manual horno templador

Upload: diseno2

Post on 24-Feb-2018

234 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/24/2019 Manual Horno Templador

    1/53

    JdTRON 04.1JdTRON 08.1

    Compact microprocessorcontroller

    B 70.3030.5

    Operating Manual11.02/00341086

  • 7/24/2019 Manual Horno Templador

    2/53

  • 7/24/2019 Manual Horno Templador

    3/53

    (ir Please rea t!is Manual care"ull#$e"ore starting up t!e instrument.%eep t!e Manual in a place &!ic! is

    at all times accessi$le to all users.Please assist us to impro'e t!is Ma(nual &!ere necessar#.)our suggestions &ill $e most &el(come.

    P!one*+erman# ,0661- 6003(725a$roa ,int. 4- 661 6003(0a*+erman# ,0661- 6003(508

    a$roa ,int. 4- 661 6003(607

    (ir ll necessar# settings an &!ereappropriate alterations insie t!einstrument are escri$e in t!isOperating Manual. " an# i""icultiess!oul arise uring start(up #ou arease not to carr# out an#manipulations on t!e unit &!ic! are

    not permitte. )ou coul enanger#our rig!ts uner t!e instrument&arrant# Please contact t!enearest o""ice or t!e main "actor#.

    E!en returning c!assis assem$liesor components t!e rules o" 9 100015 :Protection o" electrostaticall#enangere components; !a'e to

    $e o$ser'e. ,electrostatic isc!arges-

  • 7/24/2019 Manual Horno Templador

    4/53

  • 7/24/2019 Manual Horno Templador

    5/53

    Conten

    1 Introduction ............................................................... 5

    1.1 >escription .................................................................................................................. 51.2 Bloc iagram ............................................................................................................. 61.3 ?#pograp!ical con'entions ......................................................................................... 71.3.3 Presentation ................................................................................................................ 8

    2 Identifying the instrument version .............................. 9

    3 Instaation ............................................................... 11

    3.1 @ocation an climatic conitions ............................................................................... 113.2 >imensions ................................................................................................................113.2.1 ?#pe 703030 ..............................................................................................................11

    3.2.2 ?#pe 703031 ............................................................................................................. 123.2.3 ?#pe 703032.............................................................................................................123.2.4 ge(to(ege mounting ............................................................................................ 133.3 itting in position ....................................................................................................... 143.4 Cleaning t!e "ront panel............................................................................................ 143.5 Aemo'ing t!e controller c!assis ............................................................................... 14

    4 !ectrica connection ................................................. 15

    4.1 9otes on installation ..................................................................................................154.2 Connection iagram .................................................................................................. 16

    5 "re#aration .............................................................. 18

    5.1 >ispla# an e#s ....................................................................................................... 185.2 Operating moe an states ...................................................................................... 185.3 Principle o" operation ................................................................................................ 15.3.1 @e'els ........................................................................................................................ 15.3.2 =electing t!e parameter set...................................................................................... 205.3.3 nput parameter ......................................................................................................... 205.3.4 ltering t!e con"iguration coe ................................................................................. 20

    6 O#eration ................................................................. $1

    6.1 ltering setpoints ...................................................................................................... 216.2 >ispla# controller output........................................................................................... 216.3 cti'ate manual operation ........................................................................................ 226.4 =tart sel"(optimisation ............................................................................................... 226.5 nicate so"t&are 'ersion an unit............................................................................ 22

    7 "arameters ............................................................... $%

  • 7/24/2019 Manual Horno Templador

    6/53

    Conten

    8 Con&guration ............................................................$5

    8.1 C111 ( nputs ...................................................................................................... 258.2 C112 ( @ogic inputs ramp "unction o'errange unit/suppl# ............................... 268.3 C113 ( nter"ace ................................................................................................. 27

    8.4 C211 ( @imit comparators .................................................................................. 288.5 C212 ( Controller t#pe manual operation in!i$it "u# "unction output 31.............2

    8.6 C213( unctions o" t!e outputs1 ...............................................................................308.7 =C@ ( =tanar signal scaling ...................................................................................318.8 =C ( =tanar signal scaling .................................................................................. 318. =P@ ( =etpoint limit............................................................................................ 318.10 =P ( =etpoint limit........................................................................................... 318.11 O= ( Process 'alue correction ...................................................................... 31

    9 O#timisation ............................................................. %$

    .1 Optimisation .............................................................................................................. 32.1.1 =el"(optimisation ....................................................................................................... 32.1.2 u# logic ................................................................................................................ 32.2 C!ecing t!e optimisation ......................................................................................... 33

    10 'ogic in#uts .............................................................. %4

    11 Ram# function .......................................................... %5

    12 (eater current indication)monitoring ......................... %*

    12.1 eater current inication ........................................................................................... 3612.2 eater current monitoring ......................................................................................... 36

    13 Interface .................................................................. %+

    14 ,##endi- .................................................................. %8

    14.1 ?ec!nical >ata .......................................................................................................... 3814.2 @imit comparator "unctions ........................................................................................ 4014.3 larm messages ....................................................................................................... 4214.4 ternal setpoint pro'ision an setpoint priorities .................................................... 43

    "rogramming the controer

  • 7/24/2019 Manual Horno Templador

    7/53

    1

    5

    1.1 escri#tion

    ?!e compact microprocessor controllers?#pe 703030 ?#pe 703031 an ?#pe703032 &it! t!e $eel sies 6mm 6mman 48mm 6mm resp. an &it! a plug(incon( troller c!assis are particularl# suita$le"or temperature(controlle apparatusla$orato( r# eDuipment plastics mac!iner#mec!ani( cal eDuipment etc. ?!e controllersincorpo( rate t&o 4(igit 7(segment ispla#s"or process 'alue ,re- an setpoint ,green-.>u( ring programming t!e ispla#s ser'e "orcomments on t!e inputs.?!e controllers can $e programme as a

    sin( gle or ou$le setpoint controllermoulating or proportional controller &it!t!e usual con( troller structures. ?!e# also!a'e t&o limit comparators &!ic! can $eassigne to t!e input signals. ?!ere is ac!oice o" eig!t i""e( rent limit comparator"unctions. ramp "unction &it! aEusta$legraient a start(up ramp "or t!e !ot(c!annelmet!o as &ell as sel"(optimisation area'aila$le as stanar. n inter"ace,A=422/A=485- a'aila$le as an option

    ser'es "or integration into a ata net( &or.ll connections are mae t!roug! "a( stontags 4.8mm 0.8mm to >9 46 244/.

