polycab ht xlpe

Upload: pravin-narkhede

Post on 03-Jun-2018

242 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/12/2019 Polycab Ht Xlpe

    1/36

    HIGH TENSION XLPE CABLESHIGH TENSION XLPE CABLES

    IS 7098 (Part II)

    9001:2008

    14001:2004

    OHSAS18001:2007

  • 8/12/2019 Polycab Ht Xlpe

    2/36

    P R O D U C T R A N G E

    L.V. PVC & XLPE POWER CABLES WITH

    COPPER AND ALUMINIUM CONDUCTOR

    L.V. PVC & XLPE CONTROL CABLES WITH COPPER CONDUCT

    M.V. POWER CABLES UPTO 33 kV

    EHV CABLES FROM 66kV TO 220kV

    M.V. / L.V. AERIAL BUNCHED CABLES (ABC)

    ZERO HALOGEN CABLES

    FIRE SURVIVAL CABLES (FS)

    INSTRUMENTATION CABLES SCREENED / UNSCREENED

    INDUSTRIAL BRAIDED CABLES

    THERMO COUPLE / COMPENSATING CABLES

    LEAD SHEATHED CABLES

    RUBBER CABLES

    RAILWAY SIGNALLING CABLES

    TELEPHONE CABLES DRY & JELLY FILLED

    BUILDING WIRES FR / FRLS / FRZH / FRLF / FRFS

    SINGLE CORE INDUSTRIAL FLEXIBLES PVC / FR / FRFRZH / HRFR / HR / HR-FRLS / FRLF / FRFS

    MULTI CORE INDUSTRIAL FLEXIBLE CABLES

    SUBMERSIBLE FLAT AND ROUND CABLES

    SUBMERSIBLE WRAPPED WINDING WIRES

    COAXIAL CABLES

    LAN CAT-5E / CAT 6 CABLES

    WELDING CABLES

    SOLAR AC / DC CABLES

    STEEL BRAIDED CABLES

    SPECIALITY CABLES SUITED FOR MARINE / OIL & GAEXTREME FIRE CONDITIONS / HIGHLY CORROSIVEENVIRONMENT / TRAFFIC / AIRCRAFT / SPACE STATIOAUTOMOBILES

  • 8/12/2019 Polycab Ht Xlpe

    3/36

    Page No.

    COMPANY PROFILE 2

    MANUFACTURING PROCESS-AT POLYCAB 3

    FLOW CHART 4

    CONSTRUCTION OF HT CABLES 5

    QUALITY ASSURANCE 6

    FLAME RETARDANT LOW SMOKE CABLES 7

    ADVANTAGES OF POLYCAB CABLES & SELECTION OF CABLES 8

    POLYCAB GUIDLINES FOR SELECTION OF CABLES 9

    TECHNICAL DATA

    Conductor Resistance 10

    Cable Short Circuit Rating

    Capacitance & Reactance 11

    Current Rating 13

    Rating Factors 14

    WEIGHT, DIMENSION DATA & CURRENT CARRYING CAPACITY OF CABLES

    3.8 / 6.6 KV (E) HT XLPE SINGLE CORE 16

    6.35/11 KV (E) 6.6/6.6KV (UE) HT XLPE SINGLE CORE 17

    11/11 KV (UE) HT XLPE SINGLE CORE 18

    12.7/22 KV (E) HT XLPE SINGLE CORE 19

    19/33 KV (E) HT XLPE SINGLE CORE 20

    33/33 KV (UE) HT XLPE SINGLE CORE 21

    1.9/3.3 KV (E)&3.3/3.3 KV (UE) HT XLPE THREE CORE 22

    3.8/6.6 KV (E) HT XLPE THREE CORE 23

    6.35/11 KV (E) HT XLPE THREE CORE 24

    11/11 KV (UE) HT XLPE THREE CORE 25

    12.7/ 22 KV (E) HT XLPE THREE CORE 26

    19/33 KV (E) HT XLPE THREE CORE 27

    33/33 KV (UE) HT XLPE THREE CORE 28

    HANDLING STORAGE & LAYING OF CABLES 29

    IMPORTANT FORMULA 31

    DIFFERENCE BETWEEN EARTHED & UNEARTHED SYSTEM 32

    CONTENTS

  • 8/12/2019 Polycab Ht Xlpe

    4/362

    COMPANY PROFILEPOLYCAB, an ISO 9001:2008, ISO 14001:2004,

    OHSAS 18001:2004 company is the largest Wire

    & Cable manufacturer in India with a proven track

    record of over three decades. The fastest growingcompany in the Indian Cable Industry with

    consistent growth. Polycab group has crossed

    Rs. 3600 crore turnover in the year 2010 11 and

    is set to achieve Rs. 4000 crore turnover in the

    year 2011 12.

    From a modest beginning with Wires and Cables,

    over three decades ago Polycab set up State of

    Art manufacturing facilities at Daman in 1996. In

    the manufacture of cables, a competitive edge

    lies not so much in product innovation as in

    consistent quality and ready availability. Polycabs

    Daman factory was created to address these

    key market determinants. The manufacturing

    set up is sourced out from the world renowned

    Machinery and Technology suppliers with

    constant upgradation and expansions.

    In an on going process to improve Customer

    Satisfaction Polycab offers a variety of services:

    Commercially competitive prices.

    Reliable & consistent quality.

    Reliable & just in time delivery.

    Product development for a changing market.

    A targeted stocking policy.

    Technical Support for Applications/ Projects

    POLYCAB derives its strength from its customers.

    The growth of the latter is a prerequisite to the

    growth of the company and hence customers

    satisfaction is its prime objective. Over the years

    sincere service and dedication to its Customers

    has earned the Company distinguished Customers

    which includes leaders in Sectors like Utilities,

    Power Generation, Transmission & Distribution,

    Petroleum & Oil Refineries, OEMs, EPC contractors,

    Steel & Metal, Cement, Chemical, Atomic Energy,

    Nuclear Power, Consultants & Specifiers etc.

    POLYCAB has highly experienced, qualified and

    dedicated professionals with strong adherence

    to the quality management system. Polycab has

    offices all over the country and also has a wide

    network of authorized distributors and dealers to

    cater to all the customer segments in India and

    abroad.

    POLYCAB has earned the trust and reputationin India and abroad by winning the customers

    confidence. Several thousands kilometers of HV

    XLPE Cables in the voltage range of 6.6KV, 11KV,

    22KV & 33KV have been manufactured and are in

    operation in India and abroad.

    Polycab HV XLPE Cables are preferred choice

    in Power Plants, Distribution Systems, Heavy

    Industries, Various Utilities, the Titans of Indian

    Industry & Consultants / Specifiers.

    POLYCAB CABLE OF 33KV E 3 X 400 SQ.MM

    HAVE BEEN SUCCESSFULLY TYPE TESTED AT

    KEMA - NETHERLAND (AN INTERNATIONALLY

    ACCLAIMED TESTING LABORATORY).

    BASEC CERTIFICATION OF OUR BUSINESS

    DEMONSTRATES OUR COMMITMENT TO

    NOT ONLY THE QUALITY OF OUR PRODUCTS,

    BUT ALSO THE LEVEL OF OUR COMMITMENT

    FOR CONTINOUS IMPROVEMENT

  • 8/12/2019 Polycab Ht Xlpe

    5/36

    Figure 1 : 6 Nos. CCV (DRY CURE) LINES

    Figure 2 : THREE LAYER COMON TRIPLE EXTRUSION METHOD

    Figure 3 : ULTRA MODERN HV TESTING LAB

    MANU FACTURIN G PR OCESS AT PO LYCAB

    POLYCAB HV XLPE cables are manufactured at its

    most modern manufacturing setup in DAMAN.

    Manufacture of HV XLPE CABLES requires great

    care and skill at all stages of processing. Work on HV

    cables has shown to raise the electric stress of XLPEcables it is essential that the extruded insulation

    is of high cleanliness without any imperfection,

    free of contamination, voids and manufacturing

    defects, and that the screen interface is smooth. In

    addition an integrated extrusion plant employing

    a Continuous Centenary Vulcanizing (CCV) process

    line (Dry Curing Line) is required. Polycab easily met

    these two criteria by carefully selecting imported

    insulating materials and by installing 2 CCV lines

    sourced from world renowned manufacturers.(Fig 1)

    The cable core is triple extruded and crosslinked

    in the fully enclosed process in which the inner

    semi-conducting screen, the XLPE insulation

    and the outer semi conducting screen are

    applied simultaneously (Fig 2) to the pre-heated

    cable conductor. Specialized in-line inspection

    techniques using X-rays are employed to monitor

    the dimensional accuracy of the extruded core.

    These examinations confirm the correct levels of

    dimensional accuracy.

    The final stage of HV cable manufacture is

    the high voltage test, which comprises an HV

    withstand, and a partial discharge detection test.

    These tests take place in Polycabs sophisticated

    HV Test Lab (Fig 3). The tests are of short duration,

    typically 30 minutes, and are capable of detecting

    the defects that initiate partial discharges, as

    small as one pico-coulomb. Such defects lead to

    gradual deterioration of the XLPE and eventually

    breakdown may occur.

  • 8/12/2019 Polycab Ht Xlpe

    6/364

    Cables with FRLS / Zero Halogen Outer Sheath can be supplied against specific requirement.

    * Lead Sheath (optional)

    Continuous Triple Extrusion

    Inner Semicon, XLPE Insulation Outer Semicon

    Quality Checks

    T y p e o f C o m p o u n d s , B a t c h N o . d e t a i l s , T h i c k n e s s , C o r e D i a , E c c e n t r i c i t y , S u r f a c e F i n i s h , H o t S e t T e s t

    Copper Taping

    Quality Checks

    Si ze & Type of Tape, Ma rket /Lo t N o., Ove rl ap, Di a ove r ta pe, Con tinu it y, Tape Jo in ting, Core Id en tifi cat io n

    Laying Up / Twisting

    Quality Checks

    Core Sequence, No of Cores, Laylength., Binder /Roun dness

    Inner Sheathing (Extrusion*)

    Quality Checks

    Type of PVC, Batch/Lot No., Thickness of Sheath, Dia over Sh eath

    ArmouringQuality Checks

    Ar mo ur Dime nsi on s, No . of Ar mou r, Co ve ra ge, Arm our Jo in t

    Outer Sheathing

    Quality Checks

    Type of PVC, Batch/Lot No., Thickness of Sheath, Dia over Sheath, Color, Surface Finish

    Final Testing

    Quality ChecksConductor Resi stance, High Voltage Test, Partial Di scharge Test

    Packing / Marking

    Quality Checks

    Ma rk in g Det ail s, La ggi ng Co ve ra ge

    Storage / Dispatch

    Conductor

    Quality Checks

    No. of Wires, Size, Conductor Resistan ce, Surface Finish, Diameter o f Conductor

    FLOW CHART

  • 8/12/2019 Polycab Ht Xlpe

    7/36

    1. Conductor : Stranded Class 2 - Annealed Plain / Tinned Copper /

    Aluminium - IS:8130 / IEC 60228/ BS 6360.

