PROGRAMMER FOR FLAME START AND SUPERVISION, AND SAFE STOP OF BURNER MODEL: PRG-Ie-IIIMe---C-P-O TECHNICAL SHEET 1/8 Customer Service 55 11 3019-1616 For further details, see technical bulletin SELCON SISTEMAS ELETRÔNICOS DE CONTROLE LTDA. CNPJ 56.935.877/0001-29 Rua. Américo Samarone, 502 • CEP 04284-000 • Moinho Velho • São Paulo • SP • Brasil • Phone/Fax: (55 11) 3019-1616 http://www.selcon.com.br Representative or Retailer: Selcon Ltda., keeps the right to modify this technical sheet whenever it is necessary – Mar./2013 APPLICATION Programmer PRG-Ie-IIIMe is a piece of equipment used for flame start and supervision as well as for safe stop for commercial or industrial gas, oil or any type of fuel burners, used in burners with discontinuous operation (turn burner on / off in less than 24h), with power smaller than 120 KW (100 000 Kcal/h). For use in the combustion chamber closed, the user must provide safe system of pre-purge before each starting sequence, or order the programmer PRG-Ie-IIIMe with purge timer built in and since the purge time is suitable for application. This product meets the requirements of ABNT NBR 12313 regulation. 12313 – rev. Sept./2000. According to the type of sensor chosen, the options are the following: PRG-Ie-IIIMe-I input for ionization flame sensor, when gas is used as fuel in burners which operate with this type of sensor. See electrodes, line SEL-HT or SEL-HT-E (electrode assembled under draft or sample from the special-client). PRG-Ie-IIIMe-IG single input for double-function rod: - ignition and ionization flame sensor, when gas is used as fuel in burners designed to operate using such sensor. See sensor electrodes, line SEL-HT or SEL-HT-E (electrode assembled under draft or sample from the special-client). In this configuration, the sensor electrode also works as an ignitor electrode. PRG-Ie-IIIMe-L- input for photo resistance sensor of cadmium sulfide – visible radiation when using oil or any type of fuel which provokes flame with emission of yellow light. See sensors, line SEL-SV-L. PRG-Ie-IIIMe-U - input for ultraviolet radiation sensor, when using gas, light oils or any type of fuel which provokes flame with emission of ultraviolet rays. See sensor model SEL-SV-U. TECHNICAL DATA Watch dog microprocessing – safe failure Local reset with 3 (three) sec. Safety to prepare the reset system Flame sensoring inlets: I, IG, U, L or F – t To order, see code field Useful life of outlet relays: > 100.000 operations Expected mechanical life of output contacts: > 10.000.000 operations Protection of the flame circuit during the ignition period Protection against failure due to short circuit of the ionization sensor Protection against tension outbreaks Fuse protection for circuits and outlet (F1) assembled on BASE Ie-IIIMe – code MST-250V – 6,3 A. 115 VAC or 220 VAC +10 -15% feeding (phase /phase or phase / neutral non-grounded) - 50/60 Hz ± 3%. Note: Equipment originally configured for 220Vac. To alter feeding, change jumper to 115 VAC position – See figure 2. Power consumption: 5 VA Working temperature: 0ºC to 60ºC Minimum flame current (dc-uA): I 2 / U 200 / L 500 / F 2000 NOTE: The cable of flame sensor must be installed separately from the other cables that constitute the set burner control. The best type of cable recommended for this purpose is the one used for igni- tion.

Upload: others

Post on 05-Feb-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

  • PPRROOGGRRAAMMMMEERR FFOORR FFLLAAMMEE SSTTAARRTT AANNDD SSUUPPEERRVVIISSIIOONN,,

    AANNDD SSAAFFEE SSTTOOPP OOFF BBUURRNNEERR

    MODEL: PRG-Ie-IIIMe-�-�-C��-P�-O� TECHNICAL SHEET 1/8 � Customer Service 55 11 3019-1616 For further details, see technical bulletin

    SELCON SISTEMAS ELETRÔNICOS DE CONTROLE LTDA. CNPJ 56.935.877/0001-29 Rua. Américo Samarone, 502 • CEP 04284-000 • Moinho Velho

    • São Paulo • SP • Brasil • Phone/Fax: (55 11) 3019-1616

    http://www.selcon.com.br

    Representative or Retailer:

    Selcon Ltda., keeps the right to modify this technical

    sheet whenever it is necessary – Mar./2013

    • APPLICATION Programmer PRG-Ie-IIIMe is a piece of equipment used for flame start and supervision as well as for safe stop for commercial or industrial gas, oil or any type of fuel burners, used in burners with discontinuous operation (turn burner on / off in less than 24h), with power smaller than 120 KW (100 000 Kcal/h). For use in the combustion chamber closed, the user must provide safe system of pre-purge before each starting sequence, or order the programmer PRG-Ie-IIIMe with purge timer built in and since the purge time is suitable for application.

