nfpa 92a - شرکت همیار انرژیhamyarenergy.com/static/fckimages/files/nfpa/hamyar energy...

Download NFPA 92A - شرکت همیار انرژیhamyarenergy.com/static/fckimages/files/NFPA/Hamyar Energy NFPA 9… · NFPA 92A Standard for Smoke ... testing, operation ... 1.3.1 This

If you can't read please download the document

Upload: ngohuong

Post on 06-Feb-2018

341 views

Category:

Documents


128 download

TRANSCRIPT

  • CopyrightNFPA

    NFPA92AStandardfor

    SmokeControlSystemsUtilizingBarriersandPressure

    Differences

    2006Edition

    Copyright2005,NationalFireProtectionAssociation,AllRightsReserved

    ThiseditionofNFPA92A,StandardforSmokeControlSystemsUtilizingBarriersandPressureDifferences,waspreparedbytheTechnicalCommitteeonSmokeManagementSystemsandactedonbyNFPAatitsJuneAssociationTechnicalMeetingheldJune610,2005,inLasVegas,NV.ItwasissuedbytheStandardsCouncilonJuly29,2005,withaneffectivedateofAugust18,2005,andsupersedesallpreviouseditions.

    ThiseditionofNFPA92AwasapprovedasanAmericanNationalStandardonAugust18,2005.

    OriginandDevelopmentofNFPA92A

    TheNFPAStandardsCouncilestablishedtheTechnicalCommitteeonSmokeManagementSystemsinOctoberof1985andchargeditwithaddressingtheneedforguidelinesandmaterialsonbuildingfiresmokemanagement.WithhelpfromaformersubcommitteeonsmokecontroloftheTechnicalCommitteeonAirConditioning,memberswereappointedtotheSmokeManagementSystemsCommitteein1986.Asafirstattemptataddressingsmokemanagement,adraftwaspreparedofanewdocument,NFPA92A,thataddressedsmokecontrolutilizingbarriers,airflows,andpressuredifferencessoastoconfinethesmokeofafiretothezoneoffireoriginandthusmaintainatenableenvironmentinotherzones.

    The1993editionhelpedtorefinethescienceandartofsmokecontrolbyincorporatingthelatestintechnology.The1996editionaddedguidelinesoncontrolsystemsupervisionandinstrumentationitalsoprovidedsubstantialappendixmaterialontestingforleakageofsmokecontrolenclosures.

    The2000editionwasacompleterevisionandaddedinformationbasedonresearchonthedesignandtestingofsmokecontrolsystemsforareasofrefuge,elevatorlobbiesandhoistways,andvestibules.Achapteraddressingcomputermodelswasadded,andthecriteriaforcontrolsystemsandfirefighters'controlstationswasrefinedandclarified.

  • CopyrightNFPA

    The2006editionisamajorrevisionfromthepreviousedition.Thedocumenthasbeenrewrittenasastandardwithmandatoryprovisionsregardingthedesign,installation,andtestingofsmokecontrolsystemsprovided.ThedocumentalsohasbeenreorganizedtocomplywiththeManualofStyleforNFPATechnicalCommitteeDocuments.Additionally,othereditorialchangeshavebeenmadetoimprovetheapplicationofthestandard.Majortechnicalchangesaddresspowersuppliesforsmokecontrolsystems,openings,andleakagethroughsmokebarriers,includingegressdoorsinstairways,systemwiring,designdocumentation,testprocedures,andthezoningofelevatorshaftsandelevatorlobbies.

    TechnicalCommitteeonSmokeManagementSystems

    JamesA.Milke,ChairUniversityofMaryland,MD[SE]

    Elyahu(Elie)Avidor,Charlottesville,VA[RT]Rep.StandardsInstitutionofIsrael

    JosephA.Brooks,AirMovementandControlAssociationInternational,IL[M]

    JackB.Buckley,Houston,TX[SE]

    LydiaA.Butterworth,SmithsonianInstitution,DC[U]

    ChristopherS.Cahill,St.PaulDepartmentofFireandSafetyServices,MN[E]Rep.InternationalFireMarshalsAssociation

    PaulDavidCompton,ColtInternational,Ltd.,UK[M]

    RichardJ.Davis,FMGlobal,MA[I]

    MichaelEarlDillon,DillonConsultingEngineers,Inc.,CA[SE]

    RobertG.Dittrich,Honeywell,International,IL[M]Rep.NationalElectricalManufacturersAssociation

    DouglasH.Evans,ClarkCountyBuildingDepartment,NV[E]

    MichaelJ.Ferreira,HughesAssociates,Inc.,MD[SE]

    WinfieldT.Irwin,IrwinServices,PA[M]Rep.NorthAmericanInsulationManufacturersAssociation

    JohnE.Kampmeyer,TriadFireProtectionEngineeringCorporation,PA[SE]Rep.NationalSocietyofProfessionalEngineers

    JohnH.Klote,FireandSmokeConsulting,VA[SE]

  • CopyrightNFPA

    WilliamE.Koffel,KoffelAssociates,Inc.,MD[M]Rep.AAMASmokeVentTaskGroup

    GaryD.Lougheed,NationalResearchCouncilofCanada,Canada[RT]

    FranMcCabe,PrefcoProducts,PA[M]

    AnthonyJ.Militello,U.S.GeneralServicesAdministration,DC[U]

    LawrenceJ.Shudak,UnderwritersLaboratoriesInc.,IL[RT]

    PaulSimony,AcralightInternational,CA[M]

    JeffreyS.Tubbs,ArupFire,MA[SE]

    RandolphW.Tucker,TheRJAGroup,Inc.,TX[SE]

    PaulG.Turnbull,SiemensBuildingTechnology,Inc.,IL[M]

    RobertVanBecelaere,RuskinManufacturing,MO[M]Rep.AmericanSocietyofMechanicalEngineers

    StacyN.Welch,MarriottInternational,Inc.,DC[U]

    PeterJ.Willse,GEGlobalAssetProtectionServices,CT[I]

    StevenD.Wolin,CodeConsultants,Inc.,MO[SE]

    Alternates

    SanjayAggarwal,TheRJAGroup,Inc.,CA[SE](Alt.toR.W.Tucker)

    RobertM.Berhinig,UnderwritersLaboratoriesInc.,IL[RT](Alt.toL.J.Shudak)

    CraigL.Beyler,HughesAssociates,Inc.,MD[SE](Alt.toM.J.Ferreira)

    GregoryR.Miller,CodeConsultants,Inc.,MO[SE](Alt.toS.D.Wolin)

    RonaldA.Schulz,GEGlobalAssetProtectionServices,MI[I](Alt.toP.J.Willse)

    RickThornberry,TheCodeConsortium,Inc.,CA[M]

  • CopyrightNFPA

    (Alt.toW.E.Koffel)

    YibingXin,FMGlobal,MA[I](Alt.toR.J.Davis)

    Nonvoting

    E.G.Butcher,FireCheckConsultants,UK

    ChristianNorgaardMadsen,TechnoConsult,Norway(Alt.toNonvotingPrincipal)

    BentA.Borresen,TechnoConsult,Norway(MemberEmeritus)

    HaroldE.Nelson,HughesAssociates,Inc.,VA[SE]

    MiloshT.Puchovsky, NFPAStaffLiaison

    ThislistrepresentsthemembershipatthetimetheCommitteewasballotedonthefinaltextofthisedition.Sincethattime,changesinthemembershipmayhaveoccurred.Akeytoclassificationsisfoundatthebackofthedocument.

    NOTE:MembershiponacommitteeshallnotinandofitselfconstituteanendorsementoftheAssociationoranydocumentdevelopedbythecommitteeonwhichthememberserves.

    ThisCommitteeshallhaveprimaryresponsibilityfordocumentsonthedesign,installation,testing,operation,andmaintenanceofsystemsforthecontrol,removal,orventingofheatorsmokefromfiresinbuildings.

    NFPA92AStandardfor

    SmokeControlSystemsUtilizingBarriersandPressureDifferences2006Edition

    IMPORTANTNOTE:ThisNFPAdocumentismadeavailableforusesubjecttoimportantnoticesandlegaldisclaimers.ThesenoticesanddisclaimersappearinallpublicationscontainingthisdocumentandmaybefoundundertheheadingImportantNoticesandDisclaimersConcerningNFPADocuments.TheycanalsobeobtainedonrequestfromNFPAorviewedatwww.nfpa.org/disclaimers.

    NOTICE:Anasterisk(*)followingthenumberorletterdesignatingaparagraphindicatesthatexplanatorymaterialontheparagraphcanbefoundinAnnexA.

    Areferenceinbrackets[]followingasectionorparagraphindicatesmaterialthathasbeenextractedfromanotherNFPAdocument.Asanaidtotheuser,thecompletetitleandeditionofthesourcedocumentsforextractsinmandatorysectionsofthedocumentaregiveninChapter2andthoseforextractsininformationalsectionsaregiveninAnnexG.Editorialchangestoextractedmaterialconsistofrevisingreferencestoanappropriatedivisioninthis

  • CopyrightNFPA

    documentortheinclusionofthedocumentnumberwiththedivisionnumberwhenthereferenceistotheoriginaldocument.Requestsforinterpretationsorrevisionsofextractedtextshallbesenttothetechnicalcommitteeresponsibleforthesourcedocument.

    InformationonreferencedpublicationscanbefoundinChapter2andAnnexG.

    Chapter1Administration

    1.1Scope.

    Thisstandardshallapplytothedesign,installation,acceptancetesting,operation,andongoingperiodictestingofdedicatedandnondedicatedsmokecontrolsystems.

    1.2Purpose.

    1.2.1 Thepurposeofthisstandardshallbetoestablishrequirementsforsmokecontrolsystemsthatusepressuredifferencesacrossbarrierstoaccomplishoneormoreofthefollowing:

    (1) Inhibitsmokefromenteringstairwells,meansofegress,smokerefugeareas,elevatorshafts,orsimilarareas

    (2) Maintainatenableenvironmentinsmokerefugeareasandmeansofegressduringthetimerequiredforevacuation

    (3) Inhibitthemigrationofsmokefromthesmokezone

    (4) Provideconditionsoutsidethesmokezonethatenableemergencyresponsepersonneltoconductsearchandrescueoperationsandtolocateandcontrolthefire

    (5) Contributetotheprotectionoflifeandtothereductionofpropertyloss

    1.2.2 Therequirementsspecifyingtheconditionsunderwhichasmokecontrolsystemshallbeprovidedareaddressedbyothercodesandstandards.

    1.3Application.

    1.3.1 Thisstandardshallapplytodedicatedandnondedicatedsmokecontrolsystemsusingpressuredifferencestoinhibitsmokemovement.

    1.3.2* Thisstandardshallnotapplytosmokecontrolsystemsusingairflowtoinhibitsmokemovement,norshallitapplytopassivesystemsforsmokeandheatventing.

    1.3.3* Therequirementsforstandbypowerareoutsidethescopeofthisdocument.

    1.4Retroactivity.

    1.4.1 Unlessotherwisenoted,itisnotintendedthattheprovisionsofthisdocumentbeappliedtofacilities,equipment,structures,orinstallationsthatwereexistingorapprovedforconstructionorinstallationpriortotheeffectivedateofthisdocument.

    1.4.2 Inthosecaseswhereitisdeterminedbytheauthorityhavingjurisdictionthatthe

  • CopyrightNFPA

    existingsituationinvolvesadistincthazardtolifeorproperty,retroactiveapplicationoftheprovisionsofthisdocumentshallbepermitted.

    1.4.3 Whereasmokecontrolsystemisbeingaltered,extended,orrenovated,therequirementsofthisstandardshallapplyonlytotheworkbeingundertaken.

    1.4.4 Verificationisrequiredtoassurethatnewormodifiedsystemsdonotadverselyaffecttheperformanceofexistingsmokecontrolsystems.

    1.5Equivalency.

    Nothinginthisstandardisintendedtopreventtheuseofsystems,methods,ordevicesofequivalentorsuperiorquality,strength,fireresistance,effectiveness,durability,andsafetyoverthoseprescribedbythisstandard.

    1.5.1 Technicaldocumentationshallbesubmittedtotheauthorityhavingjurisdictiontodemonstrateequivalency.

    1.5.2 Thesystem,method,ordeviceshallbeapprovedfortheintendedpurposebytheauthorityhavingjurisdiction.

    1.6UnitsandFormulas.

    (Reserved)

    Chapter2ReferencedPublications

    2.1General.

    Thedocumentsorportionsthereoflistedinthischapterarereferencedwithinthisstandardandshallbeconsideredpartoftherequirementsofthisdocument.

    2.2NFPAPublications.

    NationalFireProtectionAssociation,1BatterymarchPark,Quincy,MA021697471.

    NFPA70,NationalElectricalCode,2005edition.

    NFPA72,NationalFireAlarmCode,2002edition.

    NFPA90A,StandardfortheInstallationofAirConditioningandVentilatingSystems,2002edition.

    NFPA 101,LifeSafetyCode,2006edition.

    NFPA110,StandardforEmergencyandStandbyPowerSystems,2005edition.

    NFPA221,StandardforHighChallengeFireWalls,FireWalls,andFireBarrierWalls,2006edition.

    2.3OtherPublications.

  • CopyrightNFPA

    2.3.1ULPublication.

    UnderwritersLaboratoriesInc.,333PfingstenRoad,Northbrook,IL600622096.

    UL555S,StandardforSmokeDampers,2002.

    2.3.2OtherPublication.

    MerriamWebster'sCollegiateDictionary,11thedition,MerriamWebster,Inc.,Springfield,MA,2003.

    2.4ReferencesforExtractsinMandatorySections.

    NFPA92B,StandardforSmokeManagementSystemsinMalls,Atria,andLargeSpaces,2005edition.

    NFPA318,StandardfortheProtectionofSemiconductorFabricationFacilities,2006edition.

    Chapter3Definitions

    3.1General.