    2. Conductor Screen : Extruded semi-conducting compound IS:7098 Part 2,

    IEC:60502 Part 2, BS:6622, BS:7835.

    3. Insulation : XLPE IS : 7098 Part 2, IEC:60502 Part 2, BS:6622, BS:7835.

    4. Insulation Non-metallic Screen : Extruded semi-conducting compound IS:7098 Part 2,

    IEC:60502 Part 2, BS:6622, BS:7835.

    5. Insulation Metallic Screen : Copper Wire / Tape or Aluminium Wire / Strip IS:7098 Part 2,

    IEC:60502 Part 2, BS:6622, BS:7835.

    6. Fillers : Non Hygroscopic PVC * / Polypropelene Fiber to

    maintain roundness of cable.

    7. Inner sheath/Bedding : PVC ST 2 as per IS:7098 Part 2, IEC:60502 Part 2, BS:6622,

    LSOH to BS:7835.

    8. Armour : IS:7098 Part 2, IS: 3975, IEC:60502 Part 2, BS:6622, BS:7835.

    9. Outer Sheath : PVC ST 2, FR, FRLS as per IS:7098 Part 2, IEC:60502 Part 2,

    BS:6622, LSOH to BS:7835.

    Flame Retardant (FR), Flame Retardant Low Smoke (FRLS) and Low Smoke Zero Halogen & Flame

    Retardant (LSOH) Sheathed HT XLPE cables are also manufactured.

    * Weights given in the Tables are with PVC Fillers.

    33 kV (UE) Screened XLPE Cables

    as per customer requirement.

    19/33 kV Screened Cable i.e. 33 kV (E)

    12.7/22 kV Screened Cables i.e. 22 kV (E) 11/11 kV Screened Cables. i.e. 11 kV ( UE)

    6.35/11 kV, Screened Cables i.e. 6.6 kV (UE)

    3.8/6.6 kV Screened Cables.

    3.3kV (E) and (UE) Unscreened & Screened Cables.

    SIZES:

    35 Sq.mm up to 1000 Sq.mm in Single Core Cables.

    35 Sq.mm to 400 Sq.mm in Multi Cores Cables.

    ALUMINIUM WIRE /STRIP ARMOUR

    STRANDED COMPACTEDCOPPER / ALUMINIUM CONDUCTOR

    PVC FILLERS

    INNER SEMICON

    COPPER TAPE

    ST2 PVC INNER SHEATH

    ST2 PVC OUTER SHEATH

    OUTER SEMICON

    XLPE INSULATION

    Polycab manufactures following voltage grade cables as per IS-7098[Part-2],

    IEC-60502 Part-2 and BS-6622 & BS:7835

    CONSTRUCTION OF HT CABLES

  • 8/12/2019 Polycab Ht Xlpe

    8/366

    Polycabs goal is to have satisfied customers.

    Quality assurance consisting of rigorous

    inspection followed by meticulous process and

    quality control in all phases, guarantees the

    superior quality of POLYCABS products. Up-to-Date laboratory facilities ensure that quality

    control requirements are met in full. Polycab

    XLPE Cables are tested to ensure high reliability

    in performance. Continuous process monitoring

    and post manufacturing tests ensure the

    compliance to Indian and International Standards.

    The assurance of quality is further ensured by

    ISI certification No. CM/L-7180366 on cables and

    ISO 9001 certification by UL,USA, A-7913.

    QUALITY ASSURANCE TESTING :

    Polycab is self sufficient to carry out all Routine &

    Type Tests in its own laboratory. It has world class

    Testing facilities for Routine & Type Tests.Routine

    Tests : IS:7098 Part 2, IEC:60502, BS:6622,

    BS:7835

    Partial Discharge Test

    High Voltage Test

    Conductor Resistance Test. Routine Tests are

    performed on each manufactured length ofcable in Routine Test Laboratory.

    TYPE TESTS:

    IS:7098 Part 2, IEC:60502, BS:6622, BS:7835

    a) Electrical Type Tests

    b) Non-Electrical Type Tests

    c) Special Tests.

    The cable samples are type tested in-house to

    ensure conformance as to various standards.

    Polycab cables of various voltage grades are

    type tested at CPRI Bangalore & ERDA Vadodara.

    Short circuit tests on cable conductor and armour

    are successfully carried at CPRI Bhopal & ERDA

    Vadodara.

    NON ELECTRICAL TYPE TEST LABORATORY

    QUALITY ASSURANCE

    IMPULSE TEST SET UP

  • 8/12/2019 Polycab Ht Xlpe

    9/36

    The behaviour of Electric Cables in presence

    of fire has been a matter of great concern to

    all Electrical Engineers involved in Generation,

    Transmission and Utilisation of electric power.Normally all XLPE Cables have an outer sheath of

    PVC. Although PVC by itself is flame retarding, it

    does produce highly toxic and corrosive fumes in

    the event of fire.

    As a matter of fact, in closed and crowded places

    such as power stations, subways, railways with

    long sections in tunnels, road tunnels, ships,

    hospitals, schools, hotels, cinema theatres,museums and public premises in general,

    besides the obvious danger represented by fire

    propagation, also fume toxicity and opacity are

    particularly important as they may cause, with

    equally serious consequences for human safety,

    suffocation intoxication and panic due to reduced

    visibility.

    FLAM E RETARDANT LOW SM OKE C ABLE SFRLS PVC compound should ensure the

    following :

    1) Minimum smoke emission.

    2) Very low toxic and corrosive fumes emission.

    3) Fire Retardant characteristics.

    Our laboratory is well equipped with latest

    test equipments to carry out following test

    requirements.

    a) The oxygen index and temperature index of

    sheath as per ASTM-D 2863.b) Flammability characteristics of cable as per

    IEC 60332 ( Pt. I ) & IEC 60332 ( Pt. III )

    c) Flammability characteristics of cables as per

    Swedish Standard SS 424 14 75, Class F3.

    d) Determination of the amount of halogen

    acid gas evolved during combustion of

    outersheath materials as per per IEC 60754

    ( Pt. I & II ).

    e) Determination of smoke generation of

    outersheath material under fire as per

    ASTM-D 2843

    f ) The measurement of smoke density as per

    IEC 61034.

  • 8/12/2019 Polycab Ht Xlpe

    10/368

    Power Cables are generally selected considering

    the application. However, following factors

    are important for selection of suitable cable

    construction required to transport electrical

    energy from one end to the other.

    1) Maximum operating voltage,

    2) Fault Level,

    3) Load to be carried,

    4) Possible overloading duration & magnitude,

    5) Route length and voltage drop.

    6) Mode of installation considering installation

    environment such as ambient & ground

    temperature chemical & physical properties

    of soil.

    7) Flame retardant properties.

    A D V A N TA G E S O F P O LY C A B X L P E C A B L E S

    All sizes of POLYCAB XLPE cables are designed

    to standard operating conditions in India and

    abroad. The standards adopted are considering

    the geographical/climatical conditions and

    general applications of power for utilities,

    distribution and generation purposes.

    The cables are manufactured conforming to

    Indian & International cables specifications

    for XLPE Insulated cables. Customer specific

    requirements can also be met.

    Higher Electrical Strength Retention

    Higher Short Circuit Rating

    Better Electrical , Mechanical & Thermal Properties

    Easy Jointing & Termination

    S E L E C T I O N O F C A B L E S

  • 8/12/2019 Polycab Ht Xlpe

    11/36

    Polycab is manufacturing wide range of cables, so it is important that while placing enquiries or orders,

    as much information as possible shall be given to Polycab, so that the enquiries and orders are dealt

    quickly and efficiently.

    1) Voltage Grade : 1.9 / 3.3 kV (E), 3.3 / 3.3 kV (UE), 3.8 / 6.6 kV (E) , 6.6 / 6.6 kV (UE), 6.35 / 11 kV (E),

    11 / 11 kV (UE), 12.7 / 22 kV (E) & 33 kV (E), 33 kV (UE) , 45 kV &

    66kV

    2) Relevant Indian Standard : IS 7098 (Part-2) 1985 or International standard IEC-60502 (Part-2),

    BS-6622 & BS:7835.

    3) Number of cores. : Single & Three.

    4) Conductor : Size - 35 Sq.mm to 1000 Sq.mm in Single Core Cables & 35 Sq.mm

    to 400 Sq.mm in 3 Core cables.

    5) Conductor Material : Copper / Aluminium

    6) Type of Insulation : XLPE

    7) Type of Inner Sheathing : PVC Wrapped / PVC Extruded.

    8) Type of Armour : Unarmoured / Strip Armoured / Round Wire Armoured.

    9) Type of Outer Sheath : PVC / Flame Retardant / Flame Retardant Low Smoke /

    Zero Halogen (LSOH).

    10) Length of cable required and drum length.

    POLYCAB GUIDELINE S FOR SE LECTION OF CABLES

    Note : Detailed Leaflet for 66kV & above can be available on specific request .

  • 8/12/2019 Polycab Ht Xlpe

    12/360

    The details to the above Guidelines are given in tables.

    Table - 1 *Conductor Technical Information for Single Core and Multicore cables conforming to

    IS-8130 /1984 (Stranded Class-2) Copper & Aluminium Conductors.

    Nominal

    Size ofMinimum no. of wires Max. D.C. Resistance at 20 C A.C. Resistance at 90 C

    Conductor Compacted Round Plain Copper Aluminium Plain Copper Aluminium

    Sq.mm CU. ALU. Ohm/Km Ohm/Km Ohm/Km Ohm/Km

    25 6 6 0.727 1.20 0.930 1.54

    35 6 6 0.524 0.868 0.671 1.11

    50 6 6 0.387 0.641 0.495 0.82

    70 12 12 0.268 0.443 0.343 0.567

    95 15 15 0.193 0.320 0.247 0.410

    120 18 15 0.153 0.253 0.196 0.324

    150 18 15 0.124 0.206 0.159 0.264185 30 30 0.0991 0.164 0.127 0.210

    240 34 30 0.0754 0.125 0.0965 0.160

    300 34 30 0.0601 0.100 0.0769 0.130

    400 53 53 0.0470 0.0778 0.0602 0.10

    500 53 53 0.0366 0.0605 0.0468 0.0774

    630 53 53 0.0283 0.0469 0.0362 0.060

    800 53 53 0.0221 0.0367 0.0283 0.0470

    1000 53 53 0.0176 0.0291 0.0225 0.0372

    * Conductor meeting requirements of IEC-60228 and BS 6360 can also be manufactured.

