346ni sustavi - pogl. 7
DESCRIPTION
Extraction Steam Systems. The extraction steam system is designed to ASMEB31.1. The extraction line design pressure and temperature depend upon the specificextraction point from the turbine as shown on the full-load heat balance diagramat valve wide open (VWO) and 5 percent overpressure. Extraction steam is typicallysuperheated steam except for the lowest extraction points, which are in the wetsteam region.Extraction line sizing is determined by performingTRANSCRIPT
ENERGETSKI SUSTAVI Poglavlje: 7
Prof. dr. sc. Z. Prelec, dipl. ing. List: 1
-------------------------------------------------------------------------------------------------------------------------
POMOĆNI SUSTAVI U ENERGETSKIM
PROCESIMA
• Sustav za rekuperaciju kondenzata • Rashladni sustav
SUSTAV ZA REKUPERACIJU KONDENZATA
U raznim energetskim, procesnim i industrijskim pogonima za
razna grijanja koristi se para (niskotlačna). Izmjenom topline
para predaje svoju osjetnu i latentnu toplinu pri čemu nastaje
kondenzat.
Cilj rekuperacije: • sakupiti i vratiti u proces nastali kondenzat
(demineraliziranu vodu); • rekuperirati i iskoristiti maksimalnu količinu sadržane
toplinske energije u kondenzatu. Kondenzat sadrži osjetnu toplinu koja se može iskoristiti:
� pothlañivanjem, � izmjenom topline s hladnijim medijem, � korištenjem topline otparka.
ENERGETSKI SUSTAVI Poglavlje: 7
Prof. dr. sc. Z. Prelec, dipl. ing. List: 2
-------------------------------------------------------------------------------------------------------------------------
1) POTHLAðIVANJE KONDENZATA
Cilj pothlañivanja kondenzata je da se osim latentne topline pare
maksimalno iskoristi i osjetna toplina kondenzata.
Pothlañivaje kondenzata Pothlañivanje kondenzata pomoću termostatskoga pomoću regulatora temperature odvajača kondenzata
ENERGETSKI SUSTAVI Poglavlje: 7
Prof. dr. sc. Z. Prelec, dipl. ing. List: 3
-------------------------------------------------------------------------------------------------------------------------
2) NAKNADNA IZMJENA TOPLINE S HLADNIJIM FLUIDOM
Cilj je maksimalno iskoristiti osjetnu toplinu izlaznoga
kondenzata u protustrujnoj izmjeni s nekim hladnijim fluidom.
Shema sustava korištenja osjetne topline kondenzata u protustrujnome izmjenjivaču topline
ENERGETSKI SUSTAVI Poglavlje: 7
Prof. dr. sc. Z. Prelec, dipl. ing. List: 4
-------------------------------------------------------------------------------------------------------------------------
3) KORIŠTENJE TOPLINE OTPARKA KONDENZATA
Toplina otparka kondenzata može se koristiti prigušivanjem
kondenzata na niži tlak na kojemu dolazi do isparivanja dijela
kondenzata.
h-p dijagram za vodenu paru
Količina isparena kondenzata pri prigušivanju od tlaka p2 na tlak p3 iznosi:
r
hhm
r
hhmm
KKP
4342−−−−
====−−−−
====
mP – količina isparena kondenzata mk – količina kondenzata r – latentna toplina isparivanja
ENERGETSKI SUSTAVI Poglavlje: 7
Prof. dr. sc. Z. Prelec, dipl. ing. List: 5
-------------------------------------------------------------------------------------------------------------------------
Shema korištenja otparka kondenzata jednostupanjskim prigušenjem
Shema korištenja otparka kondenzata višestupanjskim prigušivanjem
Legenda:1-trošilo topline, 2-otparivač, 3-generator pare, 4-napojni
spremnik, 5-kondenzatna pumpa, 6-napojna pumpa, 7-pokazivač protoka,
8-odvajač kondenzata, 9-nepovratni ventil.