    Thedefinitionscontainedinthischaptershallapplytothetermsusedinthisstandard.Wheretermsarenotdefinedinthischapterorwithinanotherchapter,theyshallbedefinedusingtheirordinarilyacceptedmeaningswithinthecontextinwhichthey areused.MerriamWebster'sCollegiateDictionary,11thedition,shallbethesourcefortheordinarilyacceptedmeaning.

    3.2NFPAOfficialDefinitions.

    3.2.1*Approved.Acceptabletotheauthorityhavingjurisdiction.

    3.2.2*AuthorityHavingJurisdiction(AHJ).Anorganization,office,orindividualresponsibleforenforcingtherequirementsofacodeorstandard,orforapprovingequipment,materials,aninstallation,oraprocedure.

    3.2.3Shall.Indicatesamandatoryrequirement.

    3.2.4Should.Indicatesarecommendationorthatwhichisadvisedbutnotrequired.

    3.2.5Standard.Adocument,themaintextofwhichcontainsonlymandatoryprovisionsusingthewordshalltoindicaterequirementsandwhichisinaformgenerallysuitableformandatoryreferencebyanotherstandardorcodeorforadoptionintolaw.Nonmandatoryprovisionsshallbelocatedinanappendixorannex,footnote,orfineprintnoteandarenottobeconsideredapartoftherequirementsofastandard.

    3.3GeneralDefinitions.

    3.3.1CompensatedSystem.Asystemthatadjustsforchangingconditionseitherbymodulatingsupplyairflowsorbyrelievingexcesspressure.

  • CopyrightNFPA

    3.3.2*DesignPressureDifference.Thedesiredpressuredifferencebetweentheprotectedspaceandanadjacentspacemeasuredattheboundaryoftheprotectedspaceunderaspecifiedsetofconditionswiththesmokecontrolsystemoperating.

    3.3.3EndtoEndVerification.Aselftestingmethodthatprovidespositiveconfirmationthatthedesiredresult(e.g.,airflowordamperposition)hasbeenachievedwhenacontrolleddevicehasbeenactivated,suchasduringsmokecontrol,testing,ormanualoverrideoperations.

    3.3.4*FireFighters'SmokeControlStation(FSCS).Asystemthatprovidesgraphicalmonitoringandmanualoverridingcapabilityoversmokecontrolsystemsandequipmentatdesignatedlocation(s)withinthebuildingfortheuseofthefiredepartment.

    3.3.5MultipleInjectionPressurizationSystem.Atypeofsmokecontrolsystemthathaspressurizationairsuppliedfrommultiplelocations.

    3.3.6PressurizedStairwells.Atypeofsmokecontrolsysteminwhichstairshaftsaremechanicallypressurized,withrespecttothefirearea,withoutdoorairtokeepsmokefromcontaminatingthemduringafireincident.

    3.3.7SingleInjectionPressurizationSystem.Atypeofsmokecontrolsystemthathaspressurizationairsuppliedfromonlyonelocation.

    3.3.8Smoke.Theairbornesolidandliquidparticulatesandgasesevolvedwhenamaterialundergoespyrolysisorcombustion,togetherwiththequantityofairthatisentrainedorotherwisemixedintothemass.[318,2006]

    3.3.9*SmokeBarrier.Forthepurposesofthisstandard,acontinuousmembrane,eitherverticalorhorizontal,suchasawall,floor,orceilingassembly,thatisdesignedandconstructedtorestrictthemovementofsmokeinconjunctionwithasmokecontrolsystem.

    3.3.10SmokeControlMode.Apredefinedoperationalconfigurationofasystemordeviceforthepurposeofsmokecontrol.

    3.3.11SmokeControlSystem.Anengineeredsystemthatusesmechanicalfanstoproducepressuredifferencesacrosssmokebarrierstoinhibitsmokemovement.

    3.3.11.1*DedicatedSmokeControlSystem.Smokecontrolsystemsandcomponentsthatareinstalledforthesolepurposeofprovidingsmokecontrol,anduponactivationthesesystemsoperatespecificallytoperformthesmokecontrolfunction.

    3.3.11.2*NondedicatedSmokeControlSystems.Smokecontrolsystemsandcomponentsthatsharecomponentswithsomeothersystem(s),suchasthebuildingHVACsystem,anduponactivationcausetheHVACsystemtochangeitsmodeofoperationinordertoachievethesmokecontrolobjectives.

    3.3.12SmokeControlZone.Aspacewithinabuildingenclosedbysmokebarriers,includingthetopandbottom,thatispartofazonedsmokecontrolsystem.

    3.3.13*SmokeExhaustSystem.Amechanicalorgravitysystemintendedtomovesmokefromthesmokezonetotheexteriorofthebuilding,includingsmokeremoval,purging,andventingsystems,aswellasthefunctionofexhaustfansutilizedtoreducethepressureina

  • CopyrightNFPA

    smokezone.

    3.3.14SmokeRefugeArea.Anareaofthebuildingseparatedfromotherspacesbyfireresistanceratedsmokebarriersinwhichatenableenvironmentismaintainedfortheperiodoftimethatsuchareasmightneedtobeoccupiedatthetimeoffire.

    3.3.15SmokeZone.Thesmokecontrolzoneinwhichthefireislocated.

    3.3.16StackEffect.Theverticalairflowwithinbuildingscausedbythetemperaturecreateddensitydifferencesbetweenthebuildinginteriorandexteriororbetweentwointeriorspaces.[92B,2005]

    3.3.17*TenableEnvironment.Anenvironmentinwhichsmokeandheatarelimitedorotherwiserestrictedtomaintaintheimpactonoccupantstoalevelthatisnotlifethreatening.[92B,2005]

    3.3.18ZonedSmokeControlSystem.Asmokecontrolsystemthatincludessmokeexhaustforthesmokezoneandpressurizationforallcontiguoussmokecontrolzones.

    Chapter4Fundamentals

    4.1DesignObjectives.

    4.1.1 Thedesignobjectivesshallincludeestablishmentandmaintenanceofpressuredifferencesacrosssmokezoneboundaries.

    4.1.2* Thedesignobjectivestobeachievedoverthedesignintervaltimebyasmokecontrolsystemshallincludeoneormoreofthefollowing:

    (1) Containingthesmoketothezoneoffireorigin

    (2) Maintainingatenableenvironmentwithinexitstairwellsforthetimenecessarytoallowoccupantstoexitthebuilding

    (3) Maintainingatenableenvironmentwithinallexitaccessandsmokerefugeareaaccesspathsforthetimenecessarytoallowoccupantstoreachanexitorsmokerefugearea

    (4) Otherperformancebaseddesignobjectivesacceptabletotheauthorityhavingjurisdiction

    4.2DesignBasis.

    4.2.1* Thedesignpressuredifferenceforthesmokecontrolsysteminagivenbuildingshallbebasedonthefollowingparameters:

    (1) Whetherthesmokezoneissprinklered

    (2) Theheightoftheceilinginthesmokezone

    4.2.2TemperatureRatings.

    4.2.2.1 Thetemperatureratingsfortheequipmentusedforsmokecontrolshallbebasedon

  • CopyrightNFPA

    theexpectedtemperatureexperiencedbytheequipmentwhiletheequipmentisintendedtobeoperational.

    4.2.2.2 Temperatureratingsshallbebasedonthefollowing:

    (1) Proximitytothefire

    (2) Effectsofdilutionofthesmokeandhotgasesbyentrainedair

    4.3DesignApproaches.

    Thedesignapproachforsmokecontrolsystemsshallbeoneoracombinationofthefollowing:

    (1) Stairwellpressurization

    (2) Zonedsmokecontrol

    (3) Elevatorsmokecontrol

    (4) Vestibules

    (5) Smokerefugeareas

    4.4*Tenability.

    Forsmokecontrolsystemsdesignedtomaintaintenabilityofaportionofspace,thedesignshallbebasedonmaintainingpressuresintheprotectedspaceatthespecifiedlevelwithrespecttoadjacentcontaminatedspaces.

    4.5*EgressAnalysis.

    Wherethedesignofthesmokecontrolsystemisbasedonoccupantsexitingaspacebeforebeingexposedtosmokeorbeforetenabilitythresholdsarereached,thereshallbesufficienttimeforthemovementoftheoccupantasdeterminedbyatimedegressanalysis.

    4.6DesignConsiderations.

    4.6.1*OpeningsandLeakageAreas.Designsshallincorporatetheeffectofopeningsandleakageareasinsmokebarriersontheperformanceofthesmokecontrolsystem.

    4.6.2*WeatherData.Designsshallincorporatetheeffectofoutdoortemperatureandwindontheperformanceofthesmokecontrolsystem.

    4.6.3PressureDifferences.Themaximumandminimumallowablepressuredifferencesacrosstheboundariesofsmokecontrolzonesshallbeestablished.

    4.6.3.1 Themaximumallowablepressuredifferenceshallnotresultindooropeningforcesexceedingtherequirementsof 5.2.2.

    4.6.3.2 Theminimumallowablepressuredifferenceshallrestrictsmokeleakageduringbuildingevacuationtoalevelthatmaintainsatenableenvironmentinareasoutsidethesmokezone.

    4.6.3.3 Theminimumpressuredifferenceshallbeestablishedatalevelthatishighenough

  • CopyrightNFPA

    thatitwillnotbeovercomebytheforcesofwind,stackeffect,orbuoyancyofhotsmoke.

    4.6.4*NumberofDoorsOpen.Thecalculationsshalltakeintoaccountthenumberofdoorsthatcouldbeopenedsimultaneously.(Forstairwellpressurizationsystems,see5.3.6.2.)

    4.7*GaseousFireSuppressionSystems.

    Theoperationofthesmokecontrolsystemshallnotcompromisetheperformanceofgaseousagentfireprotectionsystems.

    Chapter5SmokeControlSystemsandApplicability

    5.1*SystemOperation.

    5.1.1 Smokecontrolsystemsdesignedfortenabilityshallremaineffectiveforthetimeperiodnecessaryforevacuationoftheprotectedareas.

    5.1.2 Smokecontrolsystemsdesignedforotherconsiderationsshallremaineffectiveforthetimedictatedbytheapplication.

    5.2PressureDifferences.

    5.2.1*PressureDifferencesAcrossBarriers.

    5.2.1.1 Exceptasspecifiedby 5.2.1.2,thepressuredifferencesin Table5.2.1.1shallbeusedfordesignsthatarebasedonmaintainingminimumpressuredifferencesbetweenspecifiedspaces.

    Table5.2.1.1MinimumDesignPressureDifferencesAcrossSmokeBarriers

    BuildingTypeCeilingHeight

    (ft)

    DesignPressureDifference*(in.w.g.)

    AS Any 0.05NS 9 0.10NS 15 0.14NS 21 0.18

  • CopyrightNFPA

    Table5.2.1.1MinimumDesignPressureDifferencesAcrossSmokeBarriers

    BuildingTypeCeilingHeight

    (ft)

    DesignPressureDifference*(in.w.g.)

    ForSIunits,1ft=0.305m0.1in.w.g.=25Pa.AS:Sprinklered.NS:Nonsprinklered.Notes:(1)Thetablepresentsminimumdesignpressuredifferencesdevelopedforagastemperatureof1700F(927C)nexttothesmokebarrier.(2)Fordesignpurposes,asmokecontrolsystemshallmaintaintheseminimumpressuredifferencesunderspecifieddesignconditionsofstackeffectorwind.*Forzonedsmokecontrolsystems,thepressuredifferenceshallbemeasuredbetweenthesmokezoneandadjacentspaceswhiletheaffectedareasareinthesmokecontrolmode.

    5.2.1.2 Wherethesystemdesignerhasdeterminedthatahigherminimumpressuredifferenceisnecessarytoachievethesmokecontrolobjectives,thehigherminimumpressuredifferenceshallbeused.

    5.2.2*PressureDifferencesAcrossDoors.Thepressuredifferencesacrossdoorsshallnotcausethemaximumforcepermittedtobeginopeningthedoortoexceedthevaluestipulatedin NFPA 101,LifeSafetyCode,orlocalcodesandregulations.

    5.3StairwellPressurizationSystems.

    5.3.1*General.Thepressuredifferencebetweenthesmokezoneandthestairwellshallbeasfollows:

    (1) Notlessthantheminimumpressuredifferencespecifiedin 5.2.1

    (2) Notgreaterthanthemaximumpressuredifferencespecifiedin 5.2.2withthenumberofdoorsbetweenzeroandthedesignnumberofdoorsopen

    5.3.2LocationofSupplyAirSource.

    5.3.2.1 Thestairwellpressurizationsystemdesignshalllimitsmokefromenteringthestairwellthroughthepressurizationfanintake.

    5.3.2.2* Thesupplyairintakeshallbeseparatedfromallbuildingexhausts,outletsfromsmokeshaftsandroofsmokeandheatvents,openventsfromelevatorshafts,andotherbuildingopeningsthatmightexpelsmokefromthebuildinginafire.

    5.3.3SupplyAirFans.

  • CopyrightNFPA

    5.3.3.1*PropellerFans.Rooforexteriorwallmountedpropellerfansshallbepermittedtobeusedinsingleinjectionsystems,providedthatwindshieldsareprovidedforthefan.

    5.3.3.2OtherTypesofFans.Centrifugalorinlineaxialfansshallbepermittedtobeusedinsingleormultipleinjectionsystems.

    5.3.4*SingleandMultipleInjectionSystems.

    5.3.4.1SingleInjectionSystems.

    5.3.4.1.1* Theairinjectionpointforasingleinjectionsystemshallbepermittedtobelocatedatanylocationwithinthestairwell.

    5.3.4.1.2* Designanalysisshallbeperformedforallsinglebottominjectionsystemsandforallothersingleinjectionsystemsforstairwellsinexcessof100ft(30.5m)inheight.

    5.3.4.2*MultipleInjectionSystems.Forsystemdesignswithinjectionpointsmorethanthreestoriesapart,adesignanalysisshallbeperformedtoensurethatlossofpressurizationairthroughopendoorsdoesnotleadtostairwellpressurizationbelowtheminimumdesignpressure.

