method statement for fire

Upload: binu-gopinathan

Post on 14-Oct-2015

118 views

Category:

Documents


8 download

DESCRIPTION

method statement for hanger

TRANSCRIPT

METHOD STATEMENT

THE METHOD STATEMENT OF

MECHANICAL HANGER AND SUPPORT INSTALLATIONTable of contents

1. Gross References Page 32. Scope of worksPage 33. Flow of Works ChartPage 44. MethodologyPage 5-275. Tools and EquipmentPage286. Safety MeasuresPage 287. AppendicesPage 288. Painting Safety Fire pipePage 291.Gross References1.1 General: Refer to the general Requirements worksection

Refer to the following worksection:

Mechanical general requirements, Fire protection system, hydranlic system, air handling uint and ventilation system.1.2 Material:

Material for Hanger and support following the standards on specification Approved type by Engineer

To describe mechanical works associated with install hanger and support of mechanical system to ensure compliance with contract requirements, drawings and technical specification. The design of the pipe work installation shall be tested and certify strictly in accordance with the requirement specification,

2. Scope of Works

Scope of works install hangers and supports of Mechanical System including the Duct works system, Piping fire protection and Hydrandlic system. The scope of work for this method statement shall include all the Mechanical system.

3. Flow of Works (Flow chart):

4. Methodology

4.1. General

4.1.1. The size of Hangers and supports shall be in compliance with the contract specification,

documents, and approved shop drawings.

4.1.2 Hangers and supports of mechanical system shall be fabricated at factory from the approved and galvanized steel sheet roll.

4.1.3 To ensure that all Hangers and supports material are fabricated form the approved, worker

Shall take photo picture on the approved material for record, before starting any fabrication process.When the finished parts delivery to site, the Engineers shall check the quality and material used, by the Q/C labels together with the evidence of the photo picture or refer to shop drawing , on the

material been used in the fabrication.

4.1.4 Only the site engineers final approved Hangers and supports shall be used for the site installation works.4.1.5. Various hanger systems and components for system shall be used and shall be

Coordinated with the ceiling work at the Contractor option with the approval by the Mechanical engineer.

4.1.6 All flanged joints shall be provided with suitable gasket as approved type by the Engineer.

4.1.7 Supports shall be attached to every system using screws or bolt to prevent slippage and noise.

4.1.8.Wall or overhead supports shall be anchored to structure using bolts of suitable type and adequate size or other methods suitable for conditions or materials encountered, only as approved by the Engineer.

4.1.9. Supports insulation work will be mentioned on method statement for mechanical system insulation work.

4.2. Hangers and Supports for duck work systems4.2.1 Supports and hangers shall be L-type formed steel angles, shall be as shown in Table 1

The vibration isolation rod hanger for fans shall be indicated on shop drawings.

Table 1 Hangers and Supports Schedule ( Refer to AS 4254)Duct Size

Largest Dimension (mm)Size of L-type formed steel angle (minimum)

(mm)Hanger rods diameter (minimum)

(mm)Hanger Maximum spacing for Flange Joint

(mm)Hanger Maximum spacing for TDC Joint

(mm)

Up to 90030 x 30 x 38mm3,000mm1500mm

901 to 160040 x 40 x 310mm3,000mm 1500mm

1601 to 220040 x 40 x 312mm2,400mm-

Over 2,20050 x 50 x 312mm2,400mm-

Figure 1: Section of Hangers and Supports

(Detail refer to drawing SRF-DT-500)Note: a) Hangers and supports details please refer to approved shop drawings.

Figure 2 Details of Hangers and Supports of Duct work for Riser(Detail refer to Table HS.5 of MOS hanger support)

(SEE TO FILE AUTOCAD)4.2.2. Fix Support

4.2.2.1. Check length of duct round and weight according to Table 12-1,12-2.

4.2.2. According to Table 3, select the Steel angle and Anchor bolt. Steel angle must be fabricated at

factory.

4.2.3. Fix support must be fixed to slab or beam.

4.2.2.4. Spacing of Fix support by steel angle shall be 1500mm and below, or refer to shop drawing approved.

Figure 7: Section of Fix support(Detail refer to table HS.5))Note:

Fix supports details please refer to approved shop drawings.Table. 2 Size of Steel Angle and Anchor Bolt (refer to AS 4254)Steel angle length - LSteel angle Size(minimum)

Anchor Bolt size Slab (mm)

Up to 1000L-30302.5M8

Up to 1600L-50503.0M10

Up to 2200L-50504.0M12

Over 2200L-50505M12

Note: Fix supports details please refer to approved shop drawings.

