01.05.02. STATUS PROSTORIJA
Broj Naziv Tem. pr. Topl. gub. Tem. pr. Topl. dob.
prost. prostorije u zim. re`.u zim. re`. u let. re`. u let. re`.
- - Q Q
- - W W
01 02 03 05 04 05 06
Suteren
1 Soba 20 - NE TRETIRA SE 26 3400
2 Dnevna Soba 20 - NE TRETIRA SE 26 4535
U K U P N O: - 7935
Prizemlje
1 Dnevna soba 20 - NE TRETIRA SE 26 3548
2 Soba 20 - NE TRETIRA SE 26 1291
5 Soba 20 - NE TRETIRA SE 26 1509
7 Kuhinja 20 - NE TRETIRA SE 26 1440
U K U P N O: - 7789
Potkrovlje
1 Spavaća soba 20 - NE TRETIRA SE 26 1652
2 Spavaća soba 20 - NE TRETIRA SE 26 1690
3 Spavaća soba 20 - NE TRETIRA SE 26 1455
U K U P N O: - 4798
Ukupno rashladne energije 20522
tp tp
oC oC
Status
prostorije
-
-
07
TRETIRA SE
TRETIRA SE
TRETIRA SE
TRETIRA SE
TRETIRA SE
TRETIRA SE
TRETIRA SE
TRETIRA SE
TRETIRA SE
01.05.03. PRORA^UN KOEFICIJENATA PROLAZA TOPLOTE
Prora~un koeficijenata prolaza toplote vr{i se prema obrascu:
Ovde je:
di o vi{e slojeva razli~itih materijala;
dne povr{ine
vazduha, onda nema samo provo|enja toplote kao kod ~vrstog sloja, po{to
se u vazdu{nom sloju toplota prenosi kako provo|enjem, tako i konvekci-
jom i zra~enjem;
spoljne strane.
Materijal Debljina Koef. p. t.
- d l
- m
01 02 03
01.05.03.01. ZID SPOLJNI - Tip 01
Staklo 0.020 3.100
Argon 0.001 0.007
Staklo 0.020 3.100
U K U P N O: 0.041
Toplotni otpor sa unutra{nje strane
Toplotni otpor vazdusnog sloja
Toplotni otpor sa spolja{nje strane
UKUPNI TOPLOTNI OTPOR r
KOEFICIJENT PROLAZA TOPLOTE k
ZID SPOLJNI - tip 02
Produ~ni malter 0.020 0.850
Giter blok 0.380 0.610
k = 1 / (1/au +Sd/l + 1/L +1/as)
au [W/m2K] - koeficijent prelaza toplote sa vazduha u prostoriji na pregradnu povr{inu:
d (m) - debljina pregradne povr{ine ili jednog sloja pregradne povr{ine, ako se ra-
l [W/mK] - koeficijent provo|enja toplote za pregradnu povr{inu ili uo~eni sloj pregra-
1/L [m2K/W] - otpor prolazu toplote kroz vazdu{ni sloj. Ako se jedan od slojeva sastoji od
as [W/m2K] - koeficijent prelaza toplote sa pregrade na vazduh koji se nalazi sa njene
W/m2K
W/m2K
Stiropor 0.030 0.041
Cementni malter 0.020 1.400
Akril plast 0.001 3.500
U K U P N O: 0.451
Toplotni otpor sa unutra{nje strane
Toplotni otpor vazdusnog sloja
Toplotni otpor sa spolja{nje strane
UKUPNI TOPLOTNI OTPOR
KOEFICIJENT PROLAZA TOPLOTE k
MEĐUSPRATNA KONSTRUKCIJA
Granitna keramika 0.010 1.280
Cementna ko{uljica 0.030 1.400
PE folija 0.000 -
Stiropor 0.020 0.041
AB plo~a 0.200 2.330
Produ`ni malter 0.020 0.850
U K U P N O: 0.280
Toplotni otpor sa unutra{nje strane
Toplotni otpor vazdusnog sloja
Toplotni otpor sa spolja{nje strane
UKUPNI TOPLOTNI OTPOR
KOEFICIJENT PROLAZA TOPLOTE k
MEDJUSPRATNA KONSTRUKCIJA IZNAD GARAŽE (PO)
Granitna keramika 0.010 1.280
Cementna ko{uljica 0.030 1.400
PE folija 0.000 -
Stiropor 0.050 0.041
AB plo~a 0.200 2.330
Produ`ni malter 0.020 0.850
U K U P N O: 0.310
Toplotni otpor sa unutra{nje strane
Toplotni otpor vazdusnog sloja
Toplotni otpor sa spolja{nje strane
UKUPNI TOPLOTNI OTPOR
KOEFICIJENT PROLAZA TOPLOTE k