  • 7/24/2019 Manual Horno Templador

    8/53

    1.2 /oc diagram

  • 7/24/2019 Manual Horno Templador

    9/53

    1.3 Ty#ogra#hica conventions

    1.3.1Warnings?!e signs "or Danger an Warning areuse int!is Manual uner t!e "ollo&ing

    conitions*

    anger ?!is s#m$ol is use &!en t!ere ma# $edanger to #ersonne i" t!e instruction isisregare or not "ollo&e accuratel#.

    arning ?!is s#m$ol is use &!en t!ere ma# $e da2mage to e3ui#ment or data i" t!einstruction is isregare or not "ollo&eaccuratel#.

    arning ?!is s#m$ol is use &!en precautions !a'eto $e o$ser'e in !anling components lia$leto $e amage $# electrostatic isc!arges.

    1.3.2Note signs

    Note ?!is s#m$ol is use i" #our s#eciaattention isra&n to a remar.

    Reference ?!is s#m$ol re"ers to additiona

    informationin ot!er !an$oos c!apters or sections.

    a$c1 ootnote ootnotes are notes &!ic! re"er to certain

    points in t!e tet.ootnotes consist o" 2 parts*

    Marings in t!e tet an in t!e "ootnote tet.

    ?!e marings in t!e tet are arrange ascon( tinuous raise num$ers.

    ?!e "ootnote tet ,in smaller t#pe"ace- is pla(ce at t!e $ottom o" t!e page an starts &it!a num$er an a "ull stop.

    ,ction ?!is s#m$ol inicates t!at an action iseing descried.

    ?!e ini'iual steps are inicate $# t!isasteris e.g.

    Press4 e#

    V

    E

    e>

    (ir

  • 7/24/2019 Manual Horno Templador

    10/53

    1.%.% "resentation

    P 6eys %e#s are s!o&n in a "rame. Bot! s#m$olsan tet are possi$le. !ere a e# !as a

    multiple "unction t!e tet s!o&ncorrespons to t!e"unction &!ic! is currentl# acti'e.

    F 4 6ey com5inations %e#s s!o&n toget!er &it! a plus sign

    inicate

    t!at "irstF !as to $e presse an !elo&n an t!en a "urt!er e# is presse.

    o Item ?!is is "ollo&e $# eplanations o"iagrams an concepts.

  • 7/24/2019 Manual Horno Templador

    11/53

    $ Identifying the instrument

    ..

    ..

    ..

    ...

    ...

    ...

    ...

    ..

    ..

    ...

    ...

    ..

    ..

    ...

    ...

    ... ... .. ... .. ...

    ?!e la$el is a""ie to t!e case. ?!e t#peesignation contains all t!e "actor# settingssuc! as controller "unction signal inputsan

    Ty#e designation

    o @ @ O 0 0 &

    etra Coes.?!e Coes &are s!o&n in seDuence anseparate $# a comma.

    ?!e suppl# must agree &it! t!e 'oltages!o&n on t!e la$el.

    eivery #acage7

    G controller

    G 2 mounting $racets

    G seal

    G Operating Manual B 70.3030.5

    +0%0%0) 2+0%0%1) 2

    +0%0%$) 2

    2 2 2 2 )2 2 2 2 )

    2 2 2 2 )

  • 7/24/2019 Manual Horno Templador

    12/53

    $ Identifying the instrument

    oControer function Code

    =ingle(setpoint controller O "unction,rela# e(energise a$o'e setpoint- 10

    =ingle(setpoint controller = "unction

    ,rela# e(energise $elo& setpoint- 11

    >ou$le(setpoint controller,!eating/cooling- 3 .

    s&itc!ing/s&itc!ing . 0analogue/s&itc!ing . 1

    s&itc!ing/analogue . 2

    Moulating controller 40

    Proportional controller 5 ."alling c!aracteristic ,re'erse acting- . 0rising c!aracteristic ,irect acting- . 1

    @ In#ut 1 Code

    Pt 100 001

    e(Con H 040

    Cu(Con < 041

    e(Con @ 042

    9iCr(9i % 043

    Pt10A!(Pt = 044

    Pt13A!(Pt A 045

    Pt30A!(Pt6A! B 046

    9iCr=i(9i=i 9 048

    @inearise transucers

    0I20 m 052

    4I20 m 053

    0I10 J 063

    2I10 J 070

  • 7/24/2019 Manual Horno Templador

    13/53

    @In#ut $ Code

    no "unction 000

    eater current inication

    0I50 m C 00

    =troe retransmissionpotentiometer 101

    ternal setpoint 11 .0I20 m . . 1

    4I20 m . . 20I10 J . . 7

    2I10 J . . 8

    O unctions of ogic in#uts

    'ogic in#ut 1 'ogic in#ut $ Code

    no "unction no "unction 00

    %e# in!i$it Parameter set s&itc!ing 01

    @e'el in!i$it Parameter set s&itc!ing 02

    Aamp stop Parameter set s&itc!ing 03

    =etpoint selection Parameter set s&itc!ing 04

    %e# in!i$it =etpoint selection 05

    @e'el in!i$it =etpoint selection 06

    Aamp stop =etpoint selection 07

    %e# in!i$it Aamp stop 08

    @e'el in!i$it Aamp stop 0

  • 7/24/2019 Manual Horno Templador

    14/53

    ,ccessory

    Current transformer (ratio 1:1000 si!e: 38 mm " 20 mm " 38 mm #a$%e entr: 13 mm 'ia.a%es )o. 70*00055040

    0Out#ut % Code

    not use 000

    Aela# 101

    nalogue output0I20 m 001

    4I20 m 0050I10 J 065

    2I10 J 070

    &!-tra Codescan e comined

    Code

    no etra Coe 000

    nter"ace A=422/A=485 054

    @ogic outputs 4 an 5

    &it! 0/12 J output 015

  • 7/24/2019 Manual Horno Templador

    15/53

    +ane% #ut,out

    %

    3.1 'ocation andcimatic conditions

    ?!e instrument location s!oul as "ar as

    possi$le $e "ree "rom s!oc an 'i$ration.=tra# electromagnetic "iels. e.g. "rom motorstrans"ormers etc. s!oul $e a'oie. ?!eam$ient temperature at t!e location ma# $e$et&een 0 an 50 KC at a relati'e !umiit# noteceeing 75 L.

    3.2 imensions

    %.$.1 Ty#e +0%0%0

    mm inc!

    0.8 0.0314.8 0.1

    10.5 0.4115.5 0.6130.5 1.2033.2 1.3033.3 1.313.5 1.5643.5 1.71

    440.5 1.730.0248 1.873 2.877.3 3.1282 3.2386.4 3.40

    0.3 3.561.5 3.601.6 3.61

    20.5 3.620.026 3.78

    105.8 4.17

  • 7/24/2019 Manual Horno Templador

    16/53

    +ane%

    +ane% #ut,out to -) 43700

    %.$.$ Ty#e +0%0%1

    %.$.% Ty#e +0%0%$

  • 7/24/2019 Manual Horno Templador

    17/53

    %.$.4 !dge2to2edge mounting

  • 7/24/2019 Manual Horno Templador

    18/53

    3.3 itting in #osition

    Place t!e seal supplie onto t!e !ousingo" t!e instrument.

    nsert t!e controller "rom t!e "ront into t!epanel cut(out.

    rom t!e $ac o" t!e panel slie t!emount( ing $racets into t!e guies at t!esies. ?!e "lat $racet "aces must lieagainst t!e !ousing.

