swegon casa w230 ec ventilation/air handling... · elements caused by dampness the ventilation unit...

32
Instructions for installation, operation and maintenance Swegon CASA ® W230 EC W230_d_EN-m

Upload: phungthuan

Post on 19-Aug-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

Instructions for installation, operation and maintenance

Swegon CASA®

W230 EC

W230_d_EN-m

N.B.! The manual was originally written in Finnish.

Instructions for UseFor the user

Important information ����������������������������������������� 3

Control from a Premium control panel ����������������� 4

To replace the filters ��������������������������������������������� 5

Alarms ����������������������������������������������������������������� 5

Content

Installation, operation and mainte-nanceFor fitters and service personnel

1. Installation instructions ........................................ 61�1 General ����������������������������������������������������������������������������71�2 Condensate discharge ������������������������������������������������������71�3 Electric and control cables ������������������������������������������������71�4 Ducts �������������������������������������������������������������������������������71�5 Moisture barrier for cold timber frame constructions �������82. Operation .............................................................. 92�1 Basic functions �����������������������������������������������������������������92�1�1 Fans ������������������������������������������������������������������������������92�1�2 Temperature �����������������������������������������������������������������92�1�3 Protective functions ������������������������������������������������������92�2 Optional items of equipment – automated control system 93. Application .......................................................... 103�1 To set the airflows ����������������������������������������������������������103�2 Premium control panel ���������������������������������������������������103�3 Start menu ���������������������������������������������������������������������113�5�1 Fireplace switch function ���������������������������������������������113�3�2 Fan speed �������������������������������������������������������������������113�4 Main menu ��������������������������������������������������������������������113�4�1 Language ��������������������������������������������������������������������113�4�2 Installation and service ������������������������������������������������113�4�3 Reheating �������������������������������������������������������������������113�4�4 Clock ��������������������������������������������������������������������������113�4�5 Summer night cooling �������������������������������������������������113�4�6 Basic display ����������������������������������������������������������������113�4�7 To switch off the unit ��������������������������������������������������113�4�8 Fireplace switch function ���������������������������������������������113�4�9 Weekly timer ��������������������������������������������������������������113�4�10 Ventilation unit model �����������������������������������������������113�5 Installation and service ���������������������������������������������������123�5�1 Alarms ������������������������������������������������������������������������123�5�2 Clock ��������������������������������������������������������������������������123�5�3 Temperature ���������������������������������������������������������������123�5�4 Measurement �������������������������������������������������������������123�5�5 Control systems ����������������������������������������������������������123�5�6 Fan speeds ������������������������������������������������������������������12

3�5�7 To switch off the unit ��������������������������������������������������123�5�8 Factory settings �����������������������������������������������������������123�5�9 Actuators ��������������������������������������������������������������������123�5�10 Functions ������������������������������������������������������������������123�5�11 Electric air heater ������������������������������������������������������124. Servicing .............................................................. 134�1 Service reminder ������������������������������������������������������������134�2 To open the ventilation unit �������������������������������������������134�3 Filter change ������������������������������������������������������������������134�4 Other servicing ���������������������������������������������������������������135. Alarms and troubleshooting .............................. 145�1 Alarms ���������������������������������������������������������������������������145�1�1 Alarms from a Premium control panel �������������������������145�2 Troubleshooting: ������������������������������������������������������������145�2�1 The supply air is not sufficiently heated �����������������������146. Technical data ...................................................... 156�1 Sizing �����������������������������������������������������������������������������156�2 Wiring diagram, ventilation unit and cooker hood����������186�3 Wiring diagram, ventilation unit and cooker hood����������196�4� Wiring diagram, optional equipment ����������������������������206�5 Control diagram ������������������������������������������������������������226�6 Econo control wiring diagram ����������������������������������������236�7 Dimensions ��������������������������������������������������������������������246�8 Weight ��������������������������������������������������������������������������246�9 Optional equipment �������������������������������������������������������247. Commissioning .................................................... 25Plant data to be given when requesting serviceProject planningSee separate project planning instructions, www�swegon�com�

N.B.! The manual was originally written in Finnish.

Swegon reserves the right to alter specifications.2 www�swegon�com

W230.280612

Important information!AirflowsThe air in the home should be changed at a continuous and sufficient rate to ensure a pleas-ant indoor climate and avoid damage to building elements caused by dampness� The ventilation unit should be stopped only while service work is in progress�

The ventilation fans are controlled from a Pre-mium control panel�

• Away = a low airflow, which can be utilized when no one is in the home and there is no need for the same ventilation that is normally in use, e�g� for moisture-removal�

• Home = normal airflow�

• Boost = a high airflow, used in connection with cooking, taking a sauna bath, showering, drying laundry and similar activities�

The Away/Home operating modes (and the supply air temperature in the electrically heated models) can be controlled with the ventilation unit’s built-in weekly timer; however the oper-ating mode can always be changed from the Premium control panel or the Premium cooker hood�

A low airflow when the home is unoccupied means economical operation� This saves on fan energy and the home heating system does not have to heat as much air during the cold season�

The most important function of the ventila-tion system is to ensure that the indoor air will be continuously fresh and to remove impurities and moisture from the air. You should therefore make an appraisal of

whether a low airflow is sufficient while the home is unoccupied. The low airflow mode must absolutely not be used when someone is in the home.

If the load on the home is greater than you’ve anticipated, then you should increase the normal airflow to a correspondingly higher rate.

Drying laundryA tumbler dryer of extract air type or a drying cabinet must not be connected to the system due to the high moisture content in the air leav-ing them� We recommend a condensing tumbler dryer without duct connection�

Freeze protectionDuring periods of cold weather, the heat ex-changer is liable to freeze if the extract air is humid� A protective function then automatically reduces the speed of the supply air fan� Under such conditions, variations in the fan speed are therefore normal�

FiltersThe ventilation unit must not be operated with-out filters� Use only filters recommended by Swegon in the ventilation unit�

CommissioningThe ventilation should not be commissioned until all work that produces large quantities of grind-ing dust or other impurities has been completed�

Instructions for Use

W230.280612

Swegon reserves the right to alter specifications. www�swegon�com 3

Swegon reserves the right to alter specifications.4 www�swegon�com

W230.280612

When the power is switched on, the ventilation unit starts up in the Home operating mode� The start time is approx� 1 minute� After that, the control panel can be used� Likewise after a power failure, the ventilation unit starts up in the Home operating mode, if the power failure has cleared the memory�

The functions of the push buttons are described in the image to the right�

Fireplace switch functionThe speed of the extract air fan decreases and the speed of the supply air fan increases for a few minutes� This produces excess pressure in the home and in this way "creates" an updraught in the chimney, which makes it easier to light the log-fire�

Selection of fan speedThe fans inside the unit can be controlled to operate at three speeds: Home/Away/Boost� Select the required fan speed from the control panel�

You can select an airflow boost time of 30, 60 or 120 minutes, or continuous boosted airflow�

The operating mode can be manually changed, even when the fan speed is controlled by the weekly timer�

Menu/Installation and serviceYou can enter settings that affect the operation and functions of the ventilation unit from the Installation and service menu and submenu� You should normally enter these settings when you install the ventilation sys-tem� The settings are described in Sections 3�5 and 3�6�

Signal lampThe indicating lamp on the control panel indicates the functions and alarms of the ventilation unit with various colours� This is described in Section 5�

Fireplace switch functionReturn to previous menu levelMove to the left

MenuMove to the rightSetting function

Selection of fan speedMove upward/downwardEntering values

Signal lamp

Control from a Premium control panel

Start menu

Fireplace switch function

Menu structure

Menu

(See Section 3.5)

Installation and service

(See Section 3.6)

Fan speed

W230.280612

Swegon reserves the right to alter specifications. www�swegon�com 5

Wide-mesh filterThe filter should be cleaned every six months and should be replaced at least once per year� It may be necessary to clean or replace the filter more often in homes where there is considerable dust�

Supply air filterThe filter should be cleaned every six months and should be replaced at least once per year� If the air is highly polluted, e�g� due to heavy traffic, the filter should be replaced more often�

Service reminderThe ventilation unit’s control system is normally preset for displaying a service reminder every six months� This time setting can be changed by qualified service person-nel�

AlarmsAlarms from a Premium control panel• The indicating lamp is flashing red: The automated

protection system has stopped the fans due to a malfunction� The alarm text is shown in the display� Contact service!

