    MINI PROJECT OF PROGRAMMING IN POWER SYSTEM

    Number of prolem: 1

    Group: Nhm 1

    The below figure shows a load flow situation. There are 3 generators. Bus 1 is the

    slack bus. The generator on bus 2 is generating at unity power factor, and the another on

    bus 3 is operated under voltage control. The load is all on bus 4.

    We have:1

    U 1 and3

    U 1.05. The power of generator 2 is 70 MW andthe

    power of generator 3 is 60MW. The load powers are P + j Q = 200 + j50 (MVA). Theparameters of transmission lines are showed in below table:

    R X Y/2

    Line 1 0.05 0.2 0

    Line 2 0.04 0.2 0

    Line 3 0.05 0.35 0

    Line 4 0.04 0.2 0

    Line 5 0.10 0.35 0

    Line 6 0.05 0.3 0

    Line 7 0.08 0.35 0Line 8 0.12 0.27 0

    Calculate the bus voltages and line currents by Power system toolbox andPowerWorld Simulator (25 pts.)

    Open the line 7. Calculate again the bus voltages and line currents. (20 pts) Compare the results and show your conclusion. (10 pts.) Calculate symmetric fault in bus 6 and bus 5 by Power system toolbox. (25 pts.)

  • 7/28/2019 403707_DD3168_VP- 403707_DD3168_VP- bi

    2/7

    MINI PROJECT OF PROGRAMMING IN POWER SYSTEM

    Number of prolem: 2

    Group: Nhm 2

    The below figure shows a load flow situation. There are 3 generators. Bus 1 is the

    slack bus. The generator on bus 2 is generating at unity power factor, and the another on

    bus 3 is operated under voltage control. The load is all on bus 4.

    We have:1

    U 1.05 and3

    U 1.03. The power of generator 2 is 80 MW andthe

    power of generator 3 is 50MW. The load powers are P + j Q = 250 + j60 (MVA). Theparameters of transmission lines are showed in below table:

    R X Y/2

    Line 1 0.06 0.25 0

    Line 2 0.05 0.2 0

    Line 3 0.04 0.2 0

    Line 4 0.05 0.35 0

    Line 5 0.11 0.2 0

    Line 6 0.04 0.35 0

    Line 7 0.09 0.2 0Line 8 0.12 0.27 0

    Calculate the bus voltages and line currents by Power system toolbox andPowerWorld Simulator (25 pts.)

    Open the line 5. Calculate again the bus voltages and line currents. (20 pts) Compare the results and show your conclusion. (10 pts.) Calculate symmetric fault in bus 6 and bus 5 by Power system toolbox. (25 pts.)

  • 7/28/2019 403707_DD3168_VP- 403707_DD3168_VP- bi

    3/7

    MINI PROJECT OF PROGRAMMING IN POWER SYSTEM

    Number of prolem: 3

    Group: Nhm 3

    The below figure shows a load flow situation. There are 3 generators. Bus 1 is the

    slack bus. The generator on bus 2 is generating at unity power factor, and the another on

    bus 3 is operated under voltage control. The load is all on bus 4.

    We have:1

    U 1.02 and3

    U 1. The power of generator 2 is 90 MW andthe

    power of generator 3 is 70MW. The load powers are P + j Q = 300 + j70 (MVA). Theparameters of transmission lines are showed in below table:

    R X Y/2

    Line 1 0.07 0.3 0

    Line 2 0.06 0.25 0

    Line 3 0.05 0.2 0

    Line 4 0.11 0.3 0

    Line 5 0.05 0.25 0

    Line 6 0.09 0.2 0

    Line 7 0.10 0.25 0Line 8 0.12 0.27 0

    Calculate the bus voltages and line currents by Power system toolbox andPowerWorld Simulator (25 pts.)

    Open the line 4. Calculate again the bus voltages and line currents. (20 pts) Compare the results and show your conclusion. (10 pts.) Calculate symmetric fault in bus 6 and bus 5 by Power system toolbox. (25 pts.)