    5.3.5Vestibules.

    5.3.5.1* Vestibulesshallnotberequiredbutshallbepermittedaspartofthebuildingsmokecontrolsystem.

    5.3.5.2* Wherevestibulesareprovided,eitherpressurizedornonpressurizedvestibulesshallbepermitted.

    5.3.6*Doors.

    5.3.6.1 Doorslocatedinsmokebarriersshallbeselfclosingorshallbearrangedtocloseautomaticallyupontheactivationofthesmokecontrolsystem.

    5.3.6.2* Stairwellpressurizationsystemsshallbedesignedtoachievetherequiredpressuredifferencewithasingledooropentotheinteriorofthebuilding.

    5.4*ElevatorSmokeControl.

    Whereelevatorsmokecontrolisrequired,aseparatezoneshallbeestablished.

    5.5*ZonedSmokeControl.

    5.5.1SmokeControlZones.

    5.5.1.1 Whenzonedsmokecontrolistobeused,thebuildingshallbedividedintosmokecontrolzones,witheachzoneseparatedfromtheothersbysmokebarriers.

    5.5.1.1.1* Asmokecontrolzoneshallbepermittedtoconsistofoneormorefloors.

    5.5.1.1.2 Afloorshallbepermittedtoconsistofoneormoresmokecontrolzones.

    5.5.1.2 Thezonedsmokecontrolsystemshallbedesignedsuchthatwhenzonedsmokecontrolisactive,thepressuredifferencesbetweentheadjacentnonsmokezonesandthe

  • CopyrightNFPA

    smokezonemeetorexceedtheminimumdesignpressuredifferencesgivenin 5.2.1,andatlocationswithdoors,thepressuredifferenceshallnotexceedthevaluesgivenin 5.2.2.

    5.5.2SmokeZoneExhaust.

    5.5.2.1 Thesmokezoneexhaustshalldischargetotheoutsideofthebuilding.

    5.5.2.2 Thesmokezoneexhaustshallbepermittedtobeeithermechanicalornaturalventilation.

    5.5.2.3 Designofthesmokezoneexhaustsystemshallincludeanengineeringanalysisofthestackandwindeffects.

    5.6*SmokeRefugeAreas.

    5.6.1 Anonsmokezoneofazonedsmokecontrolsystemshallbepermittedtobeusedasanareaintendedtoprotectoccupantsfortheperiodoftimeneededforevacuationortoprovideasmokerefugearea.

    5.6.2 Forareasofrefugeadjacenttostairwellsorelevators,provisionsshallbemadetopreventthelossofpressureorexcessivepressuresduetotheinteractionbetweenthesmokerefugeareasmokecontrolandtheshaftsmokecontrol.

    5.7*CombinationofSystems.

    Smokecontrolsystemsshallbedesignedsuchthatwheremultiplesmokecontrolsystemsoperatesimultaneously,eachsystemwillmeetitsindividualdesignobjectives.

    Chapter6BuildingEquipmentandControls

    6.1General.

    EquipmentandcontrolsusedforsmokecontrolpurposesshallbeinaccordancewithChapter6.

    6.2*Heating,Ventilating,andAirConditioning(HVAC)Equipment.

    6.2.1General.HVACequipmentusedforsmokecontrolpurposesshallbepermittedtobelocatedwithintheconditionedspace,withinadjacentspaces,orwithinremotemechanicalequipmentrooms.

    6.2.2OutsideAir.HVACsystemsusedforsmokecontrolpurposesshallbeprovidedwithoutsideairforpressurization.

    6.2.3 WheresupplyandreturnairsystemsareinterconnectedaspartofnormalHVACoperation,smokedampersshallbeprovidedtoseparatethesupplyandexhaustduringsmokecontroloperation.

    6.3SmokeDampers.

    Smokedampersusedtoprotectopeningsinsmokebarriersorusedassafetyrelateddampers

  • CopyrightNFPA

    inengineeredsmokecontrolsystemsshallbelistedandlabeledinaccordancewithUL555S,StandardforSmokeDampers.

    6.4Controls.

    6.4.1Coordination.Asinglecontrolsystemshallcoordinatethesmokecontrolfunctionsprovidedbythefirealarmsystem,firefighters'smokecontrolsystem,andanyotherrelatedsystemswiththeoperationofthebuildingHVACsystemsanddedicatedsmokecontrolequipment.

    6.4.2*HVACSystemControls.OperatingcontrolsoftheHVACsystemshallbedesignedormodifiedtoprovidethesmokecontrolmodewiththehighestpriorityoverallothercontrolmodes.

    6.4.3SmokeControlSystemActivationandDeactivation.

    6.4.3.1 Smokecontrolsystemsshallbeactivatedautomatically.

    6.4.3.2 Whereapprovedbytheauthorityhavingjurisdiction,manualactivationshallbepermitted.

    6.4.3.3 Whenoperatingundereitherautomaticormanualactivation,thesmokecontrolsystemshallbecapableofbeingmanuallyoverriddenandmanuallydeactivated.

    6.4.3.4* Smokecontrolsystemsshallbeautomaticallyactivatedinresponsetosignalsreceivedfromaspecificfiredetectiondeviceoracombinationoffiredetectiondevices.

    6.4.3.5ManualActivationandDeactivation.

    6.4.3.5.1* Manualactivationanddeactivationshallbepermittedtobeatacontrolleddevice,atalocalcontrolpanel,atthebuilding'smaincontrolcenter,oratthefirecommandstation.

    6.4.3.5.2* Manualfirealarmpullstationsshallnotbeusedtoactivatesmokecontrolsystemsthatrequireinformationonthelocationofthefire.

    6.4.3.5.3* Stairwellpressurizationsystemsorothersmokecontrolsystemswheretheresponseofthesystemisidenticalforallzonealarmsshallbepermittedtobeactivatedfromamanualfirealarmpullstation.

    6.4.3.6ResponseTime.

    6.4.3.6.1 Thesmokecontrolmodeshallbeinitiatedwithin10secondsafteranautomaticormanualactivationcommandisreceivedatthesmokecontrolsystem.

    6.4.3.6.2* Smokecontrolsystemsshallactivateindividualcomponents(e.g.,dampers,fans)inthesequencenecessarytopreventphysicaldamagetothefans,dampers,ducts,andotherequipment.

    6.4.3.6.3* Thetimenecessaryforindividualcomponentstoachievetheirdesiredstateoroperationalmodefromwhenthecomponentreceivesthesignalshallnotexceedthefollowingtimeperiods:

  • CopyrightNFPA

    (1) Fanoperationatthedesiredstate:60seconds

    (2) Completionofdampertravel:75seconds

    6.4.3.7*FireFighters'SmokeControlStation(FSCS).

    6.4.3.7.1 Afirefighters'smokecontrolstation(FSCS)shallbeprovidedforallsmokecontrolsystems.

    6.4.3.7.2 TheFSCSshallbeinstalledatalocationacceptabletotheauthorityhavingjurisdiction.

    6.4.3.7.3* TheFSCSshallprovidestatusindication,faultconditionindication,andmanualcontrolofallsmokecontrolsystemcomponents.

    6.4.3.7.4 Statusindicatorsandcontrolsshallbearrangedandlabeledtoconveytheintendedsystemobjectives.

    6.4.3.7.5 Operatorcontrols,statusindication,andfaultindicationshallbeprovidedforeachsmokecontrolzone,eachpieceofequipmentcapableofactivationforsmokecontrol,oracombinationoftheseapproaches.

    6.4.3.7.6 Positivestatusindication(onandoff)shallbeprovidedindividuallyorbyzoneinaccordancewith 6.4.3.7.5forthefollowing:

    (1) Dedicatedsmokecontrolsystemfans

    (2) Nondedicatedfansusedforsmokecontrolhavingacapacityinexcessof2000ft3/min(57m3/min)

    6.4.3.7.7* Onstatusshallbesensedbyapressuredifference,anairflowswitch,orsomeotherpositiveproofofairflow.

    6.4.3.7.8 Positivestatusindication(fullyopenandfullyclosed)ofdamperpositionshallbeprovidedifindividualcontrolsforthedamperareprovidedontheFSCS.

    6.4.3.7.9 ProvisionshallbeincludedfortestingthepilotlampsontheFSCSsmokecontrolpanel(s)bymeansofoneormoreLAMPTESTmomentarypushbuttonsorotherselfrestoringmeans.

    6.4.3.7.10 Diagramsandgraphicrepresentationsofthesystemshallbeused.

    6.4.3.7.11 TheFSCSshallhavethehighestprioritycontroloverallsmokecontrolsystemsandequipment.

    6.4.3.7.12 Wheremanualcontrolsforcontrolofsmokecontrolsystemsarealsoprovidedatotherbuildinglocations,thecontrolmodeselectedfromtheFSCSshallprevail.

    6.4.3.7.13 FSCScontrolshalloverrideorbypassotherbuildingcontrolssuchashandoffautoandstart/stopswitcheslocatedonfanmotorcontrollers,freezedetectiondevices,andductsmokedetectorsexceptasprovidedby 6.4.3.7.13.1.

    6.4.3.7.13.1 TheFSCSfancontrolcapabilityshallnotberequiredtobypasshandoffautoorstart/stopswitcheslocatedonmotorcontrollersofnondedicatedsmokecontrolsystem

  • CopyrightNFPA

    fans,wherebothofthefollowingconditionsexist:

    (1) Suchfanmotorcontrollersarelocatedinmechanicalorelectricalequipmentroomsorinotherareasaccessibleonlytoauthorizedpersonnel.

    (2) Theuseofsuchamotorcontrollerswitchtoturnafanonoroffwillcauseanoffnormalindicationatthebuilding'smaincontrolcenterduringnormalHVACorbuildingcontroloperationsofthenondedicatedfan.

    6.4.3.7.14 FSCScontrolshallnottakeprecedenceoverfiresuppression,electricalprotection,orpersonnelprotectiondevices.

    6.4.4ControlsforStairwellPressurizationSystems.Stairwellpressurizationsystemsshallbeasactivatedasdescribedin 6.4.4.1through 6.4.4.3.

    6.4.4.1*AutomaticActivation.Operationofanyzoneofthebuildingfirealarmsystemshallcauseallstairwellpressurizationfanstostartexceptasindicatedin 6.4.4.1.1.

    6.4.4.1.1 Whereanengineeringanalysisdeterminesthatoperationofallstairwellpressurizationfansisnotrequiredtoachievethedesignobjective,onlythestairwellpressurizationfansidentifiedduringtheanalysisshallberequiredtobeactivated.

    6.4.4.2SmokeDetection.

    6.4.4.2.1 Asmokedetectorshallbeprovidedintheairsupplytothepressurizedstairwell.

    6.4.4.2.2 Ondetectionofsmokeintheairsupply,thesupplyfan(s)shallbestopped.

    6.4.4.3ManualActivation.ManualactivationanddeactivationcontrolofthestairwellpressurizationsystemsshallbeprovidedattheFSCS.

    6.4.4.4ManualOverride.AmanualoverrideswitchshallbepermittedtobeprovidedattheFSCStorestartthestairwellpressurizationfan(s)aftershutdownfromthesmokedetector.

    6.4.5ControlsforZonedSmokeControlSystems.

    6.4.5.1General.Whenzonedsmokecontrolsystemsareprovided,theyshallbeactivatedasdescribedin 6.4.5.1.1and6.4.5.1.2.

    6.4.5.1.1AutomaticActivation.Zonedsmokecontrolsystemsshallbeautomaticallyactivatedinresponsetosignalsreceivedfromadeviceorcombinationofdevicesthatrespondstoproductsofcombustion.

    6.4.5.1.1.1* Whensignalsfromfirealarmsystemsareusedtoactivatethezonedsmokecontrolsystem(s),thefirealarmzonesshallbearrangedtocoincidewiththesmokecontrolzones.

    6.4.5.1.1.2 Whereanautomaticsmokedetectionsystemisusedtoautomaticallyactivateazonedsmokecontrolsystem,thesmokedetectionsystemshallbepermittedtobeoflimitedcoveragehavingspacinggreaterthan900ft2(84m2)perdetector.

    6.4.5.1.1.3 Whereanautomaticsmokedetectionsystemisusedtoautomaticallyactivateazonedsmokecontrolsystem,thelocationofsmokedetectorsandthezoningofthedetectorsshallbearrangedtodetectsmokebeforeitleavesthesmokezone.

  • CopyrightNFPA

    6.4.5.1.1.4 Whereawaterflowswitchorheatdetectorisusedtoactivateazonedsmokecontrolsystem,zoningofsuchsystemsshallcoincidewiththesmokecontrolzone.

    6.4.5.1.2ManualActivation.

    6.4.5.1.2.1* Zonedsmokecontrolsystemsshallnotbeactivatedfrommanualfirealarmpullstations.

    6.4.5.1.2.2 Firealarmpullstationsshallbepermittedtocausedoorsinsmokebarrierwallstoclose.

    6.4.5.1.2.3 Keyoperatedmanualswitcheslocatedwithinasmokezonethatareclearlymarkedtoidentifytheirfunctionshallbepermittedtomanuallyactivatethezone'ssmokecontrolsystem.

    6.4.5.1.2.4 ZonedsmokecontrolsystemsshallbecapableofbeingmanuallyactivatedfromtheFSCSbyswitchesclearlymarkedtoidentifythezoneandfunction.

    6.4.5.2*SequenceofControlandPriorities.Automaticactivation,manualactivation,andmanualdeactivationofzonedsmokecontrolsystemsshallbesubjecttothesequencesofcontrolandprioritiesgivenin 6.4.5.2.1,6.4.5.2.2,and6.4.5.2.3.

    6.4.5.2.1AutomaticActivation.Automaticactivationofsystemsandequipmentforzonedsmokecontrolshallhavethehighestpriorityoverallothersourcesofautomaticcontrolwithinthebuilding.