    This product meets the requirements of ABNT NBR 12313 regulation. 12313 – rev. Sept./2000.

    According to the type of sensor chosen, the options are the following:

    ⇒ PRG-Ie-IIIMe-I – input for ionization flame sensor, when gas is used as fuel in burners which operate with this type of sensor. See electrodes, line SEL-HT or SEL-HT-E (electrode assembled under draft or sample from the special-client).

    ⇒ PRG-Ie-IIIMe-IG – single input for double-function rod: - ignition and ionization flame sensor, when gas is used as fuel in burners designed to operate using such sensor. See sensor electrodes, line SEL-HT or SEL-HT-E (electrode assembled under draft or sample from the special-client). In this configuration, the sensor electrode also works as an ignitor electrode.

    ⇒ PRG-Ie-IIIMe-L- input for photo resistance sensor of cadmium sulfide – visible radiation when using oil or any type of fuel which provokes flame with emission of yellow light. See sensors, line SEL-SV-L.

    ⇒ PRG-Ie-IIIMe-U - input for ultraviolet radiation sensor, when using gas, light oils or any type of fuel which provokes flame with emission of ultraviolet rays. See sensor model SEL-SV-U.

    • TECHNICAL DATA

    ⇒ Watch dog microprocessing – safe failure ⇒ Local reset with 3 (three) sec. Safety to prepare the reset system

    ⇒ Flame sensoring inlets: I, IG, U, L or F – t To order, see code field

    ⇒ Useful life of outlet relays: > 100.000 operations

    ⇒ Expected mechanical life of output contacts: > 10.000.000 operations

    ⇒ Protection of the flame circuit during the ignition period

    ⇒ Protection against failure due to short circuit of the ionization sensor

    ⇒ Protection against tension outbreaks

    ⇒ Fuse protection for circuits and outlet (F1) assembled on BASE Ie-IIIMe – code MST-250V – 6,3 A.

    ⇒ 115 VAC or 220 VAC +10 -15% feeding (phase /phase or phase / neutral non-grounded) - 50/60 Hz ± 3%.

    Note: Equipment originally configured for 220Vac. To alter feeding, change jumper to 115 VAC

    position – See figure 2.

    ⇒ Power consumption: 5 VA

    ⇒ Working temperature: 0ºC to 60ºC

    ⇒ Minimum flame current (dc-uA): I � 2 / U � 200 / L � 500 / F � 2000

    NOTE: The cable of flame sensor must be installed separately from the other cables that constitute

    the set burner control. The best type of cable recommended for this purpose is the one used for igni-

    tion.

  • PPRROOGGRRAAMMMMEERR FFOORR FFLLAAMMEE SSTTAARRTT AANNDD SSUUPPEERRVVIISSIIOONN,,

    AANNDD SSAAFFEE SSTTOOPP OOFF BBUURRNNEERR

    MODEL: PRG-Ie-IIIMe-�-�-C��-P�-O� TECHNICAL SHEET 2/8 � Customer Service 55 11 3019-1616 For further details, see technical bulletin

    SELCON SISTEMAS ELETRÔNICOS DE CONTROLE LTDA. CNPJ 56.935.877/0001-29 Rua. Américo Samarone, 502 • CEP 04284-000 • Moinho Velho

    • São Paulo • SP • Brasil • Phone/Fax: (55 11) 3019-1616

    http://www.selcon.com.br

    Representative or Retailer:

    Selcon Ltda., keeps the right to modify this technical

    sheet whenever it is necessary – Mar./2013

    ⇒ Verification of anticipated or false flame signal, before the start of ignition.

    ⇒ Ambient protection degree: IP 50 (with inlet / outlet cable press installed)

    ⇒ Fixation: BASE Ie to be assembled on any internal or external surface on the panel.

    ⇒ Automatic test of air flow switch or pressure switch: N.A. before fan start, and N.F. continuously, after fan

    start.