• The indicating lamp is lit with a steady red glow: Alarm or a service reminder� The alarm text is shown in the display� Contact service!

• The indicating lamp indicates certain unit functions with other colours� See Section ”3�2 Premium control panel”

To replace the filters

The home owner can change the fil-ters himself or herself. Other service work must be carried out by qualified service personnel.

The locations of the filters in a ventilation unit in the right-hand version. The locations of the filters are mirror-inverted in a ventilation unit in the left-hand version.

The ventilation unit must not be operated without filters! Use only filters recommended by Swegon in the ventila-tion unit.Find the correct filter in Section 6. Technical data

Wide-mesh filter Supply air filter

Swegon reserves the right to alter specifications.6 www�swegon�com

W230.280612

1. Installation instructions

Qualified personnel onlyThe installation work, the entering of settings and commissioning should be carried out by qualified personnel only�

Standards and requirementsThe pertinent national standards and regula-tions dealing with installation, the entering of settings and commissioning must be followed if the equipment is to operate correctly�

You will find the document entitled “Project design instructions for ventilation” at the web address www�swegon�com/casa, in which requirements on electric power, noise, airflows and duct systems are presented� Each country has specific national requirements which must be observed�

Right-hand or left-hand versionCheck whether the ventilation unit has been supplied in the right-hand or left-hand version to make certain that you are connecting the air ducts to the correct duct connection spigots on the unit� See also the dimensional drawings in Section 6, Technical data�

Drying laundryA tumbler dryer of extract air type or a drying cabinet must not be connected to the system due to the high moisture content in the air leav-ing them� We recommend a condensing tum-bler dryer without duct connection�

The covered duct connection spig-otsThe duct connection spigots of the ventilation unit must be covered by lids during transport, storage and installation�

FiltersThe ventilation unit must not be operated without filters� Use only filters recommended by Swegon in the ventilation unit�

CommissioningThe ventilation should not be commissioned until all work that produces large quantities of grinding dust or other impurities has been completed�

Important information!

1.1 General Install the ventilation unit on a base on the floor� Suit-able installation locations are machine rooms, storage spaces, etc� The temperature in the installation space must be constantly more than +10 °C� Adjust the posi-tion of the stand with the adjustable feet� Remove the heat exchanger from the ventilation unit to make it lighter for lifting� The unit should be mounted as near as possible to the wall� The space between the ventilation unit and the wall should be insulated so that the sound from the unit will not be transmitted out through the rear wall� Installation against a wall that borders on the living room or a bedroom should be avoided if possible�

1.2 Condensate dischargeConnect the condensate discharge hose to the con-densate discharge connection of the unit (3/8”, Male threads)� The condensate must be channelled to a floor drain or the like with a hose or a tube having an inner diameter of at least 12 mm� The water must not be led away directly to the sewer�

Vertically mount the water trap on the hose supplied with the unit and fill it with water� The hose must not have a second water trap or be run horizontally� The damming height of the water trap should be at least 100 mm�

1.3 Electric and control cablesThe unit has an earthed plug contact for connection to the mains power� The mains plug serves as the ventila-tion unit’s main switch and it should be connected to an electric socket at an easily accessible spot�

The room unit is equipped a 2 m long cable with plug-in contact, installed from the topside of the ventilation unit� Arrange the wall outlet at an easy-to-reach loca-tion� For power requirement particulars, see Section 6, Technical data�

Connect the ventilation unit to the Premium control panel via a modular cable� Install the Premium control panel at a place of your choice� Two modular cables are included in the supply: one approx� 3 m long cable and one 20 m long cable�

When installing the unit, make sure that you provide adequate access to the connector of each cable (loose ones as well), e�g� for servicing and adjusting the unit, if and when the need arises�

The diameter of the modular cable wiring tube should be 20 mm�

The connection of possible optional equipment is described in the wiring diagram in Section 6, Technical data� The cables for the optional items of equipment are not included in the supply�

1.4 DuctsInstall the air ducts, sound attenuators, supply air diffus-ers, air intake grilles and exhaust air ducts as shown in the ventilation drawings� To prevent the propagation of

The unit will be easier to lift into position if you first remove its plate heat exchanger.

Base

Important! If any further electrical wir-ing is required, only a qualified electrician shall be allowed to carry out this work.

The electric and control cables are located on the top side of the ventilation unit. Make sure that the electric cable can be connected to a wall outlet without ob-struction.

If you lengthen the modular cable within some building element (e.g. in a wall), you should lengthen the cable in a 20 mm dia. conduit, anticipating a possible later change of cabling.

W230.280612

Swegon reserves the right to alter specifications. www�swegon�com 7

sound, do not install the ducts directly against structural building elements�

Insulate the air ducts in order to reduce loss of heat or cooling energy and to prevent water from condensing on surfaces�

In general, ventilation ducts are insulated in the follow-ing manner:

• Outdoor air ducts are insulated in warm spaces and in attics that are used�

• Exhaust air ducts should always be insulated in ac-cordance with national regulations� See separate pro-ject planning instructions (for example Fire resistance classification requirements)�

• Insulate supply air ducts in cold spaces�

• Insulate extract air ducts in cold spaces�

• If the air inside the duct is colder than the air in the surroundings, the insulation should be protected by a moisture barrier (e�g� outdoor air and exhaust air in interior spaces, or chilled supply air)�

1.5 Moisture barrier against cold timber framesIt is important that the moisture barrier between cold stud work and the warm ceiling maintains its tightness at duct penetration points� A duct penetration piece (optional extra) will facilitate this� This item is available in sets of 5 for size 100, 125 and 160 mm dia� ducts� It can be fastened with tape in the moisture barrier�

We recommend the use of a mounting frame (optional extra) for sealing the moisture barrier in the attic tie beams�

Cut up the openings with approx� 10 mm smaller diameter than that of the ducts� Secure the mounting frame in the ceiling with screws through the holes on the sides� The plastic film of the moisture barrier should either be stretched and fastened between the mounting frame and the structural element of the building, or be taped tightly against the mounting frame�

N.B.! Remove the installation instruc-tions and the condensate hose from the venti-lation unit before commissioning it.

N.B.! WARNING: It is absolutely forbid-den to use the ventilation system during the period of building construction or if dust-raising work is in progress. The ducts should be covered with covers to prevent impurities from entering them.