    Place t!e $racets against t!e rear o" t!epanel an tig!ten t!em e'enl# &it! ascre&ri'er.

    3.4 Ceaning the front #ane

    ?!e "ront panel can $e cleane &it! t!eusu( al &as! an rinse agents anetergents. t !as a limite egree o"resistance to organic sol'ents ,e.g. petrol$enene P1 #lene an similar-. >o notuse an# !ig!(pressure cleaners.

    3.5 Removing thecontroer chassis

    ?!e controller c!assis can $e remo'e "romt!e !ousing "or ser'icing.

    Press toget!er t!e nurle areas top an$ottom on t!e "ront panel an pull outt!e controller c!assis.

  • 7/24/2019 Manual Horno Templador

    19/53

    4 !ectrica

    4.1 Notes on instaation

    % ?!e c!oice o" ca$le t!e installation ant!e electrical connection must con"ormto t!e reDuirements o" J> 0100:Aegulati( ons on t!e installation o"Po&er Circuits &it! nominal 'oltages$elo& 1000J; or t!e appropriate localregulations.

    % ?!e electrical connection must onl# $ecarrie out $# properl# Duali"ieperson( nel.

    % " contact &it! li'e parts is possi$le&!en &oring on t!e instrument it !as

    to $e isolate on $ot! poles "rom t!esuppl#.

    % current limiting resistor interrupts t!esuppl# circuit in case o" a s!ort(circuit.?!e eternal "use o" t!e suppl# s!oulnot $e rate a$o'e 1 ,slo&-. ?!e loacircuit must $e "use "or t!e maimumrela# cur( rent in orer to pre'ent&eling o" t!e out( put rela# contacts incase o" an eternal s!ort(circuit.

    % lectromagnetic compati$ilit# con"ormsto t!e stanars an regulations listeuner ?ec!nical >ata.

    v=ection14.1

    % Aun input output an suppl# linessepa( ratel# an not parallel to eac!ot!er.

    % =ensor an inter"ace lines s!oul $e ar(range as t&iste an screeneca$les. >o not run t!em close tocurrent(carr#ing components or ca$les.art! t!e screen at one en at t!einstrument on terminal ?.

    % art! t!e instrument at terminal ? tot!e eart! conuctor. ?!is line must !a'eat least t!e same cross(section as t!e

    sup( pl# lines. art! lines s!oul $e runin a star la#out to a common eart! point&!ic! is connecte to t!e eart!conuctor o" t!e suppl#. >o not loop t!eeart! connec( tions i.e. o not runt!em "rom one instru( ment to anot!er.

    % >o not connect aitional loas to t!esuppl# terminals o" t!e instrument.

    % ?!e instrument is not suita$le "orinstalla( tion in !aarous areas.

    % part "rom "ault# installation t!ere is apossi$ilit# o" inter"erence or amage tocontrolle processes ue to incorrectset( tings on t!e controller ,setpointata o" parameter an con"igurationle'els inter( nal aEustments-. =a"et#e'ices inepen( ent o" t!e controllersuc! as o'erpressu( re 'al'es ortemperature limiters/moni( tors s!oulal&a#s $e pro'ie an s!oul $e

    capa$le o" aEustment onl# $#specialist personnel. Please re"er to t!eappropriate sa"et# regulations in t!iscon( nection. =ince auto(tuning ,sel"(optimisation- can not $e epecte to!anle all possi( $le control loopst!ere is a t!eoretical possi$ilit# o"unsta$le parameter settings. ?!eresulting process 'alue s!oul t!ere("ore $e monitore "or its sta$ilit#.

    % ?!e signal inputs o" t!e controller mustnot ecee a maimum potential o" 30J C or 50 J >C against ?.

    % ll input an output lines t!at are notcon( necte to t!e suppl# net&or must$e lai out as s!iele an t&isteca$les ,o not run t!em in t!e 'icinit#o" po&er ca$les or components-.?!e s!ieling must $e groune to t!eeart! potential on t!e instrument sie.

  • 7/24/2019 Manual Horno Templador

    20/53

    4.2 Connection diagram

    V ?!e electrical connection must onl# $e mae $# properl# Duali"ie personnel.

    Out#uts Terminas :ymo

    Aela# 11 %1 142 common143 n.o. ,mae-

    Aela# 21 %2 242 common243 n.o. ,mae-

    Aela#

    31

    or

    analogue output

    %3 341 n.c. ,$rea-

    342 common343 n.o. ,mae-

    342 G

    343

    @ogic output 1 %4 80 G

    85

    @ogic output 2 %5 80 G

    87

    1. Jaristor protection circuit =14%300

  • 7/24/2019 Manual Horno Templador

    21/53

    :igna in#uts In#ut 1 In#ut $ :ymo

    ?!ermocouple 111

    112 G

    (

    Aesistance t!ermometer 111 (in 3(&ire circuit 112

    113

    Aesistance t!ermometer 111 (in 2(&ire circuit 112lea compensation 'ia 113process 'alue correction ,O=-

    Potentiometer 211 = slier

    212 en

    213 start

    Current input 111 211 112 G 212 G

    Joltage input 111 211 112 G 212 G

    eater current input ( 2110I50 m C 212

    :eriainterfaceR:4$$

    A> 1 A> 2 A> G

    Aecei'e >ata

    ?> 3 ?> 4 ?> G

    =en >ata

    +9> 0 +9>

    :eriainterfaceR:485

    A>/?>

    3 A>/?>

    4 A>/?>G

    Aecei'e/=en>ata

    +9> 0 +9>

    'ogic in#ut 1 8180

    'ogic in#ut $ 8380

    :u##y as on ae C/>C

    C*@1 line9 neutral? tec!nical

    eart!

    >C*@@(

  • 7/24/2019 Manual Horno Templador

    22/53

    5

    5.1 is#ay and eys

    o process 'alue ispla# 7(segment ispla# re

    @ setpoint/!eater current ispla# 7(segment ispla# green

    @ ecrement e# to operate t!e controller

    O P+M e#

    0 9?A e#

    0 increment e#

    & contact status inication1 to s!o& t!e status o" t!e "i'e outputs

    9 @> "or ramp "unction lig!ts up &!en a ramp "unction is acti'ate

    1. no "unction on analogue output %3

    5.2 O#erating mode and states

    =tanar ispla# t!e process 'alue ispla# s!o&s t!e process 'alue

    t!e setpoint ispla# s!o&s t!e setpoint or t!e !eater current

    nitialising all ispla#s lig!t up t!e setpoint ispla# is "las!ing

    Manual operation t!e process 'alue ispla# alternates $et&een t!e process 'aluean t!e &or :anN t!e setpoint ispla# s!o&s t!e controlleroutput.

