nbs-m016 contemporary issues in climate change and energy 2010
DESCRIPTION
N.K. Tovey ( 杜伟贤 ) M.A, PhD, CEng, MICE, CEnv Н.К.Тови М.А., д-р технических наук Energy Science Director C Red Project HSBC Director of Low Carbon Innovation. NBS-M016 Contemporary Issues in Climate Change and Energy 2010. Revision Session Some worked examples. 1. 1. Format of Exam. - PowerPoint PPT PresentationTRANSCRIPT
1
NBS-M016 Contemporary Issues in Climate Change and Energy 2010
Revision Session
Some worked examples
N.K. Tovey (杜伟贤 ) M.A, PhD, CEng, MICE, CEnv
Н.К.Тови М.А., д-р технических наук
Energy Science Director CRed Project
HSBC Director of Low Carbon Innovation1
Format of ExamDuration 2 hoursTwo sections of equal value
One Section • Three questions – choose one• Entirely descriptive - Covering all aspects of course• Do read the question - they are frequently specific –
so do not merely write everything you know on say “SOLAR” for an answer – the question is likely to be more specific
Second Section• Two questions – choose one• Part descriptive (30+%), Part Numeric (up to 70%)• Do not forget the descriptive part!!!!!!!!!
NOTE: Two sections may be ordered so that descriptive section is first or second – this is to minimise pagination problems
Energy Management
Mean Temperature
Electricity Consumption (kWh)
January 3.75 910000
February 9 700000
March 13 540000
April 16 420000
May 23 790000
June 27 1030000
July 31.5 1300000
August 29 1150000
September 25 910000
October 20 610000
November 14 500000
December 8 740000
Mean Temperature
Electricity Consumption
(kWh)
3.75 910000
9 700000
13 540000
16 420000
23 790000
27 1030000
31.5 1300000
29 1150000
25 910000
20 610000
14 500000
8 740000
Total 3810000 5790000
9600000
Building uses only electricity. What can you deduce?
• Balance Temperature for no heating cooling ~ 16o C
• Separate into two groups• <= 16o C and > 16o C
• Plot points against Mean External Temperature
• Check there is no problem with balance temperature, and if there is move data points between two categories
Intercept of two lines @ 400000 kWh and 16.5o C.
Annual functional energy use = 12 * 400000
= 4800000 kWh = 50% of total use
Heating is (3810000-6*400000)/9600000 = 14.6%)
0200000400000600000800000
100000012000001400000
0 5 10 15 20 25 30 35kW
h/mon
th)
Mean Temperature
Functional Energy Use
HeatingCooling
Range of Wind Speed
(m/s)
days mean wind speed (m/s)
output (kW)
- <1 10 0 01 - 3 30 2 03 - 5 50 4 05 - 7 101 6 977 - 9 84 8 281
9 - 11 40 10 55711 - 13 20 12 84513 - 15 10 14 98315 - 17 8 16 100017 - 19 5 18 100019 - 21 3 20 100021 - 23 2 22 1000 - >23 2 23 0
4
Predicting Output from Wind Turbines – Worked Example – part 1
Step 1:
•Work out mean wind speed•Read of Graph for output at each mean wind speed
Power Curve
0
200
400
600
800
1000
0 10 20 30
wind speed (m/s)
kW
5
Predicting Output from Wind Turbines – Worked Example – part 2
Range of Wind Speed (m/s) days
mean wind speed (m/s)
Output (kW)
Generated in period (MWh)
(1) (2)
(3) (4) from graph
(5) = (2)*(4)*24/1000
- <1 10 0 0 01 - 3 30 2 0 03 - 5 50 4 0 05 - 7 101 6 97 235.17 - 9 84 8 281 566.5
9 - 11 40 10 557 534.711 - 13 20 12 845 405.613 - 15 10 14 983 235.915 - 17 8 16 1000 19217 - 19 5 18 1000 12019 - 21 3 20 1000 7221 - 23 2 22 1000 48 - >23 2 23 0
Total 2409.8Output = 2409.8 MWh per annum – Maximum Possible = 1* 8760 = 8760 MWhSo Load Factor = 2409.8 / 8760 = 27.5%
If carbon factor = 0.52, saving in CO2 = 2409.8 * 0.52 = 1253 tonnes
Variant of previous example – wind speed data given as percentage
Wind speed output Wind speed Frequency
Power * Frequency
[m/s] [kW] % 4.5 0 0 05 30 21.8 6.547 130 18.6 24.189 280 11.1 31.0811 434 9.5 41.2313 529 6.5 34.38515 585 4.1 23.98517 600 2.1 12.619 600 1 6
cutout 0 0.8 0 Summation 180Output at 100% load factor = 600 * 1 600
Load Factor =180/600
30.00%
Electricity generated in year
= 180*8760
= 1576800 kWh
Under Feed in Tariff
Revenue is 9.7p per kWh
So annual income is
1576800 * 0.097 =
£152949.6
Question 4 from 2008 Exam
A large hotel in India has a total window area of 6000 m2 which are single glazed with a U-Value of 5 W m-2 oC-1 and is cooled by an electrically driven air conditioner having an average coefficient of performance of 2.75.