01.05.03.08. PREGRADNI ZID - Tip 01
W/m2K
W/m2K
W/m2K
Produ`ni malter 0.018 0.870
Puna opeka 0.250 0.760
Produ`ni malter 0.010 0.870
U K U P N O: 0.278
Toplotni otpor sa unutra{nje strane
Toplotni otpor vazdusnog sloja
Toplotni otpor sa spolja{nje strane
UKUPNI TOPLOTNI OTPOR r
KOEFICIJENT PROLAZA TOPLOTE k
01.05.03.09. VRATA UNUTRA[NJA
KOEFICIJENT PROLAZA TOPLOTE k
01.05.03.10. PROZOR SPOLJNI - Tip 01
KOEFICIJENT PROLAZA TOPLOTE k
01.05.03.12. VRATA SPOLJNA
KOEFICIJENT PROLAZA TOPLOTE k
W/m2K
W/m2K
W/m2K
W/m2K
vazduha, onda nema samo provo|enja toplote kao kod ~vrstog sloja, po{to
se u vazdu{nom sloju toplota prenosi kako provo|enjem, tako i konvekci-
Topl. otpor
R
04
0.01
0.14
0.01
0.15
0.13
-
0.04
0.32
3.10
0.02
0.62
- koeficijent prelaza toplote sa vazduha u prostoriji na pregradnu povr{inu:
(m) - debljina pregradne povr{ine ili jednog sloja pregradne povr{ine, ako se ra-
- koeficijent provo|enja toplote za pregradnu povr{inu ili uo~eni sloj pregra-
- otpor prolazu toplote kroz vazdu{ni sloj. Ako se jedan od slojeva sastoji od
- koeficijent prelaza toplote sa pregrade na vazduh koji se nalazi sa njene
m2K/W
0.73
0.01
0.00
1.39
0.13
-
0.04
1.56
0.64
0.01
0.02
-
0.49
0.09
0.02
0.63
0.17
-
0.13
0.92
1.09
0.01
0.02
-
1.22
0.09
0.02
1.36
0.17
-
0.13
1.65
0.60
0.02
0.33
0.01
0.36
0.13
-
0.13
0.61
1.64
2.50
3.10
3.10
PRORAČUN TOPLOTNIH DOBITAKA KROZ SPOLJNE ZIDOVE
Prora~un toplotnih dobitaka kroz spoljne zidove vr{i se prema obrascu:
Ovde je:
K -
Prora~un korigovane vrednosti ekvivalentne temperaturne razlike vr{i se prema obrascu:
Ovde je:
28
22
za industijsku atmosferu
Qsz = K x F x Dtekv1
Koeficijent prolaza toplote za zid [W/m2K] F - Neto povr{ina zida kroz koju se transportuje toplotna energija [m2] Dtekv1 - Korigovana vrednost ekvivalentne temperaturne razlike [C]
Dtekv1 = Dtekv + (tem - 24,5) + (tp - tpst) + aT
Dtekv - Ekvivalentna temperaturna razlika koja zavisi od vrste zida i strane sveta [C] tem - Stvarna srednja vrednost spoljne dnevne temperature [C]:ts =
tp - Temperatura prostorije za koju je data ekvivalentna temperaturna razlika [C]:tp =
tpst - Unutra{nja projektna temperatura [C] aT - Korektura zamu}enosti atmosfere koja uzima u obzir odstupanja od gradske i uzima vrednost +1,5 [C] za ~istu i -1,5 [C]
06 h 07 h 08 h 09 h 10 h 11 h 12 h 13 h 14 h 15 h 16 h 17 h 18 h 19 h
K K K K K K K K K K K K K K
SI 2.10 2.20 2.40 2.70 3.00 3.40 3.60 3.80 4.10 4.30 4.50 4.70 4.80 4.85
I 4.00 3.90 4.20 4.80 5.40 6.00 6.50 6.90 7.20 7.30 7.50 7.60 7.60 7.50
JI 4.40 4.00 4.20 4.50 5.10 5.90 6.60 7.20 7.70 8.10 8.30 8.40 8.40 8.30
Spoljni malter - tvrda izolacija 5 c J 4.10 3.30 3.10 3.10 3.30 3.70 4.40 5.10 5.90 6.60 7.30 7.70 7.90 7.90
armIirani beton 20 cm - opeka 12 JZ 5.30 4.40 4.00 3.80 3.70 3.80 4.10 4.60 5.40 6.20 7.20 8.00 8.70 9.00
- unutra{nji malter Z 5.20 4.20 3.90 3.60 3.50 3.50 3.70 4.00 4.40 5.10 6.00 6.90 7.80 8.30
SZ 3.10 2.30 2.00 1.80 1.80 1.80 2.00 2.20 2.60 3.00 3.50 4.20 4.80 5.25
S 1.00 0.60 0.40 0.40 0.40 0.60 0.80 1.00 1.40 1.70 2.00 2.30 2.60 2.80