4.2.3 Plenum Chamber Plenum Chamber Thickness:- Thickness for galvanized steel sheet shall be as shown in Shop drawing approved4.2.3 Reinforcing

- Requirements for Size of L-type formed steel angle reinforcing shall be as shown in Table 4.

Table 4. Size of L-type formed steel angle Reinforcing

Largest Dimension of Plenum Chamber (mm)Size of L-type formed steel angle

Size (minimum)

(mm)Maximum Spacing (mm)

Up to 1000L-30302.51500

Up to 1600L-50503.01500

Up to 2200L-50504.01500

Over 2200L-505051500

Notes

- Installation details shall be indicated on shop drawings.

- Details of plenum chamber shall be indicated on the shop drawings.

4.3. Pipe Hangers and support for system- Piping or equipment supported by wire, plumbers tape, rope or other means or arrangements shall not be permitted.

- Pipe or equipment supported by valves or other line accessories shall not be permitted.

a) Vertical piping shall be supported as follows:

i) Risers: Steel angle support to rest at least on refer to shop drawing approvedii) Copper pipe: Steel angle support with rubber and refer to shop b) Horizontal piping shall be supported as follows:

Pipes shall be attached to or supported from structure using hangers and devices as specified or approved.

c) Hanger and Fix support spacing shall be as the following Table 5.

Table 5: Hanger and Fix support spacing1520253240506580100125150200250300

Hang SpacingCarbon Steel Pipe2.0 m or less3.0 m or less

Polyvinyl chloride pipe1.5 m or less1.2 m or less

Copper pipe1.5 m or less1.5 m or less

Fix Support SpacingCarbon Steel Pipe___Span by span or less1.5m or Show on Shop Drawing

Polyvinyl chloride pipe___Span by span or lessSpan by span or less1.5m or Show on Shop 1.5m or Drawing

Copper pipe___Span by span or lessSpan by span or less1.5m or Show on Shop Drawing

d) Low temperature pipe insulation shall be required for refrigerant lines and chilled water lines at points of support between pipe and hanger using rebar sheet or wood approved.e) Copper pipe isolation shall be required for each point of contact with hangers or other ferrous materials. f) Hanger rods

i) Hanger rod size shall be as the following Table 6: Table 6: Hanger rod size (Item B of Spection)Supported pipe (mm)Rod diameter (mm)

275 to 32520

Over 32524

Table 10 U bolt Size (Spection)Diameter PipeU bolt Size

16mm 34mm6mm

42mm 90mm8mm

Over 90mm10mm

From 150 - 25025x2mm

4.4.3. Additional Support

At changes of direction in either vertical or horizontal and point near the valve, additional support shall be provided. However it may be omitted when coincidental with required standard spacing location.

Figure 9. Additional support

4.4.4. Fix Support 1. Check the pipe weight, number and support spacing (Table 5).

2. According to Table 9, select the Steel angle and Anchor bolt.

3. The method of fixing for Insulated pipe is in accordance with Section8.8.

Figure 10 : Example for connect pipe over 65mm (for Chiller water pipe)Table 9 Size of Steel Angle and Anchor BoltNote: Steel angle and bolts shall be indicated on shop drawings.Weight (kg)Steel Angle LengthSize of Steel Angle and Anchor Bolt

LHSteel angle Size(minimum)Anchor Bolt Size(minimum)

SlabWall

605001000L-50505.5M10302M10302

1500L-63635.5M10302-

10001000L-63635.5M10302M10302

1500L-63635.5M10304-

1205001000L-70706.5M10304M10302

1500U120484M10304-

10001000L-75755.5M10304M10302

1500U150484M24304-

24010001000U120484M10304M10302

1500M10304-

15001000M10304M10302

1500M10304-

36010001000U150484M10304M10302

1500M10304-

15001000M10304M10302

1500M24304-

4.4.5 Setting of Floor Drain and Clean out

Setting of Floor Drain and Clean out shall be followed as under Figures.

(Fire stopping will be supply late)Figure 12 Setting of Clean out Type A

(Fire stopping will be supply late)Figure 15 Detail of pipe penetration for water proof4.4.6.Methodologies: For all sprinkler piping installation either wall or ceiling area.