Data for total electricity consumption at selected mean average external temperatures during the summer months are shown in Table 1.
Mean daily external temperature Mean Electricity Consumption (kW)
15 15920 16025 350
30 535
35 725
40 912
b) Comment on the relationship between electricity consumption and temperature. [10%]
c) Estimate the annual carbon emissions associated with cooling if the mean cooing degree days in India are 3120 and the overall carbon emission factor for electricity in India is 979.4 g / kWh. [25%]
d) The windows are replaced by double glazing units with a U-value of 2.5 W m-2 oC-1. Estimate the annual savings in carbon emissions.
[25%].
Question 4 from 2008 Exam
• Plot consumption against consumption.
• Two parts to curve – winter – no cooling, summer cooling
• Gradient of line is 37.5 kW oC-1
• As COP of air-conditioner is 2.75 heat gain rate in summer is
• 37.5 * 2.75 = 103.125 kWoC-1
Question 4 from 2008 Exam
0
100
200
300
400
500
600
700
800
900
1000
0 10 20 30 40 50
External Temperature (oC)
Ele
ctri
city
Co
nsu
mp
tio
n (
kW)
The carbon emissions associated with cooling = 37.5 * 3120 * 24 /1000 = 2808 MWh | | | Gradient of line degree days hours in a day
As the carbon factor for India is 979.4 g/kWh, the total carbon emissions will be 2808 * 979.4 = 2750 tonnes
The change in the heat loss rate from installing double glazing will be:
( 5 – 2.5) * 6000 = 15 kW oC-1
So the saving in carbon emissions will be:
15 * 3120 * 24 * 979.4 / 2.75
Remember to include COP!
= 400 tonnes
Question 4 from 2008 Exam
• As a senior manager in a small office firm which is constructing a new building you are asked to make recommendations on the mode of heating that should be employed and have been given guidance that you should use a discount rate of 5%.
• The building is designed to have a heat loss rate of 10 kW oC-1
and have a neutral internal temperature of 15.5oC. • You have two options to consider, an oil condensing boiler
system with an efficiency of 90% or a heat pump system, the coefficient of performance of which is shown in Table 2.
• The oil boiler system costs £25000 to install while the heat pump installation would cost £105 000.
• Both systems have an expected life of 10 years and both have similar annual maintenance charges.
• Which option would you recommend? • Data relating to the climate data are given in Table 3 while other
relevant data are given in Table 4. You may assume that the energy tariffs do not change in real terms over the period.