    ⇒ Purge time: programmable (to order, see time / sequence diagram and code)

    ⇒ Anticipated flame check: up to 0.5 sec. (prior to the beginning of ignition start).

    ⇒ Ignition time: programmable

    ⇒ Confirmation time for flame inlet: < 1 sec (for anyone of the flame inlets).

    ⇒ Time for pilot light stabilization or 1st phase: programmable

    ⇒ Blocking time for flame failure: < 4 sec.

    ⇒ Automatic recycle: Programmable to make one attempt for re-lighting in case of ignition or flame failures.

    ⇒ Maximum outlet currents (250 Vacmax)

    • Vpil : 1,5 A (NA) • Vpri : 1,5 A (NA) • Fan: 1,5 A (NA) – To order, see code field • External ignition converter : 2 A (NA) – To order, see code field • Blocking remote outlet 1,5 A (NA)

    ⇒ Local ON /OFF switch (L/D) optional

    ⇒ Local Signalization – equipment on – red on

    ⇒ Local Signalization – with flame – green on

    ⇒ Local Signalization with anticipated flame – orange on

    ⇒ Assembling through the basis – code BASE Ie-IIIMe, see figure 2 underneath.

    ⇒ Electric connections: by using terminal binding rod, assembled on BASE Ie-IIIMe. We suggest the use of flex-ible and extra-flexible cables. Maximum thickness of 1.5 mm².

    ⇒ Weight: 450 grams

    ⇒ Warranty: 12 months (see terms of warranty)

  • PPRROOGGRRAAMMMMEERR FFOORR FFLLAAMMEE SSTTAARRTT AANNDD SSUUPPEERRVVIISSIIOONN,,

    AANNDD SSAAFFEE SSTTOOPP OOFF BBUURRNNEERR

    MODEL: PRG-Ie-IIIMe-�-�-C��-P�-O� TECHNICAL SHEET 3/8 � Customer Service 55 11 3019-1616 For further details, see technical bulletin

    SELCON SISTEMAS ELETRÔNICOS DE CONTROLE LTDA. CNPJ 56.935.877/0001-29 Rua. Américo Samarone, 502 • CEP 04284-000 • Moinho Velho

    • São Paulo • SP • Brasil • Phone/Fax: (55 11) 3019-1616

    http://www.selcon.com.br

    Representative or Retailer:

    Selcon Ltda., keeps the right to modify this technical

    sheet whenever it is necessary – Mar./2013

    • Dimensional Draft ( mm )

    96.6

    102.6

    101.3

    FRONT VIEW SIDE VIEW

    Site : CNPJ 56.935.877/0001-29

    PRODUTO :

    Rearme Código

    Modelo

    Série

    Ligado

    L/DIndústria Brasileira

    BloqueioChama /

    On/Off switch(optional)

    FIGURE 1

    POWER FUSE 6,3ACode MST-250V

    FEEDING VOLTAGE (EQUIPAMENT ADJUSTED TO

    115v 220v

    F16,3A

    NF-14

    NA-15

    C-16

    NF-17

    NA-18

    C-19

    20

    21

    22

    23

    24

    2526

    SAÍDA 1

    SAÍDA 2

    ALARME

    VS1

    IGNIÇÃO

    COMUM

    TRAFO

    N

    F

    3

    4

    5

    6

    7

    8

    9

    1011

    12

    ENT2

    ENT1

    MASSA

    CH2

    ENT3

    CH1

    N/L1

    L2ALIM. AC

    J3

    BASE M-III Me - Front View

    SELECTION JUMPER FOR

    220V WHEN MANUFACTURED)

    FIGURE 2

  • PPRROOGGRRAAMMMMEERR FFOORR FFLLAAMMEE SSTTAARRTT AANNDD SSUUPPEERRVVIISSIIOONN,,

    AANNDD SSAAFFEE SSTTOOPP OOFF BBUURRNNEERR

    MODEL: PRG-Ie-IIIMe-�-�-C��-P�-O� TECHNICAL SHEET 4/8 � Customer Service 55 11 3019-1616 For further details, see technical bulletin

    SELCON SISTEMAS ELETRÔNICOS DE CONTROLE LTDA. CNPJ 56.935.877/0001-29 Rua. Américo Samarone, 502 • CEP 04284-000 • Moinho Velho

    • São Paulo • SP • Brasil • Phone/Fax: (55 11) 3019-1616

    http://www.selcon.com.br

    Representative or Retailer:

    Selcon Ltda., keeps the right to modify this technical

    sheet whenever it is necessary – Mar./2013

    BASE

    LID

    SCREW OFFIXATION OF COVER

    �THE CUT THE BED OF THE PRESS-CABLE, MUST BE DONE AS ACCURATEAS POSSIBLE, SO THAT THERE INTERFERENCE IN TIME SLOT.ONLY THE ITEMS AND QUANTITIES AS MAY BE REQUIRED.

