the relay protection scheme for distribution network with distributed generations

8
The Relay Protection Scheme for Distribution Network with Distributed Generations 1a He Shien , 2 b Dong Xinzhou , 3 c Z. Q. Bo and 1 d Suonan Jiale 1 Dept. of Electrical Engineering, Xi’an Jiaotong University, Xi’an China 2 Dept. of Electrical Engineering, Tsinghua University, Beijing, China, AREVA T&D Co. Stafford, UK 3 Dept. of Electrical Engineering, Xi’an Jiaotong University, Xi’an China a [email protected], b [email protected], c [email protected], d [email protected] Keywords-non-communication protection; distributed generation; tapped-line; double-circuit Abstract. Three-zone distance protection and four-zone zero sequence over-current protection are traditional relay protection schemes used for tapped-lines that connect distributed photovoltaic, wind, and small hydro power sources into a distribution network. These protection schemes cannot quickly clear the faults that occur at the end of the protected line. A newly developed non- communication protection scheme for tapped-line and double-circuit line tested at Gansu Power Grid can significantly speed up fault clearing at the end of the lines, and achieve fast tripping for the entire line section. This protection scheme also shows advantageous results for distribution grid with distributed generation. Introduction A variety of power failures or abnormal operations caused by natural conditions (e.g. lightning), maintenance, and etc. in an electric power system may result in shortened component life expectancy, power quality disturbances, or even power outage. Protection relay is an automatic device that responses to electrical component failure or abnormal operations by tripping the circuit breakers. Protection should be selective, swift, sensitive and reliable to detect and isolate the faults so as to maintain the system stability while reduce equipment failures and power line damages. In China, there are many tapped-lines in the low-voltage transmission and distribution systems. There are many 110kV lines in Gansu Power Grid and an 110kV line may have one or more tapped- lines in a line section. Recent clean power development in the under-developed regions of Gansu has seen photovoltaic, wind, and small hydro power plants increasingly connected to power grid through tapped-lines. The main relaying protection for these lines are traditional three-zone distance and four-zone zero sequence over-current protection. These protections cannot quickly clear the faults occurring at the end of the protected lines. When the three-zone distance and four-zone zero sequence over-current protection are employed, the relay away from a fault point can only clear the fault line with the second zone time delay, normally 0.3s-0.5s for a fault at the end of the line section. This does not meet the requirement of fast fault clearing. Non-communication protections have been installed on the 110 kV Yan-Da-Gu double-circuit line with tapped lines connected to distributed power sources. The operational experience shows that the non-communication protection [1-3] can significantly improve the fault clearing speed at the line end and achieve fast fault tripping for the entire line without communication links. Its setting is simple and it can effectively improve power system security and reliability. The basic principles of non-communication protection Non-communication protection is an auxiliary speed-up protection. It can work together with distance protections for a whole line by using single-end measurement. Distance protection can only fast clear the fault in distance zone 1. Other faults can be cleared in distance zone 2 or zone 3 based Advanced Materials Research Vols. 433-440 (2012) pp 4046-4052 Online available since 2012/Jan/03 at www.scientific.net © (2012) Trans Tech Publications, Switzerland doi:10.4028/www.scientific.net/AMR.433-440.4046 All rights reserved. No part of contents of this paper may be reproduced or transmitted in any form or by any means without the written permission of TTP, www.ttp.net. (ID: 130.15.241.167, Queen's University, Kingston, Canada-02/10/13,08:56:23)

Upload: jia-le

Post on 19-Dec-2016

212 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: The Relay Protection Scheme for Distribution Network with Distributed Generations

The Relay Protection Scheme for Distribution Network with Distributed Generations

1aHe Shien ,2 b Dong Xinzhou ,3 c Z. Q. Bo and 1 d Suonan Jiale 1Dept. of Electrical Engineering, Xi’an Jiaotong University, Xi’an China

2Dept. of Electrical Engineering, Tsinghua University, Beijing, China, AREVA T&D Co. Stafford, UK

3Dept. of Electrical Engineering, Xi’an Jiaotong University, Xi’an China

[email protected], [email protected], [email protected],[email protected]

Keywords-non-communication protection; distributed generation; tapped-line; double-circuit

Abstract. Three-zone distance protection and four-zone zero sequence over-current protection are

traditional relay protection schemes used for tapped-lines that connect distributed photovoltaic,

wind, and small hydro power sources into a distribution network. These protection schemes cannot

quickly clear the faults that occur at the end of the protected line. A newly developed non-

communication protection scheme for tapped-line and double-circuit line tested at Gansu Power

Grid can significantly speed up fault clearing at the end of the lines, and achieve fast tripping for the

entire line section. This protection scheme also shows advantageous results for distribution grid

with distributed generation.