    6.4.5.2.1.1* Exceptasprovidedforin 6.4.5.2.1.2,whereequipmentusedforsmokecontrolisalsousedfornormalbuildingoperation,controlofthisequipmentshallbepreemptedoroverriddenasrequiredforsmokecontrol.

    6.4.5.2.1.2 Thefollowingcontrolsshallnotbeautomaticallyoverridden:

    (1) Staticpressurehighlimits

    (2) Ductsmokedetectorsonsupplyairsystems

    6.4.5.2.2ManualActivationandDeactivation.Manualactivationordeactivationofzonedsmokecontrolsystemsandequipmentshallhavepriorityoverautomaticactivationofsmokecontrolsystemsandequipment,aswellasoverallothersourcesofautomaticcontrolwithinthebuilding.

    6.4.5.2.3 Ifequipmentusedforzonedsmokecontrolissubjecttoautomaticactivationinresponsetoanalarmfromanautomaticfiredetectorofafirealarmsystem,orifsuchequipmentissubjecttoautomaticcontrolaccordingtobuildingoccupancyschedules,energymanagementstrategies,orothernonemergencypurposes,suchautomaticcontrolshallbepreemptedoroverriddenbymanualactivationordeactivationofthesmokecontrolequipment.

    6.4.5.2.4ManualControls.

    6.4.5.2.4.1 Manualcontrolsprovidedspecificallyformanualactivationordeactivationforsmokecontrolpurposesshallbeclearlymarkedtoindicatethezoneandfunctionserved.

  • CopyrightNFPA

    6.4.5.2.4.2 Manualcontrolsthataresharedforbothsmokecontrolfunctionsandotherbuildingcontrolpurposes,asinabuilding'smaincontrolcenter,shallfullycoverthesmokecontrolfunctionalityinoperationaldocumentationforthecontrolcenter.

    6.4.5.3*Schedule.Theequipmenttobeoperatedforeachautomaticallyactivatedsmokecontrolsystemconfigurationshallbefullydefinedintheprojectdocuments.

    6.4.5.4Sequence.Equipmentusedforsmokecontrolshallbeactivatedinthespecificsequencenecessarytominimizedamageorundesirableeffectsonductsorequipment.

    6.4.5.5*AutomaticResponsetoMultipleSignals.Intheeventthatsignalsarereceivedfrommorethanonesmokezone,thesystemshallcontinueautomaticoperationinthemodedeterminedbythefirstsignalreceivedexceptasprovidedforin 6.4.5.5.1.

    6.4.5.5.1* Forsystemsdesignedforoperationofmultiplezonesusingonlyheatactivateddetectiondevices,itshallbepermittedtoexpandthecontrolstrategytoaccommodateadditionalzones,uptothelimitsofthemechanicalsystemdesign.

    6.4.6*ControlSystemVerification.

    6.4.6.1 Everydedicatedsmokecontrolsystemandeachdedicatedsmokecontrolsubsysteminanondedicatedsmokecontrolsystemshallhaveameansofverifyingcorrectoperationwhenactivated.

    6.4.6.2 Verificationshallincludepositiveconfirmationofactuation,testing,manualoverride,andthepresenceofoperatingpowerdownstreamofallcircuitdisconnects.

    6.4.6.3 Failuretoreceivepositiveconfirmationafteractivationorcessationofsuchpositiveconfirmationwhilethesystemorsubsystemremainsactivatedshallresultinanoffnormalindicationatthesmokecontrolsystemwithin200seconds.

    6.4.6.4 Firealarmsignalingpathstothesmokecontrolsystemshallbemonitoredforintegrityinaccordancewith4.4.7.1of NFPA72,withtroubleannunciationprovidedattheFSCSexceptaspermittedby 6.4.6.4.1.

    6.4.6.4.1 Monitoringforintegrityshallnotberequiredwhentheinterconnectingwiringbetweenthefirealarmsystemandthesmokecontrolsystemislocatedwithin20ft(6.1m)ofeachotherwheretheconductorsareinstalledinconduitorequivalently protectedagainstmechanicalinjury.

    6.5EnergyManagement.

    Energymanagementsystems,particularlythosethatcyclesupply,return,andexhaustfansforenergyconservation,shallbeoverriddenwhentheircontroloroperationisinconflictwithasmokecontrolmode.

    6.6Materials.

    6.6.1 MaterialsusedforsystemsprovidingsmokecontrolshallconformtoNFPA90A,StandardfortheInstallationofAirConditioningandVentilatingSystems,andotherapplicableNFPAdocuments.

  • CopyrightNFPA

    6.6.2 Ductmaterialsshallbeselectedandductsshallbedesignedtoconveysmoke,withstandadditionalpressure(bothpositiveandnegative)bythesupplyandexhaustfanswhenoperatinginasmokecontrolmode,andmaintaintheirstructuralintegrityduringtheperiodforwhichthesystemisdesignedtooperate.

    6.6.3* Equipmentincluding,butnotlimitedto,fans,ducts,andbalancedampersshallbesuitablefortheirintendeduseandtheprobabletemperaturestowhichtheyarelikelytobeexposed.

    6.7ElectricServicesInstallation.

    6.7.1 Allelectricalinstallationsshallmeettherequirementsof NFPA70,NationalElectricalCode.

    6.7.2 Thesmokecontrolsystemshallbedesignedsothatlossofnormalpowerforaperiodofupto15minuteswillresultinthecomponentsautomaticallyperformingtheirfunctionuponrestorationofpower.

    6.7.3 Wherestandbypowerisprovidedinaccordancewith NFPA110,StandardforEmergencyandStandbyPowerSystems,thestandbypowersourceandrelatedtransferswitchesshallbeseparatedfromtransformersandswitchgearfortheprimarypowersupplyandenclosedinaroomwitha1hourfireresistanceratedfirebarrierwallinstalledinaccordancewith NFPA221,StandardforHighChallengeFireWalls,FireWalls,andFireBarrierWalls.

    Chapter7DesignDocumentation

    7.1*DocumentationRequired.

    Thefollowingdocumentsshallbegeneratedbythedesignerduringthedesignprocess:

    (1) Designreport

    (2) Operationsandmaintenancemanual

    7.1.1DesignReport.

    7.1.1.1 Thedesignreportshallprovidedocumentationofthesmokecontrolsystemasitistobeinstalled,aswellasthedesigncalculations.

    7.1.1.2 Thedesignreportshallincludethefollowingelements,ifapplicable:

    (1) Systempurpose

    (2) Systemdesignobjectives

    (3) Designapproach

    (4) Designassumptions(buildingheight,ambientconditions,relianceonotherfireprotectionsystems,leakage,etc.)

    (5) Locationofsmokezone(s)

  • CopyrightNFPA

    (6) Designpressuredifferences

    (7) Buildinguselimitationsthatariseoutofthesystemdesign

    (8) Designcalculations

    (9) Fanandductspecifications

    (10) Damperspecifications

    (11) Detailedinletorexhaustinletssiteinformation

    (12) Detailedmethodofactivation

    (13) Smokecontrolsystemoperationlogic

    (14) Systemcommissioningprocedures

    7.1.2*OperationsandMaintenanceManual.Theoperationsandmaintenancemanualshallprovidetherequirementstoensuretheproperoperationofthesystemoverthelifeofthebuilding.

    7.1.2.1 Theoperationsandmaintenancemanualshallincludethefollowing:

    (1) Theproceduresusedintheinitialcommissioningofthesystemaswellasthemeasuredperformanceofthesystematthetimeofcommissioning

    (2) Thetestingandinspectionrequirementsforthesystemandsystemcomponentsandtherequiredfrequencyoftesting(seeChapter8)

    (3) Thecriticaldesignassumptionsusedinthedesignandlimitationsonthebuildinganditsusethatariseoutofthedesignassumptionsandlimitations

    7.1.2.2 Copiesoftheoperationsandmaintenancemanualshallbeprovidedtotheownerandtheauthoritieshavingjurisdiction.

    7.1.2.3 Thebuildingownershallberesponsibleforallsystemtestingandshallmaintainrecordsofallperiodictestingandmaintenanceinaccordancewiththeoperationsandmaintenancemanual.

    7.1.2.4 Thebuildingownershallberesponsibleforlimitingtheuseofthespaceinamannerconsistentwiththelimitationsprovidedintheoperationsandmaintenancemanual.

    Chapter8Testing

    8.1*General.

    8.1.1 Eachsmokecontrolsystemshallbetestedagainstitsspecificdesigncriteria.

    8.1.2 TestingshallconfirmthatthedesignobjectivesdescribedinSection 4.1areachieved.

    8.2*PreliminaryBuildingInspections.

    8.2.1 Priortooperationalandacceptancetesting,completenessofbuildingconstruction

  • CopyrightNFPA

    shallbeverified.

    8.2.2 Thefollowingarchitecturalfeatures,whereapplicable,shallbeinspected:

    (1) Shaftintegrity

    (2) Firestopping

    (3) Doors/closers

    (4) Glazing

    (5) Partitionsandceilings

    8.3*OperationalTesting.

    8.3.1 Anoperationaltestofeachsmokecontrolsystemcomponentandsubsystemshallbeperformedpriortotheacceptancetest.

    8.3.2 Operationaltestsshallbeperformedpriortointerconnectionofindividualcomponentsandsubsystemstothesmokecontrolsystem.

    8.3.3 Smokecontrolsystemsoperationaltestingshallincludethefollowingsubsystemstotheextentthattheyaffecttheoperationofthesmokecontrolsystem:

    (1) Firealarmsystem

    (2) Energymanagementsystem

    (3) Buildingmanagementsystem

    (4) HVACequipment

    (5) Electricalequipment

    (6) Temperaturecontrolsystem

    (7) Normalpower

    (8) Standbypower

    (9) Automaticsuppressionsystems

    (10) Automaticoperatingdoorsandclosers

    (11) Dedicatedsmokecontrolsystems

    (12) Nondedicatedsmokecontrolsystems

    (13) Emergencyelevatoroperation

    8.4AcceptanceTesting.

    8.4.1*General.Acceptancetestingshalldemonstratethatthefinalintegratedsysteminstallationcomplieswiththespecifieddesignobjectivesandisfunctioningproperly.

    8.4.2*TestEquipment.Equipmentforacceptancetestingshallbeprovided.

  • CopyrightNFPA

    8.4.3*GeneralTestingProcedures.Acceptancetestingshallincludetheproceduresdescribedin 8.4.3.1through 8.4.3.8.

    8.4.3.1 Priortoacceptancetesting,allbuildingequipmentshallbeplacedinthenormaloperatingmode,includingequipmentthatisnotusedtoimplementsmokecontrol,suchasventilationforcommercialcookingoperations,toiletexhaust,elevatorshaftvents,elevatormachineroomfans,andsimilarsystems.

    8.4.3.2 Windspeed,direction,andoutsidetemperatureshallberecordedduringeachtest.

    8.4.3.3 Ifstandbypowerhasbeenprovidedfortheoperationofthesmokecontrolsystem,theacceptancetestingshallbeconductedonbothnormalandstandbypower.

    8.4.3.4 Whentestingoperationunderstandbypower,thenormalbuildingpowershallbeinterruptedatthemainservicedisconnecttosimulatetrueoperatingconditionsinthismode.

    8.4.3.5 Acceptancetestingshalldemonstratethatthecorrectoutputsareproducedforagiveninputforeachcontrolsequencespecified.

    8.4.3.6 Exceptasmodifiedby 8.4.3.6.1and8.4.3.6.2,thecompletesmokecontrolsequenceshallbetestedtoincludethefollowing:

    (1) Normalmode

    (2) Automaticsmokecontrolmodeforfirstalarm

    (3) Manualoverrideofnormalandautomaticsmokecontrolmodes

    (4) Returntonormal

    8.4.3.6.1 Testingoftheautomaticsmokecontrolmodeasindicatedin 8.4.3.6(2)shallnotberequiredwhenthismodeisnotincludedinthesystemdesign.

    8.4.3.6.2 Testingofthemanualoverridemodeasindicatedin 8.4.3.6(3)shallnotberequiredwhenthismodeisnotincludedinthesystemdesign.

    8.4.3.7* Acceptancetestsforthefirealarmsystemshallbepermittedtobeperformedinconjunctionwiththesmokecontrolsystemtests.

    8.4.3.8 Thetestmethodsdescribedin 8.4.4through 8.4.8shallbeusedtotestthesmokecontrolsubsystems.

    8.4.4StairwellPressurizationSystems.

    8.4.4.1General.

    8.4.4.1.1 Therequirementsin 8.4.4shallapplywherestairwellpressurizationistheonlysmokecontrolsysteminthebuilding.

    8.4.4.1.2 Wherestairwellpressurizationisusedincombinationwithzonedsmokecontrol,therequirementsof 8.4.8.1shallapply.

    8.4.4.1.3 Pressurizedstairwellvestibulesshallbetreatedasazoneinazonedsmokecontrolsystem.(See8.4.5.)

  • CopyrightNFPA

    8.4.4.2TestProcedures.

    8.4.4.2.1*HVACSystemTestingUnderNonSmokeControlConditions.

    8.4.4.2.1.1 WithallbuildingHVACsystemsinnormaloperation,thepressuredifferenceacrosseachstairwelldoorshallbemeasuredandrecordedwhilethedoorisclosed.

    8.4.4.2.1.2 WithallbuildingHVACsystemsinnormaloperation,theforcenecessarytoopeneachdoorshallalsobemeasuredandrecordedusingaspringtypescale.

    8.4.4.2.2HVACSystemTestingUnderSmokeControlConditions.

    8.4.4.2.2.1 Activationofthestairwellpressurizationsystem(s),asspecifiedinthedesignreportandoperationsandmaintenancemanualasspecifiedinChapter7,shallbeverifiedinresponsetoallmeansofactivation,bothautomaticandmanual.