Question 5 from 2008 Exam
Table 2. Coefficient of Performance of Heat Pump
Table 3. Mean External Temperature at location of Building
External Temperature
(oC)Coefficient of
Performance
Months Mean Temperature
(oC)0 1.7 January - March 6.5
4 2.5 April - June 13.58 3.3 July - September 16
12 3.88October -
December 7.516 4.2
Question 5 from 2008 Exam
Calorific Value of oil 37 MJ/litre
Cost of oil 42.67 per litre
Cost of electricity 4.75 p per kWh
Question 5 from 2008 Exam
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
0 2 4 6 8 10 12 14 16 18
External Temperature (oC)
Coef
ficie
nc o
f Pef
orm
ance
Question 5 from 2008 Exam
External Temperature
(oC)
COP from graph
Number of days
Difference from balance temperature
Heat Requirement
(kWh)
Heat Requirement after allowing for
COP (kWh)(1) (2) (3) (4) (5) (6) (7)Jan - Mar 6.5 3 90 9 194400 64800Apr - Jun 13.5 4 91 2 43680 10920Jul - Sept 16 4.2 92
Oct - Dec 7.5 3.2 92 8 176640 55200
Total energy requirement 414720
Boiler efficiency 90%
Energy input boiler option 460800
Total effective input via heat pump 130920
Col (2) from Table 2 Col (3) from graph
Col (4) number of days in period – i.e Jan (31) Feb (28) Mar (31) = 90 days
Col (5) balance temperature is 15.5, so col(5) = 15.5 – col(2)
Col (6) heat loss rate (10 kW oC-1 ) * col (5) * col (4) * 24 (hours in a day)
Col (7) col(6)/col(3)
Question 5 from 2008 Exam
External Temperature
(oC)
COP from graph
Number of days
Difference from balance temperature
Heat Requirement
(kWh)
Heat Requirement after allowing for
COP (kWh)(1) (2) (3) (4) (5) (6) (7)Jan - Mar 6.5 3 90 9 194400 64800Apr - Jun 13.5 4 91 2 43680 10920Jul - Sept 16 4.2 92
Oct - Dec 7.5 3.2 92 8 176640 55200
Total energy requirement 414720
Boiler efficiency 90%
Energy input boiler option 460800
Total effective input via heat pump 130920
Col (2) from Table 2 Col (3) from graph
Col (4) number of days in period – i.e Jan (31) Feb (28) Mar (31) = 90 days
Col (5) balance temperature is 15.5, so col(5) = 15.5 – col(2)
Col (6) heat loss rate (10 kW oC-1 ) * col (5) * col (4) * 24 (hours in a day)
Col (7) col(6)/col(3)
Question 5 from 2008 Exam
External Temperature
(oC)
COP from graph
Number of days
Difference from balance temperature
Heat Requirement
(kWh)
Heat Requirement after allowing for
COP (kWh)(1) (2) (3) (4) (5) (6) (7)Jan - Mar 6.5 3 90 9 194400 64800Apr - Jun 13.5 4 91 2 43680 10920Jul - Sept 16 4.2 92
Oct - Dec 7.5 3.2 92 8 176640 55200
Total energy requirement 414720
Boiler efficiency 90%
Energy input boiler option 460800
Total effective input via heat pump 130920
Col (2) from Table 2 Col (3) from graph
Col (4) number of days in period – i.e Jan (31) Feb (28) Mar (31) = 90 days
Col (5) balance temperature is 15.5, so col(5) = 15.5 – col(2)
Col (6) heat loss rate (10 kW oC-1 ) * col (5) * col (4) * 24 (hours in a day)
Col (7) col(6)/col(3)
Question 5 from 2008 Exam
External Temperature
(oC)
COP from graph
Number of days
Difference from balance temperature
Heat Requirement
(kWh)
Heat Requirement after allowing for
COP (kWh)(1) (2) (3) (4) (5) (6) (7)Jan - Mar 6.5 3 90 9 194400 64800Apr - Jun 13.5 4 91 2 43680 10920Jul - Sept 16 4.2 92
Oct - Dec 7.5 3.2 92 8 176640 55200
Total energy requirement 414720
Boiler efficiency 90%
Energy input boiler option 460800
Total effective input via heat pump 130920
Col (2) from Table 2 Col (3) from graph
Col (4) number of days in period – i.e Jan (31) Feb (28) Mar (31) = 90 days
Col (5) balance temperature is 15.5, so col(5) = 15.5 – col(2)
Col (6) heat loss rate (10 kW oC-1 ) * col (5) * col (4) * 24 (hours in a day)
Col (7) col(6)/col(3)
Question 5 from 2008 Exam
External Temperature
(oC)
COP from graph
Number of days
Difference from balance temperature