HD 0.50 0.00 -0.20 -0.20 -0.20 0.00 0.20 0.30 0.80 1.20 1.50 1.80 2.10 2.25
HO -0.30 -1.20 -1.40 -1.40 -1.10 -0.60 0.20 1.10 2.00 2.90 3.60 4.10 4.30 4.20
Ozn. Strana Deblj. Koefic. Povrina Temp. Trenutni toplotni fluks u pojedinim razdobljima dana
pregr. sveta zida pr. topl. zida prost. 06 h 07 h 08 h 09 h 10 h 11 h 12 h 13 h 14 h 15 h 16 h 17 h 18 h 19 h
- - d k F t
- - m C W W W W W W W W W W W W W W
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20
NAZIV PROSTORIJE: Soba
BROJ PROSTORIJE: 1
26
SZ JZ 0.28 0.80 10.40 26 56 34 31 29 28 29 32 36 42 49 57 64 70 72
SZ SZ 0.28 0.80 24.36 26 80 39 33 29 29 29 33 37 45 53 62 76 88 96
SZ SI 0.28 0.80 13.08 26 31 20 22 25 28 32 35 37 40 42 44 46 47 48
Ekvivalentne temperaturne razlike za unutra{nju projektnu temperaturu tp = 22 C
Dtekv Dtekv Dtekv Dtekv Dtekv Dtekv Dtekv Dtekv Dtekv Dtekv Dtekv Dtekv Dtekv Dtekv
Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr
W/m2K m2
TEMPERATURA PROSTORIJE - tp:
UKUPNO KROZ SPOLJNE ZIDOVE: 167 93 86 83 86 91 99 109 127 144 164 186 205 216
NAZIV PROSTORIJE: Dnevna Soba
BROJ PROSTORIJE: 2
26
SZ JZ 0.28 0.80 21.60 26 116 71 64 60 59 60 66 74 88 102 119 133 145 150
MK JI 0.28 0.80 20.40 26 88 60 64 69 78 91 103 113 121 127 131 132 132 131
SZ SI 0.28 0.80 21.63 26 52 33 36 42 47 54 57 61 66 69 73 76 78 79
UKUPNO KROZ SPOLJNE ZIDOVE: 256 164 164 171 184 206 226 247 275 298 322 341 355 360
NAZIV PROSTORIJE: Dnevna soba
BROJ PROSTORIJE: 1
26
SZ JZ 0.28 0.80 10.40 26 56 34 31 29 28 29 32 36 42 49 57 64 70 72
SZ SZ 0.28 0.80 24.36 26 80 39 33 29 29 29 33 37 45 53 62 76 88 96
SZ SI 0.28 0.80 13.08 26 31 20 22 25 28 32 35 37 40 42 44 46 47 48
UKUPNO KROZ SPOLJNE ZIDOVE: 167 93 86 83 86 91 99 109 127 144 164 186 205 216
NAZIV PROSTORIJE: Soba
BROJ PROSTORIJE: 2
26
SZ JZ 0.28 0.80 14.00 26 75 46 41 39 38 39 43 48 57 66 77 86 94 97
SZ JI 0.28 0.80 6.00 26 26 18 19 20 23 27 30 33 36 37 38 39 39 38
UKUPNO KROZ SPOLJNE ZIDOVE: 101 64 60 59 61 66 73 81 93 104 116 125 133 136
NAZIV PROSTORIJE: Soba
BROJ PROSTORIJE: 5
26
SZ JI 0.28 0.80 8.40 26 36 25 26 28 32 38 42 46 50 52 54 54 54 54
TEMPERATURA PROSTORIJE - tp:
TEMPERATURA PROSTORIJE - tp:
TEMPERATURA PROSTORIJE - tp:
TEMPERATURA PROSTORIJE - tp:
UKUPNO KROZ SPOLJNE ZIDOVE: 36 25 26 28 32 38 42 46 50 52 54 54 54 54
NAZIV PROSTORIJE: Kuhinja
BROJ PROSTORIJE: 7
26
SZ SI 0.28 0.80 7.28 26 17 11 12 14 16 18 19 20 22 23 24 26 26 26
SZ JI 0.28 0.80 2.00 26 9 6 6 7 8 9 10 11 12 12 13 13 13 13
UKUPNO KROZ SPOLJNE ZIDOVE: 26 17 18 21 23 27 29 31 34 36 37 39 39 39
NAZIV PROSTORIJE: Spavaća soba
BROJ PROSTORIJE: 1
26
SZ SZ 0.28 0.80 10.40 26 34 17 14 12 12 12 14 16 19 22 27 32 37 41
UKUPNO KROZ SPOLJNE ZIDOVE: 34 17 14 12 12 12 14 16 19 22 27 32 37 41
NAZIV PROSTORIJE: Spavaća soba
BROJ PROSTORIJE: 2
26
SZ JI 0.28 0.80 11.76 26 51 35 37 40 45 53 59 65 70 73 75 76 76 75
UKUPNO KROZ SPOLJNE ZIDOVE: 51 35 37 40 45 53 59 65 70 73 75 76 76 75
NAZIV PROSTORIJE: Spavaća soba
BROJ PROSTORIJE: 3
#REF!