    Aamp "unction t!e @> "or ramp "unction lig!ts up

    =el"(optimisation t!e &or :tune is "las!ing

    Operating parameterscon"iguration

    t!e setpoint ispla# s!o&s t!e parameters o" t!e i""erent le'elst!e process 'alue ispla# s!o&s t!e corresponing coes an'alues.

    larm v=ection 14.3

  • 7/24/2019 Manual Horno Templador

    23/53

    /)-- -+

    O+/)

    +/

    +

    +.0

    CO)/O)

    1

    (2 se# min.

    1

    (2 se# min.

    1

    (2 se# min.(2 se# min.

    +

    +

    +

    +

    +

    +

    + +

    +

    +

    5.3 "rinci#e of o#eration

    5.%.1'eves

    :tandard dis#ayrom t!is status manual operation an sel"(optimisation can $e acti'ate.

    ?!e ispla# s!o&s t!e setpoint an t!e pro(cess 'alue.

    " !eater current monitoring isacti'ate t!e !eater current iss!o&n on t!e setpoint ispla#,'alue precee $# :;

    O#erating eveere t!e setpoints are input t!e current con(troller output is inicate.

    "arameter eve?!e controller parameters an ot!er settingsare programme !ere.

    t is possi$le to s&itc! $et&een t&oparameter sets.v=ection 5.3.2 10

    ?!e ispla# o" t!e ini'iual parame(ters epens on t!e controller t#pe.

    Con&guration eve?!e $asic "unctions o" t!e controller are set!ere.

    C!anges can onl# $e mae a"tercal( ling up t!e con"iguration le'el'ia t!e parameter y.0 o" t!eparameter le'el.

    it!in t!e le'els t!eP e# is use tos&itc! o'er to t!e net parameter.

    Time2out" not operate t!e controller returnsautomaticall# to stanar ispla#a"ter appro. 30 sec.

    1. c!ange o" le'el occurs onl# a"ter allparameters o" t!e ini'iual le'els

    !a'e $een run t!roug!.

    H

    H

    F

    ortime(out

    H

    A

    ,n

    oinputpossi$le6-

    ,can$eeite'ia

    #.0

    6-

    H

  • 7/24/2019 Manual Horno Templador

    24/53

    +arameter set 1

    +arameter set 2

    5.%.$ :eecting the #arameter set

    ?!e controller !as t&o parameter sets $et(&een &!ic! it is possi$le to s&itc! 'ia alogic input.

    Bot! parameter sets can $e ispla#e "orparameter setting.

    C!ange $et&een t!e ispla# o" t!e para(meter sets &it!P &!en parameterP$.1 is ispla#e,!ol o&n e# "or at least 2 sec-

    ?!e parameter set &!ic! is ispla#e isini( cate $# illuminate segments atparameter P$.1.

    5.%.% In#ut #arameter

    Parameters an setpoints can $e input anc!ange $# continuous alteration o" t!e 'a(lue. ?!e spee o" t!e alteration increases&it! t!e lengt! o" time in &!ic! t!e e# is!el o&n.

    ncrease 'alue &it!

    4 >ecrease 'alue

    &it! > nter input

    &it!P

    or

    a$ort input &it!F

    "ter 2 sec t!e 'alue &!ic! !as $een set isautomaticall# entere.?!e 'alue c!anges onl# &it!in t!e permitte'alue range.

    5.%.4,tering thecon&guration code

    =elect igit &it! >,igit $lins-

    lter t!e 'alue &it!4

    nter t!e coe &it!

    P or

    a$ort t!e input &it!F

  • 7/24/2019 Manual Horno Templador

    25/53

    *

    6.1 ,tering set#oints

    ,tering the activeset#oint in thestandard dis#ay

    lter t!e setpoint &it!> an4

    ccoring to t!e status o" t!e setpoint s&it(c!o'er t!e acti'e setpoint correspons to=P1 or =P2 at t!e operating le'el.

    ,tering :"1 and:"$ on theo#erating eve

    C!ange to operating le'el &it!P

    lter t!e setpoint =P1 &it!> an4

    C!ange to setpoint =P2 &it!P

    lter t!e setpoint =P2 &it!> an4

    Aeturn to stanar ispla# &it!

    F or time(out

    6.2 is#ay controer out#ut

    C!ange to output ispla# &it! 3P

    Aeturn to stanar ispla# &it!

    F or time(out

  • 7/24/2019 Manual Horno Templador

    26/53

    6.3 ,ctivate manua o#eration

    C!ange to manual operation &it!F

    4 ,?!e process 'alue ispla#

    alternates $et&een t!e &or anan t!e process 'alue-

    lter t!e output &it! 4 an>

    Aeturntoautomaticoperation&it!F

    4

    Output limitation is acti'ate uring

    manual operation. Manual operationis loce as "actor#(setting ,C212-.

    6.4 :tart sef2o#timisation

    =tart sel"(optimisation &it!F,!ol o&n e# "or at least 2 sec-

    $ort &it!F,&!ile sel"(optimistion is running.-

    =el"(optimisation is complete &!en t!e

    ispla# is no longer "las!ing tune.

    8nter sel"(optimisation &it! F,!ol o&n e# "or at least 2 sec-,

    =tarting sel"(optimisation is notpossi$le &it! acti'ate le'el in!i$itan in manual operation.

    ?!e acti'ate parameter set is optimi(se.

    6.5 Indicate soft;areversion and unit

    nicate t!e so"t&are 'ersion an t!eunit o" t!e process 'alue &it!P 4,ol o&n e#s-

    Possi$le units are*KC K an L ,"or stanar signals-

    H

    H

  • 7/24/2019 Manual Horno Templador

    27/53

    +

    "arameter is#ay action o"t!e controller" t0 t!e controller !as no> action.On moulating controllerstrt/4 or 0 !as to $eentere.

    Aeset time rt 0I sec 350 sec n"luences t!e action o" t!econtroller." rt0 t!e controller !as no action.

    =troe time tt 15I3000 sec 60 sec On moulating controllersNutilise stroe time range o"'al'e.

    C#cle time 1 C# 1 1.0I. sec 20.0sec >uration o" s&itc!ing c#cleon s&itc!ing outputs.?!e c#cle time s!oul $eselecte so t!at t!e energ#suppl# to t!e process is'irtuall# continuous &!ile notsu$Eecting t!e s&itc!ing

    elements to ecessi'e &ear.