ENERGETSKI SUSTAVI Poglavlje: 7
Prof. dr. sc. Z. Prelec, dipl. ing. List: 6
-------------------------------------------------------------------------------------------------------------------------
Shema korištenja otparka kondenzata pomoću termosifonskoga efekta
Shema korištenja otparka kondenzata pomoću efekta
termokompresije
ENERGETSKI SUSTAVI Poglavlje: 7
Prof. dr. sc. Z. Prelec, dipl. ing. List: 7
-------------------------------------------------------------------------------------------------------------------------
RASHLADNI SUSTAV
Najveći dio neiskorištene topline iz energetskih procesa odvodi se
u okolinu putem rashladnih sustava.
Prema izvedbi, rashladni sustavi mogu biti: • protočni direktni • protočni indirektni • otvoreni cirkulacijski s vlažnim rashladnim tornjem • kombinirani (protočni/cirkulacijski) s vlažnim rashladnim
tornjem • zatvoreni cirkulacijski sa suhim rashladnim tornjevima
OSNOVNE IZVEDBE RASHLADNIH SUSTAVA
Shema direktno protočnoga rashladnog sustava
ENERGETSKI SUSTAVI Poglavlje: 7
Prof. dr. sc. Z. Prelec, dipl. ing. List: 8
-------------------------------------------------------------------------------------------------------------------------
Shema indirektno protočnoga rashladnog sustava
Shema otvorena cirkulacijskoga rashladnog sustava s vlažnim rashladnim tornjem
Turbina
Cirk. pumpa
Razni hladnjaci
Cirk. pumpa
Turbina
Cirk. pumpa
Razni hladnjaci
Pumpa za
dodatnu vodu
Rashladni toranj
Hladnjak Kondenzator
Kondenzator
ENERGETSKI SUSTAVI Poglavlje: 7
Prof. dr. sc. Z. Prelec, dipl. ing. List: 9
-------------------------------------------------------------------------------------------------------------------------
Shema kombinirana (protočno/cirkulacijskog) rashladnog sustava s vlažnim rashladnim tornjem
Shema zatvorena cirkulacijskoga rashladnog sustava sa suhim rashladnim tornjem
Turbina
Cirk. pumpa
Razni hladnjaci
Kondenzator
Turbina
Cirk. pumpa
Razni hladnjaci
Rashladni tornjevi
ENERGETSKI SUSTAVI Poglavlje: 7
Prof. dr. sc. Z. Prelec, dipl. ing. List: 10
-------------------------------------------------------------------------------------------------------------------------
TOPLINSKA I MATERIJALNA BILANCA RASHLADNOG SUSTAVA S OTVORENIM
(VLAŽNIM) RASHLADNIM TORNJEM
� Približenje temperaturi vlažnoga termometra ∆∆∆∆tvl,t=tw-tvl,t=t1-tvl,t
U praksi, vlažni rashladni tornjevi normalno hlade vodu do
temperature t1 koja je 3 do 8 0C iznad temperature vlažna
termometra tvl,t.
Temperatura vlažna termometra definira je kao temperatura
isparivanja vodena filma u struji zraka kod neke postojeće
vlažnosti i temperature okoline.
Povratna zagrijana voda mw, T2
Vlažni zagrijani zrak X2, h2, (∆∆∆∆mwi+∆∆∆∆mws)
Ulazni zrak mzr, X1, h1
Polazna ohlañena voda mw, T1
Ispuštanje (odsoljavanje) ∆∆∆∆mwo
Dodatna voda (dopunjavanje)
ENERGETSKI SUSTAVI Poglavlje: 7
Prof. dr. sc. Z. Prelec, dipl. ing. List: 11
-------------------------------------------------------------------------------------------------------------------------
� Raspon hlañenja
∆∆∆∆tw=t2-t1
Raspon hlañenja je definiran kao razlika ulazne
(zagrijane )i izlazne (ohlañene) vode iz rashladna tornja.
U praksi se kreće od 6 do 12 0C.