To detach the panel on the Premium con-

trol panel.

Connection of the control cable.

To attach the panel cover on the Premium

control panel. First place the upper edge of the cover in place

and then press the cover to secure it.

Swegon reserves the right to alter specifications.8 www�swegon�com

W230.280612

2.1 Basic functionsHow to activate and set the functions is described in Section 3, Application.

2.1.1 Fans

The fans can be controlled to three different operating modes from the control panel�

• Away = a low airflow, which can be utilized when no one is in the home and there is no need for the same ventilation that is normally in use, e�g� for moisture-removal�

• Home = normal airflow�

• Boost = a high airflow, used in connection with cook-ing, taking a sauna bath, drying laundry and similar activities�

The Away/Home operating modes can be controlled with the ventilation unit’s weekly timer; however the op-erating mode can always be changed from the Premium control panel�

You can select the airflow boost time manually to 30, 60 or 120 minutes, or for continuous boosted airflow, from a Premium control panel�

2.1.2 Temperature

The user sets a supply air temperature of his or her choice, normally 13–20 °C� This set value is a so- called setpoint, which the ventilation unit makes an effort to reach, if conditions allow this� N�B�! In the Econo models, the setpoint can be set with a thermostat inside the ventilation unit�

A heat exchanger collects heat energy from the extract air and transfers it to the supply air� When the heating output of the heat exchanger is not enough, the follow-ing takes place:

1) The electrically heated air heater is activated and heats the air to reach the preset supply air temperature�

The air heater can be switched off from the control panel if heating is not required�

2) In the Econo models, the supply air temperature can be set on the thermostat inside the ventilation unit� You can turn the thermostat dial to the minimum setting if heating is not required�

2.1.3 Protective functions

The electric air heater has two protective functions�

• The excess temperature (thermal overload) protection switches off the heater, if the temperature exceeds 50 °C� The protection automatically resets itself when the heater has cooled down�

• The excess temperature protection switches off the heater, if the temperature exceeds 90 °C� The protec-tion must be manually reset by pressing a push but-ton on the heater�

The heat exchanger is equipped with a freeze protec-

tion� When the weather is cold, there is risk of the heat exchanger freezing� To counteract this, the controller activates the air heater and reduces the speed of the supply air fan� This protective function automatically resets itself when the temperature increases�

The fans have a thermal overload cutout, which stops them if the temperature rises too high� The controller also stops the fans if a serious malfunction occurs in the ventilation unit� When the temperature drops or the malfunction has been remedied, the protection auto-matically resets itslf in both cases�

On the Econo model’s waterborne air heater, there is a temperature sensor that protects the air heater from freezing�

•Iftheairheater’stemperaturehasdroppedtoariskylevel, the red signal lamp on the control panel will flash, but the ventilation unit will operate normally�

•Iftheairheater’stemperaturedropsfurther,thecontroller will stop the ventilation unit to prevent the air heater from freezing� The freeze protection alarm can be acknowledged from the Installation and service menu: Alarms�

2.2 Optional equipment – automated control equipmentHow to activate and set the functions is described in Section 3, Application. The connection of optional equipment is described in the wiring diagram in Section 6, Technical data.

The optional items of equipment can be used for achiev-ing the type of control required in the following way:

• Boost timer. The boosted operation mode can be switched in from a control panel or a Premium cooker hood� A separate boost timer (push button) can be installed in another place, e� g� in a dressing room, laundry room, etc�

• Humidity sensor. The ventilation unit detects if the relative humidity (RH) exceeds the preset limit value, e�g� 60 %, and switches the fans to operate in the boost mode� It can be placed in a sauna, a bathroom, a scullery, etc� The sensor voltage is 24 V DC�

• Separate fireplace switch. The function can be switched in from a control panel or a Premium cooker hood� A separate fireplace switch (push button) can be installed in another place, e� g� next to an open fireplace� The speed of the extract air fan decreases and the speed of the supply air fan increases for a few minutes� This produces excess pressure in the home and in this way "creates" an updraught in the chimney, which prevents smoke from entering the room when you light the log-fire�

• Occupant detection sensor. The sensor detects movement in the home and increases the fan speed to the Home value� This improves the operational economy if the home is nor regularly occupied�

• Carbon dioxide sensor. It is suitable for use when-

2. Operation

W230.280612

Swegon reserves the right to alter specifications. www�swegon�com 9

3. Application

3.1 To set the airflowsThe home should have continuous air change to ensure a pleasant indoor climate and avoid damage to building elements due to humidity� The ventilation unit should be stopped only while service work is in progress�

The airflows should be set according to the ventilation plan and applicable regulations� For estimated values, use the sizing curves in Section 6, Technical data� A qualified person should set the ventilation unit’s and the ventilation equipment’s airflows using appropriate meas-urement equipment�

A low airflow when the home is unoccupied means economical operation� This saves on fan energy and the home heating system does not have to heat as much air during the cold season� An assessment of whether a low airflow is sufficient for removing emissions, mois-ture, etc� from the air should be made�

3.2 Premium control panelWhen the power is switched on, the ventilation unit starts up in the Home operating mode� The start time is approx� 1 minute� After that, the control panel can be used� Likewise after a power failure, the ventilation unit starts up in the Home operating mode, if the power failure has cleared the memory�

The functions of the push buttons are described in the image�

The indicating lamp on the control panel shows the vari-ous functions of the ventilation unit in different colours�

1� Steady green glow: The ventilation unit is operating normally�

Check that the ventilation unit, filters and ducts are clean and that there are no loose objects in them before commission-ing the ventilation system.

Fireplace switch functionReturn to previous menu levelMove to the left

MenuMove to the rightSetting function

Selection of fan speedMove upward/downwardEntering values

Signal lamp

Premium control panel

ever the number of occupants varies� The sensor increases the fan speed to the Boost value, when a preset maximal value is exceeded, e�g� 1000 ppm�

• Negative pressure compensation. Negative pres-sure arises in the home when a separate cooker hood or central vacuum cleaner is used, since the extract airflow becomes substantially higher than the supply airflow� A separate sensor (e�g� one that senses the difference in pressure) can transmit a signal to the controller to increase the supply air flow from the ventilation unit to restore balance�

• Supervision (DDC). Certain functions can be con-trolled from the automated building management system of the building� See the connection schedule for optional items of equipment in Section 6, Techni-cal data�

• Home/Away switch. For example, systems con-trolled from a cooker hood, generally have a separate Home/Away switch (optional extra) by the front door� The switch starts the Away function in the ventilation unit� The switch can be a standard switch of optional type�

2� Flashing green glow: The freeze protection has been activated�

3� Orange flashing glow: The electric air heater has been activated�

4� Orange glow: The heat exchanger is bypassed, e�g� for summer night cooling�

5� Flashing red glow: The automated protection system has stopped the fans due to a malfunction�

6� Steady red glow: Alarm or a service reminder�

Swegon reserves the right to alter specifications.10 www�swegon�com

W230.280612

3.3 Start menu3.3.1 Fireplace switch function

The fireplace switch function decreases the extract air fan speed and increases the supply air fan speed for approx� 10 minutes� This produces excess pressure in the home and in this way "creates" an updraught in the chimney, which prevents smoke from entering the room when you light the log-fire�

An unnecessary or longterm use of the fireplace switch function in the wintertime may easily activate the frost protection function during an unnecessarily long time, which creates negative pressure in the house and smoke can be drawn into the house via the chimney� You can cancel the fireplace switch function by pressing the fireplace function button once again within 10 minutes after you pressed it the first time�

N.B.! The ventilation unit is no source for neces-sary replacement air while a fire is burning in the fireplace.