    Table - 2 SHORT CIRCUIT RATING FOR 1 SECOND DURATION FOR COPPER AND ALUMINIUM

    XLPE CABLES (CURRENT IN K. AMPS)

    Nominal Size XLPE Insulated

    Sq.mm Copper Aluminium

    25 3.6 2.4

    35 5.0 3.3

    50 7.1 4.7

    70 10.0 6.6

    95 13.6 9.0

    120 17.1 11.3

    150 21.4 14.2

    185 26.4 17.5

    240 34.3 22.6

    300 42.9 28.3

    400 57.1 37.7

    500 71.4 47.2

    630 90.0 59.4

    800 114.3 75.5

    1000 142.9 94.3

    XLPE Cables as per IS-7098 (Part-2)-1985

    1) Max. Conductor Temperature during operation: 90 C

    2) Max. Conductor Temperature during short Circuit: 250C

    Formula relating Short Circuit Rating with duration

    It = Ish Where

    t It = Short Circuit Rating for t Seconds.

    t = duration in seconds

    Ish = Short Circuit rating for 1 second.

    CONDUCTOR RESISTANCE

  • 8/12/2019 Polycab Ht Xlpe

    13/36

    Table - 3 CAPACITANCE

    Approximate Capacitance (Microfarads/km) for Single Core Cables

    Size Voltage Grade(kV)

    1.9/3.3 & 3.3/3.3 3.8/6.6 6.6/6.6 & 6.35/11 11/11 12.7/22 19/33 33/33

    35

    50 0.30 0.27 0.23

    70 0.34 0.31 0.27 0.18

    95 0.39 0.34 0.31 0.20 0.19 0.15 0.14

    120 0.43 0.37 0.33 0.22 0.20 0.16 0.15

    150 0.49 0.42 0.36 0.24 0.22 0.17 0.16

    185 0.52 0.44 0.39 0.25 0.24 0.18 0.17

    240 0.59 0.50 0.43 0.28 0.26 0.20 0.19

    300 0.67 0.53 0.48 0.32 0.30 0.23 0.20

    400 0.76 0.55 0.53 0.36 0.33 0.25 0.23

    500 0.77 0.57 0.50 0.39 0.36 0.27 0.25

    630 0.81 0.64 0.69 0.43 0.40 0.29 0.28

    800 0.86 0.73 0.79 0.49 0.45 0.33 0.30

    1000 0.88 0.80 0.88 0.53 0.49 0.35 0.33

    Table - 4 CAPACITANCE

    Approximate Capacitance ( Microfarads/km) For Three Core Cables

    Size Voltage Grade(kV)

    1.9/3.3& 3.3/3.3 3.8/6.6 6.6/6.6 & 6.35/11 11/11 12.7/22 19/33 33/33

    35 0.24 0.25 0.21

    50 0.27 0.27 0.22

    70 0.31 0.31 0.25 0.19

    95 0.35 0.35 0.29 0.21 0.20 0.15 0.14

    120 0.39 0.38 0.31 0.23 0.22 0.16 0.15

    150 0.42 0.43 0.34 0.25 0.23 0.18 0.16

    185 0.46 0.45 0.36 0.27 0.25 0.18 0.17

    240 0.51 0.51 0.41 0.30 0.28 0.20 0.19

    300 0.57 0.54 0.46 0.33 0.31 0.23 0.20

    400 0.63 0.57 0.52 0.37 0.34 0.25 0.23

    CAPACITANCE

  • 8/12/2019 Polycab Ht Xlpe

    14/362

    Table - 5 REACTANCE

    Approximate Reactance At 50 Hz( Ohms/km) For Single Core Cables

    Size Voltage Grade(kV)

    1.9/3.3& 3.3/3.3 3.8/6.6 6.6/6.6 & 6.35/11 11/11 12.7/22 19/33 33/33

    Arm Un-Arm Arm Un-Arm Arm Un-Arm Arm Un-Arm Arm Un-Arm Arm Un-Arm Arm Un-Arm

    35

    50 0.115 0.104 0.119 0.110 0.133 0.127 0.133 0.125 0.137 0.130 0.147 0.140

    70 0.109 0.098 0.113 0.105 0.123 0.118 0.126 0.119 0.130 0.123 0.141 0.133

    95 0.104 0.095 0.108 0.100 0.116 0.111 0.120 0.114 0.124 0.116 0.135 0.127 0.143 0.137

    120 0.100 0.092 0.104 0.101 0.112 0.107 0.117 0.110 0.119 0.112 0.130 0.122 0.137 0.131

    150 0.096 0.088 0.101 0.093 0.109 0.104 0.112 0.106 0.115 0.107 0.126 0.118 0.134 0.129

    185 0.094 0.087 0.099 0.091 0.107 0.101 0.110 0.103 0.114 0.105 0.124 0.115 0.128 0.122

    240 0.091 0.084 0.096 0.089 0.104 0.097 0.106 0.100 0.110 0.101 0.118 0.110 0.124 0.118

    300 0.088 0.081 0.093 0.086 0.100 0.094 0.102 0.096 0.105 0.097 0.112 0.105 0.120 0.114

    400 0.086 0.079 0.091 0.085 0.096 0.091 0.098 0.092 0.101 0.093 0.119 0.102 0.115 0.109

    500 0.085 0.078 0.088 0.083 0.093 0.089 0.095 0.090 8.099 0.091 0.105 0.099 0.111 0.106

    630 0.083 0.077 0.087 0.081 0.092 0.086 0.094 0.087 0.095 0.089 0.101 0.096 0.108 0.103

    800 0.082 0.076 0.085 0.077 0.089 0.084 0.091 0.085 0.092 0.086 0.097 0.092 0.106 0.099

    1000 0.081 0.075 0.084 0.076 0.087 0.082 0.088 0.083 0.090 0.085 0.096 0.090 0.102 0.096

    Table - 6 REACTANCE

    Approximate Reactance At 50 Hz ( Ohms/km) For Three Core Cables

    Size Voltage Grade(kV)

    1.9/3.3& 3.3/3.3 3.8/6.6 6.6/6.6 & 6.35/11 11/11 12.7/22 19/33 33/33

    35 0.094 0.104 0.111

    50 0.087 0.098 0.104

    70 0.084 0.094 0.100 0.129

    95 0.081 0.090 0.095 0.123 0.125 0.121 0.131

    120 0.078 0.087 0.092 0.117 0.120 0.116 0.125

    150 0.076 0.085 0.089 0.114 0.116 0.112 0.122

    185 0.075 0.083 0.087 0.110 0.113 0.110 0.116

    240 0.073 0.081 0.085 0.106 0.108 0.105 0.112

    300 0.072 0.079 0.082 0.103 0.105 0.100 0.108

    400 0.071 0.078 0.079 0.099 0.101 0.097 0.103

    Note: All figures given in various tables are indicative only.

    REACTANCE

  • 8/12/2019 Polycab Ht Xlpe

    15/36

    POLYCAB RECOMMENDATIONS FOR

    CURRENT RATINGS:

    The current rating of power cable is defined by

    the maximum intensity of current (amperes)

    which can flow continuously through the cable,

    under permanent loading conditions, without

    any risk of damaging the cable or deterioration of

    its electrical properties.

    The value given in the tables are valid for one

    circuit in a three phase system under conditions

    specified. For grouping cables rating factors

    must be used.

    The current carrying capacities mentioned in

    POLYCAB technical data are intended as a guide,

    to assist operating engineers in selecting cables

    for safety and reliability.

    Basic assumptions and conditions of installation :

    1) Maximum Conductor Temperature : 90C

    2) Ambient Ground Temperature : 30 C

    3) Ambient Air Temperature : 40C

    4) Thermal resistivity of soil : 150 C.

    Cm/W

    CURRENTS RATINGSDepth of laying (to the highest point of the

    cables laid direct in the ground )

    1) 3.3, 6.6 & 11kV Cables : 90 cm

    2) 22 and 33kV Cables : 105 cm

    *Max. Conductor temperature

    at the end of a short circuit : 250 C

    To obtain the maximum current carrying capacity

    of a cable operating at different conditions from

    the standard, various rating factors are to be

    multiplied, as follows :

    I a= K X Is in amperes Where ;

    I a : Current rating at actual operating conditions

    (amperes)

    Is : Current rating at standard operating

    conditions (amperes)

    K : Rating factor as, applicable.

  • 8/12/2019 Polycab Ht Xlpe

    16/364

    A). FOR AIR AND GROUND TEMPERATURE.

    A. Rating factors for variation in ambient air temperature.

    Ambient Temp (oC) 25 30 35 40 45 50

    Rating Factors 1.14 1.10 1.04 1.00 0.95 0.90B. Rating factors for variation in ground temperature.

    Ground Temp (oC) 15 20 25 30 35 40 45

    Rating Factors 1.12 1.08 1.03 1.00 0.96 0.91 0.87

    B). FOR DEPTH OF LAYING (CABLES LAID DIRECT IN THE GROUND)

    Depth of laying (cm) 3.3kV, 6.6kV & 11kV all sizes 22kV & 33 kV all Size

    90 1 __

    105 0.99 1

    120 0.98 0.99

    150 0.96 0.97

    180 or more 0.95 0.96

    C). FOR VARIATION IN THERMAL RESISTIVITY OF SOIL

    Thermal Resistivity

    of Soil (oCcm/w)100 120 150 200 250 300

    Factor 1.20 1.11 1.0 0.89 0.80 0.73

    GROUP RATING FACTORS FOR SINGLE-CORE CABLES

    A). Cables laid direct in the ground in horizontal formation.

    Number of

    trefoils in

    group

    Spacing between trefoils 3.3 to 22kV cables 33 kV Cables.

    Touching 15 cm 30 cm 45 cm Touching 15 cm 30 cm 45 cm

    2 0.78 0.81 0.85 0.88 0.80 0.82 0.85 0.88

    3 0.68 0.71 0.77 0.81 0.68 0.71 0.76 0.79

    4 0.61 0.65 0.72 0.76 0.62 0.65 0.71 0.75

    5 0.56 0.61 0.68 0.73 0.57 0.60 0.67 0.72

    B). Cables laid on Racks / Trays in covered trench with removable covers where air circulation is restricted,

    Trefoils are separated by two cable diameter horizontally and the trays are in tiers having 300 mm distance.

    No. racks/trays in tiersNo. of Trefoils in Horizontal formation

    1 2 3

    1 0.95 0.90 0.88

    2 0.90 0.85 0.83

    3 0.88 0.83 0.81

    6 0.86 0.81 0.79

    RATIN G FACTORS

  • 8/12/2019 Polycab Ht Xlpe

    17/36

    C). As above B. but c ables laid in open air.

    No. racks/trays in tiersNo. of Trefoils in Horizontal formation

    1 2 3

    1 1 0.98 0.96

    2 1 0.95 0.93

    3 1 0.94 0.92

    6 1 0.93 0.90

    FOR MULTI-CORE CABLES:

    A) Cables laid inside concrete trench with removable covers, on cable trays where air circulation is

    restricted. The cables spaced by one cable diameter and trays are in tiers spaced by 300 mm.The clearance

    between the wall and the cable is 25 mm.