� Efikasnost hlañenja u rashladnom tornju
tvl
h
tt
tt
,2
12
−−−−
−−−−====ηηηη
Visina tornja
Ulazna voda
Ulazni zrak
t2
t1
tvl,t
∆∆∆∆tvl,t
ENERGETSKI SUSTAVI Poglavlje: 7
Prof. dr. sc. Z. Prelec, dipl. ing. List: 12
-------------------------------------------------------------------------------------------------------------------------
� Materijalna bilanca rashladnaa tornja Gubici vode koji nastaju u radu rashladna tornja:
∆∆∆∆mw=∆∆∆∆mwi+∆∆∆∆mws+∆∆∆∆mwo
gdje je:
∆∆∆∆mwi - gubici zbog otparivanja vode ∆∆∆∆mws- gubici zbog odstrujavanja (odnošenja) kapljica ∆∆∆∆mwo- gubici zbog odsoljavanja vode ∆∆∆∆mwi=(X2-X1)mzr mzr = ∆∆∆∆mwi/(X2-X1) gdje je: mzr - protok zraka kroz rashladni toranj (kg/h) X1 - sadržaj vode u ulaznome zraku u toranj (kgH2O/kgzr) X2 - sadržaj vode u izlaznome zraku iz tornja (kgH2O/kgzr) � Budući da se hlañenje vode u cirkulaciji zbiva zbog
otparivanja dijela vode u prolazu kroz toranj, iz jednadžbe
toplinske bilance slijedi da će za neki rashladni učin
količina otparene vode (gubici zbog otparivanja) biti:
mwcw(T2-T1) =∆∆∆∆mwir ∆∆∆∆mwi=mwcw(T2-T1)/r ∆∆∆∆mwi =4,18 mw(T2-T1)/2450 ∆∆∆∆mwi =0,0017mw(T2-T1) gdje je: cw - specifična toplina vode (4,18 kJ/kg K) r - latentna toplina isparivanja vode (2450 kJ/kg) Količina vode koja se može otpariti zavisi prvenstveno o stanju
okoline, odnosno o relativnoj vlažnosti okolnoga zraka te
temperaturi suhog i vlažnoga termometra.
ENERGETSKI SUSTAVI Poglavlje: 7
Prof. dr. sc. Z. Prelec, dipl. ing. List: 13
-------------------------------------------------------------------------------------------------------------------------
Porastom vlažnosti okolnoga zraka smanjuje se količina vode koja
u danim uvjetima može otpariti, pa se na taj način smanjuje i
temperaturni raspon hlañenja, odnosno rashladni učin tornja. � Gubici zbog odstrujavanja (odnošenja) kapljica vode (∆mws)
zavise prvenstveno o hidrodinamskoj konstrukciji rashladnoga
tornja (prirodna ili prisilna cirkulacija zraka), izvedbi
odstranjivača kapljica, te od uvjeta strujanja oko tornja (vjetar).
Ovisno o navedenome, gubici zbog odstrujavanja mogu biti 0,3
do 2,5 %.
� Gubici zbog odsoljavanja vode iz rashladnoga tornja zavise o
dozvoljenoj koncentraciji soli u rashladnoj vodi.
Koncentracijski broj C je omjer koncentracije soli u
cirkulacijskoj vodi unutar rashladnoga sustava u odnosu na
koncentraciju soli u dodatnoj (svježoj) vodi.
Dozvoljeni koncentracijski broj C zavisi o kemijskoj obradi
rashladne vode u cilju sprječavanja taloženja kamenca, korozije
te mikrobiološkoga rasta.
U praksi je uobičajeno koncentracijski broj C=2 do 5.
Bilanca mase soli u vodi – količina vode koju treba ispustiti odsoljavanjem Količina soli u dodatnoj vodi jednaka je količina soli odstranjenih
odsoljavanjem i odstrujavanjem, odnosno:
∆∆∆∆mwi+∆∆∆∆mws+∆∆∆∆mwo=C(∆∆∆∆mws+∆∆∆∆mwo) Iz ove jednadžbe proizlazi količina vode koju treba kontrolirano
ispuštati radi odsoljavanja da bi se konventracija soli u vodi
održala u dozvoljenim granicama, odnosno da bi se održao
odreñeni koncentracijski broj C.
ws
wi
owm
1C
mm ∆−
−
∆=∆