The function is shown in the display only if the value is On in Menu 3�5�8�

3.3.2 Fan speed

Select the appropriate fan speed� Timer-controlled airflow boost is available� The operating mode can be manually changed, even when the fan speed is con-trolled by the weekly timer�

3.4 Main menuYou can enter settings that affect the operation and functions of the ventilation unit from the menu�

N.B.! A number of functions are available in the Main menu as well as in the Installation and Ser-vice submenu.

From the Montage and service menu, you select wheth-er the function should be used and certain settings�

The function must be activated from the main menu�

3.4.1 Language

Select the appropriate language�

3.4.2 Installation and service

See Section 3�6, Installation and service�

3.4.3 Reheat (not on the Econo models)

You can choose whether or not you want to use reheat�

3.4.4 Clock

Select date and time of day�

3.4.5 Summer night cooling

Choose whether or not you want to use summer night cooling� The start temperature is the indoor air tempera-ture that you want the function to start with, and the fan speed can also be coubled to this function�

3.4.6 Basic display

Basic display 1 is selected when the fan speeds in the Away/Home/Boost steps are to be changed�

Basic display 2 is selected when the fan speeds are to be changed in five different steps�

3.4.7 To switch off the unit

The ventilation unit fans, the heat exchanger and an air heater, if fitted, are stopped� The circuit card is how-ever still energised and the settings are preserved in the memory�

3.4.8 Fireplace switch function

Select ON as the value for this function, if you wish to use the function from the control panel display, other-wise select Off� See also 3�3�1 above�

3.4.9 Weekly timer

Four different programs can be selected on the weekly timer, with the Away–Home–Boost fan speeds� Manual operation from the control panel bypasses (overrides) the weekly timer functions�

3.4.10 Ventilation unit model

Shows the model of the ventilation unit�

3.3 Start menu

3.3.1 Fireplace switch

function

3.3.2 Fan speed

• Away

• Home

• Boost

Menu structure

3.5 Installation and service

See next page!

3.4 Main menu • Language • Installation and service

Reheater (not on the Econo models)

Time switch clock (timer)

Summer night cooling

Base display

Switch off

Fireplace switch function

Weekly timer

Unit model

W230.280612

Swegon reserves the right to alter specifications. www�swegon�com 11

3.5 Installation and serviceThe menu is can be opened by entering code 1234�

3.5.1 Alarms

Sensor fault

Contact a service company�

Alarm/Service reminder

The service reminder appears on the screen at six-month intervals� On completed service, the reminder is set to zero from the menu and a new period of six months begins� The time period can be altered from the Func-tions menu�

Alarms for malfunctions are displayed in the display�

Risk of freezing (acknowledgement of the air heater freeze warning on the Econo models)

3.5.2 Clock

”On” or ”Off”� The clock is displayed in the start menu�

3.5.3 Temperature

”On” or ”Off”� The supply air temperature control function is displayed in the start menu� Select ON in order to use the function for setting the supply air temperature, otherwise select Off� (The models with reheat�)

3.5.4 Measurements

Depending on the accessories connected, the follow-ing can be measured: the carbon dioxide content (CO2), temperature, pressure differential, fan speeds and rela-tive humidity (RH)�

3.5.5 Control systems

Carbon dioxide content (CO2), supervision (DDC) or timer can be selected as a control means�

3.5.6 Fan speeds

N.B.! The Summer night cooling function should be deactivated whenever you change the fan speeds.

One of five fan modes (Away, Home, Boost) can be selected for each operating mode (1–5)�

The various fan mode speeds (expressed as a percent-age: 10–100) can then be selected (separate for supply air and extract air)�

3.5.7 To switch off the unit

The ventilation unit fans, the heat exchanger and an air heater, if fitted, are stopped� The circuit card is how-ever still energised and the settings are preserved in the memory�

3.5.8 Factory settings

All settings except the fan speeds are reset to factory values�

3.5.9 Actuators

It is possible to select settings for duct equipment, the valve actuators or circulation air regulation�

3.5.10 Functions

• Select ON as the value for Low pressure compensa-tion, e�g� if the cooker hood has a differential pres-sure guard in the extract air duct of the cooker hood for this function, otherwise select OFF�

• Select ON as the value for Service reminder, if the function is to be used, otherwise select Off� The time interval (6 months) can be changed�

• Select ON as the value for Summer night cooling, if you wish to select the function in the menu, other-wise select Off�

• Select ON as the heating setting if you have a model with electric air heater and want to reheat the supply air� 50 °C is the limit value for high temperature� This temperature limit can be changed� Supply air fan ctrl is selected as the control means; this can be changed to Room controlled ventilation�

• Select ON as the fireplace function setting if you want the fireplace function to be shown on the control panel display screen, otherwise select Off� The fireplace switch function decreases the extract air fan speed and increases the supply air fan speed� The freeze protection works in the reverse manner: It stops the supply air fan and only allows the extract air fan to run�

• Select ON as the value for Boost, if a boost timer or a presence detector is installed, otherwise select OFF�

3.5.11 Electric air heater

You can choose whether or not an electric air heater will be used (On) or (Off)�

3.6 Installation and service

(code 1234)

• Alarm/Service reminder

• Time switch clock (timer)

• Temperature

• Measurements

• Control functions

• Fan speeds

• Switch off

• Factory settings

• Controller

• Functions

• Air heater

* = 8 °C1 = 11 °C2 = 14 °C 3 = 17 °C 4 = 20 °C(5 = 23 °C)(6 = 26 °C)

Econo model’s thermostat for setting the temperature

Swegon reserves the right to alter specifications.12 www�swegon�com

W230.280612

4. Servicing

The locations of the filters in a ventilation unit in the right-hand version.

The locations of the filters are mirror-inverted in a left-hand model.

The ventilation unit must not be operated without filters!Use only filters recommended by Swegon in the ventilation unit.

Find the correct filters in Section 6. Technical data

4.1 Service reminderThe ventilation unit’s control system is normally preset for displaying a service reminder every six months� If required, this function can be altered in the Installation and Service menu� From same menu you set to zero the service reminder after performed service�

4.2 To open the ventilation unitIsolate the power supply voltage to the ventilation unit (pull out the mains plug from the wall socket)� Wait a few minutes before you open the inspection covers on the ventilation unit, so that the fans will have time to stop and the air heaters can cool down�

4.3 Filter change• Open the front covers�

• Wait a few minutes, so that the fans have time to stop and the air heaters, if fitted, have time to cool down�

• Change the filters�

• Close the front covers�

The filters should be vacuum cleaned every six months and should be replaced at least once per year.

4.4 Other servicingTo be carried out at least once per year.

• Withdraw the heat exchanger from the unit for in-spection� First remove the heat exchanger mounting brackets secured by four screws�

• Check that the heat exchanger passages are not clogged� Clean with a soft brush, vacuum cleaner or under running water, if needed� If you find it neces-sary to use detergent, choose one that does not corrode aluminium�

N.B.! The passages of the heat exchanger should be dry before you refit it.