SZ JI 0.28 0.80 10.21 26 44 30 32 34 39 46 51 56 60 64 65 66 66 65
UKUPNO KROZ SPOLJNE ZIDOVE: 44 30 32 34 39 46 51 56 60 64 65 66 66 65
TEMPERATURA PROSTORIJE - tp:
TEMPERATURA PROSTORIJE - tp:
TEMPERATURA PROSTORIJE - tp:
TEMPERATURA PROSTORIJE - tp:
Korektura zamu}enosti atmosfere koja uzima u obzir odstupanja od gradske i uzima vrednost +1,5 [C] za ~istu i -1,5 [C]
20 h
K
4.50
6.80
7.50
7.40
9.00
8.70
5.80
3.00
2.40
3.30
20 h
W
21
72
107
44
Dtekv
Qtr
224
150
118
73
341
72
107
44
224
97
35
132
48
48
24
12
36
46
46
68
68
59
59
PRORAČUN TOPLOTNIH DOBITAKA KROZ PREGRADNE ZIDOVE
Prora~un toplotnih dobitaka kroz pregradne zidove vr{i se prema obrascu:
Ovde je:
F -
Tavan, zavisno od konstrukcije i provetravanja 50
TEMPERATURE SUSE- Susedne prostorije 30
SEDNIH PROSTORIJA Zemlja 20
Prostor izme|u izloga i unutra{. stakla, zavisno od vr 45
Oznaka Debljina Koeficijent Temperatura Temperatura Temperatura Specifi~ni Povr{ina Toplotni
pregrade zida prolaza topl. prostora iza pregrade razlika topl. fluks pregrade fluks
- d k q F Q
- m K W
01 02 03 04 05 06 07 08 09
NAZIV PROSTORIJE: Soba
BROJ PROSTORIJE: 1
26
UZ 0.28 1.64 26 30 4 6.55 4.40 29
PO 0.31 0.45 26 20 -6 -2.70 38.40 -104
TOPLOTNI DOBICI KROZ PEGRADNE ZIDOVE UKUPNO: -75
NAZIV PROSTORIJE: Dnevna Soba
BROJ PROSTORIJE: 2
26
UV 0.00 26 30 4 0.00 4.40 0
UZ 0.28 1.64 26 30 4 6.55 16.80 110
PO 0.31 0.45 26 20 -6 -2.70 50.00 -135
TOPLOTNI DOBICI KROZ PEGRADNE ZIDOVE UKUPNO: -25
NAZIV PROSTORIJE: Dnevna soba
BROJ PROSTORIJE: 1
Qt = k x F x (tp - ts)
k - Koeficijent prolaza toplote kroz pregradu [W/m2K]Povr{ina pregrade [m2]
tp - Projektna temperatura prostorije u letnjem re`imu [C] ts - Temperatura susedne prostorije u letnjem re`imu [C]:
tp ts Dt
W/m2K oC oC W/m2 m2
TEMPERATURA PROSTORIJE - tp:
TEMPERATURA PROSTORIJE - tp:
26
UZ 0.28 1.64 26 30 4 6.55 11.20 73
PO 0.31 0.00 26 20 -6 0.00 38.40 0
TOPLOTNI DOBICI KROZ PEGRADNE ZIDOVE UKUPNO: 73
NAZIV PROSTORIJE: Soba
BROJ PROSTORIJE: 2
26
PO 0.31 0.00 26 20 -6 0.00 45.60 0
UZ 0.28 1.64 26 30 4 6.56 9.30 61
TOPLOTNI DOBICI KROZ PEGRADNE ZIDOVE UKUPNO: 61
NAZIV PROSTORIJE: Soba
BROJ PROSTORIJE: 5
26
UZ 0.28 1.64 26 30 4 6.55 11.70 77
UZ 0.28 1.64 26 30 4 6.55 4.98 33
TOPLOTNI DOBICI KROZ PEGRADNE ZIDOVE UKUPNO: 109
NAZIV PROSTORIJE: Kuhinja
BROJ PROSTORIJE: 7
26
UZ 0.31 1.64 26 30 4 6.56 7.28 48
TOPLOTNI DOBICI KROZ PEGRADNE ZIDOVE UKUPNO: 48
NAZIV PROSTORIJE: Spavaća soba
BROJ PROSTORIJE: 1
26
MK 0.31 0.45 26 40 14 6.30 16.00 101
UZ 0.31 1.64 26 45 19 31.16 18.00 561
TOPLOTNI DOBICI KROZ PEGRADNE ZIDOVE UKUPNO: 662
NAZIV PROSTORIJE: Spavaća soba
BROJ PROSTORIJE: 2
#REF!
UZ 0.31 1.64 26 30 4 6.56 29.85 196
MK 0.31 0.45 26 40 14 6.30 25.00 158
TOPLOTNI DOBICI KROZ PEGRADNE ZIDOVE UKUPNO: 353
NAZIV PROSTORIJE: Spavaća soba
BROJ PROSTORIJE: 3
26
UZ 0.31 1.64 26 30 4 6.56 10.25 67
TEMPERATURA PROSTORIJE - tp:
TEMPERATURA PROSTORIJE - tp:
TEMPERATURA PROSTORIJE - tp:
TEMPERATURA PROSTORIJE - tp:
TEMPERATURA PROSTORIJE - tp:
TEMPERATURA PROSTORIJE - tp:
TEMPERATURA PROSTORIJE - tp:
MK 0.31 0.45 26 40 14 6.30 9.00 57
TOPLOTNI DOBICI KROZ PEGRADNE ZIDOVE UKUPNO: 124
Projektna temperatura prostorije u letnjem re`imu [C] Temperatura susedne prostorije u letnjem re`imu [C]:
PRORAČUN TRENUTNIH TRANSMISIONIH TOPLOTNIH DOBITAKA KROZ PROZORE
Prora~un transmisionih toplotnih dobitaka kroz prozore vr{i se prema obrascu:
Ovde je:
F -
Tren. temper. spoljnjeg vazduha u mes 06 h 07 h 08 h 09 h 10 h 11 h 12 h 13 h 14 h 15 h 16 h 17 h 18 h 19 h 20 h
julu za Novi Sad, u pojedinim razd. dana 24.20 25.00 26.20 27.80 29.60 30.90 31.90 32.70 32.90 33.00 32.90 32.40 31.40 ### 28.90
-
-
Ozn. Str. Broj Koefic. Povr{ina Temp. Trenutni toplotni fluks u pojedinim razdobljima dana
preg. sveta kom. pr. topl. prozora prost. 06 h 07 h 08 h 09 h 10 h 11 h 12 h 13 h 14 h 15 h 16 h 17 h 18 h 19 h 20 h
- - - k F
- - - W W W W W W W W W W W W W W W
01 02 03 04 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
NAZIV PROSTORIJE: Soba
BROJ PROSTORIJE: 1
26
Qt = k x F x (tp - ts tr)
k - Koeficijent prolaza toplote kroz prozor [W/m2K]Povr{ina prozora [m2]
tp - Projektna temperatura prostorije u letnjem re`imu [C] ts tr - Trenutna temperatura spoljnjeg vazduha u mesecu julu za mesto u kome se nalazi gra|evinski objekt [C]:
ttr ttr ttr ttr ttr ttr ttr ttr ttr ttr ttr ttr ttr ttr ttr
oC oC oC oC oC oC oC oC oC oC oC oC oC oC oC
tp Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr
W/m2K m2 oC
TEMPERATURA PROSTORIJE - tp:
PS SZ 1 1.50 6.72 26 -18 -10 2 18 36 49 59 68 70 71 70 65 54 42 29
PS JZ 1 1.50 3.36 26 -9 -5 1 9 18 25 30 34 35 35 35 32 27 21 15
UK. TREN. TRANSMIS. TOPL. DOBICI: -27 -15 3 27 54 74 89 101 104 106 104 97 82 64 44
NAZIV PROSTORIJE: Dnevna Soba
BROJ PROSTORIJE: 2
26
PS JI 1 1.50 6.72 26 -18 -10 2 18 36 49 59 68 70 71 70 65 54 42 29
UK. TREN. TRANSMIS. TOPL. DOBICI: -18 -10 2 18 36 49 59 68 70 71 70 65 54 42 29
NAZIV PROSTORIJE: Dnevna soba
BROJ PROSTORIJE: 1
26
PS SZ 1 1.50 6.72 26 -18 -10 2 18 36 49 59 68 70 71 70 65 54 42 29
PS JZ 1 1.50 3.36 26 -9 -5 1 9 18 25 30 34 35 35 35 32 27 21 15
UK. TREN. TRANSMIS. TOPL. DOBICI: -27 -15 3 27 54 74 89 101 104 106 104 97 82 64 44
NAZIV PROSTORIJE: SobaBROJ PROSTORIJE: 2
26
PS JI 1 1.50 3.22 26 -9 -5 1 9 17 24 28 32 33 34 33 31 26 20 14
UK. TREN. TRANSMIS. TOPL. DOBICI: -9 -5 1 9 17 24 28 32 33 34 33 31 26 20 14
NAZIV PROSTORIJE: SobaBROJ PROSTORIJE: 5
26
PS JI 1 1.50 3.36 26 -9 -5 1 9 18 25 30 34 35 35 35 32 27 21 15
UK. TREN. TRANSMIS. TOPL. DOBICI: -9 -5 1 9 18 25 30 34 35 35 35 32 27 21 15
TEMPERATURA PROSTORIJE - tp:
TEMPERATURA PROSTORIJE - tp:
TEMPERATURA PROSTORIJE - tp:
TEMPERATURA PROSTORIJE - tp:
NAZIV PROSTORIJE: Kuhinja
BROJ PROSTORIJE: Kuhinja26
PS JI 1 1.50 3.36 26 -9 -5 1 9 18 25 30 34 35 35 35 32 27 21 15
UK. TREN. TRANSMIS. TOPL. DOBICI: -9 -5 1 9 18 25 30 34 35 35 35 32 27 21 15
NAZIV PROSTORIJE: Spavaća soba
BROJ PROSTORIJE: 1
26
PS JI 1 1.50 0.00 26 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
PS JZ 1 1.50 0.00 26 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
UK. TREN. TRANSMIS. TOPL. DOBICI: 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
NAZIV PROSTORIJE: Spavaća soba
BROJ PROSTORIJE: 2
#REF!
PS JI 1 1.50 3.36 26 -9 -5 1 9 18 25 30 34 35 35 35 32 27 21 15
UK. TREN. TRANSMIS. TOPL. DOBICI: -9 -5 1 9 18 25 30 34 35 35 35 32 27 21 15
NAZIV PROSTORIJE: Spavaća soba
BROJ PROSTORIJE: 3
26
PS JI 1 1.50 3.36 26 -9 -5 1 9 18 25 30 34 35 35 35 32 27 21 15