Heat Requirement
(kWh)
Heat Requirement after allowing for
COP (kWh)(1) (2) (3) (4) (5) (6) (7)Jan - Mar 6.5 3 90 9 194400 64800Apr - Jun 13.5 4 91 2 43680 10920Jul - Sept 16 4.2 92
Oct - Dec 7.5 3.2 92 8 176640 55200
Total energy requirement 414720
Boiler efficiency 90%
Energy input boiler option 460800
Total effective input via heat pump 130920
Col (2) from Table 2 Col (3) from graph
Col (4) number of days in period – i.e Jan (31) Feb (28) Mar (31) = 90 days
Col (5) balance temperature is 15.5, so col(5) = 15.5 – col(2)
Col (6) heat loss rate (10 kW oC-1 ) * col (5) * col (4) * 24 (hours in a day)
Col (7) col(6)/col(3)
Question 5 from 2008 Exam
External Temperature
(oC)
COP from graph
Number of days
Difference from balance temperature
Heat Requirement
(kWh)
Heat Requirement after allowing for
COP (kWh)(1) (2) (3) (4) (5) (6) (7)Jan - Mar 6.5 3 90 9 194400 64800Apr - Jun 13.5 4 91 2 43680 10920Jul - Sept 16 4.2 92
Oct - Dec 7.5 3.2 92 8 176640 55200
Total energy requirement 414720
Boiler efficiency 90%
Energy input boiler option 460800
Total effective input via heat pump 130920
Col (2) from Table 2 Col (3) from graph
Col (4) number of days in period – i.e Jan (31) Feb (28) Mar (31) = 90 days
Col (5) balance temperature is 15.5, so col(5) = 15.5 – col(2)
Col (6) heat loss rate (10 kW oC-1 ) * col (5) * col (4) * 24 (hours in a day)
Col (7) col(6)/col(3)
• From above table input energy = 460800 kWh = 1658880 MJ
• But calorific value of oil is 37 MJ/litre – so number of litres required = 460800/37 = 44834.59 litres
• Annual running costs with oil = 44834.59* 42.67 /100 = £19130.92
• Annual running costs of heat pump = 130920 * 4.75/100 = £6218.70
• Annual saving in running costs = £19130.92 - £6218.70 = £12912.22
• From discount tables the cumulative discount factor is 8.721735
• So the discounted savings over life of project
= 8.721735 * 12912.22 = £112617
• Net present Value = £25000 – 105000 + 112617 = £32617 i.e Heat Pump scheme is best option to choose.
Question 5 from 2008 Exam
0
1
2
3
4
5
6
7
8
9
0 1 2 3 4 5 6 7 8 9 10 11 12
3 units
7.6 units
Gradient of Line = 3/7.6 = 0.40
Working out the gradient of a line
CHP worked exampleA firm is considering installing a CHP scheme to replace the existing gas boiler (which has an efficiency of 80%) It is proposed to have three 400 kW CHP power plants to provide electricity and heat the buildings. The buildings have a heat loss rate of 250 kWoC-1 and there is a requirement of 100 kW for hot water. Assuming that there are 30 days in each month estimate the saving in energy compared to the existing system if the external temperature and electricity demand data are as follows:
Month Temp (oC) Electricity (kW)
Jan 1.9 1600Feb 4.5 1450Mar 9 1300Apr 12 1200May 14 1000June 16 1000July 17 1000Aug 16 1000Sep 13 1200Oct 11 1350Nov 9 1450Dec 4.1 1600
In the proposed scheme 1.4 units of heat are rejected for each unit of electricity generated.
Overall efficiency of CHP plant is 80%
What proportion of heat is supplied by CHP?
What are CO2 savings if emission factors are0.186 tonnes per MWh for gas and 0.544 tonnes per MWh for electricity
Month Temp (oC) Space Heat Demand (kW)
Total Heat Demand (kW)
Electricity (kW) given info
[1] [2] [3] [4] [5]
Jan 1.9 3400 3500 1600
Feb 4.5 2750 2850 1450
Mar 9 1625 1725 1300
Apr 12 875 975 1200
May 14 375 475 1000
June 16 0 100 1000
July 17 0 100 1000
Aug 16 0 100 1000
Sep 13 625 725 1200
Oct 11 1125 1225 1350
Nov 9 1625 1725 1450
Dec 4.1 2850 2950 1600
CHP worked example
Heat demand =
Heat loss rate * (temp. diff)
= 250 * (15.5 – ext temp)
e.g. for January = 250 * (15.5 – 1.9)
= 3400 kW
15.5 oC is the balance or neutral temperature and is the temperature at which no heating is required.