    C#cle time 2 C# 2 1.0I. sec 20.0sec

    Contact spacing $ 0.0I100.0 igit 0.0 or s&itc!ing ou$le(setpoint controllers anmoulating controllers.

    1. "or setting Pt100 or stanar signal &it! one ecimal place.

    v=ection 8.1

  • 7/24/2019 Manual Horno Templador

    28/53

    "arameter is#ay i""erential 1 #=.1 0.1I. igit 1.0 or controllers &it! P$0

    >i""erential 2 #=.2 0.1I. igit 1.0

    oring point #.0 G100 to 100L 0L Output at &

    Maimum output #.1 0I100L 100L ample*analogue controller &it!"alling c!aracteristic.

    HOn controllers &it!outcontroller structure,P$0-

    #.1 must $e 100L

    an #.2 G100L

    HOn ou$le(setpoint

    controllers &it!out outputlimit #.2 G100L must

    $e set.

    Minimum output #.2 G100 to 100L G100L

    ilter timeconstant

    0.0I100.0 sec 0.6sec or aEusting t!e igital input"ilter

    Aamp slope r= 0.0I. igit/!or igit/min

    0.0 vC!apter 11

  • 7/24/2019 Manual Horno Templador

    29/53

    8

    0 0

    0I20 m / 0I10 J 0

    4I20 m / 2I10 J 1

    ,naogue in#ut $ 2 unction5

    no "unction 0

    eater current ispla#3

    ,input* 0I50m C- 1

    Output retransmission ,input* potentiometer- 2

    ternal setpoint4 ,input* 0I20m/4I20m- 3

    ,naogue in#ut $ 2 :tandard signa$

    0I20 m / 0I10 J 0

    4I20 m / 2I10 J 1

    1. On t!e $asic controller it is possi$le to recon"igure "reel# $et&een t!e sensor t#pes Pt100 all t!ermo(couples an t!e stanar signal 0I20m/4I20m ,see secon place "rom t!e le"t-.

    2. or t!e stanar signal 0I10J/2I10J t!e !ar&are !as to $e recon"igure in t!e "actor#.

    3. ?!e measurement o" t!e !eater current is s!o&n on t!e setpoint ispla# an ienti"ie $# t!e pre"i .

    ?!e measurement range 0I50 m C is scale to an inication range 0I50.0 . ?!e !eater currentmonitoring o" t!e measurement is implemente $# con"iguring t!e limit comparators.

    v =ection 8.412.24. ?!e input signal is scale &it! t!e parameters =P.@ an =P..

    v =ection 8.8.10

    5. On t!e $asic controller it is possi$le to recon"igure "reel# $et&een t!e "unctions :!eater current ispla#;an :eternal setpoint; ,0I20m/4I20m-. ?!e "unctions :output retransmission; or :eternal setpoint;,0I10J/2I10J- reDuire a !ar&are recon"iguration in t!e "actor#.

    ?!e "actor#(set Coes are s!o&n in t!e item $oes.n F ienti"ies a setting &!ic! epens on t!e instrument 'ersion,see "ootnote.-

    8.1 C111 2 In#uts0 0

    ,naogue in#ut 12 sensor ty#e1

    Pt 100 &it!out ecimal place 0

    Pt 100 &it! ecimal place 1

    e(Con @ 2

    9iCr(9i % 3

    Pt10A!(Pt = 4

    Pt13A!(Pt A 5

    Pt30A!(Pt6A! B 6

    Cu(Con < 7

    9iCr=i(9i=i 9 8

    e(Con H

    =tanar signal &it!out ecimal place

    =tanar signal &it! ecimal place $

    ,nao ue in ut 1 2 :tandard si na$

    H

  • 7/24/2019 Manual Horno Templador

    30/53

    0

    Out ut 100 L @imit com arator O 1

    Output 50 L12

    @imit comparator O 2Output unc!ange

    3@imit comparator O 3

    Output 0 L @imit comparator O9 4

    Output 100 L @imit comparator O9 5

    Output 50L12

    @imit comparator O9 6

    Output unc!ange3

    @imit comparator O9 7

    =nit):u##y4

    >egree Celsius 50 0

    >egree a!ren!eit 50 1

    >egree Celsius 60 2>egree a!ren!eit 60 3

    1. G100 L on ou$le(setpoint controller.

    2. On moulating controller t!e position o" t!e actuator is retaine.

    3. ?!e a'erage 'alue o" t!e last outputs is retaine.

    4. ?!e suppl# "reDuenc# must agree &it! t!e setting.

    8.$ C11$ 2 'ogic in#uts> ram# function>overrange> unit)su##y 0 0

    unction of the ogic in#uts

    'ogic in#ut 1 'ogic in#ut $no "unction no "unction 0

    %e# in!i$it Parameter set s&itc!ing 1

    @e'el in!i$it Parameter set s&itc!ing 2

    Aamp stop Parameter set s&itc!ing 3

    =etpoint s&itc!ing Parameter set s&itc!ing 4

    %e# in!i$it =etpoint s&itc!ing 5

    @e'el in!i$it =etpoint s&itc!ing 6

    Aamp stop =etpoint s&itc!ing 7

    %e# in!i$it Aamp stop 8@e'el in!i$it Aamp stop

    Ram# functions

    Aamp "unction O 0

    0

    Aamp "unction O9 slope

    Aamp "unction O9 slope

    :igna on overrange

    KC/min

    KC/!

    1

    2

    Output 0 L @imit comparator O 0

  • 7/24/2019 Manual Horno Templador

    31/53

    %

    o parit# MO>$us protocol 1

    e'en parit# MO>$us protocol 2no parit# H$us protocol 3

    o parit# H$us protocol 4

    e'en parit# H$us protocol 5

    /aud rate

    1200 $au 0

    2400 $au 1

    4800 $au 2

    600 $au 3

    1. ress 0 is a $roacast instructionN see nter"ace >escription B 70.3030.2

    8.% C11% 2 Interface0 1

    Instrument address

    ress 01 0 0

    0

    ress

    ress

    ress

    "arity

    1

    2

    3

    0

    0

    3

    1

    2

    no parit# MO>$us protocol 0

  • 7/24/2019 Manual Horno Templador

    32/53

    0 $

    l 11 1

    l 21

    2

    l 3 3

    l 4 4

    l 5 5

    l 6 6

    l 7 7

    l 8 8

    In#ut monitored

    'imit com#arator 1 'imit com#arator $

    nput 1 nput 1 0

    nput 1 nput 2 1

    nput 2 nput 1 2

    nput 22

    nput 22

    3

    :;itching di?erentia of imit com#arators @:d

    0 igit 01 igit 1

    2 igit 24 igit 36 igit 48 igit 510 igit 616 igit 720 igit 8

    1.?!e conition F=/2 @ must $e met.2.nput 2 can onl# $e monitore &it! t!e limit comparator "unctions l7 an l8.

    n t!e ramp "unction t!e limit comparators l1to l6 re"er to t!e ramp setpoint

    ,current setpoint-.?!e limit 'alue @ is set at t!e parameter le'el.