    No. of cables trays

    in tier

    No. of cables

    1 2 3 6 91 0.95 0.90 0.88 0.85 0.84

    2 0.90 0.85 0.83 0.81 0.80

    3 0.88 0.83 0.81 0.79 0.78

    6 0.86 0.81 0.79 0.77 0.76

    B) Cable laid on cable trays exposed to air , the cables spaced by one cable diameter and trays are in

    tiers spaced by 300 mm. The clearance of the cable from the wall is 25 mm.

    No. of cables trays

    in tier

    No. of cables

    1 2 3 6 9

    1 1 0.98 0.96 0.93 0.92

    2 1 0.95 0.93 0.90 0.89

    3 1 0.94 0.92 0.89 0.88

    6 1 0.93 0.90 0.87 0.86

    C) Cables laid on cable trays exposed to air, the cables touching and trays are in tiers spaced by 300 mm.

    The clearance between the wall and the cable is 25 mm.

    No. of cables trays.No. of cables per tray

    1 2 3 6 9

    1 1 0.84 0.80 0.75 0.73

    2 1 0.80 0.76 0.71 0.69

    3 1 0.78 0.74 0.70 0.686 1 0.76 0.72 0.68 0.66

    D) Cables laid direct in ground in horizontal formation

    No. of cables in groupDistance of cables

    Touching 15 mm 30 mm 45 mm

    2 0.79 0.82 0.87 0.90

    3 0.69 0.75 0.79 0.83

    4 0.62 0.69 0.74 0.79

    5 0.58 0.65 0.72 0.76

    6 0.54 0.61 0.69 0.75

    RATIN G FACTOR S

  • 8/12/2019 Polycab Ht Xlpe

    18/366

    The above data is approximate and subject to manufacturing tolerance.

    * Delivery Length tolerance is 5 %. Length more than normal as per customer request.

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    UNARMOURED CABLE

    Minimum

    Thickness

    of Inner

    Sheath

    ALUMINIUM STRIP ARMOURED CABLE ALUMINIUM ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACITY

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diaeter

    of

    Cable

    Approx.

    Weight of

    Cable.

    Nominal

    Dimesion

    of

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimesion

    of

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable.

    Approx.

    Weight of

    Cable.

    In

    Ground at

    30 C.

    In Duct at

    30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    35 2.8 2.0 19 450 0.30 0.8 1.4 20 550 1.6 1.40 21.5 620 120 105 145 500

    50 2.8 2.0 20 500 0.30 0.8 1.4 21 600 1.6 1.40 22.5 700 140 125 170 500

    70 2.8 2.0 22 600 0.30 0.8 1.4 23 750 1.6 1.40 24.5 800 175 155 215 500

    95 2.8 2.0 23.5 750 0.30 0.8 1.4 24.5 850 1.6 1.40 26 950 205 180 260 500

    120 2.8 2.0 25 850 0.30 0.8 1.4 26 950 1.6 1.40 28 1050 235 205 305 500

    150 2.8 2.0 26 950 0.30 0.8 1.4 27.5 1100 1.6 1.56 29.5 1200 260 230 345 500

    185 2.8 2.0 28 1100 0.30 0.8 1.56 30 1250 1.6 1.56 31.5 1400 295 260 395 500

    240 2.8 2.2 31 1350 0.40 0.8 1.56 32 1500 2.0 1.56 34.5 1700 340 300 470 500

    300 3.0 2.2 33.5 1550 0.40 0.8 1.56 35 1750 2.0 1.56 37 2000 385 335 540 500

    400 3.3 2.2 37.5 1950 0.40 0.8 1.56 39 2200 2.0 1.72 41.5 2450 440 380 630 500

    500 3.5 2.4 41 2400 0.50 0.8 1.72 42.5 2650 2.0 1.88 45.5 2950 495 430 730 500

    630 3.5 2.4 44.5 2850 0.50 0.8 1.88 46.5 3200 2.0 1.88 49 3450 560 480 840 500

    800 3.5 2.6 49 3450 0.50 0.8 1.88 50 3750 2.5 2.04 54 4300 620 530 960 500

    1000 3.6 2.8 54 4250 0.60 0.8 2.04 55.5 4600 2.5 2.20 59.5 5150 680 580 1070 500

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    UNARMOURED CABLE

    Minimum

    Thickness

    of Inner

    Sheath

    ALUMINIUM STRIP ARMOURED CABLE ALUMINIUM ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACITY

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diaeter

    of

    Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimesion

    of

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable.

    Nominal

    Dimesion

    of

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground at

    30 C.

    In Duct at

    30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    35 2.8 2.0 19 670 0.30 0.8 1.4 20 750 1.6 1.40 21.5 850 155 140 185 500

    50 2.8 2.0 20 850 0.30 0.8 1.4 21 900 1.6 1.40 22.5 1000 185 160 220 500

    70 2.8 2.0 22 1050 0.30 0.8 1.4 23 1150 1.6 1.40 24.5 1250 225 195 275 500

    95 2.8 2.0 23.5 1300 0.30 0.8 1.4 24.5 1450 1.6 1.40 26 1550 265 235 340 500

    120 2.8 2.0 25 1600 0.30 0.8 1.4 26 1700 1.6 1.40 28 1800 300 265 390 500150 2.8 2.0 26 1900 0.30 0.8 1.4 27.5 2050 1.6 1.56 29.5 2150 335 295 440 500

    185 2.8 2.0 28 2250 0.30 0.8 1.56 30 2400 1.6 1.56 31.5 2550 380 330 510 500

    240 2.8 2.2 31 2850 0.40 0.8 1.56 32 3000 2.0 1.56 34.5 3200 435 380 600 500

    300 3.0 2.2 33.5 3450 0.40 0.8 1.56 35 3600 2.0 1.56 37 3850 490 425 680 500

    400 3.3 2.2 37.5 4450 0.40 0.8 1.56 39 4650 2.0 1.72 41.5 4950 550 480 790 500

    500 3.5 2.4 41 5500 0.50 0.8 1.72 42.5 5750 2.0 1.88 45.5 6050 610 530 910 500

    630 3.5 2.4 44.5 6750 0.50 0.8 1.88 46.5 7100 2.0 1.88 49 7350 680 580 1030 500

    800 3.5 2.6 49 8450 0.50 0.8 1.88 50 8700 2.5 2.04 54 9250 740 630 1140 500

    1000 3.6 2.8 54 10450 0.60 0.8 2.04 55.5 10800 2.5 2.20 59.5 11350 790 670 1250 500

    TABLE 7-3.8 / 6.6 KV (E) HT XLPE SINGLE CORE ALUMINIUM CONDUCTOR CABLES

    POLYCAB SINGLE CORE ALUMINIUM CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING

    TO IS: 7098 PART-2/1985:

    TABLE 8 - 3.8 / 6.6 KV (E) HT XLPE SINGLE CORE COPPER CONDUCTOR CABLES

    POLYCAB SINGLE CORE COPPER CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING

    TO IS: 7098 PART-2/1985:

    WEIGHT, DIMENSION DATA & CURRENT CARRYING CAPACITY OF CABLES

  • 8/12/2019 Polycab Ht Xlpe

    19/36

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    UNARMOURED CABLEMinimum

    Thickness

    of Inner

    Sheath

    ALUMINIUM STRIP ARMOURED CABLE ALUMINIUM ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACITY

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diaeter

    of

    Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimesion

    of

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable.

    Nominal

    Dimesion

    of

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground at

    30 C.

    In Duct at

    30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    35 3.6 2.0 20.5 550 0.30 0.8 1.4 23.0 650 1.6 1.40 23.5 750 120 105 145 500

    50 3.6 2.0 22 600 0.30 0.8 1.4 24.0 700 1.6 1.40 24.5 800 140 125 170 500

    70 3.6 2.0 23.3 700 0.30 0.8 1.4 25.5 800 1.6 1.40 26.5 950 175 155 215 500

    95 3.6 2.0 25 800 0.30 0.8 1.4 27.5 950 1.6 1.40 28 1050 205 180 260 500

    120 3.6 2.0 27 950 0.30 0.8 1.4 29.0 1050 1.6 1.56 30 1200 235 205 305 500

    150 3.6 2.0 28 1050 0.30 0.8 1.56 30.5 1200 1.6 1.56 31.5 1350 260 230 345 500

    185 3.6 2.2 30.5 1250 0.40 0.8 1.56 33.0 1400 2.0 1.56 33.5 1600 295 260 395 500

    240 3.6 2.2 34 1450 0.40 0.8 1.56 35.0 1600 2.0 1.56 36 1850 340 300 470 500

    300 3.6 2.2 34.5 1650 0.40 0.8 1.56 37.0 1850 2.0 1.56 38 2100 385 335 540 500

    400 3.6 2.2 37.5 2000 0.40 0.8 1.72 40.5 2250 2.0 1.72 41.5 2550 440 380 630 500

    500 3.6 2.4 41 2450 0.50 0.8 1.72 43 2650 2.0 1.88 44.5 3000 495 430 730 500

    630 3.6 2.4 44.5 2900 0.50 0.8 1.88 46.5 3200 2.0 1.88 43 3450 560 480 840 500

    800 3.6 2.6 48.5 3500 0.50 0.8 1.88 50.5 3800 2.5 2.04 53 4300 620 530 960 500

    1000 3.6 2.8 53.5 4250 0.60 0.8 2.04 55.5 4600 2.5 2.20 58.5 5150 680 580 1070 500

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    UNARMOURED CABLE

    Minimum

    Thickness

    of Inner

    Sheath

    ALUMINIUM STRIP ARMOURED CABLE ALUMINIUM ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACITY

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diaeter

    of

    Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimesion

    of

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable.

    Nominal

    Dimesion

    of

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground at

    30 C.

    In Duct at

    30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    35 3.6 2.0 21.5 750 0.30 0.8 1.4 23.0 850 1.6 1.40 24.5 950 155 140 185 500

    50 3.6 2.0 23.0 900 0.30 0.8 1.4 24.0 1000 1.6 1.40 25.5 1110 185 160 220 500

    70 3.6 2.0 24.5 1150 0.30 0.8 1.4 25.5 1250 1.6 1.40 27.5 1350 225 195 275 500

    95 3.6 2.0 26.0 1400 0.30 0.8 1.4 27.5 1550 1.6 1.40 29.0 1650 265 235 340 500

    120 3.6 2.0 28.0 1650 0.30 0.8 1.4 29.0 1800 1.6 1.56 31.0 1950 300 265 390 500150 3.6 2.0 29.0 1950 0.30 0.8 1.56 30.5 2150 1.6 1.56 32.5 2250 335 295 440 500

    185 3.6 2.2 31.5 2400 0.40 0.8 1.56 33.0 2550 2.0 1.56 35.5 2750 380 330 510 500

    240 3.6 2.2 33.5 2900 0.40 0.8 1.56 35.0 3100 2.0 1.56 38.0 3350 435 380 600 500

    300 3.6 2.2 36.0 3500 0.40 0.8 1.56 37.0 3700 2.0 1.56 40.0 3950 490 425 680 500

    400 3.6 2.2 39.0 4500 0.40 0.8 1.72 40.5 4750 2.0 1.72 43.5 5050 550 480 790 500

    500 3.6 2.4 42.5 5500 0.50 0.8 1.72 44.0 5800 2.0 1.88 46.5 6100 610 530 910 500

    630 3.6 2.4 46.0 6800 0.50 0.8 1.88 47.5 7100 2.0 1.88 50.0 7350 680 580 1030 500

    800 3.6 2.6 50.0 8450 0.50 0.8 1.88 51.5 8750 2.5 2.04 55.0 9250 740 630 1140 500

    1000 3.6 2.8 55.0 10450 0.60 0.8 2.04 56.5 10800 2.5 2.20 60.5 11350 790 670 1250 500

    TABLE 9 - 6.35/11 KV (E), 6.6/6.6 KV (UE) HT XLPE SINGLE CORE ALUMINIUM CONDUCTOR CABLES

    POLYCAB SINGLE CORE ALUMINIUM CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING

    TO IS: 7098 PART-2/1985:

    TABLE 10 - 6.35/11 KV (E), 6.6/6.6 KV (UE) HT XLPE SINGLE CORE COPPER CONDUCTOR CABLES

    POLYCAB SINGLE CORE COPPER CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING

    TO IS: 7098 PART-2/1985:

    The above data is approximate and subject to manufacturing tolerance.