Work will be executed by fixing anchor bolt into concrete structure or brick wall with approved bracket support and dimension according to approved shop drawing All brackets supports shall be factory-fabricated and hot dipped galvanized to JIS H8641 Standard prior to delivery to site for installation.

Deliver pipes and fittings to designated area of site work. Check and ensure sufficient quantity for area installation.

All supports shall be fabricated at workshop factory shall be approved type based on sample submitted and approved by the Engineer.

Installed supports will be checked by the Engineer.

All bolt and nuts accessories shall be approved brand/ types by the Engineer based on submission and approved.

Locate position of pipe installation as according to shop drawing.

Siamese fire department connection shall be as per approved drawing location easily be approached by fire engines for emergency fire fitting. Type of connection shall be compatible with hose fitting used by the local fire department and based on Vietnamese standard.

a) Pipe shaft area :

Carry pipe by manual labor to location. Chain block may be used to lift bigger pipe for installation.

b) On ceiling area :

Carry pipe to designated area of installation: for bigger pipe, chain block shall be used to hoist pipe to ceiling area.

Pipe shall be cleaned before installation.

Pipe shall be adjusted to fix location as according to approved shop drawing indicated and according to the construction schedule.

Mark and determine the location of pipe support.

Installed pipe shall be pressure tested and inspected by the Engineer for approval.

- Shall be cleaned system before pressure test / leak test.4.4.7 Marking and cutting.

All pipes size diameter 150mm and smaller shall be cut by electric powered, circular machine with abrasive wheel. Metallic wheel cutters shall not be permitted.

For pipes with outside diameter 150mm and greater shall be cut by Oxyacetylene torch.

After cutting, edges of pipe shall be grinded forming an angle of 300. Refer to Figure 104.4.8 Cut a hole to join smaller pipe: For steel pipe connect to steel pipe that is two times smaller than diameter of main pipe Cut a hole on main pipe by using oxyacetylene torch to create a hole.

Use grinder machine to smoothen the edges and burrs of the cut hole before joining the main pipe and the smaller pipe together forming a 900C Seam of joining shall be welded in three passes.

During work not in progress, the opening of hole shall be temporary capped to prevent entry of foreign object.

- Take out galvanize for Fire protection

For flange weld, spot weld at 1 point, then connect flange surface perpendicular to pipe and spot weld at 3-4 points prior to full welding and after that take down floor weld complete for Fire protection pipe. Note that seam of weld in outside face shall not be out off flange face. Remove water, oil and paint off completed weld.

Weld at 3-4 points on seam, then roll pipe to continue welding from up and down. Completed weld shall be clean by using wire brush and prime paint.

Inspection of weld. Refer to Figure 10 Weld seam shall be checked visually.

Weld joint will be thicker than edge of pipe maximum 3mm.

Weld defects shall be remoed and repaired under the Engineers supervision.

a. Screwed threaded connection. Pipe will be threaded by using the threading machine JIS B0203 Standard with automatic thread defining dimension.

Add suitable oil onto the cutting part or filling oil regularly onto cutting part of threading machine. When oil changes color due to mixing with water, change new oil.

Change threading teeth when pitches are not threading in regular manner due to wear and tear.

Check length and surface of pitches visually and adjust selection of threading range by hand.

Remove oil and dust on pitches, inside and outside pipe prior to start threading.

b. Tightening threaded pipe and fitting. Apply teflon sealing tape around the threaded pipe.

Screw pipe and fitting by hand, and then use pipe wrench to tighten slowly till pipe and fitting firmly tighten.

After tighten screw connection, cover odd pitches with primer paint and mark of pipe wrench.

Pressure test shall be carried out after area pipe work completed and jointed area paint dry up.

d.Sprinkler heads installation and coverage.

A sprinkler head shall be installed at every part of a ceiling divided by beam, etc. projected 0.4m above from the surface of installation for the said heads. However, this shall not apply in case the mutual central distance of the said beams does not exceed 1.8m or less.

In case there should be 1.2 m above of width and length for air duct, shelf etc, a sprinkler head shall be installed at the bottom surface of the said duct etc.

A distance between the deflector of sprinkler heads and the surface of installation for the said heads, shall be 0.3m below.

Sprinkler heads shall be so installed that the spindle thereof is perpendicular to the surface to which the said head is fitted.