    AFTER FIXING THEPRESS-CABLE GLANDS, SNAPTHEM TEARS IN ITS COVER,AFTER CLOSE IN BASE.(SUPPLIED BY SELCON)

    CABLEGROUNDING(PROVIDED BYSELCON).ACCORDANCE WITH THECODE OF REQUEST.

    CABLES CONNECTIONS(EXECUTED BY THE CUSTOMER)(Figure Illustrative QUANTITIES OFCABLES AS YOU NEED.)

    OPEN THE PRESS-CABLEAND WRAP IT TO THE CAPE,PRESS THE PARTIES.LEAVE A SLACK IN THECABLE ENOUGH FORASSEMBLY.HIGH VOLTAGE CABLE

    (PROVIDED BY SELCON).

    DO NOT FORCE THE FITTINGDURING CLOSING THE LID ONBASE, FOR BOLT FIXING TOTHIS WILL SCREW IT.

    FIGURE 3

  • PPRROOGGRRAAMMMMEERR FFOORR FFLLAAMMEE SSTTAARRTT AANNDD SSUUPPEERRVVIISSIIOONN,,

    AANNDD SSAAFFEE SSTTOOPP OOFF BBUURRNNEERR

    MODEL: PRG-Ie-IIIMe-�-�-C��-P�-O� TECHNICAL SHEET 5/8 � Customer Service 55 11 3019-1616 For further details, see technical bulletin

    SELCON SISTEMAS ELETRÔNICOS DE CONTROLE LTDA. CNPJ 56.935.877/0001-29 Rua. Américo Samarone, 502 • CEP 04284-000 • Moinho Velho

    • São Paulo • SP • Brasil • Phone/Fax: (55 11) 3019-1616

    http://www.selcon.com.br

    Representative or Retailer:

    Selcon Ltda., keeps the right to modify this technical

    sheet whenever it is necessary – Mar./2013

    • DIAGRAM FOR ELECTRIC CONNECTIONS

    Ps Ar

    PsAr

    F N(L1)

    L/D

    Vpr Vpi V

    12

    VS PRINCIPAL

    (6,3A)

    L2

    N/L1

    ALIM. AC

    N(L1)F 1817 19

    VAC115

    F1

    220VAC

    VS PILOTO

    EXTERNO

    1413 11

    VENT.

    109 7

    REARME

    LL/D

    CH/BL

    BLRr

    Q

    IG

    T

    IO/IG TI EXT

    REARME

    8 15 516

    ALARME

    6 20 2221

    AZ

    BR/IO

    43

    ACS-TE-

    PRG-Ie

    ELECTRIC DIAGRAM OF CONNECTION IN THE BASE OF THE INTERNAL TRANSFORMER PROGRAMMER WITH ONE IGNITOR ELECTRODE AND FLAME SENSOR

    FIGURE 4

    Vpr

    L/D

    CH/BL

    PRG-Ie

    LINHA III Me

    Vpi

    V ArPs

    Rr BL

    REARMEBR/IO

    AZ

    G

    Q

    TIG

    L2

    (6,3A)F1

    N/L1

    VS PRINCIPAL

    VS PILOTO

    VENT.

    EXTERNO

    L/D

    IO/IG TI EXT

    +

    _uA

    ALIM. AC

    VAC220

    VAC115

    Ps Ar

    ALARME

    REARME

    L

    17 18 19 12 13 14 11 9 10 7 8 15 16 5 6 20 21 3422

    N(L1)F

    N(L1)F

    I

    ICC>500 uA-DC

    ICC ~1500 uA-DCU

    LAz

    Br_

    ICC>2 mA-DCF _

    Az Br

    ELECTRIC DIAGRAM OF CONNECTION IN THE BASE OF THE INTERNALTRANSFORMER PROGRAMMER, FLAME SENSOR I, U OR L.