Introduction

A variety of power failures or abnormal operations caused by natural conditions (e.g. lightning),

maintenance, and etc. in an electric power system may result in shortened component life

expectancy, power quality disturbances, or even power outage. Protection relay is an automatic

device that responses to electrical component failure or abnormal operations by tripping the circuit

breakers. Protection should be selective, swift, sensitive and reliable to detect and isolate the faults

so as to maintain the system stability while reduce equipment failures and power line damages.

In China, there are many tapped-lines in the low-voltage transmission and distribution systems.

There are many 110kV lines in Gansu Power Grid and an 110kV line may have one or more tapped-

lines in a line section. Recent clean power development in the under-developed regions of Gansu

has seen photovoltaic, wind, and small hydro power plants increasingly connected to power grid

through tapped-lines. The main relaying protection for these lines are traditional three-zone distance

and four-zone zero sequence over-current protection. These protections cannot quickly clear the

faults occurring at the end of the protected lines.

When the three-zone distance and four-zone zero sequence over-current protection are employed,

the relay away from a fault point can only clear the fault line with the second zone time delay,

normally 0.3s-0.5s for a fault at the end of the line section. This does not meet the requirement of

fast fault clearing.

Non-communication protections have been installed on the 110 kV Yan-Da-Gu double-circuit

line with tapped lines connected to distributed power sources. The operational experience shows

that the non-communication protection [1-3] can significantly improve the fault clearing speed at

the line end and achieve fast fault tripping for the entire line without communication links. Its

setting is simple and it can effectively improve power system security and reliability.

The basic principles of non-communication protection

Non-communication protection is an auxiliary speed-up protection. It can work together with

distance protections for a whole line by using single-end measurement. Distance protection can only

fast clear the fault in distance zone 1. Other faults can be cleared in distance zone 2 or zone 3 based

Advanced Materials Research Vols. 433-440 (2012) pp 4046-4052Online available since 2012/Jan/03 at www.scientific.net© (2012) Trans Tech Publications, Switzerlanddoi:10.4028/www.scientific.net/AMR.433-440.4046

All rights reserved. No part of contents of this paper may be reproduced or transmitted in any form or by any means without the written permission of TTP,www.ttp.net. (ID: 130.15.241.167, Queen's University, Kingston, Canada-02/10/13,08:56:23)

Page 2: The Relay Protection Scheme for Distribution Network with Distributed Generations

on protection selectivity, which usually means there is a time delay of 0.3s or longer. In order to

shorten the time delay, non-communication protection bundled with distance protection can

improve the performance of traditional relays. For different applications based on system

configurations, two types of non-communication protections are used in Gansu Power Grid. 1. Tapped line non-communication protection [4, 6]; 2. Double-circuit non-communication protection [5]. See Table 1 for the characteristics of these two types.

The basic principles of non-communication protection for tapped-line. When an asymmetric

fault near remote end occurs on a power line with tapped lines, the circuit breaker at remote end of

faulted line will trip. This will change the configuration of the system and lead to increase or

decrease of the non-fault phase current. When this change takes place within the time window of

the non-communication protection at the line end, and the distance zone 2 maintains the pick-up

state, the non-communication protection ascertains that the fault occurred in its zone and will

accelerate the distance zone 2 to trip out.

The time period for line distance zone 1 trip plus the circuit breaker trip is normally fixed. When

the non-communication protection detects the current change point is within this time window, it

can distinguish the current change caused by the remote end circuit breaker tripping from other

disturbances. If an internal fault near remote end occurs on the line, the distance zone 2 remains at

pick-up state when the remote circuit breaker tripped out. Therefore the distance zone 2 acts as the

necessary condition for the non-communication protection picking-up. On the contrary, if the fault

occurs on an adjacent line, then the tripping of circuit breaker of that line must clear the fault and

the distance zone 2 of this line should be drop-off.