    8.4.4.2.2.2 Whereautomaticactivationisrequiredinresponsetoalarmsignalsreceivedfromthebuilding'sfirealarmsystem,eachseparatealarmsignalshallbeinitiatedtoensurethatproperautomaticactivationoccurs.

    8.4.4.2.3*PressureTesting.

    8.4.4.2.3.1 Withthestairwellpressurizationsystemactivated,thepressuredifferenceacrosseachstairwelldoorshallbemeasuredandrecordedwithallinteriordoorsclosed.

    8.4.4.2.3.2 Iftheexteriordoorwouldnormallybeopenduringevacuation,itshallbeopenduringtesting.

    8.4.4.2.3.3 TheHVACsystemshallbeoffunlessthenormalmodeistoleavetheHVACsystemonduringsmokecontroloperations.

    8.4.4.2.3.4* Withthestairwellpressurizationsystemactivated,andthenumberofdoorsusedinthesystemdesignopen,thepressuredifferenceacrosseachremainingcloseddoorshallbemeasuredandrecorded.

    8.4.4.2.3.5 Nopressuredifferenceshallbelessthantheminimumdesignpressuredifferencesin Table5.2.1.1orthepressuresspecifiedinthedesigndocuments.

    8.4.4.2.4*ForceTesting.

    8.4.4.2.4.1 Withthestairwellpressurizationsystemactivated,theforcenecessarytoopeneachstairwelldoorshallbemeasuredandrecorded,usingaspringtypescale.

    8.4.4.2.4.2 Allotherstairwelldoorsshallbeclosedwhenthemeasurementsspecifiedin8.4.4.2.4.1aremade.

    8.4.4.2.4.3 Withthestairwellpressurizationsystemactivated,andthenumberofdoorsusedinthesystemdesignopen,theforcenecessarytoopeneachdoorshallbemeasuredusingaspringtypescaleandrecorded.

    8.4.4.2.4.4 Dooropeningforcesshallnotexceedthoseallowedbythebuildingcode.

    8.4.5*ZonedSmokeControlSystem.

  • CopyrightNFPA

    8.4.5.1NormalHVACMode.

    8.4.5.1.1 ThepressuredifferenceacrossallsmokecontrolzonesthatdivideabuildingfloorshallbemeasuredandrecordedwhiletheHVACsystemsservingthefloor'ssmokezonesareoperatingintheirnormal(nonsmokecontrol)modeandwhileallsmokebarrierdoorsthatseparatethefloorzonesareclosed.

    8.4.5.1.2 Onemeasurementshallbemadeacrosseachsmokebarrierdoororsetofdoors,andthedatashallclearlyindicatethehigherandlowerpressuresidesofthedoors.

    8.4.5.2SmokeControlMode,General.

    8.4.5.2.1 Activationofeachzonedsmokecontrolsysteminresponsetoallmeansofactivation,bothautomaticandmanual,asspecifiedinthedesignreportandoperationsandmaintenancemanualasspecifiedinChapter7,shallbeverifiedandrecorded.

    8.4.5.2.2 Whereautomaticactivationisrequiredinresponsetoalarmsignalsreceivedfromthebuilding'sfirealarmsystem,eachseparatealarmsignalshallbeinitiatedtoensurethatproperautomaticactivationofthecorrectzonedsmokecontrolsystemoccurs.

    8.4.5.2.3 Theproperoperationofallfans,dampers,andrelatedequipmentforeachseparatezonedsmokecontrolsystem,asoutlinedbytheprojectdocumentsreferencedin 6.4.5.3,shallbeverifiedandrecorded.

    8.4.5.3SmokeControlModeforEachSmokeControlZone.

    8.4.5.3.1 Eachseparatesmokecontrolzoneshallbeactivatedbyasimulatedfirealarminput.

    8.4.5.3.2 Thepressuredifferenceacrossallsmokebarriersthatseparatethesmokezonefromadjacentzonesshallbemeasuredandrecorded.

    8.4.5.3.3 Themeasurementsshallbemadewhileallsmokebarrierdoorsthatseparatethesmokezonefromtheotherzonesarefullyclosed.

    8.4.5.3.4 Onemeasurementshallbemadeacrosseachsmokebarrierorsetofdoors,andthedatashallclearlyindicatethehigherandlowerpressuresidesofthedoorsorbarriers.

    8.4.5.3.5 Doorsthathaveatendencytoopenslightlyduetothepressuredifferenceshallhaveonepressuremeasurementmadewhileheldclosedandanothermadewhilenotheldclosed.

    8.4.5.3.6* Testing,asdescribedin 8.4.5.3.1,shallcontinueuntilallfirealarminputshavebeenactivated.

    8.4.5.3.7PressureDifferences.

    8.4.5.3.7.1 Allpressuredifferencesshallbedocumented.

    8.4.5.3.7.2 Nopressuredifferenceshallbelessthantheminimumdesignpressuredifferencesin Table5.2.1.1orthepressuresspecifiedinthedesigndocuments.

    8.4.5.3.8 Dooropeningforcesshallbedocumented.

  • CopyrightNFPA

    8.4.6ElevatorSmokeControlSystems.

    8.4.6.1ElevatorHoistwayPressurizationSystems.

    8.4.6.1.1General.

    8.4.6.1.1.1 Therequirementsin 8.4.6.1shallapplywhereelevatorhoistwaypressurizationistheonlysmokecontrolsysteminthebuilding.

    8.4.6.1.1.2 Whereelevatorhoistwaypressurizationisusedincombinationwithzonedsmokecontrol,therequirementsof 8.4.8.3shallapply.

    8.4.6.1.2TestProcedures.

    8.4.6.1.2.1 Activationoftheelevatorpressurizationsystem(s),asdescribedinthedesigndocuments,shallbeverifiedinresponsetoallmeansofactivation,bothautomaticandmanual.

    8.4.6.1.2.2 Whereautomaticactivationisrequiredinresponsetoalarmsignalsreceivedfromthebuilding'sfirealarmsystem,eachseparatealarmsignalshallbeinitiatedtoensurethatproperautomaticactivationoccurs.

    8.4.6.1.2.3*PressureTesting.

    (A) Withtheelevatorpressurizationsystemactivated,thepressuredifferenceacrosseachelevatordoorwithallelevatordoorsclosedshallbemeasuredandrecorded.

    (B) Iftheelevatordoorontherecallfloorwouldnormallybeopenduringsystempressurization,itshallbeopenduringtesting.

    8.4.6.1.2.4 TheHVACsystemshallbeoffunlessthenormalmodeistoleavetheHVACsystemonduringsmokecontroloperations.

    8.4.6.1.2.5 Iftheelevatorpressurizationsystemhasbeendesignedtooperateduringelevatormovement,thetestsin 8.4.6.1.2.1through 8.4.6.1.2.4shallberepeatedundertheseconditions.

    8.4.6.2LobbyPressurizationSystems.

    8.4.6.2.1General.

    8.4.6.2.1.1 Therequirementsin 8.4.6.2shallapplywhereenclosedelevatorlobbypressurizationistheonlysmokecontrolsysteminthebuilding.

    8.4.6.2.1.2 Whereelevatorlobbypressurizationisusedincombinationwithzonedsmokecontrol,therequirementsof 8.4.8.3shallapply.

    8.4.6.2.1.3* Whereenclosedelevatorlobbiesarepressurizedbyanelevatorlobbypressurizationsystem,orwhereenclosedenclosedelevatorlobbiesreceivesecondarypressurizationfromtheelevatorhoistway,therequirementsof 8.4.5shallapply.

    8.4.6.2.2TestProcedures.

    8.4.6.2.2.1MeasurementEquipment.Withtheelevatorlobbypressurizationsystemactivated,theforcenecessarytoopeneachlobbydoorshallbemeasuredusingaspringtype

  • CopyrightNFPA

    scaleandrecorded.

    8.4.6.2.2.2PressureDifferences.

    (A) Allpressuredifferencesshallbedocumented.

    (B) NopressuredifferenceshallbelessthantheminimumdesignpressuredifferencesinTable5.2.1.1orthepressuresspecifiedinthedesigndocuments.

    8.4.6.2.2.3DoorOpeningForces.

    (A) Elevatorlobbydooropeningforcesshallbedocumented.

    (B) Elevatorlobbydooropeningforcesshallnotexceedthoseindicatedin 5.2.2.

    8.4.7SmokeRefugeArea.

    8.4.7.1 Asmokerefugeareashallbetreatedasazoneinazonedsmokecontrolsystem.

    8.4.7.2 Thetestsoutlinedin 8.4.5shallbeconducted.

    8.4.8CombinationofSmokeControlSystems.

    8.4.8.1*StairwellandZonedSmokeControlSystem.

    8.4.8.1.1 Thestairwellpressurizationsystemshallbeconsideredasonezoneinazonedsmokecontrolsystem.

    8.4.8.1.2 Thetestsoutlinedin 8.4.5,8.4.4.2.3,and8.4.4.2.4shallbeconducted.

    8.4.8.1.3 Alltestsshallbeconductedwithbothsystemsoperatinginresponsetoasimulatedfirealarminput.

    8.4.8.2SmokeRefugeAreaandZonedSmokeControlSystem.

    8.4.8.2.1 Asmokerefugeareashallbetreatedasaseparatezoneinazonedsmokecontrolsystem.

    8.4.8.2.2 Thetestsoutlinedin 8.4.5shallbeconducted.

    8.4.8.3ElevatorPressurizationandZonedSmokeControlSystem.

    8.4.8.3.1 Theelevatorpressurizationsystemshallbeconsideredasonezoneinazonedsmokecontrolsystem.

    8.4.8.3.2 Eachelevatorlobbyinanenclosedelevatorlobbypressurizationsystemshallbeconsideredasonezoneinazonedsmokecontrolsystem.

    8.4.8.3.3 Thetestsoutlinedin 8.4.5shallbeconducted.

    8.4.8.3.4 Thetestsoutlinedin 8.4.6.1shallbeconductedifahoistwaypressurizationsystemispresent.

    8.4.8.3.5 Thetestsoutlinedin 8.4.6.2shallbeconductedifalobbypressurizationsystemispresent.

    8.4.8.3.6 Thetestsoutlinedinboth 8.4.6.1and8.4.6.2shallbeconductedifbothsystems

  • CopyrightNFPA

    arepresent.

    8.5Modifications.

    8.5.1* Alloperationalandacceptancetestingshallbeperformedontheapplicablepartofthesystemwheneverthesystemischangedormodified.

    8.5.2 Ifthesmokecontrolsystemorthezoneboundarieshavebeenmodifiedsincethelasttest,acceptancetestingshallbeconductedontheportionmodified.

    8.6*PeriodicTesting.

    8.6.1 ThetestsinSection 8.6shallbeperformedonaperiodicbasistodeterminethattheinstalledsystemscontinuetooperateinaccordancewiththeapproveddesign.

    8.6.2 Thesystemshallbetestedinaccordancewith 8.6.4and8.6.5bypersonswhoarethoroughlyknowledgeableintheoperation,testing,andmaintenanceofthesmokecontrolsystems.

    8.6.3 Theresultsofthetestsshallbedocumentedandmadeavailableforinspection.

    8.6.4DedicatedSystems.

    8.6.4.1 Dedicatedsystemsshallbetestedatleastsemiannually.

    8.6.4.2 Thesmokecontrolsystemshallbeoperatedforeachcontrolsequenceinthecurrentdesigncriteria.

    8.6.4.3 Operationofthecorrectoutputsforeachgiveninputshallbeverified.

    8.6.4.4 Wherestandbypowerisprovided,testsshallalsobeconductedunderstandbypower.

    8.6.5NondedicatedSystems.

    8.6.5.1 Nondedicatedsystemsshallbetestedatleastannually.

    8.6.5.2 Thesmokecontrolsystemshallbeoperatedforeachcontrolsequenceinthecurrentdesigncriteria.

    8.6.5.3 Operationofthecorrectoutputsforeachgiveninputshallbeverified.

    8.6.5.4 Ifstandbypowerisprovided,testsshallalsobeconductedunderstandbypower.

    AnnexAExplanatoryMaterial

    AnnexAisnotapartoftherequirementsofthisNFPAdocumentbutisincludedforinformationalpurposesonly.Thisannexcontainsexplanatorymaterial,numberedtocorrespondwiththeapplicabletextparagraphs.

    A.1.3.2 Airflowatsufficientvelocitycanalsobeusedtorestrictsmokemovement.Thisprincipleismostcommonlyusedtocontrolsmokemovementthroughopenings.Theflowofairthroughtheopeningintothesmokezonemustbeofsufficientvelocitytolimitmigration

  • CopyrightNFPA

    ofsmokefromthatzonethroughsuchopenings.

    Althoughairflowcanbeusedtoinhibitsmokemovementthroughaspace,theflowratesneededtopreventsmokebackflowaresolargethatthereisconcernabouttheamountofcombustionairthatissuppliedtothefire.Whenairflowisusedtomanagesmokemovement,theflowofairthroughtheopeningintothesmokezonemustbeofsufficientvelocitytopreventsmokefromleavingthatzonethroughsuchopenings.Theairvelocitynecessarytoinhibitsmokemovementthroughlargeopeningsresultsinairquantitiesthataresufficienttosupportfiregrowthtoapproximately10timesthesizeoffiregrowthwithoutthisadditionalairflow.MoreinformationonfiregrowthcanbefoundintheSFPEHandbookofFireProtectionEngineering.

    RefertoNFPA92B,StandardforSmokeManagementSystemsinMalls,Atria,andLargeSpaces,forsystemsusingairflowtomaintaintenableconditionswithinlargezonesoffireorigin,suchasatriaandshoppingmalls.RefertoNFPA204,StandardforSmokeandHeatVenting,forpassivesystemsforsmokeandheatventing.

    A.1.3.3 Standbypowershouldbeconsideredforsmokecontrolsystemsandtheircontrolsystems.Normalelectricalpowerservingairconditioningsystemsgenerallyhassufficientreliabilityfornondedicatedzonedsmokecontrolsystems.