• Withdraw the fans from the unit for inspection� First remove the four nuts that secure the fan plate and push the telescopic fan collar upward� Withdraw the fan downward from the front edge and then out-ward� If you withdraw the entire fan, you must also disconnect the quick-fit connector� Clean with a soft brush, vacuum cleaner, compressed air or wipe with a moist cloth, if needed� If you find it necessary to use detergent, choose one that does not corrode aluminium� Be careful not to dislocate the fan impeller’s counter weights� Protect the fan motor to prevent contact with liquid�

• Clean the inner surfaces of the ventilation unit, if needed�

• Check that the condensate discharge outlet is not clogged and check its outflow by pouring water on the bottom of the ventilation unit�

Heat exchanger

Wide-mesh filter Supply air filter

W230.280612

Swegon reserves the right to alter specifications. www�swegon�com 13

5.1 Alarms5.1.1 Alarms from a Premium control panel

• The indicating lamp is flashing red: The automated protection system has stopped the fans due to a malfunction� The alarm text is shown in the display� Remedy the malfunction�

• The indicating lamp is lit with a steady red glow: Alarm or a service reminder� The alarm text is shown in the display� Remedy the malfunction or perform service on the ventilation unit�

• The indicating lamp indicates certain unit functions with other colours� See Section ”3�2 Premium control panel”

5.2 Troubleshooting:Eventual malfunctions are shown by alarm texts in ac-cordance with 5�1�1� Investigate the components related to the malfunction and remedy the malfunction�

5.2.1 The supply air is not sufficiently heated

Low temperature setting for the supply air

Investigate and, if necessary, increase the temperature from the menu, or on the Econo model with the ther-mostat inside the ventilation unit�

The electric air heater is faulty (electrically heated models)

The air heater has one excess temperature and one overheating protection functions� The alarm is initiated in accordance with Section 5�1�1� if either of these are activated�

The over temperature protection resets itself automati-cally when the temperature decreases� The overheating protection must be reset by pressing a push button on the air heater� If you hear a click when you press in the button, this indicates that the overheating protection has been reset�

Excessively high temperature may be due to too low an air flow through the air heater� The cause can be that a filter, outer wall grille or supply air device is clogged� Replace and clean, if needed�

Tip: In most models, the outer wall grill has an insekt net� If the net has small mesh, dust and insects can clog it� During certain conditions it it is also liable to freeze� Remove the net or replace it with a net with larger mesh�

An excessively high temperature can also be due to the supply air fan having stopped or that the temperature sensor has been shaken loose from its position in the fan intake�

Badly isolated ventilation ducts

If the unit emits warm air but the supply air discharged from the air diffuser feels cold, this may be due to poorly insulated ventilation duct�

5. Alarms and troubleshooting

Freeze protection

During periods of cold weather, the heat exchanger is liable to freeze if the extract air is humid. A protective function then automatically reduces the speed of the supply air fan. Under such conditions, variations in the fan speed are therefore normal.

The LED on a Premium control panel flashes green when the freeze protection is activated.

Faulty air heater for preheating

During the thawing period, the outdoor air is heated by the air heater for preheating, so that the thawing phase will be shorter� If the thawing phase goes on for a long time, the cause may be that the overheating protection in the air heater for preheating has tripped� The over-heating protection in the cubicle inside the ventilation unit�

For acknowledging the overheating protection

The ventilation unit does not obey commands

If two overlapping commands are issued, the unit obeys the command with the highest priority, e�g� the freeze protection�

Priority 1: Commands from outer sensor or the ventila-tion unit’s protective functions�

Priority 2: External supervision (DDC)�

Priority 3: A normal control panel or the operation of the cooker hood�

Swegon reserves the right to alter specifications.14 www�swegon�com

W230.280612

6. Technical data

Water-heated air heater + thermostat

Water flow, l/h

Supply airflow

Extract air flow

Connection outputs

Supply airflow, Econo

Power consumption

Ava

ilabl

e pr

essu

re, P

a

Airflow, l/s Airflow, l/s

Airflow, l/sAirflow, l/s

The SFP is below 2�5 kW/m3/s in the thicker parts of the curves�

Ava

ilabl

e pr

essu

re, P

a

Ava

ilabl

e pr

essu

re, P

a

Tota

l out

put,

W

Total output

Preheating

Reheating

Fan power

Voltage

Fuse protection

Electricity

2670 W

750 W

900 W

1020 W

230 V, power plug

16A

Econo

1770 W

750 W

-

1020 W

230 V, power plug

10A

Pressure loss in the air heater, Econo

6.1 Sizing

W230.280612

Swegon reserves the right to alter specifications. www�swegon�com 15

Fan setting%

Sound power level broken down into octave bands, Lwokt, dB Weighted sound power level,LWA, dB(A)

63Hz

125Hz

250Hz

500Hz

1000Hz

2000Hz

4000Hz

8000Hz

47 69 60 54 54 52 47 51 31 56

52 72 63 57 56 55 50 45 35 60

56 74 66 60 58 57 52 48 39 62

61 76 68 63 60 59 55 50 42 64

65 78 70 65 61 60 56 51 43 65

69 80 72 67 62 62 58 53 45 67

74 81 73 70 64 64 61 56 48 69

77 81 74 70 64 64 62 57 50 70

81 82 75 72 66 65 63 58 51 71

86 84 77 73 67 67 65 60 53 73

100 85 79 75 69 68 67 62 54 74

Sound emitted to supply air duct

Fan setting%

Sound power level broken down into octave bands, Lwokt, dB Weighted sound power level,LWA, dB(A)

63Hz

125Hz

250Hz

500Hz

1000Hz

2000Hz

4000Hz

8000Hz

47 64 47 32 30 26 19 10 5 39

52 58 48 37 33 33 24 15 3 38

56 52 49 39 35 32 25 18 6 39

61 63 53 42 37 34 27 20 9 42

65 60 54 44 39 36 30 22 11 43

69 61 54 45 40 37 31 24 13 44

74 65 56 47 42 39 34 27 16 47

77 60 57 48 43 41 35 28 17 47

81 62 58 49 44 41 36 29 18 48

86 64 60 51 45 42 38 31 20 49

100 64 61 52 46 43 38 31 21 50

Sound emitted to extract air duct

Fan setting%

Sound power level broken down into octave bands, Lwokt, dB Weighted sound power level,LWA, dB(A)

63Hz

125Hz

250Hz

500Hz

1000Hz

2000Hz

4000Hz

8000Hz

47 63 49 38 37 35 20 9 5 41

52 61 49 35 32 28 20 13 5 39

56 63 49 39 34 28 23 16 5 40

61 58 51 43 36 31 25 19 8 40

65 62 53 44 39 33 26 21 10 43

69 54 47 46 40 35 28 23 12 42

74 60 57 50 45 41 36 26 15 48

77 62 57 51 45 42 37 28 16 49

81 63 59 52 47 42 38 29 18 50

86 66 61 53 48 44 40 31 19 51

100 66 61 55 50 45 41 33 22 53

Sound emitted to outdoor air duct

Acoustical performance

Swegon reserves the right to alter specifications.16 www�swegon�com

W230.280612

Fan setting%

Sound power level broken down into octave bands, Lwokt, dB Weighted sound power level,LWA, dB(A)