TABLE I. THE TWO TYPE OF NON-COMMUNICATION PROTECTIONS

Type Advantages Disadvantages

Tapped line non-

communication

protection

No need for communication with remote

protections;

Applicable to any line with or without tapped

line;

Applicable to single line or double-circuit

lines.

Can only be applied to asymmetric

fault;

Can only be applied to three-phase

trip system.

Double-circuit non-

communication

protection

No need for communication with remote

protections;

Suitable for all types of fault;

Setting is simple;

Can be applied to the three-phase trip or

single-phase trip system.

When the non-communication

protection system is installed at the

strong system side, the protection

may refuse to trip three phase fault;

Can only be applied to double-circuit

system.

The non-communication protection accelerates the distance zone 2 only for asymmetry fault. For

the three-phase fault there is no so-called non-fault phase, the criteria of the non-communication

protection cannot work properly.

The conclusion can be drawn. When asymmetric fault occurs on lines with tapped lines, if the

non-communication protection detects that the current ratio is greater than the ratio of setting within

the setting time window τ, and at the same time the current change is greater than that of the setting,

this is an internal fault and accelerated tripping decision is made. Otherwise, the protection will take

no action if the fault is outside. Figure 1 shows the logic of tapped line non-communication

protection.

Figure 1. Non-communication protection logic for tapped line

The setting menu for tapped line non-communication protection is shown in Table 2.

Advanced Materials Research Vols. 433-440 4047

Page 3: The Relay Protection Scheme for Distribution Network with Distributed Generations

The basic principles of non-communication protection for double-circuit Lines. The overall configuration of non-communication protection for double-circuit lines is shown in Figure 2.

TABLE II. TAPPED LINE NON-COMMUNICATION PROTECTION SETTINGS MENU

Setting Meaning Range Default

Delta Acc Status Enabled/Disabled Enabled/Disabled Disabled

Ratio Set Current unbalance ratio,

(I2+I0)/I1

0.05-2 0.1

Time Delay The middle point of time

window

50-200ms 100ms

Delta Time Half of time window 10-200ms 90ms

Current Set Low load 0.01-2A 0.05A

Delta Current Current change 0.01-2A 0.1A

In Figure 2 the distance relays RS1 and RS2 are installed on each line of the double-circuit lines.

Two double-circuit non-communication protection modules are incorporated into each distance

relay respectively. The double-circuit non-communication protection of the two lines are connected

through the cross-connected cables, which will be used to enable the mutual transfer permission /

latch-up signal to speed up the clearing of line end fault. The two modules together with the

communication link between them constitute the double-circuit non-communication protection

(RS12 in Figure 2).

Figure 2. Double-circuit non-communication protection

When a short circuit occurs on one line of the double-circuit and the remote end circuit breaker is

tripped out, the electrical symmetry of the two lines no longer exists. The detected fault directions

of the near end of the two lines should be opposite. The fault direction of the faulted-line is forward

and that of the healthy-line is backward. The double-circuit non-communication protection can

distinguish an internal fault from an external one based on this feature.

The permission signal is exchanged between the two double-circuit non-communication

protections. If one protection ascertains that fault direction is backward and the distance zone 2 does

not pick up, it transmits the permission signal to the same end protection at the other line. If zone 2

of the other distance protection pickups and the relay receives this permission signal, then the fault

is confirmed and a tripping-signal is activated. Otherwise, non-communication protection will be

blocked. In order to protect symmetry fault and asymmetry fault, the positive-sequence power

direction component and negative-sequence power direction component are adopted in fault

direction detection unit of the relay. The basic logic of non-communication protection is shown in

Figure 3.

4048 Materials Science and Information Technology

Page 4: The Relay Protection Scheme for Distribution Network with Distributed Generations

Figure 3. Double-circuit non-communication protection logic

As seen from Figure 3, the key component of the protection is fault direction detection. Negative

sequence component is fault super-imposed quantity, which is sensitive and used for asymmetry

fault. The positive sequence component is for symmetry fault.

The settings for double-circuit non-communication protection are shown in Table 3.