    * Delivery Length tolerance is 5 %. Length more than normal as per customer request.

    WEIGHT, DIMENSION DATA & CURRENT CARRYING CAPACITY OF CABLES

  • 8/12/2019 Polycab Ht Xlpe

    20/368

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    UNARMOURED CABLEMinimum

    Thickness

    of Inner

    Sheath

    ALUMINIUM STRIP ARMOURED CABLE ALUMINIUM ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACITY

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diaeter

    of

    Cable

    Approx.

    Weight of

    Cable.

    Nominal

    Dimesion

    of

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable.

    Approx.

    Weight of

    Cable.

    Nominal

    Dimesion

    of

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground at

    30 C.

    In Duct at

    30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    70 5.5 2.0 28 850 0.30 0.8 1.56 30.0 1050 1.6 1.56 31.5 1150 175 155 215 500

    95 5.5 2.0 29.5 980 0.30 0.8 1.56 31 1200 2.0 1.56 33.5 1350 205 180 260 500

    120 5.5 2.2 31.5 1150 0.40 0.8 1.56 32.5 1300 2.0 1.56 35.5 1500 235 205 305 500

    150 5.5 2.2 33 1260 0.40 0.8 1.56 34 1450 2.0 1.56 36 1650 260 230 345 500

    185 5.5 2.2 34.5 1430 0.40 0.8 1.56 36 1600 2.0 1.56 38 1850 295 260 395 500

    240 5.5 2.2 36.5 1650 0.40 0.8 1.56 38 1850 2.0 1.72 41 2150 340 300 470 500

    300 5.5 2.2 38.5 1900 0.40 0.8 1.72 40.5 2150 2.0 1.72 43 2400 385 335 540 500

    400 5.5 2.4 42 2300 0.50 0.8 1.72 44 2600 2.0 1.88 46.5 2900 440 380 630 500

    500 5.5 2.4 45 2700 0.50 0.8 1.88 47 3000 2.5 2.04 51 3500 495 430 730 500

    630 5.5 2.6 48.5 3200 0.50 0.8 1.88 50.5 3500 2.5 2.04 53.5 4050 560 480 840 500

    800 5.5 2.8 52.5 3880 0.60 0.8 2.04 54.5 4200 2.5 2.2 58.5 4800 620 530 960 500

    1000 5.5 2.8 57.5 4600 0.60 0.8 2.2 59.5 5000 2.5 2.36 63.5 5650 680 580 1070 500

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    UNARMOURED CABLE

    Minimum

    Thickness

    of Inner

    Sheath

    ALUMINIUM STRIP ARMOURED CABLE ALUMINIUM ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACITY

    *Normal

    Delivery

    Length.

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diaeter

    of

    Cable.

    Approx.

    Weight of

    Cable.

    Nominal

    Dimesion of

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable.

    Approx.

    Weight of

    Cable.

    Nominal

    Dimesion

    of

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable.

    Approx.

    Weight of

    Cable.

    In

    Ground at

    30 C.

    In Duct

    at 30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    70 5.5 2.0 28.5 1300 0.30 0.8 1.56 30.0 1500 1.6 1.56 31.5 1600 225 195 275 500

    95 5.5 2.0 30.0 1550 0.30 0.8 1.56 32.0 1800 2.0 1.56 34.0 1950 265 235 340 500

    120 5.5 2.2 32.0 1900 0.40 0.8 1.56 33.5 2050 2.0 1.56 36.0 2250 300 265 390 500

    150 5.5 2.2 33.5 2200 0.40 0.8 1.56 35.0 2400 2.0 1.56 37.0 2600 335 295 440 500185 5.5 2.2 35.5 2600 0.40 0.8 1.56 37.0 2750 2.0 1.56 39.0 3000 380 330 510 500

    240 5.5 2.2 37.5 3150 0.40 0.8 1.56 39.0 3350 2.0 1.72 42.0 3650 435 380 600 500

    300 5.5 2.2 39.5 3750 0.40 0.8 1.72 41.5 4000 2.0 1.72 44.0 4250 490 425 680 500

    400 5.5 2.4 43.0 4800 0.50 0.8 1.72 45.0 5100 2.0 1.88 47.5 5400 550 480 790 500

    500 5.5 2.4 46.0 5800 0.50 0.8 1.88 48.0 6100 2.5 2.04 52.0 6600 610 530 910 500

    630 5.5 2.6 50.0 7100 0.50 0.8 1.88 51.5 7400 2.5 2.04 55.0 7950 680 580 1030 500

    800 5.5 2.8 54.0 8850 0.60 0.8 2.04 56.0 9150 2.5 2.2 60.0 9750 740 630 1140 500

    1000 5.5 2.8 59.0 10800 0.60 0.8 2.2 61.0 11200 2.5 2.36 65.0 11850 790 670 1250 500

    TABLE 11 - 11/ 11 KV (UE) HT XLPE SINGLE CORE ALUMINIUM CONDUCTOR CABLES

    POLYCAB SINGLE CORE ALUMINIUM CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING

    TO IS: 7098 PART-2/1985:

    TABLE 12 - 11 / 11 KV (UE) HT XLPE SINGLE CORE COPPER CONDUCTOR CABLES

    POLYCAB SINGLE CORE COPPER CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMINGTO IS: 7098 PART-2/1985:

    The above data is approximate and subject to manufacturing tolerance.

    * Delivery Length tolerance is 5 %. Length more than normal as per customer request.

    WEIGHT, DIMENSION DATA & CURRENT CARRYING CAPACITY OF CABLES

  • 8/12/2019 Polycab Ht Xlpe

    21/36

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    UNARMOURED CABLE

    Minimum

    Thickness

    of Inner

    Sheath

    ALUMINIUM STRIP ARMOURED CABLE ALUMINIUM ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACITY

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diaeter

    of

    Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimesion

    of

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimesion

    of

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground at

    30 C.

    In Duct at

    30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    95 6.0 2.2 32.0 1650 0.40 0.8 1.56 33.0 1850 2.0 1.56 36.0 2050 265 230 345 500

    120 6.0 2.2 34.0 1950 0.40 0.8 1.56 35.0 2150 2.0 1.56 37.5 2350 300 260 400 500

    150 6.0 2.2 35.0 2250 0.40 0.8 1.56 36.0 2450 2.0 1.56 39.0 2700 330 290 450 500

    185 6.0 2.2 37.0 2650 0.40 0.8 1.56 38.0 2850 2.0 1.72 41.0 3150 375 325 510 500

    240 6.0 2.2 39.0 3200 0.40 0.8 1.56 40.5 3450 2.0 1.72 43.0 3750 430 370 600 500

    300 6.0 2.2 41.0 3850 0.40 0.8 1.72 43.0 4100 2.0 1.72 45.0 4350 480 415 690 500

    400 6.0 2.4 45.0 4900 0.50 0.8 1.88 47.0 5200 2.0 1.88 49.0 5500 540 465 790 500

    500 6.0 2.6 48.0 5950 0.50 0.8 1.88 50.0 6200 2.5 2.04 53.5 6750 600 520 910 500

    630 6.0 2.6 51.5 7200 0.50 0.8 2.04 54.0 7600 2.5 2.04 57.0 8050 660 570 1020 500

    800 6.0 2.8 56.0 8950 0.60 0.8 2.04 58.0 9300 2.5 2.2 61.0 9900 720 620 1140 500

    1000 6.0 3.0 61.0 11000 0.60 0.8 2.2 62.5 11350 2.5 2.36 66.0 12000 760 660 1240 500

    TABLE 13 - 12.7/22 KV (E) HT XLPE SINGLE CORE ALUMINIUM CONDUCTOR CABLES

    POLYCAB SINGLE CORE ALUMINIUM CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING

    TO IS: 7098 PART-2/1985:

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    UNARMOURED CABLEMinimum

    Thickness

    of Inner

    Sheath

    ALUMINIUM STRIP ARMOURED CABLE ALUMINIUM ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACITY

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diaeter

    of

    Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimesion

    of

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable.

    Nominal

    Dimesion

    of

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground at

    30 C.

    In Duct at

    30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    95 6.0 2.2 32.0 1100 0.40 0.8 1.56 33.0 1250 2.0 1.56 36.0 1450 205 180 270 500

    120 6.0 2.2 34.0 1200 0.40 0.8 1.56 35.0 1400 2.0 1.56 37.5 1600 230 200 310 500

    150 6.0 2.2 35.0 1350 0.40 0.8 1.56 36.0 1530 2.0 1.56 39.0 1750 260 225 350 500

    185 6.0 2.2 37.0 1500 0.40 0.8 1.56 38.0 1700 2.0 1.72 41.0 2000 290 255 400 500

    240 6.0 2.2 39.0 1750 0.40 0.8 1.56 40.5 1950 2.0 1.72 43.0 2250 335 290 470 500

    300 6.0 2.2 41.0 2000 0.40 0.8 1.72 43.0 2250 2.0 1.72 45.0 2500 380 325 540 500

    400 6.0 2.4 45.0 2400 0.50 0.8 1.88 47.0 2700 2.0 1.88 49.0 3000 430 370 630 500

    500 6.0 2.6 48.0 2850 0.50 0.8 1.88 50.0 3100 2.5 2.04 53.5 3650 485 420 730 500

    630 6.0 2.6 51.5 3300 0.50 0.8 2.04 54.0 3700 2.5 2.04 57.0 4150 550 470 840 500

    800 6.0 2.8 56.0 4000 0.60 0.8 2.04 58.0 4350 2.5 2.2 61.0 5000 610 520 950 500

    1000 6.0 3.0 61.0 4800 0.60 0.8 2.2 62.5 5150 2.5 2.36 66.0 5800 660 560 1060 500

    TABLE 14 - 12.7 / 22 KV (E) HT XLPE SINGLE CORE COPPER CONDUCTOR CABLES

    POLYCAB SINGLE CORE COPPER CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING

    TO IS: 7098 PART-2/1985:

    The above data is approximate and subject to manufacturing tolerance.