Total Heat demand = Space Heat Demand + Hot Water/Process Demand
Month Temp (oC) Space Heat Demand (kW)
Total Heat Demand (kW)
Electricity (kW) given info
[1] [2] [3] [4] [5]
Jan 1.9 3400 3500 1600
Feb 4.5 2750 2850 1450
Mar 9 1625 1725 1300
Apr 12 875 975 1200
May 14 375 475 1000
June 16 0 100 1000
July 17 0 100 1000
Aug 16 0 100 1000
Sep 13 625 725 1200
Oct 11 1125 1225 1350
Nov 9 1625 1725 1450
Dec 4.1 2850 2950 1600
CHP worked example
Month Total Heat
Demand (kW)
Electricitydemand
(kW)
Potential CHP Heat available
(kW)
Useful CHP Heat
(kW)
Supple-mentary
Heat (kW)
Actual Electricity Generated
(kW)
Supple-mentary
Electricity Needed (kW)
[1] [4] [5] [6] [7] [8] [9] [10]
Jan 3500 1600 1680 1680 1820 1200 400
Feb 2850 1450 1680 1680 1170 1200 250
Mar 1725 1300 1680 1680 45 1200 100
Apr 975 1200 1680 975 696*** 504
May 475 1000 1400 475 339*** 661
June 100 1000 1400 100 71*** 929
July 100 1000 1400 100 71*** 929
Aug 100 1000 1400 100 71*** 929
Sep 725 1200 1680 725 518*** 682
Oct 1225 1350 1680 1225 875 475
Nov 1725 1450 1680 1680 45 1200 250
Dec 2950 1600 1680 1680 1270 1200 400
When there is insufficient heat provided by CHP units, supplementary heat must be provided by existing boilers.
Thus supplementary heat (col[8])
= Col [4] – col 7]
However, not all CHP heat may be needed.
Need to compare with actual demand.
If CHP heat available is less than demand we can use all the heat.
col [7] = col [6] in Jan – Mar and Nov – Dec
If CHP heat is greater than demand we can only utilise actual heat demand.
col [7] = col [4]
Heat available from CHP units will be 1.4 times electrical output. But maximum electrical output = 3 *400 = 1200 kW
If electrical demand is greater than 1200 kW, the maximum heat available from CHP Units will be 1200 *1.4 = 1680 kW
If electrical demand is less than 1200, then heat available will be actual electricity demand * 1.4
e.g. for May – August heat available = 1000 * 1.4 = 1400 kW
Unless there is export of electricity.
Start by assuming no export.
CHP worked example
Month Total Heat
Demand (kW)
Electricitydemand
(kW)
Potential CHP Heat available
(kW)
Useful CHP Heat
(kW)
Supple-mentary
Heat (kW)
Actual Electricity Generated
(kW)
Supple-mentary
Electricity Needed (kW)
[1] [4] [5] [6] [7] [8] [9] [10]
Jan 3500 1600 1680 1680 1820 1200 400
Feb 2850 1450 1680 1680 1170 1200 250
Mar 1725 1300 1680 1680 45 1200 100
Apr 975 1200 1680 975 696*** 504
May 475 1000 1400 475 339*** 661
June 100 1000 1400 100 71*** 929
July 100 1000 1400 100 71*** 929
Aug 100 1000 1400 100 71*** 929
Sep 725 1200 1680 725 518*** 682
Oct 1225 1350 1680 1225 875 475
Nov 1725 1450 1680 1680 45 1200 250
Dec 2950 1600 1680 1680 1270 1200 400
When there is insufficient heat provided by CHP units, supplementary heat must be provided by existing boilers.
Thus supplementary heat (col[8])
= Col [4] – col 7]
However, not all CHP heat may be needed.
Need to compare with actual demand.
If CHP heat available is less than demand we can use all the heat.
col [7] = col [6] in Jan – Mar and Nov – Dec
If CHP heat is greater than demand we can only utilise actual heat demand.
col [7] = col [4]
Heat available from CHP units will be 1.4 times electrical output. But maximum electrical output = 3 *400 = 1200 kW
If electrical demand is greater than 1200 kW, the maximum heat available from CHP Units will be 1200 *1.4 = 1680 kW
If electrical demand is less than 1200, then heat available will be actual electricity demand * 1.4
e.g. for May – August heat available = 1000 * 1.4 = 1400 kW
Unless there is export of electricity.
Start by assuming no export.
CHP worked example
Month Total Heat
Demand (kW)
Electricitydemand
(kW)
Potential CHP Heat available
(kW)
Useful CHP Heat
(kW)
Supple-mentary
Heat (kW)
Actual Electricity Generated
(kW)
Supple-mentary
Electricity Needed (kW)
[1] [4] [5] [6] [7] [8] [9] [10]
Jan 3500 1600 1680 1680 1820 1200 400
Feb 2850 1450 1680 1680 1170 1200 250
Mar 1725 1300 1680 1680 45 1200 100
Apr 975 1200 1680 975 696*** 504
May 475 1000 1400 475 339*** 661
June 100 1000 1400 100 71*** 929
July 100 1000 1400 100 71*** 929
Aug 100 1000 1400 100 71*** 929
Sep 725 1200 1680 725 518*** 682
Oct 1225 1350 1680 1225 875 475
Nov 1725 1450 1680 1680 45 1200 250
Dec 2950 1600 1680 1680 1270 1200 400
When there is insufficient heat provided by CHP units, supplementary heat must be provided by existing boilers.