    A.3.2.1Approved.TheNationalFireProtectionAssociationdoesnotapprove,inspect,orcertifyanyinstallations,procedures,equipment,ormaterialsnordoesitapproveorevaluatetestinglaboratories.Indeterminingtheacceptabilityofinstallations,procedures,equipment,ormaterials,theauthorityhavingjurisdictionmaybaseacceptanceoncompliancewithNFPAorotherappropriatestandards.Intheabsenceofsuchstandards,saidauthoritymayrequireevidenceofproperinstallation,procedure,oruse.Theauthorityhavingjurisdictionmayalsorefertothelistingsorlabelingpracticesofanorganizationthatisconcernedwithproductevaluationsandisthusinapositiontodeterminecompliancewithappropriatestandardsforthecurrentproductionoflisteditems.

    A.3.2.2AuthorityHavingJurisdiction(AHJ).Thephraseauthorityhavingjurisdiction,oritsacronymAHJ,isusedinNFPAdocumentsinabroadmanner,sincejurisdictionsandapprovalagenciesvary,asdotheirresponsibilities.Wherepublicsafetyisprimary,theauthorityhavingjurisdictionmaybeafederal,state,local,orotherregionaldepartmentorindividualsuchasafirechieffiremarshalchiefofafirepreventionbureau,labordepartment,orhealthdepartmentbuildingofficialelectricalinspectororothershavingstatutoryauthority.Forinsurancepurposes,aninsuranceinspectiondepartment,ratingbureau,orotherinsurancecompanyrepresentativemaybetheauthorityhavingjurisdiction.Inmanycircumstances,thepropertyownerorhisorherdesignatedagentassumestheroleoftheauthorityhavingjurisdictionatgovernmentinstallations,thecommandingofficerordepartmentalofficialmaybetheauthorityhavingjurisdiction.

    A.3.3.2DesignPressureDifference.Protectedspacesincludethenonsmokezonesinazonedsmokecontrolsystem,thestairwellsinastairwellpressurizationsystem,asmokerefugearea,andtheelevatorshaftinanelevatorhoistwaysystem.

    A.3.3.4FireFighters'SmokeControlStation(FSCS).Otherfirefighters'systems(suchasvoicealarm,publicaddress,firedepartmentcommunication,andelevatorstatusand

  • CopyrightNFPA

    controls)arenotcoveredinthisdocument.

    A.3.3.9SmokeBarrier.Asmokebarriermightormightnothaveafireresistancerating.Suchbarriersmighthaveprotectedopenings.Smokebarriersasusedwithsmokecontrolsystemsdescribedinthisstandardcouldhaveopeningsprotectedeitherbyphysicalopeningprotectivesorbypressuredifferencescreatedbythesmokecontrolsystem.Smokebarriersdescribedinsomeothercodesandstandardsmightrequirethattheopeningsbeprotectedbyphysicalopeningprotectives.

    A.3.3.11.1DedicatedSmokeControlSystem.Dedicatedsmokecontrolsystemsareseparatesystemsofairmovinganddistributionequipmentthatdonotfunctionundernormalbuildingoperatingconditions.

    Advantagesofdedicatedsystemsincludethefollowing:

    (1) Modificationofsystemcontrolsafterinstallationislesslikely.

    (2) Operationandcontrolofthesystemisgenerallysimpler.

    (3) Relianceonorimpactbyotherbuildingsystemsislimited.

    Disadvantagesofdedicatedsystemsincludethefollowing:

    (1) Systemimpairmentsmightgoundiscoveredbetweenperiodictestsormaintenanceactivities.

    (2) Systemscanrequiremorephysicalspace.

    A.3.3.11.2NondedicatedSmokeControlSystems.Advantagesofnondedicatedsystemsincludethefollowing:

    (1) Impairmentstosharedequipmentrequiredfornormalbuildingoperationarelikelytobecorrectedpromptly.

    (2) Limitedadditionalspaceforsmokecontrolequipmentisnecessary.

    Disadvantagesofnondedicatedsystemsincludethefollowing:

    (1) Systemcontrolmightbecomeelaborate.

    (2) Modificationofsharedequipmentorcontrolscanimpairsmokecontrolfunctionality.

    A.3.3.13SmokeExhaustSystem.Maintenanceofatenableenvironmentinthesmokezoneisnotwithinthecapabilityofthesesystems.

    A.3.3.17TenableEnvironment.Itisnotexpectedthatatenableenvironmentwillbecompletelyfreeofsmoke.

    A.4.1.2 Inadditiontothedesignobjectiveslisted,smokecontrolsystemscanalsobeusedforthefollowingobjectives:

    (1) Allowingfiredepartmentpersonnelsufficientvisibilitytoapproach,locate,andextinguishafire

    (2) Limitingthespreadoftoxicgasesthatcanaffectbuildingoccupants

  • CopyrightNFPA

    (3) Limitingthespreadofproductsofcombustiontoprovideprotectionforbuildingcontents

    A.4.2.1 TheperformanceobjectiveofautomaticsprinklersinstalledinaccordancewithNFPA13,StandardfortheInstallationofSprinklerSystems,istoprovidefirecontrol,whichisdefinedasfollows:limitingthesizeofafirebydistributionofwatersoastodecreasetheheatreleaserateandprewetadjacentcombustibles,whilecontrollingceilinggastemperaturestoavoidstructuraldamage.Alimitednumberofinvestigationshavebeenundertakeninwhichfullscalefiretestswereconductedinwhichthesprinklersystemwaschallengedbutprovidedtheexpectedlevelofperformance(MadrzykowskiandVettori,1992Lougheed,Mawhinney,andO'Neill,1994).Theseinvestigationsindicatethat,forafirecontrolsituation,theheatreleaserateislimitedbutsmokecancontinuetobeproduced.However,thetemperatureofthesmokeisreducedandthepressuredifferencesprovidedinthisdocumentforsmokecontrolsystemsinfullysprinkleredbuildingsareconservative.Inaddition,withthereducedsmoketemperatures,thetemperaturerequirementforsmokecontrolcomponentsincontactwithexhaustgasescanbelimited.

    A.4.4 Tenabilitycanbeachievedthroughmethodsotherthanpressurization.SeeNFPA92B,StandardforSmokeManagementSystemsinMalls,Atria,andLargeSpaces,forothertypesofactivesmokecontrolsystemsorNFPA 101,LifeSafetyCode,forpassivesystemsandotherfiresafetyapproaches.

    A.4.5 Timedegressanalysisisoutsidethescopeofthisdocument.However,otherreferencesareavailablethatpresentanalyticalmethodsforuseinegressanalysis.(SeePrinciplesofSmokeManagementbyKloteandMilke.)

    A.4.6.1 Inthedesignofsmokecontrolsystems,airflowpathsmustbeidentifiedandevaluated.Someleakagepathsareobvious,suchasgapsaroundcloseddoors,opendoors,elevatordoors,windows,andairtransfergrilles.Constructioncracksinbuildingwallsandfloorsarelessobviousbutnolessimportant.Theflowareaofmostlargeopeningscanbecalculatedeasily.Theflowareaofconstructioncracksisdependentonworkmanshipforexample,howwelladoorisfittedorhowwellweatherstrippingisinstalled.Typicalleakageareasofconstructioncracksinwallsandfloorsofcommercialbuildingsarelistedin TableA.4.6.1.Doorsopenforshortperiodsoftimeresultinatransitionconditionthatisnecessaryinordertoprovideegressfromoraccesstothesmokezone.

    TableA.4.6.1TypicalLeakageAreasforWallsandFloorsofCommercialBuildings

    ConstructionElement Tightness AreaRatioa

    Exteriorbuildingwalls(includesconstructioncracksandcracksaroundwindowsanddoors)

    Tightb

    Averageb

    Looseb

    Verylooseb

    0.50104

    0.17103

    0.35103

    0.12102

    Stairwellwalls(includesconstructioncracks,butnotcracksaroundwindowsanddoors)

    Tightc

    Averagec

    Loosec

    0.14104

    0.111030.35103

  • CopyrightNFPA

    TableA.4.6.1TypicalLeakageAreasforWallsandFloorsofCommercialBuildings

    ConstructionElement Tightness AreaRatioa

    Elevatorshaftwalls(includesconstructioncracks,butnotcracksandgapsarounddoors)

    TightcAveragec

    Loosec

    0.18103

    0.84103

    0.18102

    Floors(includesconstructioncracksandgapsaroundpenetrations)

    Tightd

    Averagee

    Loosed

    0.66105

    0.52104

    0.17103aForawall,thearearatio istheareaoftheleakagethroughthewalldividedbythetotalwallarea.Forafloor,thearearatioistheareaoftheleakagethroughthefloordividedbythetotalareaofthefloor.bValuesbasedonmeasurementsofTamuraandShaw(1976)TamuraandWilson(1966)andShaw,Reardon,andCheung(1993).cValuesbasedonmeasurementsofTamuraandWilson(1966)andTamuraandShaw(1976b).dValuesextrapolatedfromaveragefloortightnessbasedonrangeoftightnessofotherconstructionelements.eValuesbasedonmeasurementsofTamuraandShaw(1978).

    A.4.6.2 Thetemperaturedifferencesbetweentheexteriorandinteriorofthebuildingcausestackeffectanddeterminethestackeffect'sdirectionandmagnitude.Thestackeffectmustbeconsideredwhenselectingexhaustfans.Theeffectoftemperatureandwindvelocityvarieswithbuildingheight,configuration,leakage,andopeningsinwallandfloorconstruction.OnesourceofweatherdataistheASHRAEHandbookofFundamentals,Chapter26,ClimaticDesignInformation.Itissuggestedthatthe99.6percentheatingdrybulb(DB)temperatureandthe0.4percentcoolingDBtemperaturebeusedasthewinterandsummerdesignconditions,respectively.Itisalsosuggestedthatthe1percentextremewindvelocitybeusedasthedesigncondition.Whereavailable,moresitespecificwinddatashouldbeconsulted.

    A.4.6.4 Thisnumberdependslargelyonthebuildingoccupancyandthetypeofsmokecontrolsystem.Insomesystems,doorsmostlikelyareopenforonlyshortperiodsoftimeandsmokeleakageisnegligible.Inothersystems,frequentegressfromthesmokezonecouldcauseatleastonedoortobeopenmostofthetime.

    A.4.7 Intheeventthatthesmokecontrolandthesuppressionsystemsareactivatedconcurrently,thesmokecontrolsystemmightdilutethegaseousagentinthespace.Becausegaseoussuppressionsystemscommonlyprovideonlyoneapplicationoftheagent,thepotentialarisesforrenewedgrowthofthefire.

    A.5.1 Thefollowingfactorsshouldbeconsideredindeterminingtheabilityofthesystemtoremaineffectiveforthetimeperiodnecessary:

    (1) Reliabilityofpowersource(s)

    (2) Arrangementofpowerdistribution

    (3) Methodandprotectionofcontrolsandsystemmonitoring

  • CopyrightNFPA

    (4) Equipmentmaterialsandconstruction

    (5) Buildingoccupancy

    A.5.2.1 Asmokecontrolsystemshouldbedesignedtomaintaintheminimumdesignpressuredifferencesunderlikelyconditionsofstackeffectorwind.Pressuredifferencesproducedbysmokecontrolsystemstendtofluctuateduetothewind,fanpulsations,doorsopening,doorsclosing,andotherfactors.Shorttermdeviationsfromthesuggestedminimumdesignpressuredifferencemightnothaveaseriouseffectontheprotectionprovidedbyasmokecontrolsystem.Thereisnoclearcutallowablevalueofthisdeviation.Itdependsontightnessofdoors,tightnessofconstruction,toxicityofsmoke,airflowrates,andthevolumesofspaces.Intermittentdeviationsupto50percentofthesuggestedminimumdesignpressuredifferenceareconsideredtolerablein mostcases.

    Theminimumdesignpressuredifferencesof Table5.2.1.1fornonsprinkleredspacesarevaluesthatwillnotbeovercomebybuoyancyforcesofhotgases.Themethodusedtoobtainthevaluesof Table5.2.1.1fornonsprinkleredspacesfollows.Thismethodcanbeusedifitisdesiredtocalculatepressuredifferencesforgastemperaturesotherthan1700F(927C).

    Thepressuredifferenceduetobuoyancyofhotgasesiscalculatedbythefollowingequation:

    where:

    P =pressuredifferenceduetobuoyancyofhotgases(in.w.g.)To=absolutetemperatureofsurroundings(R)TF=absolutetemperatureofhotgases(R)h=distanceaboveneutralplane(ft)

    where:

    P =pressuredifferenceduetobuoyancyofhotgases(Pa)To=absolutetemperatureofsurroundings(K)TF=absolutetemperatureofhotgases(K)h=distanceaboveneutralplane(m)

    Theneutralplaneisahorizontalplanebetweenthefirespaceandasurroundingspaceatwhichthepressuredifferencebetweenthefirespaceandthesurroundingspaceiszero.ForTable5.2.1.1,hwasconservativelyselectedattwothirdsofthefloortoceilingheight,thetemperatureofthesurroundingswasselectedat70F(20C),thetemperatureofthehotgaseswasselectedat1700F(927C),andasafetyfactorof0.03in.w.g.(7.5Pa)wasused.

    Forexample,calculatetheminimumdesignpressuredifferenceforaceilingheightof12ftas

  • CopyrightNFPA

    follows:

    Fromtheaboveequation, P =0.087in.w.g.Addingthesafetyfactorandroundingoff,theminimumdesignpressuredifferenceis0.12in.w.g.

    A.5.2.2 Theforcesonadoorinasmokecontrolsystemareillustratedin FigureA.5.2.2.Theforcerequiredtoopenadoorinasmokecontrolsystemisasfollows:

    where:

    F =totaldooropeningforce(lb)Fr=forcetoovercomethedoorcloserandotherfriction(lb)W =doorwidth(ft)A=doorarea(ft2)P =pressuredifferenceacrossthedoor(in.w.g.)

    d=distancefromthedoorknobtotheknobsideofthedoor(ft)

    FIGUREA.5.2.2ForcesonaDoorinaSmokeControlSystem.