    * Delivery Length tolerance is 5 %. Length more than normal as per customer request.

    WEIGHT, DIMENSION DATA & CURRENT CARRYING CAPACITY OF CABLES

  • 8/12/2019 Polycab Ht Xlpe

    22/360

    Nominal

    Size of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    UNARMOURED CABLE

    Minimum

    Thickness

    of Inner

    Sheath

    ALUMINIUM STRIP ARMOURED CABLE ALUMINIUM ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACITY

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimension

    of Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimension

    of

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground

    at 30 C.

    In Duct

    at 30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    95 8.8 2.2 37.5 2000 0.40 0.8 1.56 39.0 2200 2.0 1.72 41.5 2550 265 230 345 500

    120 8.8 2.2 39.0 2300 0.40 0.8 1.72 41.0 2550 2.0 1.72 43.0 2800 300 260 400 500

    150 8.8 2.2 40.0 2600 0.40 0.8 1.72 42.0 2850 2.0 1.72 44.5 3100 330 290 450 500

    185 8.8 2.4 43.0 3050 0.50 0.8 1.72 44.5 3300 2.0 1.88 47.0 3650 375 325 510 500

    240 8.8 2.4 45.0 3650 0.50 0.8 1.88 47.0 4000 2.0 1.88 49.5 4250 430 370 600 500300 8.8 2.6 48.0 4350 0.50 0.8 1.88 49.0 4600 2.0 2.04 52.0 4950 480 415 690 500

    400 8.8 2.6 51.0 5350 0.50 0.8 2.04 52.5 5700 2.0 2.04 55.0 6050 540 465 790 500

    500 8.8 2.8 54.0 6450 0.60 0.8 2.04 56.0 6800 2.5 2.2 60.0 7350 600 520 910 500

    630 8.8 2.8 57.5 7000 0.60 0.8 2.2 60.0 8200 2.5 2.36 63.0 8800 660 570 1020 500

    800 8.8 3.0 62.0 9550 0.60 0.8 2.36 64.0 10000 2.5 2.36 67.0 10600 720 620 1140 500

    1000 8.8 3.2 67.0 11600 0.70 0.8 2.36 69.0 12100 2.5 2.52 72.5 12750 760 660 1240 500

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    UNARMOURED CABLEMinimum

    Thickness

    of Inner

    Sheath

    ALUMINIUM STRIP ARMOURED CABLE ALUMINIUM ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACITY

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diaeter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimesion

    of

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimesion

    of

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground at

    30 C.

    In Duct at

    30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    95 8.8 2.2 36.5 1400 0.40 0.8 1.56 38.5 1600 2.0 1.72 41 1900 200 180 270 500

    120 8.8 2.2 38 1550 0.40 0.8 1.72 40.5 1800 2.0 1.72 42.5 2050 230 200 310 500

    150 8.8 2.2 39 1700 0.40 0.8 1.72 41 1950 2.0 1.72 44 2200 260 225 350 500

    185 8.8 2.4 42 1900 0.50 0.8 1.72 43.5 2200 2.0 1.88 46 2500 290 255 400 500

    240 8.8 2.4 44 2200 0.50 0.8 1.88 46 2500 2.0 1.88 48.5 2760 335 290 470 500

    300 8.8 2.6 47 2500 0.50 0.8 1.88 48 2750 2.0 2.04 51 3100 380 325 540 500

    400 8.8 2.6 50 2900 0.50 0.8 2.04 51.5 3250 2.0 2.04 54 3550 430 370 630 500

    500 8.8 2.8 52.5 3400 0.60 0.8 2.04 55 3700 2.5 2.2 59 4250 485 420 730 500

    630 8.8 2.8 56 3900 0.60 0.8 2.2 59 4300 2.5 2.36 62 4900 550 470 840 500

    800 8.8 3.0 60.5 4600 0.60 0.8 2.36 63 5050 2.5 2.36 65.5 5600 610 520 950 500

    1000 8.8 3.2 65 5450 0.70 0.8 2.36 67.5 5900 2.5 2.52 71 6550 660 560 1060 500

    TABLE 15 - 19 / 33 KV (E) HT XLPE SINGLE CORE ALUMINIUM CONDUCTOR CABLES

    POLYCAB SINGLE CORE ALUMINIUM CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING

    TO IS: 7098 PART-2/1985:

    TABLE 16 - 19 / 33 KV (E) HT XLPE SINGLE CORE COPPER CONDUCTOR CABLES

    POLYCAB SINGLE CORE COPPER CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING

    TO IS: 7098 PART-2/1985:

    The above data is approximate and subject to manufacturing tolerance.

    * Delivery Length tolerance is 5 %. Length more than normal as per customer request.

    WEIGHT, DIMENSION DATA & CURRENT CARRYING CAPACITY OF CABLES

  • 8/12/2019 Polycab Ht Xlpe

    23/36

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    UNARMOURED CABLE

    Minimum

    Thickness

    of Inner

    Sheath

    ALUMINIUM STRIP ARMOURED CABLE ALUMINIUM ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACITY

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diaeter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimesion

    of

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimesion

    of

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground at

    30 C.

    In Duct at

    30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    120 9.5 2.2 41.5 2450 0.40 0.8 1.72 43.0 2750 2.0 1.72 45.5 3000 300 260 400 500

    150 9.5 2.4 43.0 2850 0.40 0.8 1.72 44.5 3050 2.0 1.88 47.5 3400 330 290 450 500

    185 9.5 2.4 45.0 3250 0.50 0.8 1.72 46.5 3500 2.0 1.88 49.5 3850 375 325 510 500

    240 9.5 2.4 47.5 3850 0.50 0.8 1.88 49.5 4200 2.5 2.04 53.0 4650 430 370 600 500300 9.5 2.6 50.0 4550 0.50 0.8 1.88 51.5 4850 2.5 2.04 55.0 5350 480 415 690 500

    400 9.5 2.6 53.0 5600 0.50 0.8 2.04 55.0 5950 2.5 2.2 58.5 6500 540 465 790 250

    500 9.5 2.8 56.5 6700 0.60 0.8 2.04 58.0 7050 2.5 2.2 62.0 7650 600 520 910 250

    630 9.5 3.0 60.0 8100 0.60 0.8 2.2 61.5 8450 2.5 2.36 65.5 9100 660 570 1020 250

    800 9.5 3.0 64.0 9800 0.60 0.8 2.36 66.0 10250 3.15 2.52 71.0 11200 720 620 1140 250

    1000 9.5 3.2 69.0 11900 0.70 0.8 2.52 71.0 12450 3.15 2.68 76.0 13450 760 660 1240 200

    TABLE 17 - 33 / 33 KV (UE) HT XLPE SINGLE CORE ALUMINIUM CONDUCTOR CABLE

    POLYCAB SINGLE CORE ALUMINIUM CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING

    TO IS: 7098 PART-2/1985:

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    UNARMOURED CABLEMinimum

    Thickness

    of Inner

    Sheath

    ALUMINIUM STRIP ARMOURED CABLE ALUMINIUM ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACITY

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diaeter

    of Cable

    Approx.

    Weight of

    Cable.

    Nominal

    Dimesion

    of

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimesion

    of

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground at

    30 C.

    In Duct at

    30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    120 9.5 2.2 40 1700 0.40 0.8 1.72 42 2000 2.0 1.72 45.5 2250 230 200 310 500

    150 9.5 2.4 41.5 1900 0.40 0.8 1.72 43.5 2150 2.0 1.88 47.5 2500 260 225 350 500

    185 9.5 2.4 43.5 2100 0.50 0.8 1.72 45 2400 2.0 1.88 49.5 2700 290 255 400 500

    240 9.5 2.4 46 2350 0.50 0.8 1.88 48 2700 2.5 2.04 53.0 3200 335 290 470 500

    300 9.5 2.6 48.5 2650 0.50 0.8 1.88 50 3000 2.5 2.04 55.0 3500 380 325 540 500

    400 9.5 2.6 51 3100 0.50 0.8 2.04 53.5 3450 2.5 2.2 58.5 4000 430 370 630 500

    500 9.5 2.8 54.5 3600 0.60 0.8 2.04 56.5 3950 2.5 2.2 62.0 4550 485 420 730 500

    630 9.5 3.0 58 4200 0.60 0.8 2.2 60 4550 2.5 2.36 65.5 5200 550 470 840 500

    800 9.5 3.0 62 4850 0.60 0.8 2.36 64 5300 3.15 2.52 71.0 6200 610 520 950 500

    1000 9.5 3.2 67 5700 0.70 0.8 2.52 69 6250 3.15 2.68 76.0 7250 660 560 1060 500

    TABLE 18 - 33 / 33 KV (UE) HT XLPE SINGLE CORE COPPER CONDUCTOR CABLE

    POLYCAB SINGLE CORE COPPER CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMINGTO IS: 7098 PART-2/1985:

    The above data is approximate and subject to manufacturing tolerance.

    * Delivery Length tolerance is 5 %. Length more than normal as per customer request.

    WEIGHT, DIMENSION DATA & CURRENT CARRYING CAPACITY OF CABLES

  • 8/12/2019 Polycab Ht Xlpe

    24/362

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    Minimum

    Thickness

    of PVC

    Inner

    Sheath

    UNARMOURED CAB LE FORMED WIRE / STRI P ARMOURED CAB LE ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACIT Y

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx

    Weight

    of Cable

    Nominal

    Dimension

    of GI Flat

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimension

    of GI

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground at

    30 C.

    In Duct at

    30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    35 2.2 0.4 2.2 36.5 1500 0.8 1.56 37.0 1950 2.0 1.72 39.5 2600 115 97 125 500

    50 2.2 0.4 2.2 38.5 1700 0.8 1.72 39.5 2200 2.0 1.72 41.5 2900 130 115 150 500

    70 2.2 0.5 2.4 43 2150 0.8 1.72 43 2650 2.0 1.88 46 3450 160 140 190 500

    95 2.2 0.5 2.6 46 2600 0.8 1.88 46.5 3150 2.5 2.04 50.5 4400 190 165 230 500

    120 2.2 0.5 2.6 48.5 3000 0.8 2.04 50.5 3650 2.5 2.04 53.5 5000 220 190 260 500

    150 2.2 0.6 2.8 53 3500 0.8 2.04 53 4100 2.5 2.2 56.5 5550 245 210 295 500

    185 2.2 0.6 3.0 57.5 4150 0.8 2.2 57.5 4800 2.5 2.36 61 6350 275 240 335 500

    240 2.2 0.7 3.0 62.5 4900 0.8 2.36 63 5750 2.5 2.36 66 7350 315 275 395 500

    300 2.2 0.7 3.2 67 5850 0.8 2.52 68 6650 3.15 2.68 72 9250 355 310 450 500

    400 2.2 0.7 3.6 75 7300 0.8 2.68 74.5 8100 3.15 2.84 79 11000 400 350 520 500

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    Minimum

    Thickness

    of PVC

    Inner

    Sheath

    UNARMOURED CAB LE FORMED WIRE / STRI P ARMOURED CAB LE ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACIT Y

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx

    Weight

    of Cable

    Nominal

    Dimension

    of GI Flat

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimension

    of GI

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground at

    30 C.

    In Duct at

    30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    35 2.2 0.4 2.2 38.0 2150 0.8 1.56 37.0 2600 2.0 1.72 40.5 3250 145 125 165 500