    8.4 C$11 2 'imit com#arators0 0

    'imit com#arator 1

    no "unction 0l 1

    11

    l 21

    2

    l 3 3

    l 4 4

    l 5 5

    l 6 6

    l 7 7

    l 8 8

    'imit com#arator $

    l O 0

    H

  • 7/24/2019 Manual Horno Templador

    33/53

    @0

    Manual operation in!i$ite u# O 0

    Manual operation ena$le u# O 1

    Manual operation in!i$ite u# O9 2

    Manual operation ena$leOut#ut % 2 :tandard

    u# O9 3

    0I20 m 0

    4I20 m 1

    0I10 J 2

    2I10 J 3

    Out#ut % 2 unction%

    no "unction 0

    Controller output 1 1

    Controller output 2 2@imit comparator 1 3

    @imit comparator 2 4

    1. actor# setting C212* 0000 on controllers &it!out analogue output ,%3-N6001 on controllers &it! analogue output ,%3-

    2. !en t!e controller t#pe is c!ange t!e controller parameters !a'e to $e c!ece ,on ou$le(setpoint controllers set #.2 (100L-

    3. n analogue output , output 3- must $e a'aila$le.

    8.5 C$1$ 2 Controer ty#e> manuao#eration

    @ 0

    Controer

    ty#e$ Controer Controer=ingle(setpoint controller,!eating-

    O "unction G 0

    =ingle(setpointcontroller = "unction G 1,cooling-

    >ou$le(setpoint controller s&itc!ing s&itc!ing 2,!eating/cooling->ou$le(setpoint controller "alling s&itc!ing 3,!eating/cooling- c!aracteristic

    3

    >ou$le(setpoint controller s&itc!ing rising c!aracteristic3

    4,!eating/cooling-Moulating controller open close 5

    Proportional controller "alling c!aracteristic3

    G 6,!eating-

    Proportional controller rising c!aracteristic3

    G 7,cooling-

    Banua o erat on n t) uAA

  • 7/24/2019 Manual Horno Templador

    34/53

  • 7/24/2019 Manual Horno Templador

    35/53

    4

    Controller output 1 1

    Controller output 2 2

    @imit comparator 1 3

    @imit comparator 2 4

    Out#ut 5 2 function ogic out#ut

    no "unction 0

    Controller output 1 1Controller output 2 2

    @imit comparator 1 3

    @imit comparator 2 4

    1. actor# setting C213* 1034 on controllers &it!out analogue output ,%3-N

    3400 on controllers &it! analogue output ,%3-

    8.* C$1%2 unctions of the out#uts1

    @ 0Out#ut 1 2 function reay

    no "unction 0Controller output 1 1

    Controller output 2 2

    @imit comparator 1 3

    @imit comparator 2 4

    Out#ut $ 2 function reay

    no "unction 0

    %

    Controller output 1 1

    Controller output 2 2

    @imit comparator 1 3@imit comparator 2 4

    Out#ut 4 2 function ogic out#ut

    no "unction 0

  • 7/24/2019 Manual Horno Templador

    36/53

    8.7 :C' 2 :tandard signa scaing

    =tart o" 'alue range "or stanar signals.

    ample* 0I20 m $0I 200KC* =C@ 20

    Jalue range* G1 to igit/G1. to . igit1

    actor# setting* 0 igit

    8.8 :C( 2 :tandard signa scaing

    n o" 'alue range "or stanar signals.

    ample* 0I$0 m 20I$00KC* =C

    200

    Jalue range* G1 to igit/G1. to . igit1

    actor# setting* 100 igit

    8.9 :"' 2 :et#oint imit

    @o& setpoint limit/start o" ispla# &it! eternal setpointnputs o" setpoints $elo& t!is limit are not accepte.?!e 'alue o" =P@ "las!es on t!e ispla#.

    Jalue range* G1 to igit/G1. to . igit1

    actor# setting* G200 igit

    8.10:"( 2 :et#oint imit

    ig! setpoint limit/en o" ispla# &it! eternal setpointnputs o" setpoints a$o'e t!is limit are not accepte.?!e 'alue o" =P "las!es on t!e ispla#.

    Jalue range* G1 to igit /G1. to . igit1

    actor# setting* 850 igit

    8.11O: 2 "rocess vaue correction

    ?!e o""set can $e use to correct t!e measure 'alue $# acertain amount up or o&n.

    t is also use as a lea compensation &!en connecting resistance t!ermometersin 2(&ire circuit

    Jalue range* G1 to igit /G1. to . igit1

    actor# setting* 0 igit

    amples*

    measured vaue o?set dis#ayed vaue

    24.7 0.3 25.0

    25.3 G 0.3 25.0

    1. On Pt100 an stanar signals &it! ecimal place ,C111-.

  • 7/24/2019 Manual Horno Templador

    37/53

    9

    9.1 O#timisation

    9.1.1 :ef2o#timisation

    ?!e sel"(optimisaton "unction ,=O- is purel#

    a so"t&are "unction an is incorporate int!e controller. =O in'estigates t!e reactiono" t!e process to steps in controller outputusing a special proceure. ?!roug! an e(tensi'e computing algorit!m t!e processresponse ,process 'alue- is use to calcula(te t!e controller parameters "or a P> or Pcontroller ,set t 0- an to store t!em.?!e =O proceure can $e repeate asman# times as reDuire.

    ?!e =O operates $# t&o i""erent met!os&!ic! are selecte automaticall# epeningon t!e #namic conition o" t!e process 'a(lue an its separation "rom t!e setpoint att!e start o" optimisation. =O can $e starte"rom an# #namic process 'alue conition.

    " t!ere is a large separation $et&een pro(cess 'alue an setpoint &!en =O is acti'a(te a s&itc!ing line is selecte a$out &!ic!t!e process 'alue per"orms a "orce oscilla(

    tion uring t!e =O proceure. ?!e s&itc!ingline is c!osen so t!at t!e process 'alueoes not ecee t!e setpoint i" possi$le.it! a small e'iation $et&een process 'a(lue an setpoint e.g. &!en t!e control loop!as sta$ilise a "orce oscillation is prou(ce a$out t!e setpoint.?!e process ata o" t!e "orce oscillationare recore an use to calculate t!e con(troller parameters rt t P$.1 P$.2 C#1C#2 as &ell as a "ilter time constant optimal

    "or t!is process in orer to "ilter t!e process'alue.

    =el"(optimisation s&itc!es o"" t!e "u(# logic.