63Hz

125Hz

250Hz

500Hz

1000Hz

2000Hz

4000Hz

8000Hz

47 69 64 57 57 54 49 44 34 59

52 71 65 60 58 57 52 47 38 61

56 74 68 63 60 60 55 50 42 64

61 76 70 65 61 62 57 53 45 66

65 77 72 67 63 64 59 55 47 68

69 78 73 69 64 65 61 57 49 69

74 80 73 71 65 66 63 59 51 71

77 80 75 71 66 67 64 59 52 71

81 81 76 73 67 67 65 60 53 73

86 82 77 74 68 68 67 62 54 74

100 84 79 76 69 69 69 63 56 75

Sound emitted to exhaust air duct

Sound emitted to the surroundings

Fan setting%

Sound power level broken down into octave bands, Lwokt, dB Weighted sound power level,LWA, dB(A)

63Hz

125Hz

250Hz

500Hz

1000Hz

2000Hz

4000Hz

8000Hz

47 55 47 40 39 32 27 21 12 40

52 55 50 43 42 36 30 26 12 43

56 58 53 46 43 37 33 29 12 45

61 59 55 48 45 38 35 31 13 47

65 60 57 51 46 40 36 33 13 48

69 61 58 53 48 41 38 35 14 50

74 62 59 54 49 42 40 37 19 51

77 63 61 56 50 43 41 38 20 52

81 65 62 57 51 44 42 39 21 54

86 65 63 58 53 45 44 41 24 55

100 66 64 59 54 45 45 41 26 56

W230.280612

Swegon reserves the right to alter specifications. www�swegon�com 17

RE

SET

ELE

CTR

ICA

FTER

HEAT

EX

HA

UST

SU

PPLY

M 1~24V

14

13

24

23

S1

X11 N

MU

SI

X11 2

SI

KE

VA

X12 N

SI

X12 2

KEVA

CO

2 INP

UT

%R

H IN

PU

TTE

MP

INPU

T

EC

EC

SIKEVARU

X21,N

X21,2X21,1

X22,NX22,1X22,2

750W

14

13

24

23

S2

SIMU

900 W

6.2 Wiring diagram, ventilation unit and cooker hood

FREEZEPROTEC

TION

SENSO

R

SENSO

R, SUPPLY

AIR

SENSO

R, OU

TDO

OR A

IR

SENSO

R, OV

ERHEA

TING

PROTEC

TION

, PREH

EAT

SENSO

R, OV

ERHEA

TING

PROTEC

TION

SEN

SOR, EX

HA

UST A

IR SEN

SOR, EX

TRAC

T AIR

SENSO

R, SUPPLY

AIR/

CO

NTRO

L PAN

EL

POW

ER SUPPLY:

230V 16ASERIES RESISTA

NC

E

HEA

T EXC

HA

NG

ER BY

PASS

TRIAC

CO

N-

TROLLER

AIR H

EATER FO

R REH

EATIN

G

X11 =

SUPPLY

AIR FA

N’S PLU

G C

ON

TAC

T X

12 = EX

TRAC

T AIR FA

N’S PLU

G C

ON

TAC

T X

21 = SU

PPLY A

IR FAN

’S EC C

ON

TAC

T X

22 = EX

TRAC

T AIR FA

N’S EC

CO

NTA

CT

Swegon reserves the right to alter specifications.18 www�swegon�com

W230.280612

RESET

ELE

CTR

ICA

FTERH

EAT

EXH

AU

STS

UP

PLY

M 1~24V

14

13

24

23

S1

X11 N

MU

SI

X11 2

SI

KE

VA

X12 N

SI

X12 2

KEVA

CO

2 INP

UT

%R

H IN

PUT

TEMP IN

PUT

EC

EC

X21,N

X21,2X21,1

X22,NX22,1X22,2

750W

14

13

24

23

S2

SIMU

6.3 Wiring diagram, ventilation unit and cooker hood, Econo

FREEZEPROTEC

TION

SENSO

R

SENSO

R, SUPPLY

AIR

SENSO

R, OU

TDO

OR A

IR

SENSO

R, OV

ERHEA

TING

PROTEC

TION

, PREH

EAT

FREEZE PROTEC

TION

SENSO

R, WA

TERBORN

E A

IR HEA

TER FREEZE PRO

TECTIO

N SEN

SOR, EX

HA

UST A

IR SEN

SOR, EX

TRAC

T AIR

SENSO

R, SUPPLY

AIR/

CO

NTRO

L PAN

EL

POW

ER SUPPLY:

230V 10ASERIES RESISTA

NC

E

HEA

T EXC

HA

NG

ER BY

PASS

X11 =

SUPPLY

AIR FA

N’S PLU

G C

ON

TAC

T X

12 = EX

TRAC

T AIR FA

N’S PLU

G C

ON

TAC

T X

21 = SU

PPLY A

IR FAN

’S EC C

ON

TAC

T X

22 = EX

TRAC

T AIR FA

N’S EC

CO

NTA

CT

W230.280612

Swegon reserves the right to alter specifications. www�swegon�com 19

CO

2 IN

PUT

TEM

P IN

PUT

G+

G0

OU

T1O

UT2

M Rel

ayR

elay

OU

T4

G+

G0

OU

T1O

UT2

M Rel

ayR

elay

OU

T4

24V AC/DC

CNC

NO

1NC

23NO

L N

230V AC 50Hz

NC

NO

PN

C

P

2

1

3

2

1

3

105TK

102TKC

117PK2

117HDL

117HDL

102LT

117KHH

105A1

2 x 0,5

2 x 0,5

2 x 0,5

2 x 0,5

2 x 0,5

3 x 0,5

4 x 0,5

5 x 0,5

2 x 1,5

2 x 0,5

230V AC 50Hz

2 x 1,5

P-RTG

2 x 0,5

2 x 0,5

M24 VDC 2W (3,5VA)

M24 VDC 2W (3,5VA)

6.4. Wiring diagram, optional equipmentPriority 1: Commands from outer sensor or the ventila-

tion unit’s protective functions�

Priority 2: External supervision (DDC)�

Priority 3: A normal control panel or the operation of the cooker hood�

To connect the modular cable.

Control priority 3

Control priority 1

*) One of the following functions: Connect negative pressure compen-sation or boost leads to the BOOST/COMP� contact from the SEPARATE FUNCTIONS� A separate function can also be connected to Input 4 on the row of DDC wiring terminals� See DDC�

To cooker hood, control panel or Modbus gateway

To the cooker hood or the control panel

Fireplace switch

CO² sensor with a relay

Presence detector

Room tempera-ture sensor

Humidity sensor

Boost timer

Timer

CO² sensor

Negative pressure compensation

Duct actuator with spring return

Duct actuator with spring return

A Outdoor air duct

B Exhaust air duct

Swegon reserves the right to alter specifications.20 www�swegon�com

W230.280612

Supervision (DDC)

Control priority 2

• The functions of wiring terminals 2-5 can be activat-ed/deactivated from the control panel’s service menu�

• The status outputs (terminals 6 and 7) can always be used

8: 0 V (GND)

7: The supply air temperature actual value 0-10 V DC (corre-sponds to 10–30 °C)�

6: Fan speed actual value: 0-10 V DC

5: The supply air temperature control system 0-10 VDC (cor-responds to 10–30 °C) Not on the econo models�

4: Fan speed, 0-10 V DC

3: Alarm – signal from the ventilation unit (earthed contact)

2: Emergency stop (if contact between terminals 1-2 is broken, the ventilation unit will stop)�

1: 0 V (GND)

Separate function via DDC terminal row (e.g. Home/Away switch)

• The following changes should be made in the op-erating parameters of the ventilation unit using the Premium control panel:

• Change the fan speed in the Boost mode from speed 5 to speed 4 from the menu: Installation and ser-vice/Fan speeds/Situations menu.