TABLE III. SETTINGS OF DOUBLE-CIRCUIT NON-COMMUNICATION PROTECTION

Settings Meaning Range Default

DL Acc Status Enabled/Disabled Enabled/Disabled Disabled

Angle1 Positive sequence direction angle 20-90° 70°

Angle2 Negative sequence direction angle 20-90° 90°

V1pol Set Positive sequence voltage threshold 0.5-25V 5V

V2pol Set Negative sequence voltage threshold 0.5-25V 5V

The fault direction detection unit is the key component of double-circuit non-communication

protection. It compares the angle between voltage phasor and current phasor to determine fault

direction. Angle 1 and angle 2 in the menu represent the angle between the real axis and the central

line in the operation characteristics diagram of positive sequence direction unit and negative

sequence direction unit respectively, as shown in Figure 4.

In general, Angle 1 is set as line positive sequence impedance angle, while Angle 2 is set as 90°

because the impedance of the negative sequence equivalent circuit of the system can be considered

as reactance. Since voltage should be used in the direction detection unit, and sometimes positive

sequence and negative sequence voltage may be too low to calculate accurately, positive sequence

voltage threshold V1pol Set and negative sequence voltage threshold V2pol Set should be set in the

menu. When measured voltage is less than the settings, the direction component will be blocked.

(a) Positive sequence direction

(b) Negative sequence direction

Figure 4. Direction component characteristic

110 kV Yan-Da-Gu double-circuit line protection configuration and operational problems

The topology of 110 kV Yan-Da-Gu double-circuit is shown in Figure 5. The protection of the

Yanguoxia is CSL-164B, and that of Guchen Substation is PSL-621C. These two kinds of

microprocessor based relays have three-zone phase to phase and phase to ground distance elements

as well as four-zone zero sequence over-current element and reclosing element.

Advanced Materials Research Vols. 433-440 4049

Page 5: The Relay Protection Scheme for Distribution Network with Distributed Generations

The settings of Yan-Da-Gu II Guchen side relay is as follows: positive sequence impedance

angle is 73°, the phase to phase impedance zone I, II, Ⅲ are 0.15Ω/Φ, 0s; 1.96Ω/Φ, 0.6s; 7.63Ω/

Φ, 5.2s respectively; the phase to ground impedance zone I, II, Ⅲ are 0.12Ω/Φ, 0 s; 1.78Ω/ Φ,

0.6s; 3.05Ω/Φ, 2.3s respectively; zero sequence current zone I, II, III, IV are 44.1A, 0 s; 4.05A,

0.6s; 0.98A, 4.4s; 0.98A, 4.4s respectively; reclosing time 2.6s.

Figure 5. 110 kV Yan-Da-Gu double-circuit with tapped lines.

As shown above, the time setting of zone II and III are long. And the power line supplies power

to loads in Linxia and Gannan districts, in which there are many small hydro power plants. So the

operation modes will be changed frequently. Sometimes the load is heavy. However, when a fault

occurs at the remote end of the protected line, the long time delay to clear the fault can still threaten

system safety.

Because the electrical distance from tapped line connection node to substation Guchen is less

than 20% of the whole line, and the length of tapped line to substation Dagou is very short, if only

distance protection is configured without non-communication protection in the substation, zone I

setting of distance protection at substation Guchen must be very small, and most of the protected

line can only be protected by zone II of distance protection, which can not meet the operational

requirements.

In upgrading and retrofitting of above protection system, three zones distance protection and

tapped line and double-circuit non-communication protection are adopted, which can trip a fault at

any point of the protected line with high speed based on single-terminal measurement. Two tapped

line non-communication protection relays have been installed at substation Guchen and hydro plant

Yanguoxia respectively and one double-circuit non-communication protection relay has been

installed at substation Guchen. They have been put into operation after commissioning test.

Non-communication protection operation in the field

The correctness and reliability of non-communication protection principle and scheme have been

validated by many simulation and tests. The protection relay has been implemented based on

AREVA relay platform and passed the tests. AREVA P540 series relay integrated with non-

communication protection module can trip a fault at any point of the protected line with high speed.

Although non-communication is based on distance protection, it will not affect distance protection.

Whether non-communication protection is activated or not, it will not block distance protection and

will not affect the operation characteristics of distance protection. If distance protection is blocked,

non-communication protection will be blocked too. But if non-communication protection is

blocked, distance protection will operate normally. Setting of tapped line non-communication protection. P543 protection relay integrated with tapped line non-communication protection has three zone distance protection and over-current protection.

The functions and logics of the relay based on P543 can be configured according to the field

requirements. The key setting of the scheme for tapped line non-communication protection is shown

in Table IV.