    50 2.2 0.4 2.2 40.0 2650 0.8 1.72 39.5 3150 2.0 1.72 42.5 3800 170 150 195 500

    70 2.2 0.5 2.4 44.5 3450 0.8 1.72 44.0 3950 2.0 1.88 47.0 4750 210 180 240 500

    95 2.2 0.5 2.6 48.5 4350 0.8 1.88 47.5 4950 2.5 2.04 51.5 6150 250 215 295 500

    120 2.2 0.5 2.6 52.0 5250 0.8 2.04 51.5 5900 2.5 2.04 55.5 7200 280 240 335 500

    150 2.2 0.6 2.8 55.5 6300 0.8 2.04 54.5 6900 2.5 2.2 58.5 8350 310 270 380 500

    185 2.2 0.6 3.0 60.0 7600 0.8 2.2 59.0 8250 2.5 2.36 63.0 9800 350 305 430 500

    240 2.2 0.7 3.0 65.0 9350 0.8 2.36 64.5 10250 2.5 2.36 68.0 11800 400 350 500 500

    300 2.2 0.7 3.2 70.0 11400 0.8 2.52 70.0 12250 3.15 2.68 75.0 14850 445 390 510 500

    400 2.2 0.7 3.6 78.0 14750 0.8 2.68 76.5 15550 3.15 2.84 82.0 18450 500 440 650 250

    TABLE 19 - 1.9/3.3 KV (E) & 3.3/3.3 KV (UE) HT XLPE THREE CORE ALUMINIUM CONDUCTOR CABLES

    POLYCAB THREE CORE ALUMINIUM CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED SCREENED CABLES

    CONFORMING TO IS: 7098 PART-2/1985:

    TABLE 20 - 1.9/3.3 KV (E) & 3.3/3.3 (UE) KV HT XLPE THREE CORE COPPER CONDUCTOR CABLES

    POLYCAB THREE CORE COPPER CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED SCREENED CABLESCONFORMING TO IS: 7098 PART-2/1985:

    The above data is approximate and subject to manufacturing tolerance.

    * Delivery Length tolerance is 5 %. Length more than normal as per customer request.

    WEIGHT, DIMENSION DATA & CURRENT CARRYING CAPACITY OF CABLES

  • 8/12/2019 Polycab Ht Xlpe

    25/36

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    MinimumThickness

    of PVC

    Inner

    Sheath

    UNARMOURED CAB LE FORMED WIRE / STRI P ARMOURED CAB LE ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACIT Y

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable.

    Approx

    Weight

    of Cable

    Nominal

    Dimension

    of GI Flat

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimension

    of GI

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground at

    30 C.

    In Duct at

    30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    35 2.8 0.4 2.2 38.5 1600 0.8 1.72 40.0 2200 2.0 1.72 42 2800 115 97 125 500

    50 2.8 0.5 2.4 41.5 1950 0.8 1.72 42.5 2500 2.0 1.88 44.5 3200 130 115 150 500

    70 2.8 0.5 2.6 45.5 2350 0.8 1.88 46 3000 2.0 1.88 48 3700 160 140 190 500

    95 2.8 0.5 2.6 49 2800 0.8 1.88 49.5 3400 2.5 2.04 52.5 4700 190 165 230 500

    120 2.8 0.6 2.8 53 3300 0.8 2.04 54 4000 2.5 2.20 57 5400 220 190 260 500

    150 2.8 0.6 2.8 56 3800 0.8 2.2 56.5 4500 2.5 2.2 59.5 5900 245 210 295 500

    185 2.8 0.6 3.0 61 4400 0.8 2.2 60.5 5150 2.5 2.36 63.5 6700 275 240 335 500

    240 2.8 0.7 3.2 65 5300 0.8 2.36 68 6100 3.15 2.52 70.5 8600 315 275 395 500

    300 3.0 0.7 3.4 71 6300 0.8 2.52 71.5 7160 3.15 2.68 76 9900 355 310 450 500

    400 3.3 0.7 3.8 80 8000 0.8 2.84 80 9000 4.0 3.0 86.5 13200 400 350 520 500

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    Minimum

    Thickness

    of PVC

    Inner

    Sheath

    UNARMO URED CABLE FORMED WIRE / STRIP ARMOURED CAB LE ROUND WI RE ARMOURED CAB LE CURRENT CARRYING CAPACIT Y

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx

    Weight

    of Cable

    Nominal

    Dimension

    of GI Flat

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimension

    of GI Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground at

    30 C.

    In Duct

    at 30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    35 2.8 0.4 2.2 40.0 2250 0.8 1.72 40.0 2850 2.0 1.72 43.0 3450 145 125 165 500

    50 2.8 0.5 2.4 43.0 2850 0.8 1.72 42.5 3400 2.0 1.88 45.5 4150 170 150 195 500

    70 2.8 0.5 2.6 47.0 3650 0.8 1.88 47.0 4250 2.0 1.88 49.5 5000 210 180 240 500

    95 2.8 0.5 2.6 51.0 4550 0.8 1.88 50.5 5200 2.5 2.04 54.0 6500 250 215 295 500

    120 2.8 0.6 2.8 55.0 5500 0.8 2.04 55.0 6200 2.5 2.20 58.5 7600 280 240 335 500

    150 2.8 0.6 2.8 58.0 6550 0.8 2.2 58.0 7250 2.5 2.2 61.0 8700 310 270 380 500

    185 2.8 0.6 3.0 63.0 7850 0.8 2.2 62.0 8600 2.5 2.36 66.0 10150 350 305 430 500

    240 2.8 0.7 3.2 68.0 9800 0.8 2.36 67.5 10550 3.15 2.52 73.0 13050 400 350 500 500

    300 3.0 0.7 3.4 74.0 11900 0.8 2.52 73.5 12750 3.15 2.68 78.5 15450 445 390 570 250

    400 3.3 0.7 3.8 83.0 15400 0.8 2.84 82.0 16400 4.0 3.0 89.0 20650 500 440 650 200

    TABLE 21 - 3.8 / 6.6 KV (E) HT XLPE THREE CORE ALUMINIUM CONDUCTOR CABLES

    POLYCAB THREE CORE ALUMINIUM CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING

    TO IS: 7098 PART-2/1985:

    TABLE 22 - 3.8/6.6 KV (E) HT XLPE THREE CORE COPPER CONDUCTOR CABLES

    POLYCAB THREE CORE COPPER CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING

    TO IS: 7098 PART-2/1985:

    The above data is approximate and subject to manufacturing tolerance.

    * Delivery Length tolerance is 5 %. Length more than normal as per customer request.

    WEIGHT, DIMENSION DATA & CURRENT CARRYING CAPACITY OF CABLES

  • 8/12/2019 Polycab Ht Xlpe

    26/364

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    MinimumThickness

    of PVC

    Inner

    Sheath

    UNARMOURED CAB LE FORMED WIRE / STRI P ARMOURED CAB LE ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACIT Y

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx

    Weight

    of Cable

    Nominal

    Dimension

    of GI Flat

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimension

    of GI

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground at

    30 C.

    In Duct at

    30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    35 3.6 0.5 2.4 43.5 1950 0.8 1.72 44.0 2500 2.0 1.88 45.5 3250 115 97 125 500

    50 3.6 0.5 2.6 46.5 2250 0.8 1.88 46.5 2850 2.5 2.04 49.5 4000 130 115 150 500

    70 3.6 0.5 2.6 50.5 2650 0.8 1.88 50.5 3300 2.5 2.04 53.5 4600 160 140 190 500

    95 3.6 0.6 2.8 54.5 3150 0.8 2.04 54.5 3850 2.5 2.20 58.0 5250 190 165 230 500

    120 3.6 0.6 2.8 58.0 3600 0.8 2.2 58.5 4400 2.5 2.20 61.5 5850 220 190 260 500

    150 3.6 0.6 3.0 61.0 4100 0.8 2.2 61.0 4900 2.5 2.36 64.5 6450 245 210 295 500

    185 3.6 0.7 3.2 66.0 4850 0.8 2.36 66.0 5650 3.15 2.52 71.0 8100 275 240 335 500

    240 3.6 0.7 3.4 71.5 5700 0.8 2.52 71.5 6600 3.15 2.68 76.0 9250 315 275 395 500

    300 3.6 0.7 3.6 76.5 6650 0.8 2.68 76.5 7600 3.15 2.84 81.0 10400 355 310 450 250

    400 3.6 0.7 3.8 83.5 8100 0.8 2.84 83.5 9100 4.0 3.0 90.0 13450 400 350 520 250

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    Minimum

    Thickness

    of PVC

    Inner

    Sheath

    UNARMOURED CAB LE FORMED WIRE / STRI P ARMOURED CAB LE ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACIT Y

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx

    Weight

    of Cable

    Nominal

    Dimension

    of GI Flat

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimension

    of GI

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground at

    30 C.

    In Duct at

    30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    35 3.6 0.5 2.4 43.5 2600 0.8 1.72 44.0 3150 2.0 1.88 45.5 3900 145 125 165 500

    50 3.6 0.5 2.6 46.5 3150 0.8 1.88 46.5 3750 2.5 2.04 49.5 4950 170 150 195 500

    70 3.6 0.5 2.6 50.5 3950 0.8 1.88 50.5 4600 2.5 2.04 53.5 5900 210 180 240 500

    95 3.6 0.6 2.8 54.5 4950 0.8 2.04 54.5 5600 2.5 2.20 58.0 7000 250 215 295 500

    120 3.6 0.6 2.8 58.0 5850 0.8 2.2 58.5 6650 2.5 2.20 61.5 8100 280 240 335 500

    150 3.6 0.6 3.0 61.0 6900 0.8 2.2 61.0 7650 2.5 2.36 64.5 9250 310 270 380 500

    185 3.6 0.7 3.2 66.0 8300 0.8 2.36 66.0 9100 3.15 2.52 71.0 11550 350 305 430 500

    240 3.6 0.7 3.4 71.5 10200 0.8 2.52 71.5 11050 3.15 2.68 76.0 13700 400 350 500 250

    300 3.6 0.7 3.6 76.5 12200 0.8 2.68 76.5 13150 3.15 2.84 81.0 15950 445 390 570 250

    400 3.6 0.7 3.8 83.5 15550 0.8 2.84 83.5 16550 4.0 3.0 90.0 20900 500 440 650 250

    TABLE 23 - 6.35 / 11 KV (E) HT XLPE THREE CORE ALUMINIUM CONDUCTOR CABLES

    POLYCAB THREE CORE ALUMINIUM CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING

    TO IS: 7098 PART-2/1985:

    TABLE 24 - 6.35 / 11 KV (E) HT XLPE THREE CORE COPPER CONDUCTOR CABLES

    POLYCAB THREE CORE COPPER CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING

    TO IS: 7098 PART-2/1985:

    The above data is approximate and subject to manufacturing tolerance.