• Set the separate supply and extract airflow functions to speed5 from the menu: Installation and service/Fan speeds/Speeds menu.

• Activate control of the fan speed via DDC from the: Installation and service/Control systems/DDC/Fan control system.

1 2 3 24V P2 P1 0

DD

C C

ON

TRO

L

1

2

3

4

5

6

7

8

Closed contact = Activation of the separate function

Open contact = Normal use of the separate function

Fan speed 1 = 1 - 2,9 VDC

Fan speed 2 = 3 - 4,9 VDC

Fan speed 3 = 5 - 6,9 VDC

Fan speed 4 = 7 - 8,9 VDC

Fan speed 5 = 9 - max 24 VDC

A1

A2

24VDCmax 500mA

Alarm outputmax 40V, 500mAClose = alarmOpen = no alarm

Delivery demarcation

W230.280612

Swegon reserves the right to alter specifications. www�swegon�com 21

6.5 Control diagram

SYMBOL DESIGNATION EXPLANATION

TC1 TEMPERATURE CONTROLS Temperature control for the reheating air heater

T1 TEMPERATURE SENSOR Temperature sensor, outdoor air

T2 TEMPERATURE SENSOR Temperature sensor for supply air downstream of the heat exchanger

T3 TEMPERATURE SENSOR Temperature sensor, extract air

T4 TEMPERATURE SENSOR Temperature sensor, supply air, heating

T5 TEMPERATURE SENSOR Temperature sensor, exhaust air

T6 TEMPERATURE SENSOR Excess temperature sensor for air heater for reheat/ tem-perature sensor, air heater for hot water

T7 TEMPERATURE SENSOR Excess temperature sensor for the preheating air heater

T8 TEMPERATURE SENSOR Temperature sensor, exhaust air

TZ01 OVERHEATING PROTEC-TION

Overheating protection with manual reset

TZ02 OVERHEATING PROTEC-TION

Overheating protection with manual resetDESCRIPTION OF THE FUNCTIONSCONTROL OPTIONS:

The ventilation unit is controlled from a separate Premium control panel� The speeds of the fans can be changed independently of one another� When the ventilation unit is controlled from the cooker hood in the Home/Away/Boost modes and for local extraction, the time can be set to 30, 60 or 120 min�

The temperature of the supply air is controlled from the Premium control panel� When necessary, the reheating function can also be switched off from the control panel�

Summer operation: The supply air is controlled in the summer to bypass the heat exchanger by opening the bypass cover�

- Overheating protection for the reheating air heater: The air heater for reheating is equipped with a TZ01 automatic thermostat with manual reset (preset limit value: 90 °C) as protection against overheating�

- Overheating protection for the preheating air heater: The air heater is equipped with a TZ02 automatic thermostat with manual reset as protection against overheating�

- The fans have automatic overheating protection�

IF THE SAFETY EQUIPMENT TRIPS:

- If an overheating protection with manual reset trips, it can be reset by pressing a reset button on the air heater�

- The automatic overheating protection of the fans will reset themselves when the temperature has dropped below the setpoint�

750

900

T4

TC01

THE DELIVERY DEMARCATION OF THE VENTILATION UNIT

EXTRACT AIROUTDOOR AIR

SUPPLY AIREXHAUST AIR

JUNCTION BOX

GROUP ELECTRICAL DISTRIBUTION BOX

CONTROL PANEL

Swegon reserves the right to alter specifications.22 www�swegon�com

W230.280612

EF1 SF1

HR

F1+F2

M

T1

M

01

01

SD1

F3

T8

T4

1000 W

TZ02

T7

T5

T3

T2

OHJAINPANEELI

TC01

M

TV1

TC01

T6

6.6 Control wiring diagram, Econo

SYMBOL DESIGNATION EXPLANATION

TC01 TEMPERATURE CONTROLS Manual temperature control, factory setting, approx� 17 °C

TV1 THERMOSTAT Automatic thermostat valve

T1 TEMPERATURE SENSOR Temperature sensor, outdoor air

T2 TEMPERATURE SENSOR Temperature sensor for supply air downstream of the heat exchanger

T3 TEMPERATURE SENSOR Temperature sensor, extract air

T4 TEMPERATURE SENSOR Temperature sensor, supply air, heating

T5 TEMPERATURE SENSOR Temperature sensor, exhaust air

T6 TEMPERATURE SENSOR The freeze protection sensor of the water-heated air heater

T7 TEMPERATURE SENSOR Excess temperature sensor for the preheating air heater

T8 TEMPERATURE SENSOR Temperature sensor, exhaust air

TZ02 OVERHEATING PROTEC-TION

Overheating protection with manual resetDESCRIPTION OF THE FUNCTIONSCONTROL OPTIONS:

The ventilation unit can be operated from a separate Premium control panel or a Premium cooker hood� The speeds of the fans can be changed independently of one another� When the ventilation unit is controlled from the cooker hood in the Home/Away/Boost modes and for local extraction, the time can be set to 30, 60 or 120 min�

The supply air temperature can be manually set with the water-heated air heater thermostat valve�

Summer operation: The supply air is controlled in the summer to bypass the heat exchanger by opening the bypass cover�

- Frost damage protection a water-heated air heater: If the temperature of the return water from the air heater is lower than the limit value, the controller stops the supply air fan�

- Overheating protection for the preheating air heater: The air heater for preheat is equipped with a TZ02 automatic thermostat with manual reset (presetvalue 90 °C) as protection against overheating�

- The fans have automatic overheating protections�

IF THE SAFETY EQUIPMENT TRIPS:

- If an overheating protection with manual reset trips, it can be reset by pressing a reset button on the air heater�

- The automatic overheating protection of the fans will reset themselves when the temperature has dropped below the setpoint�

THE DELIVERY DEMARCATION OF THE VENTILATION UNIT

EXTRACT AIR

E�G�: 15Cu+LE(PU)

E�G�: FLOOR HEATING CIRCUITS

OUTDOOR AIR

SUPPLY AIREXHAUST AIR

JUNCTION BOX

GROUP ELECTRICAL DISTRIBUTION BOX

W230.280612

Swegon reserves the right to alter specifications. www�swegon�com 23

6.7 Dimensions

1234

� 200 � 200 � 200 � 200

Swegon CASA W230 R

W230 and base

Swegon CASA W230 L

Condensate drain connections

Duct Connections

Supply air Extract air Outdoor air Exhaust air

1

2 3

4

4

3 2

1

1420

122

122

6.8 WeightVentilation unit: 155 kg�

6.9 Optional equipment•Humiditysensor

•Carbondioxidesensor

•Temperaturethermostat

•Presencedetector

•Fireplaceswitch

•Weeklytimer/24-hourtimer

•Boostswitchwithtimer

•Humiditysensor

•Modbusgateway

•Roomtemperaturesensor

•Sensorfornegativepressurecompensation

•20mmodularcablewithRJ9connector

•20mmodularcablewithRJ9outlet

•RJ9extensionconnector

•Base(R/L)