UK. TREN. TRANSMIS. TOPL. DOBICI: -9 -5 1 9 18 25 30 34 35 35 35 32 27 21 15
TEMPERATURA PROSTORIJE - tp:
TEMPERATURA PROSTORIJE - tp:
TEMPERATURA PROSTORIJE - tp:
TEMPERATURA PROSTORIJE - tp:
PRORAČUN TRENUTNIH TOPLOTNIH DOBITAKA KROZ PROZORE OD SUNČEVOG ZRAČENJA
Ozn.Strana Broj [irina Visina Povr{inaDubina Trenutni toplotni fluks od sun~evog zra~enja u pojedinim razdobljima dana
preg.sveta kom. prozora prozora prozorapr. ni{e 06 h 07 h 08 h 09 h 10 h 11 h 12 h 13 h 14 h 15 h 16 h
- - n a b h
- - - m m m W W W W W W W W W W W
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18
NAZIV PROSTORIJE: Soba
BROJ PROSTORIJE: 1
PS SZ 2 4.80 1.40 6.72###4.80 1.40 6.72 61 81 103 123 135 152 152 155 188 541 1255
PS JZ 1 2.40 1.40 3.36###2.40 1.40 3.36 11 15 19 23 26 47 122 309 439 499 431
UK. TREN. TOPL. DOBICI OD SUN. ZRA^.: 72 97 122 146 161 199 274 464 627 1040 1687
NAZIV PROSTORIJE: Dnevna Soba
BROJ PROSTORIJE: 2
PS JI 2 4.80 1.40 6.72###4.80 1.40 6.72 381 1015 1591 1972 ### 1345 579 257 151 128 113
UK. TREN. TOPL. DOBICI OD SUN. ZRA^.: 381 1015 1591 1972 1824 1345 579 257 151 128 113
NAZIV PROSTORIJE: Dnevna soba
Fpr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr
m2
BROJ PROSTORIJE: 1
PS SZ 2 4.80 1.40 6.72###4.80 1.40 6.72 61 81 103 123 135 152 152 155 188 541 1255
PS JZ 1 2.40 1.40 3.36###2.40 1.40 3.36 11 15 19 23 26 47 122 309 439 499 431
UK. TREN. TOPL. DOBICI OD SUN. ZRA^.: 72 97 122 146 161 199 274 464 627 1040 1687
NAZIV PROSTORIJE: Soba
BROJ PROSTORIJE: 2
PS JI 1 2.30 1.40 3.22###2.30 1.40 3.22 91 243 381 472 437 322 139 62 36 31 27
UK. TREN. TOPL. DOBICI OD SUN. ZRA^.: 91 243 381 472 437 322 139 62 36 31 27
NAZIV PROSTORIJE: Soba
BROJ PROSTORIJE: 5
PS JI 1 2.40 1.40 3.36###2.40 1.40 3.36 95 254 398 493 456 336 145 64 38 32 28
UK. TREN. TOPL. DOBICI OD SUN. ZRA^.: 95 254 398 493 456 336 145 64 38 32 28
NAZIV PROSTORIJE: Kuhinja
BROJ PROSTORIJE: 7
PS JI 1 2.40 1.40 3.36###2.40 1.40 3.36 95 254 398 493 456 336 145 64 38 32 28
UK. TREN. TOPL. DOBICI OD SUN. ZRA^.: 95 254 398 493 456 336 145 64 38 32 28
NAZIV PROSTORIJE: Spavaća soba
BROJ PROSTORIJE: 1
PS JZ 1 0.00 6.20 0.00###0.00 6.20 0.00 0 0 0 0 0 0 0 0 0 0 0
PS JI 1 0.00 6.20 0.00###0.00 6.20 0.00 0 0 0 0 0 0 0 0 0 0 0
UK. TREN. TOPL. DOBICI OD SUN. ZRA^.: 0 0 0 0 0 0 0 0 0 0 0
NAZIV PROSTORIJE: Spavaća soba
BROJ PROSTORIJE: 2
PS JI 1 2.40 1.40 3.36###2.40 1.40 3.36 95 254 398 493 456 336 145 64 38 32 28
UK. TREN. TOPL. DOBICI OD SUN. ZRA^.: 95 254 398 493 456 336 145 64 38 32 28
NAZIV PROSTORIJE: Spavaća soba
BROJ PROSTORIJE: 3
PS JI 1 2.40 1.40 3.36###2.40 1.40 3.36 95 254 398 493 456 336 145 64 38 32 28
UK. TREN. TOPL. DOBICI OD SUN. ZRA^.: 95 254 398 493 456 336 145 64 38 32 28
Trenutni toplotni fluks od sun~evog zra~enja u pojedinim razdobljima dana
17 h 18 h 19 h 20 h
W W W W
19 20 21 22
1692 1294 609 190
300 133 73 35
1992 1427 682 225
86 71 51 30
86 71 51 30
Qtr Qtr Qtr Qtr
1692 1294 609 190
300 133 73 35
1992 1427 682 225
21 17 12 7
21 17 12 7
22 18 13 8
22 18 13 8
22 18 13 8
22 18 13 8
0 0 0 0
0 0 0 0
0 0 0 0
22 18 13 8
22 18 13 8
22 18 13 8
22 18 13 8
PRORAČUN TOPLOTNIH DOBITAKA OD LJUDI
Oznaka Naziv Broj ljudi koji Topl. koju odaje ~ovek u pro Ukupna topl. od ljudi u prost.