    * Delivery Length tolerance is 5 %. Length more than normal as per customer request.

    WEIGHT, DIMENSION DATA & CURRENT CARRYING CAPACITY OF CABLES

  • 8/12/2019 Polycab Ht Xlpe

    27/36

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    Minimum

    Thickness

    of PVC

    Inner

    Sheath

    UNARMOURED CAB LE FORMED WIRE / STRI P ARMOURED CAB LE ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACIT Y

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx

    Weight

    of Cable

    Nominal

    Dimension

    of GI Flat

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimension

    of GI

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground at

    30 C.

    In Duct at

    30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    70 5.5 0.6 3.0 59.5 3550 0.8 2.2 59.5 4300 2.5 2.36 63.0 5900 160 140 190 500

    95 5.5 0.6 3.2 63.5 4100 0.8 2.36 63.5 4900 3.15 2.52 68.5 7250 190 165 230 500

    120 5.5 0.7 3.2 67.5 4650 0.8 2.36 67.5 5500 3.15 2.52 72.0 8000 220 190 260 500

    150 5.5 0.7 3.4 70.5 5200 0.8 2.52 70.5 6100 3.15 2.68 75.0 8650 245 210 295 500

    185 5.5 0.7 3.4 74.5 5900 0.8 2.68 74.5 6950 3.15 2.84 80.0 9650 275 240 335 500

    240 5.5 0.7 3.6 80.0 6850 0.8 2.84 80.0 7900 3.15 3.0 85.0 10850 315 275 395 250

    300 5.5 0.7 3.8 85.0 7850 0.8 3.0 85.5 8950 4.0 3.0 91.0 13250 355 310 450 250

    400 5.5 0.7 4.0 92.0 9400 0.8 3.0 92.0 10500 4.0 3.0 98.0 15200 400 350 520 250

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    Minimum

    Thickness

    of PVC

    Inner

    Sheath

    UNARMO URED CABLE FORMED WIRE / STRIP ARMOURED CAB LE ROUND WI RE ARMOURED CAB LE CURRENT CARRYING CAPACIT Y

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx

    Weight

    of Cable

    Nominal

    Dimension

    of GI Flat

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimension

    of GI Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground at

    30 C.

    In Duct

    at 30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    70 5.5 0.6 3.0 59.5 4900 0.8 2.2 59.5 5600 2.5 2.36 63.0 7150 210 180 240 500

    95 5.5 0.6 3.2 63.5 5900 0.8 2.36 63.5 6700 3.15 2.52 68.5 9000 250 215 295 500

    120 5.5 0.7 3.2 67.5 6900 0.8 2.36 67.5 7750 3.15 2.52 72.0 10250 280 240 335 500

    150 5.5 0.7 3.4 70.5 8000 0.8 2.52 70.5 8900 3.15 2.68 75.0 11450 310 270 380 500

    185 5.5 0.7 3.4 74.5 9300 0.8 2.68 74.5 10300 3.15 2.84 80.0 13100 350 305 430 250

    240 5.5 0.7 3.6 80.0 11300 0.8 2.84 80.0 12350 3.15 3.0 85.0 15350 400 350 500 250

    300 5.5 0.7 3.8 85.0 13400 0.8 3.0 85.5 14500 4.0 3.0 91.0 18850 445 390 570 250

    400 5.5 0.7 4.0 92.0 16850 0.8 3.0 92.0 17950 4.0 3.0 98.0 22650 500 440 650 250

    TABLE 25 - 11 / 11 KV (UE) HT XLPE THREE CORE ALUMINIUM CONDUCTOR CABLES

    POLYCAB THREE CORE ALUMINIUM CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING

    TO IS: 7098 PART-2/1985:

    TABLE 26 - 11 / 11 KV (UE) HT XLPE THREE CORE COPPER CONDUCTOR CABLES

    POLYCAB THREE CORE COPPER CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING

    TO IS: 7098 PART-2/1985:

    The above data is approximate and subject to manufacturing tolerance.

    * Delivery Length tolerance is 5 %. Length more than normal as per customer request.

    WEIGHT, DIMENSION DATA & CURRENT CARRYING CAPACITY OF CABLES

  • 8/12/2019 Polycab Ht Xlpe

    28/366

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    Minimum

    Thickness

    of PVC

    Inner

    Sheath

    UNARMOURED CAB LE FORMED WIRE / STRI P ARMOURED CAB LE ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACIT Y

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx

    Weight

    of Cable

    Nominal

    Dimension

    of GI Flat

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimension

    of GI

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground at

    30 C.

    In Duct at

    30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    95 6.0 0.7 3.2 66.0 4450 0.8 2.36 66.0 5300 3.15 2.52 71.0 7750 190 170 230 500

    120 6.0 0.7 3.4 70.0 5050 0.8 2.52 70.0 5900 3.15 2.68 75.0 8500 215 190 265 500

    150 6.0 0.7 3.4 72.5 5550 0.8 2.68 72.5 6500 3.15 2.68 77.5 9200 240 215 300 250

    185 6.0 0.7 3.6 77.5 6300 0.8 2.68 77.5 7250 3.15 2.84 82.0 10150 270 240 340 250

    240 6.0 0.7 3.8 82.5 7300 0.8 2.84 82.5 8300 4.0 3.0 89.0 12600 310 275 400 250

    300 6.0 0.7 4.0 87.5 8300 0.8 3.0 87.5 9350 4.0 3.0 93.5 13850 350 310 455 250

    400 6.0 0.7 4.0 94.5 9850 0.8 3.0 94.5 10950 4.0 3.0 100.0 15800 395 355 530 250

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    Minimum

    Thickness

    of PVC

    Inner

    Sheath

    UNARMOURED CAB LE FORMED WIRE / STRI P ARMOURED CAB LE ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACIT Y

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx

    Weight

    of Cable

    Nominal

    Dimension

    of GI Flat

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimension

    of GI

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground at

    30 C.

    In Duct at

    30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    95 6.0 0.7 3.2 66.0 6200 0.8 2.36 66.0 7050 3.15 2.52 71.0 9500 245 215 300 500

    120 6.0 0.7 3.4 70.0 7300 0.8 2.52 70.0 8150 3.15 2.68 75.0 10750 275 245 340 500

    150 6.0 0.7 3.4 72.5 8300 0.8 2.68 72.5 9300 3.15 2.68 77.5 11950 305 275 385 250

    185 6.0 0.7 3.6 77.5 9750 0.8 2.68 77.5 10700 3.15 2.84 82.0 13600 345 305 435 250

    240 6.0 0.7 3.8 82.5 11750 0.8 2.84 82.5 12750 4.0 3.0 89.5 17050 395 350 510 250

    300 6.0 0.7 4.0 87.5 13900 0.8 3.0 87.5 14950 4.0 3.0 93.5 19400 440 390 580 250

    400 6.0 0.7 4.0 94.5 17250 0.8 3.0 94.5 18400 4.0 3.0 100.0 23250 495 440 660 200

    TABLE 27 - 12.7/22 KV (E) HT XLPE THREE CORE ALUMINIUM CONDUCTOR CABLES

    POLYCAB THREE CORE ALUMINIUM CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING

    TO IS: 7098 PART-2/1985:

    TABLE 28 - 12.7 / 22 KV (E) HT XLPE THREE CORE COPPER CONDUCTOR CABLES

    POLYCAB THREE CORE COPPER CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING

    TO IS: 7098 PART-2/1985:

    The above data is approximate and subject to manufacturing tolerance.

    * Delivery Length tolerance is 5 %. Length more than normal as per customer request.

    WEIGHT, DIMENSION DATA & CURRENT CARRYING CAPACITY OF CABLES

  • 8/12/2019 Polycab Ht Xlpe

    29/36

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    Minimum

    Thickness

    of PVC

    Inner

    Sheath

    UNARMOURED CAB LE FORMED WIRE / STRI P ARMOURED CAB LE ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACIT Y

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable.

    Approx

    Weight

    of Cable

    Nominal

    Dimension

    of GI Flat

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimension

    of GI

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable.

    In

    Ground at

    30 C.

    In Duct at

    30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    95 8.8 0.7 3.6 79.0 6050 0.8 2.84 79.0 7100 3.15 3.0 84.0 10050 190 170 230 500

    120 8.8 0.7 3.8 83.0 6750 0.8 2.84 83.0 7750 4.0 3.0 89.5 12100 215 190 265 500

    150 8.8 0.7 4.0 86.5 7400 0.8 3.0 86.5 8400 4.0 3.0 92.0 12800 240 215 300 250

    185 8.8 0.7 4.0 90.5 8150 0.8 3.0 90.0 9250 4.0 3.0 96.5 13900 270 240 340 250

    240 8.8 0.7 4.0 95.5 9150 0.8 3.0 95.5 10300 4.0 3.0 101.0 15150 310 275 400 250

    300 8.8 0.7 4.0 100.0 10200 0.8 3.0 100.0 11350 4.0 3.0 105.5 16450 350 310 455 250

    400 8.8 0.7 4.0 106.5 11800 0.8 3.0 106.5 13100 4.0 3.0 112.5 18550 395 355 530 250

    Nominal

    Size

    of

    Conductor

    Nominal

    Thickness

    of XLPE

    Insulation

    Minimum

    Thickness

    of PVC

    Inner

    Sheath

    UNARMOURED CAB LE FORMED WIRE / STRI P ARMOURED CAB LE ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACIT Y

    *Normal

    Delivery

    Length

    Nominal

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx

    Weight

    of Cable

    Nominal

    Dimension

    of GI Flat

    Strip

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    Nominal

    Dimension

    of GI

    Round

    Wire

    Minimum

    Thickness

    of PVC

    Outer

    Sheath

    Approx.

    Overall

    Diameter

    of Cable

    Approx.

    Weight of

    Cable

    In

    Ground at

    30 C.

    In Duct at

    30 C.

    In Air at

    40 C.

    Sq.mm. mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km Amps. Amps. Amps. Mtrs.

    95 8.8 0.7 3.6 79.0 7850 0.8 2.84 79.0 8900 3.15 3.0 84.0 11800 245 215 300 250

    120 8.8 0.7 3.8 83.0 9000 0.8 2.84 83.0 10000 4.0 3.0 89.5 14300 275 245 340 250

    150 8.8 0.7 4.0 86.5 10150 0.8 3.0 86.5 11200 4.0 3.0 92.0 15600 305 275 385 250

    185 8.8 0.7 4