    9.1.$ uAAy ogiccti'ation o" t!e "u# moule can impro'et!e setpoint response an t!e istur$anceresponse o" t!e controller.

    v=ection8.5

    H

  • 7/24/2019 Manual Horno Templador

    38/53

    +$ too %are

    rt; 't too sma%%

    9.2 Checing theo#timisation

    ?!e optimum aEustment o" t!e controller to

    t!e process can $e c!ece $# recoring astart(up &it! t!e control loop close.?!e iagrams $elo& inicate possi$le incor(rect aEustments an t!eir correction.

    ?!e# are $ase on t!e control response o" at!ir(orer process "or a P> controller. ?!eproceure "or aEusting t!e controller para(

    meters can also $e applie to ot!er pro(cesses.

    "a'oura$le 'alue "or t is rt/4.

  • 7/24/2019 Manual Horno Templador

    39/53

    +$ too sma%%

    rt; 't too %are

    o

  • 7/24/2019 Manual Horno Templador

    40/53

    10 'ogic

    6ey inhiit Operation is possi$le $# e#s. No operation $# e#s.

    'eve inhiit ccess possi$le to parameteran con"iguration le'el.=tarting o" sel"(optimisation ispossi$le.

    No access to parameteran con"iguration le'el.No starting o" sel"(optimisation.

    Ram# sto# Aamp running.," ramp "unction is acti'ate-

    Aamp stoppe.

    vC!apter 11

    :et#oint s;itching =etpoint 1 ,=P1- is acti'ate.?!e corresponing 'alue iss!o&n on t!e ispla#.

    =etpoint 2 ,=P2- is acti'ate.?!e corresponing 'alue iss!o&n on t!e ispla#.

    "arameter set Parameter set 1 is acti'ate. Parameter set 2 is acti'ate.

    1. ?!e "ollo&ing parameters are s&itc!e* P$.1 P$.2 t rt tt C#1 C#2 $ #=1 #=2 #.0 #.1 #.2 r=

  • 7/24/2019 Manual Horno Templador

    41/53

    C>ane of ram< s%oane of ram< en' ane of ram< set

  • 7/24/2019 Manual Horno Templador

    42/53

    1$ (eater current

    12.1 (eater current indication

  • 7/24/2019 Manual Horno Templador

    43/53

    1%

    ?!e controller can $e integrate into a atanet&or t!roug! t!e inter"ace. ?!e "ollo&ingapplications can $e realise e.g.*

    ( process 'isualisation

    ( s#stem control( report

    ?!e $us s#stem is esigne accoring tot!e master(sla'e principle. mastercomputer can control up to 31 controllersan instru( ments ,sla'es-. ?!e inter"ace isa serial inter( "ace &it! t!e stanarsA=422 or A=485.

    ?!e "ollo&ing ata protocols are possi$le*

    ( MO>$us protocol( H$us protocol

    nter"ace escriptionB 70.3030.2

    Aetro"itting can onl# $e per"orme int!e "actor#.

    H

    H

  • 7/24/2019 Manual Horno Templador

    44/53

    14

    Ty#ee,Con e,Con )iCr,)i A Cu,Con )iCri,)ii ) +t10>,+t +t13>,+t +t30>,+t6> B

    Range200 to D 900EC200 to D1200EC200 to D1372EC200 to D 600EC100 to D1300EC0 to D1768EC0 to D1768EC0 to D1820EC

    :ignas

    0(2 F 10 0(4 F 20 m

    Interna resistance Ri

    votage dro#G=ei H 500 IJ

    Ge H 1

    :ignas

    0(2 F 10 0(4 F 20 m

    Interna resistance Ri

    votage dro#G=ei H 500 IJ

    Ge H 1

    14.1 Technica ata

    In#ut 1?!e c!ange $et&een Pt100 t!ermocouples0 I 20m an 4 I 20m can $e con"igu(re in t!e so"t&are.Joltage inputs 0,2- I 10 J reDuire a !ar(&are alteration in t!e "actor#.

    Controer for use ;ithresistance thermometers

    In#utPt100 in 2(&ire or 3(&ire circuit

    Contro rangeG1. to 850.0KC

    G200 to 850KC

    'ead resistance* 30 ma.

    'ead com#ensationnot reDuire &it! 3(&ire circuit.!en use &it! a resistance t!ermometerin 2(&ire circuit lea compensation can $epro'ie $# an eternal compensationresistor ,Acomp Aline-. n aition t!e learesistance can $e compensate in t!eso"t&are t!roug! process 'alue correction.

    Controer for use ;iththermocou#es

    Tem#erature com#ensation* internal

    Controer for use ;ithinearised transducers ;ithstandard signa

    In#ut $C!ange $et&een 0,4- I 20m ,eternalset( point- an 0 I 50m C ,!eatercurrent monitoring- can $e con"igure in t!e

    so"t( &are.Joltage inputs 0,2- I 10 J an potentiome(ter input reDuire a !ar&are alteration in t!e"actor#.

    Controer for use ;ith inearisedtransducers ;ith standard signa

    >ispla# &it! or &it!out ecimal place

    Controer for use ;ith#otentiometer

    A 100 to 10

    Controer for use ;ith currenttransformer heater currentmonitoringConnection t!roug! current trans"ormer

    ,trans"ormer ratio 1*1000-0 I 50 m C sinusoial=caling* 0 I 50.0

    Out#uts2 rela# outputs an 2 logic outputs area'aila$le as stanar 1 rela# or analogueoutput as option.

    1. Aela# outputs %1/%2n.o. ,mae- contactAating *

    3 250 J C on resisti'e loaContact li"e*more t!an 510

    5operations at rate loa.

    2. Aela# output %3c!angeo'er contactAating*3 250 J C on resisti'e loaContact li"e*more t!an 510

    5operations at rate loa.

    >ispla# &it! or &it!out ecimal place

    3. @ogic outputs %4/%5

    0/5 J Aloa more t!an 250 0/12 J Aloa more t!an 650

  • 7/24/2019 Manual Horno Templador

    45/53

    4. nalogue output %3

    0,2- I 10 J Aloa more t!an 500

    0,4- I 20 m Aloa less t!an 500 isolation to t!e inputs*

    < less t!an 30 J C< less t!an 50 J >C

    enera controer data

    Controer ty#eCan $e con"igure as single or ou$le set(point controller moulating or proportionalcontroller

    ,) converter7 resolution $etter t!an 15$it

    :am#ing time7 210 msec

    :u##y3 I 263 J C 48 I 63 or20 I 53 J >C/C 48 I 63

    "o;er rating7 8 J appro.

