soft starter training - zest weg group · soft starter training ... this method allows a torque...

39
1 Soft Starter Training Trainer: Andre van der Linde Soft Starter Theory of Operation

Upload: phungkhue

Post on 28-Jun-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

1

Soft Starter Training

Trainer: Andre van der Linde

Soft Starter Theory of Operation

Page 2: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

2

Main Methods for Starting

Induction Motors

Main Methods for Starting Induction Motors :

A soft starter offers nearly the best starting characteristics

reduced current and a controlled ramp

Direct on-line starter

Star-delta starter

Auto-transformer starter

Soft Starter

Page 3: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

3

Direct on-line Star-delta

Soft-Starter

Starting Currents Comparison

Current

Time

Soft-Starter Applications

Typical soft-starter applications include the following:

Pumps

Fans

Compressors

Conveyors

Page 4: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

4

Soft-Starter Advantages

Smooth starting ramp

Reduced peak currents

Precise current limit during starting

Reduced mechanical stress (shock on the load)

Reduced water hammer

No moving parts to wear out

Fault detection

Soft-starters use SCRs (Thyristors) to regulate the amount of voltage

applied to the motor. When correctly set it provides the minimum amount of

voltage necessary to develop the required starting torque.

The voltage is then increased via a programmable ramp thereby providing

the motor with a smooth starting torque and step less ramp to full speed.

Soft-Starter Method of Operation

Page 5: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

5

Soft Starter Simplified Diagram

Soft Starter Trigering (resistive load)

Page 6: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

6

SCR Trigering (Inductive load)

Page 7: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

7

Page 8: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

8

Model Number Identification

Page 9: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

9

Control Mode

Voltage ramp

Voltage increases according to a preset ramp time and starting current is a

function of ramp time and type of load.

Current Limit

Voltage is applied in order to maintain a preset current level according to

the application

Current Ramp

Maximum current level is also limited during start-up however higher or

lower start-up current limits can be set

Pump Control Optimized control method providing the required torque to start/stop

Hydraulic centrifugal pumps smoothly.

Torque Control

This method allows a torque control with 1 up to 3 setting points

SSW-06 5 Types of control (P202)

Page 10: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

10

Page 11: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

11

Page 12: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

12

Page 13: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

13

5 Types of control (P202)

When a soft-starter and when a VSD?

A soft-starter only gives a reduced voltage start-up (like a light

dimmer switch)

This reduces starting current and starting torque and

therefore the mechanical stress

What does a soft-starter do?

It gradually ramps up the voltage in a controlled manner and

thereby reduces the starting current

No Speed control on SoftStarter

Soft Starters - Practical Considerations:

Page 14: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

14

Some practical soft-starter considerations:

Reduced voltage gives reduced torque – MUCH REDUCED!

T is proportional to V²

E.g. A typical motor has a starting torque of 200%, also a

typical soft-starter starting voltage is 30%. The motor starting

torque would then be:

18% - very soft !

Best suited for the type of applications that use reduced

torque like centrifugal pumps & fans mainly.

Practical Considerations

Soft Starter torque & current curves

0.00

1.00

2.00

3.00

4.00

5.00

6.00

7.00

0 10 20 30 40 50 60 70 80 90 100

I DOL T DOL T @ 50% V T @ 30% V I @ 50% V I @ 30% V

Page 15: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

15

Soft Starter torque & current curves

0.00

0.50

1.00

1.50

2.00

2.50

0 10 20 30 40 50 60 70 80 90 100

T DOL T @ 50% V T @ 30% V

Soft Starter torque curves

0.00

0.50

1.00

1.50

2.00

2.50

0 10 20 30 40 50 60 70 80 90 100

T DOL T @ 500% I T @ 300% I T @ 50% V T @ 30% V

Page 16: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

16

VSD & Soft-Starterconveyor torque curves

0.0

0.5

1.0

1.5

2.0

2.5

0 10 20 30 40 50 60 70 80 90 100

DOL starting torque Load torque VSD starting torque T @ 30% V Soft-Starter starting torque @ 500% I lim.

The WEG soft-starters can deliver up to 500% current and can

therefore also be used in “high torque” applications such as

conveyors, crushers, screw feeders, large high inertia fans with a

long run-up time etc.