    Whenthemaximumdooropeningforceisspecifiedat30lbf,TableA.5.2.2canbeusedtodeterminethemaximumpressuredifferenceacrossthedoor.

    TableA.5.2.2MaximumPressureDifferencesAcrossDoors

    DoorCloserForce*(lbf)

    DoorWidth(in.w.g.)32 36 40 44 48

    6 0.45 0.40 0.37 0.34 0.318 0.41 0.37 0.34 0.31 0.2810 0.37 0.34 0.30 0.28 0.2612 0.34 0.30 0.27 0.25 0.2314 0.30 0.27 0.24 0.22 0.21

  • CopyrightNFPA

    TableA.5.2.2MaximumPressureDifferencesAcrossDoors

    DoorCloserForce*(lbf)

    DoorWidth(in.w.g.)32 36 40 44 48

    ForSIunits,1lbf=4.4N1in.=25.4mm0.1in.w.g.=25Pa.Notes:(1)Totaldooropeningforceis30lbf.(2)Doorheightis7ft.(3)Thedistancefromthedoorknobtotheknobsideofthedooris3in.(4)Forotherdooropeningforces,otherdoorsizes,orhardwareotherthanaknobforexample,panichardwareusethecalculationprocedureprovidedinASHRAE/SFPEpublication,PrinciplesofSmokeManagement.*Manydoorclosersrequirelessforceintheinitialportionoftheopeningcyclethanthatrequiredtobringthedoortothefullyopenposition.Thecombinedimpactofthedoorcloserandtheimposedpressurecombineonlyuntilthedoorisopenedenoughtoallowairtopassfreelythroughtheopening.Theforceimposedbyaclosingdevicetoclosethedoorisoftendifferentfromthatimposedonopening.Doorwidthsapplyonlyifthedoorishingedatoneendotherwise,usethecalculationprocedureprovidedinASHRAE/SFPE,PrinciplesofSmokeManagement.

    A.5.3.1 SeeAnnex Bforinformationontypesofstairwellpressurizationsystems.

    A.5.3.2.2 Thisseparationshouldbeasgreatasispracticable.Becausehotsmokerises,considerationshouldbegiventolocatingsupplyairintakesbelowsuchcriticalopenings.However,outdoorsmokemovementthatmightresultinsmokefeedbackdependsonthelocationofthefire,thelocationofpointsofsmokeleakagefromthebuilding,thewindspeedanddirection,andthetemperaturedifferencebetweenthesmokeandtheoutsideair.

    A.5.3.3.1 Simplesinglepointinjectionsystemssuchasthatillustratedin FigureA.5.3.3.1canuserooforexteriorwallmountedpropellerfans.Theuseofpropellerfanswithoutwindshieldsisnotpermittedbecauseoftheextremeeffectwindcanhaveontheperformanceofsuchfans.

    FIGUREA.5.3.3.1StairwellPressurizationbyRoofMountedPropellerFan.

  • CopyrightNFPA

    Onemajoradvantageofusingpropellerfansforstairwellpressurizationisthattheyhavearelativelyflatpressureresponsecurvewithrespecttovaryingflow.Therefore,asdoorsareopenedandclosed,propellerfansquicklyrespondtoairflowchangesinthestairwellwithoutmajorpressurefluctuations.Asecondadvantageofusingpropellerfansisthattheyarelesscostlythanothertypesoffansandcanprovideadequatesmokecontrolwithlowerinstalledcosts.

    Adisadvantageofusingpropellerfansisthattheyoftenrequirewindshieldsattheintakebecausetheyoperateatlowpressuresandarereadilyaffectedbywindpressureonthebuilding.Thisislesscriticalonroofswherethefansareoftenprotectedbyparapetsandwherethedirectionofthewindisatrightanglestotheaxisofthefan.

    Propellerfansmountedonwallsposethegreatestsusceptibilitytotheadverseeffectsofwindpressures.Theadverseeffectisatamaximumwhenwinddirectionisindirectoppositiontothefanairflow,resultinginalowerintakepressureandthussignificantlyreducingfaneffectiveness.Windsthatarevariableinintensityanddirectionalsoposeathreattotheabilityofthesystemtomaintaincontroloverthestairwellstaticpressure.

    A.5.3.4 FigureA.5.3.4(a)andFigureA.5.3.4(b)aretwoexamplesofthemanypossiblemultipleinjectionsystemsthatcanbeusedtoovercomethelimitationsofsingleinjectionsystems.Thepressurizationfanscanbelocatedatgroundlevel,rooflevel,oratanylocationinbetween.

    FIGUREA.5.3.4(a)StairwellPressurizationbyMultipleInjectionwiththeFanLocatedatGroundLevel.

  • CopyrightNFPA

    FIGUREA.5.3.4(b)StairwellPressurizationbyMultipleInjectionwithRoofMountedFan.

    In FigureA.5.3.4(a)andFigureA.5.3.4(b),thesupplyductisshowninaseparateshaft.However,systemshavebeenbuiltthathaveeliminatedtheexpenseofaseparateductshaftbylocatingthesupplyductinthestairenclosureitself.Careshouldbetakensothattheductdoesnotreducetherequiredexitwidthorbecomeanobstructiontoorderlybuildingevacuation.

    A.5.3.4.1.1 Themostcommoninjectionpointisatthetopofthestairwell,asillustratedinFigureA.5.3.4.1.1.

    FIGUREA.5.3.4.1.1StairwellPressurizationbyTopInjection.

    A.5.3.4.1.2 Singleinjectionsystemscanfailwhenafewdoorsareopenneartheairsupplyinjectionpoint.Allthepressurizationaircanbelostthroughtheseopendoors,atwhichtimethesystemwillfailtomaintainpositivepressuresacrossdoorsfartherfromtheinjectionpoint.

    Becauseagroundlevelstairwelldoorislikelytobeintheopenpositionmuchofthetime,asinglebottominjectionsystemisespeciallypronetofailure.Carefuldesignanalysisisneededforallsinglebottominjectionsystemsandforallothersingleinjectionsystemsforstairwellsinexcessof100ft(30.5m)inheighttoensureproperpressurizationthroughoutthestairwell.

  • CopyrightNFPA

    A.5.3.4.2 Manymultipleinjectionsystemshavebeenbuiltwithsupplyairinjectionpointsoneachfloor.Thesesystemsrepresenttheultimateinpreventinglossofpressurizationairthroughafewopendoorshowever,thatmanyinjectionpointsmightnotbenecessary.Forsystemdesignswithinjectionpointsmorethanthreestoriesapart,thedesignershoulduseacomputeranalysissuchastheoneinASHRAE/SFPE,PrinciplesofSmokeManagement.Thepurposeofthisanalysisistoensurethatlossofpressurizationairthroughafewopendoorsdoesnotleadtosubstantiallossofstairwellpressurization.

    A.5.3.5.1 Stairwellsthatdonothavevestibulescanbepressurizedusingsystemscurrentlyavailable.Somebuildingsareconstructedwithvestibulesbecauseofbuildingcoderequirements.

    A.5.3.5.2 NonpressurizedVestibules.Stairwellsthathavenonpressurizedvestibulescanhaveapplicationsinexistingbuildings.Withbothvestibuledoorsopen,thetwodoorsinseriesprovideanincreasedresistancetoairflowcomparedtoasingledoor.Thisincreasedresistancewillreducetherequiredairflowsoastoproduceagivenpressureinthestairwell.ThissubjectisdiscussedindetailinASHRAE/SFPE,PrinciplesofSmokeManagement.

    Inbuildingswithlowoccupantloads,itispossiblethatoneofthetwovestibuledoorsmightbeclosed,oratleastpartiallyclosed,duringtheevacuationperiod.Thiswillfurtherreducetherequiredairflowtoproduceagivenpressure.

    PressurizedVestibules.Closingbothdoorstoavestibulecanlimitthesmokeenteringavestibuleandprovideatenableenvironmentasasmokerefugearea.Theadjacentstairwellisindirectlypressurizedbyairflowfromthepressurizedvestibule.However,thispressurizationcanbelostiftheexteriordoorisopen.Also,smokecanflowintothestairwellthroughanyleakageopeningsinthestairwellwallsadjacenttothefloorspace.Suchwallsshouldbeconstructedtominimizeleakagesforastairwellprotectedbyapressurizedvestibulesystem.

    PressurizedVestibulesandStairwells.Tominimizetheamountofsmokeenteringavestibuleandstairwell,boththevestibuleandstairwellcanbepressurized.Thecombinedsystemwillenhancetheeffectivenessofthestairwellpressurizationsystem.Also,thepressurizedvestibulecanprovideatemporarysmokerefugearea.

    PurgedorVentedVestibules.Purgedorventedvestibulesystemsfalloutsidethescopeofthisdocument.AhazardanalysiswouldberequiredusingtheproceduresprovidedintheSFPEHandbookofFireProtectionEngineering.Anengineeringanalysisshouldbeperformedtodeterminethebenefits,ifany,ofpressurizing,purging,orexhaustingvestibulesonthestairwell.

    A.5.3.6 Forastairwellpressurizationsystemthathasnotbeendesignedtoaccommodatetheopeningofdoors,pressurizationwilldropwhenanydoorsopen,andsmokecaninfiltratethestairwell.Forabuildingoflowoccupantdensity,theopeningandclosingofafewdoorsduringevacuationhaslittleeffectonthesystem.Forabuildingwithahighoccupantdensityandtotalbuildingevacuation,itcanbeexpectedthatmostofthedoorswillbeopenatsometimeduringevacuation.Themethodsprovidedin ASHRAE/SFPE,PrinciplesofSmokeManagement,canbeusedtodesignsystemstoaccommodateanywherefromafewopendoorstoalmostallthedoorsbeingopen.

  • CopyrightNFPA

    Duringthetimethatoccupantsofthesmokezoneareexitingthearea,theconditionsinthesmokezonearestilltenable.Althoughopeningthestairwelldooronthefirefloorduringthistimemightreleasesomesmokeintothestairwell,itwillnotcreateuntenableconditionsthere.Onceconditionsinthesmokezonebecomeuntenable,itisunlikelythatthedoortothefirefloorwouldbeopenedbyoccupantsofthatfloor.Forthisreason,designingforanopenstairwelldooronthefirefloorisnormally notrequired.Doorsblockedopeninviolationofapplicablecodesarebeyondthecapabilityofthesystem.

    A.5.3.6.2 Wherethebuildingegressstrategyanticipatesmultiplefloorstobeevacuatedsimultaneouslyorthedesignforthestairwellpressurizationsystemassumestheexitdoorisopen,thestairwellpressurizationsystemshouldbedesignedtoaccommodatemorethanonedooropen,atleastoneofwhichshouldbethedischargedoorfromthestair.

    Theeffectofopeningadoortotheoutsideisusuallymuchgreaterthanthatofopeninginteriordoors.Theimportanceoftheexteriorstairwelldoorcanbeexplainedbyconsideringtheconservationofmassofthepressurizationair.Thisaircomesfromtheoutsideandmusteventuallyflowbacktotheoutside.Foranopeninteriordoor,therestofthebuildingonthatflooractsasflowresistancetotheairflowingouttheopendoorway.Whentheexteriordoorisopen,thereisnootherflowresistance,andtheflowcanbe10to30timesmorethanthroughanopeninteriordoor.

    A.5.4 Ifelevatorsareintendedtobeusedforevacuationduringafire,theelevatorsystemshouldbeprotectedagainstheat,flame,smoke,lossofelectricalpower,lossofelevatormachineroomcooling,waterintrusion,andinadvertentactivationofcontrols.

    Historically,elevatorhoistwayshaveprovedtobeareadilyavailableconduitforthemovementofsmokethroughoutbuildings.Thereasonisthatelevatordoorshavenotbeentightfittingandelevatorhoistwayshavebeenprovidedwithopeningsintheirtops.Thebuildingstackeffecthasprovidedthedrivingforcethathasreadilymovedsmokeintoandoutofthelooselyconstructedelevatorhoistways.Severalmethodsofcorrectingthisproblemhavebeenproposedandinvestigated.Thesemethodsincludethefollowing:

    (1) Exhaustofthefirefloor

    (2) Pressurizationofenclosedelevatorlobbies

    (3) Constructionofsmoketightelevatorlobbies

    (4) Pressurizationoftheelevatorhoistway

    (5) Closingofelevatordoorsafterautomaticrecall

    (Note:Rule211.3a,PhaseIEmergencyRecallOperations,ofASME/ANSIA17.1,SafetyCodeforElevatorsandEscalators,requiresthatelevatordoorsopenandremainopenaftertheelevatorsarerecalled.Thisresultsinlargeopeningsintotheelevatorhoistways,whichcangreatlyincreasetheairflowrequiredforpressurization.NFPA80,StandardforFireDoorsandFireWindows,permitsclosingofelevatordoorsafterapredeterminedtimewhenrequiredbytheauthorityhavingjurisdiction.Localrequirementsonoperationofelevatordoorsshouldbedeterminedandincorporatedintothesystemdesign.)

    Themethodslistedin A.5.4(1)through A.5.4(5)havebeenemployedeithersinglyorin

  • CopyrightNFPA

    combination.However,theirapplicationtoaparticularproject,includingtheeffectofanyventsintheelevatorhoistway,shouldbecloselyevaluated.Theopenventatthetopoftheelevatorhoistwaycouldhaveanundesirableeffectonelevatorsmokecontrolsystems.

    Thefollowingreferencesdiscussresearchconcerningelevatoruseduringfiresituations:KloteandBraun(1996)Klote(1995)Klote,Levin,andGroner(1995)Klote,Levin,andGroner(1994)Klote(1993)Klote,Deal,Donoghue,Levin,andGroner(1993) andKlote,Alvord,Levin,andGroner(1992).