prostorije prostorije borave u prost. Osetljiva Latentna Osetljiva Latentna
- - n
- - - W W W W
01 02 03 04 05 06 07
Suteren
1 Soba 5 100 80 500 400
2 Dnevna soba 10 100 80 1000 800
1 Dnevna soba 5 100 80 500 400
2 Soba 3 100 80 300 240
5 Soba 4 100 80 400 320
7 Kuhinja 4 100 80 400 320
1 Spavaća soba 4 100 80 400 320
2 Spavaća soba 4 100 80 400 320
3 Spavaća soba 4 100 80 400 320
qlat qos Qlat Qos
PRORAČUN TOPLOTNIH DOBITAKA OD OSVETLJENJA
Oznaka Naziv Inst. Trenutno toplotno optere}enje od osvetljenja
prostorijeprostorije snaga 06 h 07 h 08 h 09 h 10 h 11 h 12 h 13 h 14 h 15 h 16 h 17 h 18 h 19 h 20 h
- -
- - W W W W W W W W W W W W W W W W
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18
1 Soba 380 380 380 0 0 0 0 0 0 0 0 0 0 0 380 380
2 Dnevna 520 520 520 0 0 0 0 0 0 0 0 0 0 0 520 520
1 Dnevna 380 380 380 0 0 0 0 0 0 0 0 0 0 0 380 380
2 Soba 150 150 150 0 0 0 0 0 0 0 0 0 0 0 150 150
5 Soba 150 150 150 0 0 0 0 0 0 0 0 0 0 0 150 150
7 Kuhinja 150 150 150 0 0 0 0 0 0 0 0 0 0 0 150 150
1 Spavać 150 150 150 0 0 0 0 0 0 0 0 0 0 0 150 150
2 Spavać 150 150 150 0 0 0 0 0 0 0 0 0 0 0 150 150
3 Spavać 150 150 150 0 0 0 0 0 0 0 0 0 0 0 150 150
Pinst Ptr Ptr Ptr Ptr Ptr Ptr Ptr Ptr Ptr Ptr Ptr Ptr Ptr Ptr Ptr
PRORAČUN TOPLOTNIH DOBITAKA OD OPREME
Oznaka Naziv Inst. Stepen Pros. Fakt. Trenutno toplotno optere}enje od opreme
prostorijeprostorije snaga korisn.optereć. istovr. 06 h 07 h 08 h 09 h 10 h 11 h 12 h 13 h 14 h 15 h 16 h 17 h 18 h 19 h
- - h
- - W - - - W W W W W W W W W W W W W W
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17
1 Soba 2000 0.85 1.00 1.00 300 300 300 300 300 300 300 300 300 300 300 300 300 300
1 Dnevna4000 0.85 1.00 1.00 600 600 600 600 600 600 600 600 600 600 600 600 600 600
2 Dnevna2000 0.85 1.00 1.00 300 300 300 300 300 300 300 300 300 300 300 300 300 300
1 Soba 1000 0.85 1.00 1.00 150 150 150 150 150 150 150 150 150 150 150 150 150 150
5 Soba 1000 0.85 1.00 1.00 150 150 150 150 150 150 150 150 150 150 150 150 150 150
7 Kuhinja1000 0.85 1.00 1.00 150 150 150 150 150 150 150 150 150 150 150 150 150 150
1 Spavać 500 0.85 1.00 1.00 75 75 75 75 75 75 75 75 75 75 75 75 75 75
2 Spavać 500 0.85 1.00 1.00 75 75 75 75 75 75 75 75 75 75 75 75 75 75
3 Spavać 500 0.85 1.00 1.00 75 75 75 75 75 75 75 75 75 75 75 75 75 75
Pinst Ptr Ptr Ptr Ptr Ptr Ptr Ptr Ptr Ptr Ptr Ptr Ptr Ptr Ptr
20 h
W
18
300
600
300
150
150
150
75
75
75
Ptr
REKAPITULACIJA TOPLOTNIH DOBITAKA PO PROSTORIJAMA
OznakaNaziv Izvor toplotnih Trenutni toplotni dobici u pojedinim razdobljima dana
prost.prostorije dobitaka 06 h 07 h 08 h 09 h 10 h 11 h 12 h 13 h 14 h 15 h 16 h 17 h 18 h 19 h 20 h
- - -
- - - W W W W W W W W W W W W W W W
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18
Kroz spoljne zidove 167 93 86 83 86 91 99 109 127 144 164 186 205 216 224
Kroz pregradne zidove -75 -75 -75 -75 -75 -75 -75 -75 -75 -75 -75 -75 -75 -75 -75
Kroz prozore - transmisi -27 -15 3 27 54 74 89 101 104 106 104 97 82 64 44
Kroz prozore - od sun. z 72 97 122 146 161 199 274 464 627 1040 1687 1992 1427 682 225
1 Soba Od ljudi - osetljiva toplot 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500
Od ljudi - latentna toplot 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400
Od osvetljenja 380 380 0 0 0 0 0 0 0 0 0 0 0 380 380
Od opreme 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300
Od ostalih izvora - - - - - - - - - - - - - - -
U K U P N O: 1717 1679 1336 1382 1426 1489 1588 1800 1984 2415 3080 3400 2838 2467 1998
Kroz spoljne zidove 256 164 164 171 184 206 226 247 275 298 322 341 355 360 341
Kroz pregradne zidove -25 -25 -25 -25 -25 -25 -25 -25 -25 -25 -25 -25 -25 -25 -25
Kroz prozore - transmisi -18 -10 2 18 36 49 59 68 70 71 70 65 54 42 29
Kroz prozore - od sun. z 381 1015 1591 1972 1824 1345 579 257 151 128 113 86 71 51 30
2 DnevnOd ljudi - osetljiva toplot 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Od ljudi - latentna toplot 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800
Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr Qtr
Od osvetljenja 520 520 0 0 0 0 0 0 0 0 0 0 0 520 520
Od opreme 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600
Od ostalih izvora - - - - - - - - - - - - - - -
U K U P N O: 3514 4064 4132 4535 4419 3975 3240 2947 2870 2872 2880 2867 2856 3348 3295
Kroz spoljne zidove 167 93 86 83 86 91 99 109 127 144 164 186 205 216 224
Kroz pregradne zidove 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73
Kroz prozore - transmisi -27 -15 3 27 54 74 89 101 104 106 104 97 82 64 44
Kroz prozore - od sun. z 72 97 122 146 161 199 274 464 627 1040 1687 1992 1427 682 225
1 DnevnOd ljudi - osetljiva toplot 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500