Thus supplementary heat (col[8])
= Col [4] – col 7]
However, not all CHP heat may be needed.
Need to compare with actual demand.
If CHP heat available is less than demand we can use all the heat.
col [7] = col [6] in Jan – Mar and Nov – Dec
If CHP heat is greater than demand we can only utilise actual heat demand.
col [7] = col [4]
CHP worked example
Month Total Heat
Demand (kW)
Electricitydemand
(kW)
Potential CHP Heat available
(kW)
Useful CHP Heat
(kW)
Supple-mentary
Heat (kW)
Actual Electricity Generated
(kW)
Supple-mentary
Electricity Needed (kW)
[1] [4] [5] [6] [7] [8] [9] [10]
Jan 3500 1600 1680 1680 1820 1200 400
Feb 2850 1450 1680 1680 1170 1200 250
Mar 1725 1300 1680 1680 45 1200 100
Apr 975 1200 1680 975 696*** 504
May 475 1000 1400 475 339*** 661
June 100 1000 1400 100 71*** 929
July 100 1000 1400 100 71*** 929
Aug 100 1000 1400 100 71*** 929
Sep 725 1200 1680 725 518*** 682
Oct 1225 1350 1680 1225 875 475
Nov 1725 1450 1680 1680 45 1200 250
Dec 2950 1600 1680 1680 1270 1200 400
When there is insufficient heat provided by CHP units, supplementary heat must be provided by existing boilers.
Thus supplementary heat (col[8])
= Col [4] – col 7]
CHP worked example
Month Total Heat
Demand (kW)
Electricity demand
(kW)
Potential CHP Heat available
(kW)
Useful CHP Heat
(kW)
Supple-mentary
Heat (kW)
Actual Electricity Generated
(kW)
Supple-mentary
Electricity Needed (kW)
[1] [4] [5] [6] [7] [8] [9] [10]
Jan 3500 1600 1680 1680 1820 1200 400
Feb 2850 1450 1680 1680 1170 1200 250
Mar 1725 1300 1680 1680 45 1200 100
Apr 975 1200 1680 975 696*** 504
May 475 1000 1400 475 339*** 661
June 100 1000 1400 100 71*** 929
July 100 1000 1400 100 71*** 929
Aug 100 1000 1400 100 71*** 929
Sep 725 1200 1680 725 518*** 682
Oct 1225 1350 1680 1225 875 475
Nov 1725 1450 1680 1680 45 1200 250
Dec 2950 1600 1680 1680 1270 1200 400
In Jan – Mar CHP units will run fully with 1200 kW electricity and 1680 kW heat.
However, electricity will be restricted if less than 1680 kW of heat is supplied.
In April only 975 kW heat is required.
1.4 units of heat are rejected for each unit of electricity.
So actual output of electricity will be less than rated output at 975/1.4 = 696 kW.
*** indicates electricity is restricted.
CHP worked example
Month Total Heat
Demand (kW)
Electricity demand
(kW)
Potential CHP Heat available
(kW)
Useful CHP Heat
(kW)
Supple-mentary
Heat (kW)
Actual Electricity Generated
(kW)
Supple-mentary
Electricity Needed (kW)
[1] [4] [5] [6] [7] [8] [9] [10]
Jan 3500 1600 1680 1680 1820 1200 400
Feb 2850 1450 1680 1680 1170 1200 250
Mar 1725 1300 1680 1680 45 1200 100
Apr 975 1200 1680 975 696*** 504
May 475 1000 1400 475 339*** 661
June 100 1000 1400 100 71*** 929
July 100 1000 1400 100 71*** 929
Aug 100 1000 1400 100 71*** 929
Sep 725 1200 1680 725 518*** 682
Oct 1225 1350 1680 1225 875 475
Nov 1725 1450 1680 1680 45 1200 250
Dec 2950 1600 1680 1680 1270 1200 400
Col [9] shows the maximum electricity that can be generated.
Where the output is 1200 kW, the units will be running at their rated output.