    FIGURE 5

  • PPRROOGGRRAAMMMMEERR FFOORR FFLLAAMMEE SSTTAARRTT AANNDD SSUUPPEERRVVIISSIIOONN,,

    AANNDD SSAAFFEE SSTTOOPP OOFF BBUURRNNEERR

    MODEL: PRG-Ie-IIIMe-�-�-C��-P�-O� TECHNICAL SHEET 6/8 � Customer Service 55 11 3019-1616 For further details, see technical bulletin

    SELCON SISTEMAS ELETRÔNICOS DE CONTROLE LTDA. CNPJ 56.935.877/0001-29 Rua. Américo Samarone, 502 • CEP 04284-000 • Moinho Velho

    • São Paulo • SP • Brasil • Phone/Fax: (55 11) 3019-1616

    http://www.selcon.com.br

    Representative or Retailer:

    Selcon Ltda., keeps the right to modify this technical

    sheet whenever it is necessary – Mar./2013

    10

    F N(L1)

    L/D

    Vpr Vpi V

    L2N/L1

    ALIM. AC

    VS PRINCIPAL

    N(L1)F 17 18

    VAC

    (6,3A)

    115

    F1VAC220

    VENT.

    EXTERNO

    VS PILOTO

    19 12 13 14 11 9

    L/DL

    CH/BLREARME

    ACS-TE-

    RrPsAr BL

    IG

    QT

    REARME

    ALARME

    Ps Ar

    167 158 5 6 20

    AZ

    BR/IO

    IO/IG TI EXT

    2221 3 4

    PRG-Ie

    ELECTRIC DIAGRAM OF CONNECTION IN THE BASE OF THE EXTERNAL TRANSFORMER PROGRAMMER WITH ONE IGNITOR ELECTRODE AND FLAME SENSOR

    FIGURE 6

    F

    N/L1

    F1(6,3A)

    Vpi

    N(L1)F

    L/D

    Vpr VPsAr

    13

    VS PRINCIPAL

    L2

    ALIM. AC

    17N(L1) 1918 12

    115VAC

    220VAC

    EXTERNO

    Ps Ar

    VENT.

    VS PILOTO

    1114 9 10 7 8

    REARME

    L/DL

    CH/BL

    GRr BL Q

    ACS-TE-

    IO/IG TI EXT

    REARME

    ALARME

    15 16 5 6

    T

    2120 22

    PRG-IeLINHA III Me

    BR/IO

    AZ

    +

    _uA

    34

    I

    ICC>500 uA-DC

    ICC ~1500 uA-DCU

    LAzBr

    _

    ICC>2 mA-DCF _

    Az Br

    ELECTRIC DIAGRAM OF CONNECTION IN THE BASE OF THE EXTERNAL TRANSFORMERPROGRAMMER , FLAME SENSOR I, U OR L.

    FIGURE 7

  • PPRROOGGRRAAMMMMEERR FFOORR FFLLAAMMEE SSTTAARRTT AANNDD SSUUPPEERRVVIISSIIOONN,,

    AANNDD SSAAFFEE SSTTOOPP OOFF BBUURRNNEERR

    MODEL: PRG-Ie-IIIMe-�-�-C��-P�-O� TECHNICAL SHEET 7/8 � Customer Service 55 11 3019-1616 For further details, see technical bulletin

    SELCON SISTEMAS ELETRÔNICOS DE CONTROLE LTDA. CNPJ 56.935.877/0001-29 Rua. Américo Samarone, 502 • CEP 04284-000 • Moinho Velho

    • São Paulo • SP • Brasil • Phone/Fax: (55 11) 3019-1616

    http://www.selcon.com.br

    Representative or Retailer:

    Selcon Ltda., keeps the right to modify this technical

    sheet whenever it is necessary – Mar./2013

    • LEGEND:

    L: Programmer signalization on

    L/D: On/Off switch

    REARME: Local front reset of PRG-IeIIIMe / remote reset via bar terminal (BASE Ie-IIIMe)

    CH/BL: flame signalization (VD) / local blocking (VM) / Anticipated flame (LJ)

    Alarm: remote block signalization via bar terminal (BASE Ie-IIIMe)

    IG: Ignitor electrode / ionization flame sensor inlet – line SEL-HT

    I: Sensor Electrode– line SEL-HT

    U: Ultraviolet radiation sensor– line SEL-SV

    L: Visible radiation sensors – line SEL-SV

    TI EXT.: Ignition transformer outside the programmer– line ACS-TE

    Ignition Transformer (Tig):

    •••• Internal when incorporated to PRG-Ie: : With ignition transformer ACS-TE-�1-C5

    •••• External to the PRG-Ie: Of any power, except the version with only one ignitor/sensor electrode, which should operate with an isolated transformer MODELS: ACS-TE-��-C5 or ACS-TE-�1-C6.