Od ljudi - latentna toplot 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400
Od osvetljenja 380 380 0 0 0 0 0 0 0 0 0 0 0 380 380
Od opreme 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300
Od ostalih izvora - - - - - - - - - - - - - - -
U K U P N O: 1866 1828 1484 1530 1575 1637 1736 1948 2132 2563 3228 3548 2987 2615 2146
Kroz spoljne zidove 101 64 60 59 61 66 73 81 93 104 116 125 133 136 132
Kroz pregradne zidove 61 61 61 61 61 61 61 61 61 61 61 61 61 61 61
Kroz prozore - transmisi -9 -5 1 9 17 24 28 32 33 34 33 31 26 20 14
Kroz prozore - od sun. z 91 243 381 472 437 322 139 62 36 31 27 21 17 12 7
2 Soba Od ljudi - osetljiva toplot 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300
Od ljudi - latentna toplot 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240
Od osvetljenja 150 150 0 0 0 0 0 0 0 0 0 0 0 150 150
Od opreme 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150
Od ostalih izvora - - - - - - - - - - - - - - -
U K U P N O: 1085 1203 1193 1291 1266 1163 991 926 913 919 927 928 927 1069 1054
Kroz spoljne zidove 36 25 26 28 32 38 42 46 50 52 54 54 54 54 48
Kroz pregradne zidove 109 109 109 109 109 109 109 109 109 109 109 109 109 109 109
Kroz prozore - transmisi -9 -5 1 9 18 25 30 34 35 35 35 32 27 21 15
Kroz prozore - od sun. z 95 254 398 493 456 336 145 64 38 32 28 22 18 13 8
5 Soba Od ljudi - osetljiva toplot 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400
Od ljudi - latentna toplot 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320
Od osvetljenja 150 150 0 0 0 0 0 0 0 0 0 0 0 150 150
Od opreme 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150
Od ostalih izvora - - - - - - - - - - - - - - -
U K U P N O: 1252 1403 1404 1509 1486 1378 1196 1124 1101 1099 1096 1088 1079 1217 1200
Kroz spoljne zidove 26 17 18 21 23 27 29 31 34 36 37 39 39 39 36
Kroz pregradne zidove 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48
Kroz prozore - transmisi -9 -5 1 9 18 25 30 34 35 35 35 32 27 21 15
Kroz prozore - od sun. z 95 254 398 493 456 336 145 64 38 32 28 22 18 13 8
7 KuhinOd ljudi - osetljiva toplot 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400
Od ljudi - latentna toplot 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320
Od osvetljenja 150 150 0 0 0 0 0 0 0 0 0 0 0 150 150
Od opreme 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150
Od ostalih izvora - - - - - - - - - - - - - - -
U K U P N O: 1180 1334 1335 1440 1415 1306 1122 1047 1024 1021 1018 1010 1002 1141 1126
Kroz spoljne zidove 34 17 14 12 12 12 14 16 19 22 27 32 37 41 46
Kroz pregradne zidove 662 662 662 662 662 662 662 662 662 662 662 662 662 662 662
Kroz prozore - transmisi 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Kroz prozore - od sun. z 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
1 SpavaOd ljudi - osetljiva toplot 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400
Od ljudi - latentna toplot 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320
Od osvetljenja 150 150 0 0 0 0 0 0 0 0 0 0 0 150 150
Od opreme 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75
Od ostalih izvora - - - - - - - - - - - - - - -
U K U P N O: 1643 1623 1471 1469 1469 1469 1471 1472 1476 1479 1483 1489 1494 1648 1652
Kroz spoljne zidove 51 35 37 40 45 53 59 65 70 73 75 76 76 75 68
Kroz pregradne zidove 353 353 353 353 353 353 353 353 353 353 353 353 353 353 353
Kroz prozore - transmisi -9 -5 1 9 18 25 30 34 35 35 35 32 27 21 15
Kroz prozore - od sun. z 95 254 398 493 456 336 145 64 38 32 28 22 18 13 8
2 SpavaOd ljudi - osetljiva toplot 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400
Od ljudi - latentna toplot 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320
Od osvetljenja 150 150 0 0 0 0 0 0 0 0 0 0 0 150 150
Od opreme 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75
Od ostalih izvora - - - - - - - - - - - - - - -
U K U P N O: 1435 1582 1584 1690 1668 1562 1382 1311 1290 1289 1287 1278 1270 1407 1388
Kroz spoljne zidove 44 30 32 34 39 46 51 56 60 64 65 66 66 65 59
Kroz pregradne zidove 124 124 124 124 124 124 124 124 124 124 124 124 124 124 124
Kroz prozore - transmisi -9 -5 1 9 18 25 30 34 35 35 35 32 27 21 15
Kroz prozore - od sun. z 95 254 398 493 456 336 145 64 38 32 28 22 18 13 8
3 SpavaOd ljudi - osetljiva toplot 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400
Od ljudi - latentna toplot 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320
Od osvetljenja 150 150 0 0 0 0 0 0 0 0 0 0 0 150 150
Od opreme 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75
Od ostalih izvora - - - - - - - - - - - - - - -
U K U P N O: 1199 1348 1350 1455 1432 1326 1145 1073 1052 1050 1047 1039 1030 1168 1150