Otherwise output is restricted because of limited heat requirements.
Supplementary electricity must be imported – i.e.
Col[10] = col[5] – col[9]
CHP worked example
Month Temp (oC)
Space Heat Demand
(kW)
Total Heat
Demand (kW)
Electricitydemand
(kW)
CHP Heat
available (kW)
Useful CHP Heat (kW)
Supple-mentary
Heat (kW)
Actual Electricity Generated
Supple-mentary
Electricity Needed
[1] [2] [3] [4] [5] [6] [7] [8] [9] [10]Jan 1.9 3400 3500 1600 1680 1680 1820 1200 400Feb 4.5 2750 2850 1450 1680 1680 1170 1200 250Mar 9 1625 1725 1300 1680 1680 45 1200 100Apr 12 875 975 1200 1680 975 696*** 504May 14 375 475 1000 1400 475 339*** 661June 16 0 100 1000 1400 100 71*** 929July 17 0 100 1000 1400 100 71*** 929Aug 16 0 100 1000 1400 100 71*** 929Sep 13 625 725 1200 1680 725 518*** 682Oct 11 1125 1225 1350 1680 1225 875 475Nov 9 1625 1725 1450 1680 1680 45 1200 250Dec 4.1 2850 2950 1600 1680 1680 1270 1200 400Sum of numbers in column 16450 15150 19040 12100 4350 6875 6509
GWh GWh GWh GWh GWh GWh GWhequals numbers in red
* 30 *2411.84 10.91 13.71 8.71 3.13 4.95 4.69
Assumes number of days in each month is 30
Month Temp (oC)
Space Heat Demand
(kW)
Total Heat
Demand (kW)
Electricity (kW)
CHP Heat
available (kW)
Useful CHP Heat (kW)
Supple-mentary
Heat (kW)
Actual Electricity Generated
Supple-mentary
Electricity Needed
[1] [2] [3] [4] [5] [6] [7] [8] [9] [10]Jan 1.9 3400 3500 1600 1680 1680 1820 1200 400Dec 4.1 2850 2950 1600 1680 1680 1270 1200 400Sum of numbers in column 16450 15150 19040 12100 4350 6875 6509
GWh GWh GWh GWh GWh GWh GWhequals numbers in red
* 30 *2411.84 10.91 13.71 8.71 3.13 4.95 4.69
% heat supplied by CHP = 8.71/11.84 = 73.6%
Carbon Emissions – situation before installation
Total Demand
Efficiency CO2 factor
(tonnes/MWh)
CO2 (tonnes)
GWh
heating col [4] 11.84 0.8 0.186 2753
electricity col [5] 10.91 1 0.544 5935
total 22.75 8688
CHP worked example
Total Demand
Efficiency CO2 factor
(tonnes/MWh)
CO2
(tonnes)
GWh GWh
CHP heating [7] 8.71
CHP electricity [9] 4.95
Total CHP 13.66 0.8 0.186 3176
supplementary heating [8]
3.13 0.8 0.186 728
supplementary electricity [10]
4.69 1 0.544 872
4776
CHP worked exampleCarbon emissions before installation 8688 tonnes
Carbon emissions after installation: 4776 tonnes
Saving = 8688 – 4776 = 3911 tonnes or 45%
0
1
2
3
4
5
6
7
8
9
0 1 2 3 4 5 6 7 8 9 10 11 12
3 units
7.3 units
Gradient of Line = 3/7.3 = 0.411
Month Total Heat
Demand (kW)
Electricity (kW)
Potential CHP Heat available
(kW)
Useful CHP Heat
(kW)
Supple-mentary
Heat (kW)
Actual Electricity Generated
(kW)
Supple-mentary
Electricity Needed (kW)
[1] [4] [5] [6] [7] [8] [9] [10]
Jan 3500 1600 1680 1680 1820 1200 400
Feb 2850 1450 1680 1680 1170 1200 250
Mar 1725 1300 1680 1680 45 1200 100
Apr 975 1200 1680 975 696*** 504
May 475 1000 1400 475 339*** 661
June 100 1000 1400 100 71*** 929
July 100 1000 1400 100 71*** 929
Aug 100 1000 1400 100 71*** 929
Sep 725 1200 1680 725 518*** 682
Oct 1225 1350 1680 1225 875 475
Nov 1725 1450 1680 1680 45 1200 250
Dec 2950 1600 1680 1680 1270 1200 400
CHP worked example