•SetofreplacementfiltersOneG3+1pcs.F7+ one PPI-20

400 400

Swegon reserves the right to alter specifications.24 www�swegon�com

W230.280612

7. Commissioning

Operation Factory setting Setting value

Temperature, supply air 17 ℃

Base display 1

Time switch clock (timer) On

Temperature On

Fan speeds (situations)�

Away 1

Home 3

Boost 5

Cool off 4

Cooling 4

Heating 3

Fan speeds

Speed 1, supply air fan 40 %

Speed 1, extract air fan 60 %

Speed 2, supply air fan 65 %

Speed 2, extract air fan 65 %

Speed 3, supply air fan 75 %

Speed 3, extract air fan 75 %

Speed 4, supply air fan 85 %

Speed 4, extract air fan 85 %

Speed 5, supply air fan 100 %

Speed 5, extract air fan 100 %

Negative pressure compensation Off

Service reminder On

Interval 6 months

Summer night cooling On

Start temperature (in start menu) 22 ℃

Fan speed (in start menu) No change

neutral zone (in Installation and service menu) 1 ℃

Temperature limiting (in Installation and service menu) 14 ℃

Heating Off

Temp� limitation 50 ℃

Control Supply air controlled

Filter guard (extra equipment) On

Fireplace switch function (with fireplace switch) Off

Boost (with extra timer or presence detector) On

Input, heat exchange limit

Min� temperature 12 °C

Neutral zone 3 °C

Outdoor temperature limit, for activation of air heater 10 °C

W230.280612

Swegon reserves the right to alter specifications. www�swegon�com 25

Airflows Project planning values Setting value

Supply air, total l/s l/s

Away

Home

Boost

Extract air, total l/s l/s

Away

Home

Boost

Other comments

Data for the ventilation unit

Write down the unit-specific data here (on the identification plate of the ventilation unit) for use when you contact a service company�

Remember to explain the use of the item of optional equipment and how to service it to the user/caretaker!

Preset by: Date:

Swegon reserves the right to alter specifications.26 www�swegon�com

W230.280612

GUARANTOR

Swegon ILTO Oy

Asessorinkatu 10, FI-20780 St� KARINS, Finland�

GUARANTEE PERIOD

The product has a two (2) year guarantee as from the date of purchase�

SCOPE OF THE GUARANTEE

The guarantee covers defects that have arisen during the guarantee period, which have been reported to the manufacturer, or been declared by the guarantor or a representative of the guarantor, and which refers to design, manufacture or material defects as well as consequential defects that have arisen on the product itself� The above mentioned defects are to be cleared by putting the product in working order�

GENERAL GUARANTEE LIMITATIONS

The guarantor’s guarantee liability is limited in accordance with these guarantee conditions and the guarantee does not cover damages to property or personal injury� The guarantor is not bound to comply with verbal promises in addition to this guarantee�

LIMITATIONS ON GUARANTEE LIABILITY

This guarantee is granted on condition that the product is used in a normal way or under comparable circumstances for the intended purpose, and that the instructions for use have been observed�

The guarantee does not cover faults that have been caused by the following:

- Transport of the product�

- Careless use or overloading the product�

- Failure to follow the instructions dealing with installation, operation, maintenance and care�

- Incorrect installation of the product or incorrect location at the place where it is used�

- Circumstances which are not the fault of the guarantor, such as excessive variations in voltage, damage by lightning and fire or other accidents�

- Repairs, maintenance or design modifications that have been done by unauthorized parties�

- The guarantee does not cover insignificant defects from an operational standpoint such as scratches on surfaces�

- Parts, which through handling or normal wear are exposed to a greater than normal risk of failure, such as lamps, glass, porcelain, paper and plastic parts as well as fuses are not covered by the guarantee�

- The guarantee does not cover settings, information about usage, maintenance, service or cleaning which is normally described in the instructions for use or the work required to rectify faults caused by the user neglecting to observe the warning or installation instructions, or investigation of such�

CHARGES DURING THE GUARANTEE PERIOD

The authorized service partner will not charge the client for repairs, replaced parts, repair work, transport or travelling expenses necessary for carrying out the repair work that are within the scope of the guarantee�

This however assumes the following:

- The defective parts are handed over to the authorized service partner�

- that the repair begins and the work is carried out during normal working hours� The authorized service partner has the right to charge the client for extra costs for urgent repairs, or repairs carried out outside of normal working hours� However if the defects are likely to cause a health risk or substantial economic damage, then the defects will be repaired immediately without extra charge�

- A service vehicle or public means of transportation that follows a timetable (boats, airplanes or snow vehicles are not considered public means of transportation) can be used in conjunction with the repair of the product or replacement of defective parts�

- The costs for dismantling and installation of equipment, which is securely mounted to the place where it is used, cannot be considered abnormal�

REMEDIAL MEASURES WHEN A FAULT HAS BEEN DISCOVERED

If a defect is discovered, the client must without delay report the defect to the manufacturer or to an authorized service partner� Specify which product has a fault (product model, type designation on the guarantee card or on the product identification plate, serial number); describe the type of fault as accurately as possible, and the circumstances under which the fault has arisen� If there is risk that the fault may have consequential impact on the environment, steps must be immediately taken to prevent this from occurring� A prerequisite for valid guarantee liability is that the manufac-turer or a representative of the manufacturer is given opportunity to inspect the fault reported in the guarantee claim before the repair work begins� A prerequisite for repair under guarantee is also that the client, in a satisfactory manner, can prove that the guarantee is valid (= written receipt of purchase)� After the guarantee period has expired, guarantee claims, which have not been submitted in writing prior to the expiration date of the guarantee, are not valid�

Guarantee Conditions

W230.280612

Swegon reserves the right to alter specifications. www�swegon�com 27

We at:

Swegon ILTO Oy Asessorinkatu 10 20780 St. Karins FINLAND

We hereby affirm thatthe Swegon CASA ventilation units comply with the following EC Directives:

The machinery Directive (2006/42/EC) Low Voltage Directive (2006/95/EC) The EMC Directive (2004/108/EC)

and that the following harmonised standards have been applied:

EN 60335-1:2002 +A1:2004 +A11:2004 +A12:2006 +A13:2008 +A2:2006 EN 60204-1:2006 +A1:2009 EN 60034-5:2001 +A1:2007 EN 55014-1:2006 EN 55014-2:1997 +A1:2001 +A2:2008 EN 61000-3-2:2006 EN 61000-3-3:2008

Person authorised to compile the technical documentation:

Name: Rami Wiberg Address: Asessorinkatu 10, 20780 S:t Karins, Finland E-mail: rami�wiberg@ilto�fi

Date: S:t Karins 01�11�2010

Signature:

Ilari Niittymäki CEO Swegon ILTO Oy

N.B.! The original language of the document on this page is English.

EG Compliancy Declaration

Swegon reserves the right to alter specifications.28 www�swegon�com

W230.280612

W230.280612

Swegon reserves the right to alter specifications. www�swegon�com 29

Swegon reserves the right to alter specifications.30 www�swegon�com

W230.280612

W230.280612

Swegon reserves the right to alter specifications. www�swegon�com 31

www�swegon�com