    !ectrica connectiont!roug! "aston ta$s to >9 46 244/4.8 mm 0.8 mm

    "ermitted amient tem#eraturerange0 to 50KC

    "ermitted storage tem#eraturerangeG40 to 70KC

    Cimatic conditionsrelati'e !umiit# not to ecee 75L

    Beasurement accuracy

    ,mienttem#eratureerror

    no conensation

    "rotection

    &!en use &it! resistance t!ermometers

    0.05L or $etter 25 ppm ma. per KC

    &!en use &it! t!ermocouples &it!in t!e

    &oring range

    0.25L or $etterQ 100 ppm ma. per KC&!en use &it! linearise transucers

    &it! stanar signal

    0.1L or $etter 100 ppm ma. per KC

    ?!ese 'alues inclue t!e linearisation to(lerances.

    Q on Pt30A!(Pt6A! B &it!in t!e range300 I 1820KC

    Beasurement circuit monitoringTransducer :ensor :hort2

    resistancet!ermometer

    F F

    t!ermocouples F G

    0 I 10J G G

    2 I 10J F F

    0 I20m G G

    4 I20m F F

    F recognise G not recognise

    ?!e outputs mo'e to a e"ine status.ata #rotection7 PAOM

    to 9 60 52

    "ront P 65$ac P 20

    !ectrica safety

    to 9 61 010Class 2clearance an creepage istances "or( o'er'oltage categor# 2( pollution egree 2

    !ectromagnetic com#ati5iity9 61 326nter"erence emission* Class B

    mmunit# to inter"erence* nustrialreDuirements

    (ousing"or "lus! panel mounting to >9 43 700in conucti'e plastic $ase material B=&it! plug(in controller c!assis

    O#erating #ositionunrestricte

    eight430 g appro.

    Interface R:4$$)R:485

    isolate

  • 7/24/2019 Manual Horno Templador

    46/53

    /aud rate7 1200 I 600

    $au "rotoco7 MO>$us

    /H$us Instrument

    address7 1I 31

  • 7/24/2019 Manual Horno Templador

    47/53

    14.2 'imitcom#aratorfunctions

    unction 1ino& "unction* t!e output is O9 &!en t!emeasurement is &it!in a certain rangea$out t!e setpoint ,&-.

    ample* & 200KC @ 20 F= 10Measurement increasing* rela# is energiseat 185KC an e(energise at 225KC.Measurement ecreasing* rela# is energiseat 215KC an e(energise at 175 KC.

    unction $

    as l1 $ut rela# "unction re'erse

    unction %lo& alarmunction* output is O &!en measurementis $elo& ,setpointG limit 'alue-

    ample* & 200KC @ 20 F= 10Measurement increasing*rela# is energise at 185KC.

    Measurement ecreasing*rela# is e(energise at 175KC.

    unction 4as l3 $ut rela# "unction re'erse

    & setpoint

    measurementF= i""erential

    @ limit 'alue

  • 7/24/2019 Manual Horno Templador

    48/53

    unction 5!ig! alarmunction* output is O &!en t!e measure(ment is a$o'e ,setpointlimit 'alue-.

    ample* & 200KC @ 20 F= 10Measurement increasing*rela# is e(energise at 225KC.Measurement ecreasing*rela# is energise at 215KC.

    unction *as l5 $ut rela# "unction re'erse

    unction +

    =&itc!ing point is inepenent o" controllersetpoint an epens onl# on @.unction* output is O9 &!en measurementis a$o'e limit 'alue.ample* @ 150 F= 10Measurement increasing*rela# is energise at 155KC.Measurement ecreasing*rela# is e(energise at 145KC.

    unction 8as l7 $ut rela# "unction re'erse

    & setpoint

    measurementF= i""erential

    @ limit 'alue

  • 7/24/2019 Manual Horno Templador

    49/53

    14.3 ,arm messages

    O'errange an unerrange is a com$ination o" t!e "ollo&ing e'ents*( sensor $rea/s!ort circuit( measurement is outsie t!e 'alue range o" t!e connecte sensor( inication o'er"lo&

    H

    is#ay escri#tion Cause),ction

    Process 'alue ispla#

    "las!es :1;.=etpoint ispla# s!o&ssetpoint or !eater current.

    O'errange or unerrange o"

    measurement on input 1.Controller an limit compara(tors relate to input 1 $e!a'eas con"igure ,C112-.

    Process 'alue ispla# "las!est!e process 'alue.=etpoint ispla# s!o&s t!esetpoint &!en outputretransmission !as $een

    con"igure.

    O'errange or unerrange o"measurement on input 2.Moulating controller &it!output retransmission $e!a'esas con"igure ,C112-N

    t!e same applies i" eternalsetpoint is programme.@imit comparators relate toinput 2 $e!a'e as con"igure,C112-.

    Process 'alue ispla# "las!est!e process 'alue.=etpoint ispla# "las!es:1; i" !eater currentinication or eternal setpoint!as $een con"igure.

    Operating le'el*

    " input 2 is con"igure "oroutput retransmission

    t!e process 'alue ispla#"las!es :1; &!enparameter :#; is calle up.

  • 7/24/2019 Manual Horno Templador

    50/53

    14.4 !-terna set#oint #rovision and set#oint#riorities

  • 7/24/2019 Manual Horno Templador

    51/53

  • 7/24/2019 Manual Horno Templador

    52/53

    "rogramming the controer

    =tart programming "rom t!e stan(ar ispla#.

    C!ange to parameterle'el &it!P ,2 sec-

    Continue s&itc!ing &it! Puntil parameter #.0 appears ont!e is( pla#

    C!ange to con"iguration le'el&it!P ,2 sec-

    ,?!e parameters appear in t!e se(Duence s!o&n alongsie. Certainparameters are omitte epeningon t!e settings at t!e con"iguration

    le'el.-

    nput t!e Coe

    nter &it!P

    Continue s&itc!ing &it!P tot!e su$seDuent parameters aninput appropriate Coes an'a( lues until setpoint ispla#=P1 appears.

    nput t!e setpoint =P1 Continue s&itc!ing &it!

    P nput t!e setpoint =P2

    Continue s&itc!ing &it! P

    Aeturn to stanar ispla#&it! 2P

    In#ut of the second#arameter set7

    =tart programming "rom t!e stan(ar ispla#.

    C!ange to parameterle'el &it!P ,2 sec-

    Continue s&itc!ing &it!Puntil parameter P$.1 isispla#e

    =elect t!e parameterset &it!P ,2sec-

    nput t!e parameters

    Code

    C111

    C112

    C113

    C211

    C212

    C213

    =C@

    =C

    =P@=P

    O=

    "aramete "arameter set "arameter set

    @1 D

    @2 D

    P$.1

    P$.2

    t

    rt

    tt

    C#1

    C#2

    $

    #=.1

    #=.2

    #.0

    #.1

    #.2

    r=

  • 7/24/2019 Manual Horno Templador

    53/53

    E=BO m( F Co.6

    =treet aress*

    MoltestraRe 13 ( 31

    E=BO Instrument Co.'td.

    H