Nothing shall be either installed or placed in the section within the distance of 0.45 m from the deflector of a sprinkler head, and 0.3m below of horizontal direction, or installation refer to Spec4.4.9 Support installation a. For ceiling support. Refer to Section on ceiling (file Autocad) Drill a hole and insert anchor bolt into concrete structure according to construction working schedule and approved shop-drawing.

Fix threaded rod support into insert anchor bolt and fix C-channel into location before laying pipe onto the bracket support.

Check the level of bracket support to ensure the pipe work have been done as according to the approved shop drawings and location.

Support hanger sizes on ceiling

Supported pipe (mm)Rod diameter (mm)

50 and smaller08

50-10010

125 through 20016

250 and larger24

b. For support on wall and pipe shaft. Refer to Figure Riser (file AutoCad) - Mark sure & fabricate support and then Galvanize for level B3, B2, B1, Roof, Riser Check support by plump-line to ensure bracket support are in a vertical straight line

- Fix bracket support onto wall and fastened with nuts to get support in position.

- Mark the location of pipe support as according to approved shop drawing.

- Drive a hole into wall of concrete structure or brick wall.

- Drill an anchor bolt into drilled hole.

- Fix bracket support onto wall and fastened with nuts to get support in position.

4.4.10 Prime paint and identification of pipe Completed pipe will be prime paint by the approved color code.

Symbol of identification of pipe will be suitable to diameter of pipe.

Direction of arrow denote the way of water flow

Schedule of lettering sizes (or refer to spection)

Outside diameter of pipe or covering (mm)Size of stencil letter (mm)Minimum length of flow arrow (mm)

20 to 40 incl.1260

50 to 100 incl.25100

125 to 175 incl.50125

200 and larger75150

Schedule of hanger support spacing Location

Pipe20mm diameter or less25mm to 40mm diameter50mm to 80mm diameter100mm diameter or more

Steel pipe 2.0mm2.0mm2.0mm3.0mm

5 Machinery & Tools

Power hacksaw Circular cutting machine with abrasive wheel Pipe clamp Plump-line Power drill. Chain block. Threading machine. Scaffolding Pipe wrench Spanner

Hammer

Water level ruler6. Safety Measures

Temporary barricade and warning sign shall be set up at area of site work

Any worker works at the height of 2m and above shall wear safety belt.

Workers shall be trained about safety condition.

Machineries, equipments and staging should be inspected by safety supervisor prior to work

A safety forms signed by workers and briefing before work will be provided to control the safety working condition (forms enclosed).

7. Appendix

Leaking test record. Available for Inspection (AFI) Inspection Record (IR)8. Paniting sefety fire pipeStep 1: Carry pipe to location area installation, properti floor at work area to be done.Step 2: Clean pipe

Step 3: Painting Iron-Mould safety and (Break-Zinc if need) by Grey color

Step 4: Painting one undercoat by Red color

Step 5: Painting complete safety by Red color 1STStep 6: Painting complete safety by Red color 2NDStep 7: Check after instal finish

Approved

Not approved

Approved

Define position of support

Installation of pipe

Approved

Not approved

Proceed

Engineer s inspection

In-house Inspection

Marking

Determine pipe as per approved location & level

Material Approved

Shop drawings (Approved)

Sealing compound

Process 3)

1. Install Equipment.

2. Apply sealing compound.

Process 2)

1. Finishing work by Architectural work.

2. Cut pipe.

Process 1)

1. Install pipe and steel panel.

2. Fill concrete. Make slope

for water proofing.

3. Water proofing

( Architectural work )

Connect Sanitary Fixtures

Finishing work

(Architectural work)

Cut pipe

Water proofing

(Architectural work)

Steel panel

PVC pipe

Concrete

Slab

Cap

Process 3)

Install COA ( upper part ).

Process 2)

1. Finishing work by Architectural work.

2. Cut pipe.

Process 1)

1. Install pipe and steel panel.

2. Fill concrete.

Clean out (COA)

Finishing work (Architectural work)

Cut pipe

Steel panel

PVC pipe

Concrete

Slab

Cap

Support

300 or below

300 or below

Support

Support

Support

Support

Support

Support

Support near bent

Support near bent

Support near bent

Support near branch

300 or below

600mm and above

Valve size is 100mm and above

45

Support near branch

600mm and above

Support near valve

Valve size is Less than 100mm

Support

Type

Diameter

Beam

L-type formed steel angle

Anchor bolt (Approved type by the engineer)

Duct including insulation

Page 1

_1307969667.dwg

_1308426497.dwg

_1307357192.dwg