Practical Considerations

Page 17: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

17

Soft Starter & Motor selection

Soft Starter & Motor selection

Page 18: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

18

Important To Know To Size a Soft-Starter :

Starts/Hour

Ambient Application

Absorbed power

Torque characteristic

Inertia

Motor Current

Motor Power

Supply Voltage

Number of Conditions

These values can be entered into the SDW software on the

WEG website to make an accurate selection.

Pumps

Starter Method:

Start with acceleration ramp

Function “ Pump Control”

Advantages:

Reduction of “Water hammer”

Reduced current

Page 19: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

19

Fans

Starter Method:

Start with “current limit”.

Advantage:

Reduced mechanical stress and wear

Reduced current

Compressors

Starter Method:

“Kick-Start” function

Start with voltage ramp

Advantage:

Able to accelerate the inertia

process of the load smoothly

Page 20: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

20

Starter Method:

Start with “current limit”

Advantage:

Reduction of mechanical wear

Mixers

Conveyor Belt

Starter Method:

Start with “voltage ramp”

Advantage:

Reduction of mechanical

wear

Page 21: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

21

Soft Starter Installation

INTRODUCTION

Soft-Starters are considered to be “Industrial Electronic” items and

as such should be able to withstand rough working conditions.

This is true.

However, fact is, a Soft-starter is an electronic item. The better the

installation, the less problems and greater reliability the user will

enjoy.

Page 22: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

22

Mechanical Installation

As for as possible avoid the following:

Direct exposure to sunlight, rain, high moisture and sea air

Exposure to corrosive liquids or gasses

Exposure to excessive vibration

Conductive dust, oil or any conductive particles or materials

Mechanical Installation

Environmental conditions:

Temperature: 0…40ºC – nominal conditions

0…55ºC - with current derating

Relative Air Humidity: 5% to 90%, non-condensing

Maximum Altitude: 1000m – nominal conditions.

1000 - 4000m – with 1% current derating for each

100m above1000m.

Page 23: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

23

Cooling Airflow

1. Always ensure sufficient room and

ventilation for cooling air flow.

2. Sufficient space – top, bottom and sides.

3. Avoid direct sunlight.

Hints:

1. Use panel fans if in doubt.

2. Remember that trunking impedes air

flow.

3. Rather allow more flow and space than

the minimum requirements.

4. Allow for heating from other

components within the VSD panel.

5. A sealed, clean air conditioned

environment is best.

Panel Ventilation

A totally sealed panel circulates the Soft Starter hot air causing a steady

temperature rise.

Panel design must allow for hot air to be vented.

Page 24: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

24

Electrical Installation

Important notes:

The AC input voltage must be compatible with the SS rated voltage.

Capacitors for power factor correction must be disconnect at the input (R, S, T) while you are accelerating the load and they must be re-connected after the BY-PASS contactor closed.

The SS MUST be earthed for safety purposes (resistance ≤ 10Ω).

Command Wiring

- Shielded cable;

-Separated from power

cables;

Fuses:

- Slow Blow: installation;

- Ultra rápid: soft-starter

COMMAND

Power Cabling

If there is any risk of

EMI interference with

other equipments.

SSW06 Installation

Contactor

- Maintenance;

- Emergency;

Page 25: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

25

Electrical Installation

OTHER

LOADS

Controls

Main disconnect switch

For safety purposes – isolation,

protection and maintenance

Page 26: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

26

OTHER

LOADS

CAPACITORS

BANK

Controls

Fuses

To protect the installation input.

Correctly rated ultra rapid fuses

should be used for SS

OTHER

LOADS

CAPACITORS

BANK

Controls

Contactor

If customer practice demands the

use of a contactor, it may be

used.

Page 27: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

27

OTHER

LOADS

CAPACITORS

BANK

Controls

Control wiring

Keep seperate from power cables

Cross power cables at 90º

Use screened cables for analogue

signals

Signal and Control Wiring

4 6 3 5

Digital

Inputs

Relay Outputs

7 11

24V 19 21 23

18 20 22 24

Page 28: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

28

Microcontroller

with software

version label

Relays

SCR firing

connection

Thermostat and current

transformers (CT) input

Inputs and Outputs

Ground

Connector

HMI Conector

Serial RS232

connector

Control Board

CCS6

Signal and Control

connections

Terminal X1A Power board

Terminal X1D Power board

Page 29: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

29

Terminal X1A Power board

4 6 3 5

Digital

Inputs

Relay Outputs

7 11

24V 19 21 23

18 20 22 24

X1B & X1C Connection

Page 30: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

30

X1D Connection

X1D Connection

Page 31: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

31

Thermal Protection for Different Classes

(P640)

