacent perimeter columns versus stand alone mega columns, 5. outrigger truss depths, 6. and the primary structural materials used

Reduce bending moment and add building stiffness

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

Lokasi Outrigger

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

Lokasi Link Beam padaDinding Outrigger

4 buah linked beam padadinding outrigger

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

Momen guling diubah menjadi gaya tarik tekan

M1 = 80.000tonM2L

Vu

M2 = M1 + Vu.LNilai M1 = 68% M2Nilai Vu.L = 32% M2

M1 = 80000 t.m

M2 = 117000 t.m

Vu = 1420 t

L = 26.7m

Overturning moment less 32%

Page 3: Latar Belakang Composite Shear Plate Coupling Beamdavysukamta.com/media/5090/presentasi_isems_suryani.pdf · Composite Shear Plate Coupling Beam ... terhadap roof deflection ... Nilai

3

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

Gaya Geser Core Wall dan Gaya Axial Kolom Outrigger

Hanya akibat beban gempa, belum digabung dengan beban

mati dan beban hidup

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

Gedung tinggi harus KUAT dan KAKU terhadap beban gempa dan angin.

Gunakan outrigger dinding beton

Tidak ada ‘complete perimeter column frame’ maka harusmengandalkan kekakuan core

Semakin kaku core wall, semakin besar gaya geser pada coupling beam.

CEK COUPLING RATIO

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

COUPLING BEAM(Linked Beam)

Menggabungkan (coupled) dua atau lebih RCwall agar bekerja bersama-sama, sehinggalebih efisien

Keuntungan dari coupling beam1. Mereduksi bending momen di dasar coupled

shear wall2. Menambah kekakuan gedung3. Mendisipasi energi gempa. Sebagai

penghubung yang daktail sehingga dapat mengalami simpangan yang relatif besar setelah leleh tanpa kehilangan kekuatan

Perilaku coupling beam sangat menentukan perilaku secara keseluruhan dari sistem coupled walls

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

Moment vs displacement

Efek coupling ratio

terhadap roof deflection

Hasil Study Hybrid Coupled Wall 12 lantai

Page 4: Latar Belakang Composite Shear Plate Coupling Beamdavysukamta.com/media/5090/presentasi_isems_suryani.pdf · Composite Shear Plate Coupling Beam ... terhadap roof deflection ... Nilai

4

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

Coupling Beam

Ratio (CR)

Nilai proporsi overturning moment

yang ditahan oleh system coupled

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

CR = 0 % Tidak ada coupling action (balok di modelkan sebagai pin)

CR 50% Coupling action menahan setengah overturning moment, sisanya ditahan oleh reaksi momen individu tiap wall (m 1 dan m 2)

CR = 100% Kedua dinding beton berperilaku efektif sebagai satu kesatuan. Yang mana akan tercapai jika jarak coupling beam mendekati nol.

Performance based design approach

Dilakukan berbagai analisa & percobaan untuk mencari nilai CR optimum

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

CR < 50% agar Vu < Ø Vn.

Tetapi struktur kurang efisien

Gunakan CR 60%-80%

dengan pembatasan tegangan tekan pada

dinding beton < 35% kapasitas tekannya. Untuk

mengatasi Vu yang besar, dilakukan modifikasi

Peraturan yang ada (strength based design)

Rekomendasi

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

Flow chart desain Coupling Beams Ln/H<4

Vu < Ø Vn

O/S shear re-check

dimensi

Ln/H<2 dan Vu>1/3√fc’Acw

Tidak

Coupling Beams

Konvensional

Ya Coupling Beams

dengan tul. diagonal

Alternatif lain

2

31

Composite Shear Plate

H

Ln

Ya

Page 5: Latar Belakang Composite Shear Plate Coupling Beamdavysukamta.com/media/5090/presentasi_isems_suryani.pdf · Composite Shear Plate Coupling Beam ... terhadap roof deflection ... Nilai

5

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

Perbandingan gaya geser pada coupling beam tipikal dan coupling beam pada outrigger

Nilai CR = 74%

Tipe Spandrel Concrete grade

Geometry Factored Loads

Width (mm)

Depth(mm)

Span(mm)

Shear(kN)

Moment(kN-m)

Ø Vn

Spandrel tipikal SP2 Fc’ 30 MPa 300 1300 950 700 - 1000 400-550 1424

Spandrel outrigger Fc’ 45 MPa 450 1300 1020 4270 2216 2510

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

Composite Shear Plate Linked Beam

Pasang tulangan horisontal

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

Langkah Perhitungan Composite Shear Plate Coupling Beam

1. Embedded plate didesain untuk mentransfer semua gaya geser dan momen ujung pelat baja ke dalam dinding beton.

2. Gaya geser Vu ditahan seluruhnya oleh pelat baja tentukan tebal pelat 3. Hitung panjang penyaluran pelat baja ke dalam dinding berdasarkan diagram

keseimbangan di atas4. Nilai w adalah tegangan tumpu beton akibat gaya geser dan momen yang

dipindahkan dari pelat baja ke beton lewat shear stud. Dengan menghitung keperluan jumlah shearstud, diperoleh nilai w

5. Perhatikan syarat jarak antar shear stud dan ketentuan desain baja lainnya

Page 6: Latar Belakang Composite Shear Plate Coupling Beamdavysukamta.com/media/5090/presentasi_isems_suryani.pdf · Composite Shear Plate Coupling Beam ... terhadap roof deflection ... Nilai

6

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

PHOTO PELAKSANAAN DINDING OUTRIGGER

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013Shear stud groups 352 buah

pada pelat tebal 32mm

Page 7: Latar Belakang Composite Shear Plate Coupling Beamdavysukamta.com/media/5090/presentasi_isems_suryani.pdf · Composite Shear Plate Coupling Beam ... terhadap roof deflection ... Nilai

7

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

REFERENSI1. Tata Cara Perhitungan Struktur Beton untuk Bangunan Gedung

SK SNI 03-2847-2002. Indonesia2. T.Paulay, M.J.N. Priestley, Seismic Design of Reinforced Concrete

and Masonry Buildings (1991)3. Structural Engineering Institute (SEI) of the American Society of

Civil Engineers (ASCE) (2010). Recommendations for Seismic Design of Hybrid Coupled Wall Systems. USA.

4. Final Report – Structural Loads: Wind Tunnel Test Pakubuwono Signature Tower, CPP (March 2011)

5. Ho Jung Lee, Daniel A. Kuchma, William Baker, and Lawrence C. Novak (2008). Design and Analysis of Heavily Loaded Reinfoced Concrete Link Beams for Burj Dubai., ACI Structural Journal.

6. Wai-Yin Lam, Ray Kai-Leung Su and Hoat-Joen Pam, Experimental Study on Embedded Steel Plate Composite Coupling Beam, Journal of Structural Engineering @ASCE/August 2005

7. Council on Tall Building and Urban Habitat (2012). Outrigger Design for High-Rise

Page 8: Latar Belakang Composite Shear Plate Coupling Beamdavysukamta.com/media/5090/presentasi_isems_suryani.pdf · Composite Shear Plate Coupling Beam ... terhadap roof deflection ... Nilai

8

DAVYSUKAMTA & PARTNERSStructural EngineersDAVYSUKAMTA & PARTNERSStructural Engineers ISEMS, 7 – 8 Nov 2013

http://www.davysukamta.com

TERIMA KASIHTERIMA KASIHTERIMA KASIHTERIMA KASIH