    •••• Consult Selcon Ltda in case you wish to use other transformers.

    Fan (V) : Combustion fan

    PS AR: Sensor-Inlet for induced air flow/ pressure switch

    VS pilot (Vpi): pilot fuel valve or of 1st phase

    Main VS (Vpr): mail fuel valve or of 2nd phase

    F1: Miniature fuse assembled on BASE Ie – code MST-250V – 6,3 A

    uA/mA: Meter to monitor flame signal (uA/mA) (see figures 4 and 6)

    Q: Burner

  • PPRROOGGRRAAMMMMEERR FFOORR FFLLAAMMEE SSTTAARRTT AANNDD SSUUPPEERRVVIISSIIOONN,,

    AANNDD SSAAFFEE SSTTOOPP OOFF BBUURRNNEERR

    MODEL: PRG-Ie-IIIMe-�-�-C��-P�-O� TECHNICAL SHEET 8/8 � Customer Service 55 11 3019-1616 For further details, see technical bulletin

    SELCON SISTEMAS ELETRÔNICOS DE CONTROLE LTDA. CNPJ 56.935.877/0001-29 Rua. Américo Samarone, 502 • CEP 04284-000 • Moinho Velho

    • São Paulo • SP • Brasil • Phone/Fax: (55 11) 3019-1616

    http://www.selcon.com.br

    Representative or Retailer:

    Selcon Ltda., keeps the right to modify this technical

    sheet whenever it is necessary – Mar./2013

    • CODE FOR ORDERS: PRG-Ie-IIIMe-�-�-C��-P�-O�

    PRG-IE-

    IIIME

    -

    SENSOR

    -

    IGNITION

    TRANSFORME

    R INCLUDED IN

    THE OUTER

    COVERING

    -

    C- CONFIGURATION -

    P- PROGRAM

    REQUESTED

    - O- ON/OFF

    Switch With

    Front

    Signalization

    I IONIZATION

    IG

    SINGLE ELECTRODE (sensor and ignitor) U

    ULTRAVIOLET

    L VISIBLE

    (d1)

    d1 = S => Yes

    OR

    d1 = N => no

    PURGE TIME

    Fan outlet +

    air switch inlet

    (d4)

    d4 = 1 => standard

    OR

    d4 = 2 a “n” =>other

    (under consultation)

    (d5)

    d5 = 1 => no OR

    d5 = 2 => yes

    (d2) d2 = 1=> 3 sec. OR d2 = 2=> 10 sec.

    (d3)

    d3 = 1 => no OR d3 = 2 => yes

    Obs.: The sensor and other accessories must be specified separately, according to a specific code.

    • BE AWARE:

    ⇒ Use the programmers and/or detector relays exclusively with flame sensors of Selcon manufacturing.

    • OTHER PRODUCTS AND ACCESSORIES:

    ⇒ Flame Relays – CHM-E, CHM-P, CHM-M e CHM-F ⇒ Tightness Test Relay of blocking valves – CHM -T ⇒ Ignition Programmers and flame monitoring – PRG-E, PRG-Ie, PRG-Ie -IIIMe (with base), PRG-I, PRG-M e

    PRG–M-IIIMe (with base) ⇒ Optical Flame Sensors– SEL- SV ⇒ Flame sensors by ionization and ignitor electrodes – SEL-HT e SEL-HT-E (sensors and electrodes assembled

    under draft or sample from the special-client). ⇒ Flame signal transmitter– ACS –TX (until 500 meters between the sensor and relay or programmer) ⇒ Flame Signal Converter for 4 -20 mA – ACS - CV ⇒ Ignition transformers – ACS -TE (for feeding in VAC or VCC) ⇒ Portable ignitor – ACS-IP (works with common alkaline battery AA type) ⇒ Several Cables– ACS - CB (ignition / sensoring / communication / control) ⇒ Connector and protector to touch for ignition cable – ACS - CP ⇒ Temporized ignition panel ACS – IT ⇒ Ignition and flame panel – ACS - PI ⇒ Articulated socket joint – ACS - CN ⇒ Ignition and monitoring panel – ACS-PN (under consultation) ⇒ Reform services of pilot burners (under consultation) ⇒ PRODUCTION DATA SUPERVISION LINE