M1

(DI1)

3

(DI3)

5

COM

8

PTC

B A

12 13

(DI2)

4

(DI4)

6

(DI5)

7

COM

9

0V

10

24V

11

PTC

ST

AR

T

ST

O

P

GE

NE

RA

L

EN

AB

LE

K1 FAULT

U W V

PE

Soft Starter Commissioning

Page 32: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

32

1. Check that all connections are correct and tight.

2. Verify that the SS is correctly rated for the motor.

3. Verify that the SS is correctly rated for the supply voltage.

4. Uncouple the load from the motor, or ensure that the load may be

safely turned.

5. Check that the control voltage matches the SS unit control

voltage rating – 220VAC is standard.

Pre-Power Checks

Thermal Protection for

different classes (P640)

36s

Page 33: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

33

1. Check that the supply voltage is within acceptable range.

(nominal Voltage -15% to +10%)

2. Power up the Electronics Supply

3. Check that the power up was successful.

Initial Power-up

Page 34: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

34

Soft Starter Parameters

Types of Parameters

Read Only Parameters: Are variables that can only be viewed on the

keypad display, but not changed by the user.

Regulation Parameters: Are Programmable values to be used by the SSW

SSW-06 functions.

Configuration Parameters: Define the SSW characteristics, the functions

to be executed, as well as the Inputs and Outputs functions of the control

board

Motor Parameters: Motor data that are indicated on the motor nameplate

Special Function Parameters: Included here are the stop and kick start

functions

Protection Parameters: Included here are the actuation levels and

actuation time of the motor protection

Page 35: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

35

Read Only Parameters: P01...P99

Regulation Parameters: P00 & P100 – P199

Configuration Parameters: P200 – P399

Motor Parameters: P400 – P499

Special function Parameters: P500 – P599

Protection Parameters: P600 – P699

Parameters Description

For ease of understanding, the parameters were grouped according to function, as follows:

The SSW06 HMI

It is a very simple and functional interface to operate and

program the soft starter:

Visualization and Parameter Changes

Status Indication

Fault Indication

Soft starter Operation

On/Off, Jog Function, Forward/Reverse

Local/Remote

Detachable

Page 36: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

36

Use of the SSW06 HMI

7 segment LED Display

with 4 digits

Liquid Crystal

Display with 2 lines

of 16 alphanumeric

characters

Start Key

Stop Key

Local/Remote Key

“ Program ” Key

Increase Key

Decrease Key

FWD/REV Key Jog Key

During this start-up routine the following parameters are set:

1. P201 – Language

2. P150 – Motor connection (Inside delta)

3. P202 – Control mode

4. Parameters relevant to control mode chosen

5. Motor nameplate parameters

6. Motor protection parameter, rated thermal class

Automatically guided start-up routine (P204=5)

Page 37: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

37

SSW-03

3 Wire

Delta Connection

SSW-03

3 Wire

Star Connection

Normal Connection

Drives and Controls

6 Wire

Inside Delta Connection

Soft Starter line current

reduced to 0.58% Inom.

( 42% reduction )

Inside Delta Connection

Page 38: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

38

R

S

T

U V W

I TOTAL

I SSW

F1

F2

F3

Circuit-Breaker

1 6

3

2 5

4

R

S

T

U V W

I TOTAL

I SSW

F1

F2

F3

Circuit-Breaker

2

5 6

3

4

1

Motor Connection

Recommended Connection

SSW06

M1

X1A

Q1

Q2

T1

Q2

PE

(DI1)

3

(DI3)

5

COM

8

PTC

B A

12 13

3~

50Hz

380V

(DI2)

4

(DI4)

6

(DI5)

7

COM

9

0V

10

24V

11

1 2 PE 33 34 18 19

RL1 RL2

20 21 22 23 24

RL3

PTC

ST

AR

T

ST

O

P

GE

NE

RA

L

EN

AB

LE

K1 K1 FAULT

R S T

U W V

PE

Page 39: Soft Starter Training - Zest WEG Group · Soft Starter Training ... This method allows a torque control with 1 up to 3 ... DOL starting torque Load torque VSD starting torque T @

39

End of Course

Thank You