4050 Materials Science and Information Technology

Page 6: The Relay Protection Scheme for Distribution Network with Distributed Generations

TABLE IV. THE SETTING OF TAPPED LINE NON-COMMUNICATION PROTECTION

Settings Delta

Acc

Status

Ratio

Set

Time

Delay

Delta

Time

Current

Set

Delta

Current

Value Enabled 0.2 90ms 60ms 0.05A 0.5A

Wiring and setting of double-circuit non-communication protection. Unlike general single-terminal protection, the double-circuit non-communication protection need to exchange permission / block signal between two relays installed at the same terminal of the double-circuit, which is implemented by connecting the output of one protection relay to the input interface of the other protection relay. The connection is as shown in Figure 6.

Figure 6. Wiring of double-circuit protection relays

P543 has many output and input interfaces. Depending on the requirements, field applications

can be configured by setting PSL logics. In the application presented in the paper, the connections

are that 220VDC+ to F16 (opto input) of P543 relay at Gu side of line Yan-Da-Gu I, F15 of P543

relay to G11 of P543 relay at Gu side of line Yan-Da-Gu II, and G12 of P543 relay at Gu side of

line Yan-Da-Gu II to 220VDC-; 220VDC+ to F16 of P543 relay at Gu side of line Yan-Da-Gu II,

F15 of P543 relay to G11 of P543 relay at Gu side of line Yan-Da-Gu I, and G12 of P543 relay at

Gu side of line Yan-Da-Gu I to 220VDC-.

The settings of double-circuit non-communication protection are given in Table V.

TABLE V. SETTINGS OF DOUBLE-CIRCUIT NON-COMMUNICATION PROTECTION

Setting DL Acc

Status

Angle1 Angle2 V1pol Set V2pol Set

Value Enabled 70° 90° 5V 5V

Non-communication protection operation. The non-communication protection relay has

experienced three external faults, of which one is a close-to-busbar phase to ground fault, and one internal fault on the tapped line, the relays respond correctly for each fault since it has been put into operation [7].

Conclusions

Non-communication protection can trip a fault at any point of the protected line with high speed

without communication channels. It can reduce the protection coordination time, simplify the

settings, improve the sensitivity, and ease the installations. It helps to improve system operation

safety and reliability.

It is suitable for the smart distribution grid. With the rapid development of renewable energy, the

non-communication protection can be widely used in distribution networks with distributed power

sources such as photovoltaic, wind, and small hydro power as these distributed power sources are

tapped onto the distribution networks.

Advanced Materials Research Vols. 433-440 4051

Page 7: The Relay Protection Scheme for Distribution Network with Distributed Generations

References

[1] Dong Xinzhou, Subin, Shi Shenxing. Secondary Disturbance Information and Its Applications

in Relay Protection. Automation of Electric Power Systems. 2004, 28 (2)

[2] Dong Xinzhou, Subin, Shi Shenxing. Fault Information, Wavelet Transforms and Relay

Protection. China Power, 2003, 4.

[3] Shi Shenxing, Dong Xinzhou, Liu Jianzheng. Research for Non-Unit Protection in Distribution

Power System. Automation of Electric Power System, 25(6), 2001p.31-34

[4] Gan Zhong, Dong Xinzhou, Z.Q. Bo. Non-communication Protection in Power Transmission

Lines-Basic Principle. Automation of Electric Power System, 26(6), 2002 p.31-34

[5] Dong Xinzhou, Li Youyi, Z.Q. Bo. Non-communication Protection of Double-Circuit Line

Systems Part One:Fault Analysis and Protection Principle. Automation of Electric Power

Systems, 2004, 4 (1)

[6] Liu Jiankai, Dong Xinzhou, Z.Q. Bo. Non-communication Protection for Distribution Systems

with the Tapped-Load. Automation of Electric Power Systems, 2003, 27 (1): 37-41

[7] He Shien, Dong Xinzhou, Z.Q. Bo. The Application of Non-communication Protection in

Gansu Electric Power Grid. Tsinghua-Mingji Joint Seminar on Automation of Electric Power

Systems, 2008, Seoul.

4052 Materials Science and Information Technology

Page 8: The Relay Protection Scheme for Distribution Network with Distributed Generations

Materials Science and Information Technology 10.4028/www.scientific.net/AMR.433-440 The Relay Protection Scheme for Distribution Network with Distributed Generations 10.4028/www.scientific.net/AMR.433-440.4046