    A.5.5 ThepressurizedstairwellsdiscussedinSection 5.3areintendedtocontrolsmoketotheextentthattheyinhibitsmokeinfiltrationintothestairwell.However,inabuildingwithapressurizedstairwellasthesolemeansofsmokecontrol,smokecanflowthroughcracksinfloorsandpartitionsandthroughothershaftstothreatenlifeandtodamagepropertyatlocationsremotefromthefire.Theconceptofzonedsmokecontroldiscussedinthissectionisintendedtolimitthistypeofsmokemovementwithinabuilding.

    Limitingfiresize(massburningrate)increasesthereliabilityandviabilityofsmokecontrolsystems.Firesizecanbelimitedbyfuelcontrol,compartmentation,orautomaticsprinklers.Itispossibletoprovidesmokecontrolinbuildingsnothavingfirelimitingfeatures,butinthoseinstances,carefulconsiderationmustbegiventofirepressure,hightemperatures,massburningrates,accumulationofunburnedfuels,andotheroutputsresultingfromuncontrolledfires.

    A.5.5.1.1.1 Arrangementsofsomesmokecontrolzonesareillustratedin FigureA.5.5.1.1.1.

    FIGUREA.5.5.1.1.1ArrangementsofSmokeControlZones.

  • CopyrightNFPA

    In FigureA.5.5.1.1.1,thesmokezoneisindicatedbyaminussignandpressurizedspacesareindicatedbyaplussign.Eachfloorcanbeasmokecontrolzone,asin(a)and(b),orasmokezonecanconsistofmorethanonefloor,asin(c)and(d).Asmokezonecanalsobelimitedtoapartofafloor,asin(e).

    Whenafireoccurs,allofthenonsmokezonesinthebuildingcanbepressurizedasshownin FigureA.5.5.1.1.1,parts(a),(c),and(e).Thissystemrequireslargequantitiesofoutsideair.Thecommentsconcerninglocationofsupplyairinletsofpressurizedstairwellsalsoapplytothesupplyairinletsfornonsmokezones.

    Incoldclimates,theintroductionoflargequantitiesofoutsideaircancauseseriousdamagetobuildingsystems.Therefore,seriousconsiderationshouldbegiventoemergencypreheatsystemsthattempertheincomingairandhelptoavoidorlimitdamage.Alternatively,pressurizingonlythosezonesimmediatelyadjacenttothesmokezonescouldlimitthequantityofoutsideairrequired,asin FigureA.5.5.1.1.1,parts(b)and(d).However,thedisadvantageofthislimitedapproachisthatitispossibletohavesmokeflowthroughshaftspastthepressurizedzoneandintounpressurizedspaces.Whenthisalternativeisconsidered,acarefulexaminationofthepotentialsmokeflowsinvolvedshouldbeaccomplishedandadeterminationofacceptabilitymade.

    Smokezonesshouldbekeptassmallaspracticablesothatevacuationfromthesezonescanbereadilyachievedandsothatthequantityofairrequiredtopressurizethesurroundingspacescanbekepttoamanageablelevel.However,thesezonesshouldbelargeenoughsothatheatbuildupfromthefirewillbecomesufficientlydilutedwithsurroundingairsoastopreventfailureofmajorcomponentsofthesmokecontrolsystem.DesignguidanceondilutiontemperatureisprovidedinASHRAE/SFPE,PrinciplesofSmokeManagement.

    A.5.6 MethodsofdesignforsmokerefugeareasarepresentedintheASHRAETransactionspaper,DesignofSmokeControlSystemsforAreasofRefuge(Klote,1993).

    A.5.7 Examplesofsmokecontrolsystemsthatcaninteractwhenoperatingsimultaneouslyincludethefollowing:

    (1) Pressurizedstairwellsthatconnecttofloorareasthatarepartofazonedsmokecontrolsystem

    (2) Elevatorhoistwaysthatarepartofanelevatorsmokecontrolsystemthatconnectstofloorareasthatarepartofazonedsmokecontrolsystem

    (3) Elevatorsmokecontrolsystemsthatareconnectedtoareasofrefugethatareinturnconnectedwithfloorareasthatarepartofazonedsmokecontrolsystem

    (4) Pressurizedstairwellsthatarealsoconnectedtoasmokerefugearea

    Oftensmokecontrolsystemsaredesignedindependentlytooperateunderthedynamicforcestheyareexpectedtoencounter(e.g.,buoyancy,stackeffect,wind).Oncethedesigniscompleted,itisnecessarytostudytheimpactthesmokecontrolsystem(s)willhaveononeanother.Forexample,anexhaustedsmokezoneoperatinginconjunctionwithastairwellpressurizationsystemcantendtoimprovetheperformanceofthestairwellpressurizationsystem.Atthesametime,itcouldincreasethepressuredifferenceacrossthedoor,causing

  • CopyrightNFPA

    difficultyinopeningthedoorintothestairwell.Forcomplexsystems,itisrecommendedthatacomputernetworkmodelbeusedfortheanalysis.

    Unlessventingorexhaustisprovidedinthefirezones,therequiredpressuredifferencesmightnotbedeveloped.Eventuallypressureequalizationbetweenthefirezoneandtheunaffectedzoneswillbecomeestablishedandtherewillbenothingtoinhibitsmokespreadintoallotherzones.

    A.6.2 SeeAnnex CforinformationontypesofHVACairhandlingsystems.

    A.6.4.2 VarioustypesofcontrolsystemsarecommonlyusedforHVACsystems.Thesecontrolsystemsutilizepneumatic,electric,electronic,andprogrammablelogicbasedcontrolunits.AllthesecontrolsystemscanbeadaptedtoprovidethenecessarylogicandcontrolsequencestoconfigureHVACsystemsforsmokecontrol.Programmableelectroniclogicbased(i.e.,microprocessorbased)controlunits,whichcontrolandmonitorHVACsystemsaswellasprovideotherbuildingcontrolandmonitoringfunctions,arereadilyapplicableforprovidingthenecessarylogicandcontrolsequencesforanHVACsystem'ssmokecontrolmodeofoperation.

    Thecontrolsystemshouldbedesignedassimplyaspossibletoattaintherequiredfunctionality.Complexcontrols,ifnotproperlydesignedandtested,canhavealowlevelofreliabilityandcanbedifficulttomaintain.

    A.6.4.3.4 Forpurposesofautomaticactivation,firedetectiondevicesincludeautomaticdevicessuchassmokedetectors,waterflowswitches,andheatdetectors.

    A.6.4.3.5.1 Manualcontrolsexclusivelyforotherbuildingcontrolpurposes,suchashandoffautoswitcheslocatedonathermostat,arenotconsideredtobemanualcontrolsinthecontextofsmokecontrol.Manualactivationanddeactivationforsmokecontrolpurposesshouldoverridemanualcontrolsforotherpurposes.

    A.6.4.3.5.2 Manualpullstationsarenotusedtoactivatesmokecontrolstrategiesthatrequireinformationonthelocationofthefirebecauseofthelikelihoodofapersonsignalinganalarmfromastationoutsidethezoneoffireorigin.

    A.6.4.3.5.3 Generally,stairwellpressurizationsystemscanbeactivatedfromamanualpullstation,providedtheresponseiscommonforallzones.Othersystemsthatrespondidenticallyforallzonealarmscanalsobeactivatedfromamanualpullstation.Anactivetrackingstairwellpressurizationsystemthatprovidescontrolbasedonthepressuremeasuredatthefirefloorshouldnotbeactivatedfromamanualpullstation.

    A.6.4.3.6.2 Topreventdamagetoequipment,itmightbenecessarytodelayactivationofcertainequipmentuntilotherequipmenthasachievedaprerequisitestate(i.e.,delaystartingafanuntilitsassociateddamperispartiallyorfullyopen).

    A.6.4.3.6.3 Thetimesgivenforcomponentstoachievetheirdesiredstatearemeasuredfromthetimeeachcomponentisactivated.

    A.6.4.3.7 SeeAnnex Dforadditionalconsiderationsforafirefighters'smokecontrolstation.

  • CopyrightNFPA

    A.6.4.3.7.3 Forcomplexsmokecontrolsystemdesigns,statusindication,faultindication,ormanualcontrolcanbeprovidedforgroupsofcomponentsorbysmokecontrolzone.

    A.6.4.3.7.7 Indirectindicationoffanstatusisnotpositiveproofofairflow.

    A.6.4.4.1 Inlimitedinstances,itcanbedesirabletopressurizeonlysomestairwellsduetoparticularbuildingconfigurationsandconditions.

    A.6.4.5.1.1.1 Iffirealarmzonesandsmokecontrolzonesdonotcoincide,thereisapossibilitythatthewrongsmokecontrolsystem(s)canbeactivated.

    A.6.4.5.1.2.1 Manualpullstationsarenotusedtoactivatezonedsmokecontrolstrategiesbecausethesetypesofsystemrequireinformationonthelocationofthefire,andthereisnoassurancethatthepullstationthatwasactivatedislocatedinthesmokezone.

    A.6.4.5.2 Manualcontrolsusedexclusivelyforotherbuildingcontrolpurposes,suchashandoffautoswitcheslocatedonathermostat,arenotconsideredtobemanualcontrolsinthecontextofsmokecontrol.Manualactivationanddeactivationforsmokecontrolpurposesshouldoverridemanualcontrolsforotherpurposes.

    A.6.4.5.2.1.1 Thisequipmentincludesairsupply/returnfansanddamperssubjecttoautomaticcontrolaccordingtobuildingoccupancyschedules,energymanagement,orotherpurposes.

    A.6.4.5.3 Documentationoftheequipmenttobeoperatedforeachautomaticallyactivatedsmokecontrolsystemconfigurationincludes,butisnotlimitedto,thefollowingparameters:

    (1) Firezoneinwhichasmokecontrolsystemautomaticallyactivates.

    (2) Typeofsignalthatactivatesasmokecontrolsystem,suchassprinklerwaterfloworsmokedetector.

    (3) Smokezone(s)wheremaximummechanicalexhausttotheoutsideisimplementedandnosupplyairisprovided.

    (4) Positivepressuresmokecontrolzone(s)wheremaximumairsupplyisimplementedandnoexhausttotheoutsideisprovided.

    (5) Fan(s)ONasrequiredtoimplementthesmokecontrolsystem.MultiplespeedfansshouldbefurthernotedasFASTorMAX.VOLUMEtoensurethattheintendedcontrolconfigurationisachieved.

    (6) Fan(s)OFFasrequiredtoimplementthesmokecontrolsystem.

    (7) Damper(s)OPENwheremaximumairflowmustbeachieved.

    (8) Damper(s)CLOSEDwherenoairflowshouldtakeplace.

    (9) Auxiliaryfunctionsmightberequiredtoachievethesmokecontrolsystemconfigurationormightbedesirableinadditiontosmokecontrol.Changesoroverrideofnormaloperationstaticpressurecontrolsetpointsshouldalsobeindicatedifapplicable.

    (10) Damperpositionatfanfailure.

  • CopyrightNFPA

    Examplesofauxiliaryfunctionsthatcanbeuseful,butarenotrequired,aretheopeningandclosingofterminalboxeswhilepressurizingorexhaustingasmokezone.Thesefunctionsareconsideredauxiliaryifthedesiredstateisachievedwithoutthesefunctions.Thesefunctionscan,however,helptoachievethedesiredstatemorereadily.

    A.6.4.5.5 Duringafire,itislikelythatenoughsmoketoactivateasmokedetectormighttraveltootherzonesandsubsequentlycausealarminputsforotherzones.Systemsactivatedbysmokedetectorsshouldcontinuetooperateaccordingtothefirstalarminputreceived,ratherthandivertingcontrolstorespondtoanysubsequentalarminput(s).

    A.6.4.5.5.1 Systemsinitiatedbyheatactivateddevices,anddesignedwithsufficientcapacitytoexhaustmultiplezones,canexpandthenumberofzonesbeingexhaustedtoincludetheoriginalzoneandsubsequentadditionalzones,uptothelimitofthemechanicalsystem'sabilitytomaintainthedesignpressuredifference.Exceedingthedesigncapacitywilllikelyresultinthesystem'sfailingtoadequatelyexhaustthefirezoneortoachievethedesiredpressuredifferences.Ifthenumberofzonesthatcanbeexhaustedwhilestillmaintainingthedesignpressureisnotknown,thisnumbershouldbeassumedtobe1.

    A.6.4.6 Themeansandfrequencyofverificationmethodswillvaryaccordingtothecomplexityandimportanceofthesystemasfollows:

    (1) Positiveconfirmationoffanactivationshouldbebymeansofductpressure,airflow,orequivalentsensorsthatrespondtolossofoperatingpower,problemsinthepowerorcontrolcircuitwiring,airflowrestrictions,andfailureofthebelt,shaftcoupling,ormotoritself.

    (2) Positiveconfirmationofdamperoperationshouldbebycontact,proximity,orequivalentsensorsthatrespondtolossofoperatingpowerorcompressedairproblemsinthepower,controlcircuit,orpneumaticlinesandfailureofthedamperactuator,linkage,ordamperitself.

    (3) Otherdevices,methods,orcombinationsofmethodsasapprovedbytheauthorityhavingjurisdictionmightalsobeused.

    ItemsA.6.4.6(1)through A.6.4.6(3)describemultiplemethodsthatcanbeused,eithersinglyorincombination,toverifythatallportionsofthecontrolsandequipmentareoperational.Forexample,conventional(electrical)supervisionmightbeusedtoverifytheintegrityoftheconductorsusedtosendanactivationsignalfromafirealarmsystemcontrolunittotherelaycontactwithin3ft(1m)ofthesmokecontrolsysteminput(seeNFPA72,NationalFireAlarmCode,Section6.15),andendtoendverificationmightbeusedtoverifyoperationfromthesmokecontrolsysteminputtothedesiredendresult.Ifdifferentsystemsareusedtoverifydifferentportionsofthecontrolcircuit,controlledequipme