  • 7/28/2019 403707_DD3168_VP- 403707_DD3168_VP- bi

    4/7

    MINI PROJECT OF PROGRAMMING IN POWER SYSTEM

    Number of prolem: 4

    Group: Nhm 4

    The below figure shows a load flow situation. There are 3 generators. Bus 1 is the

    slack bus. The generator on bus 2 is generating at unity power factor, and the another on

    bus 3 is operated under voltage control. The load is all on bus 4.

    We have:1

    U 1.04 and3

    U 1.05. The power of generator 2 is 60 MW andthe

    power of generator 3 is 60MW. The load powers are P + j Q = 180 + j80 (MVA). Theparameters of transmission lines are showed in below table:

    R X Y/2

    Line 1 0.08 0.35 0

    Line 2 0.07 0.3 0

    Line 3 0.06 0.25 0

    Line 4 0.05 0.2 0

    Line 5 0.04 0.3 0

    Line 6 0.10 0.2 0

    Line 7 0.11 0.3 0Line 8 0.12 0.27 0

    Calculate the bus voltages and line currents by Power system toolbox andPowerWorld Simulator (25 pts.)

    Open the line 3. Calculate again the bus voltages and line currents. (20 pts) Compare the results and show your conclusion. (10 pts.) Calculate symmetric fault in bus 6 and bus 5 by Power system toolbox. (25 pts.)

  • 7/28/2019 403707_DD3168_VP- 403707_DD3168_VP- bi

    5/7

    MINI PROJECT OF PROGRAMMING IN POWER SYSTEM

    Number of prolem: 5

    Group: Nhm 5

    The below figure shows a load flow situation. There are 3 generators. Bus 1 is the

    slack bus. The generator on bus 2 is generating at unity power factor, and the another on

    bus 3 is operated under voltage control. The load is all on bus 4.

    We have:1

    U 1 and3

    U 1.03. The power of generator 2 is 50 MW andthe

    power of generator 3 is 60MW. The load powers are P + j Q = 200 + j90 (MVA). Theparameters of transmission lines are showed in below table:

    R X Y/2

    Line 1 0.09 0.2 0

    Line 2 0.08 0.35 0

    Line 3 0.07 0.3 0

    Line 4 0.06 0.25 0

    Line 5 0.05 0.2 0

    Line 6 0.11 0.25 0

    Line 7 0.05 0.35 0Line 8 0.12 0.27 0

    Calculate the bus voltages and line currents by Power system toolbox andPowerWorld Simulator (25 pts.)

    Open the line 2. Calculate again the bus voltages and line currents. (20 pts) Compare the results and show your conclusion. (10 pts.) Calculate symmetric fault in bus 6 and bus 5 by Power system toolbox. (25 pts.)

  • 7/28/2019 403707_DD3168_VP- 403707_DD3168_VP- bi

    6/7

    MINI PROJECT OF PROGRAMMING IN POWER SYSTEM

    Number of prolem: 6

    Group: Nhm 6

    The below figure shows a load flow situation. There are 3 generators. Bus 1 is the

    slack bus. The generator on bus 2 is generating at unity power factor, and the another on

    bus 3 is operated under voltage control. The load is all on bus 4.

    We have:1

    U 1.05 and3

    U 1. The power of generator 2 is 70 MW andthe

    power of generator 3 is 50MW. The load powers are P + j Q = 250 + j90 (MVA). Theparameters of transmission lines are showed in below table:

    R X Y/2

    Line 1 0.10 0.25 0

    Line 2 0.09 0.2 0

    Line 3 0.08 0.35 0

    Line 4 0.07 0.3 0

    Line 5 0.06 0.25 0

    Line 6 0.05 0.2 0

    Line 7 0.04 0.2 0Line 8 0.12 0.27 0

    Calculate the bus voltages and line currents by Power system toolbox andPowerWorld Simulator (25 pts.)

    Open the line 1. Calculate again the bus voltages and line currents. (20 pts) Compare the results and show your conclusion. (10 pts.) Calculate symmetric fault in bus 6 and bus 5 by Power system toolbox. (25 pts.)

  • 7/28/2019 403707_DD3168_VP- 403707_DD3168_VP- bi

    7/7

    MINI PROJECT OF PROGRAMMING IN POWER SYSTEM

    Number of prolem: 7

    Group: Nhm 7

    The below figure shows a load flow situation. There are 3 generators. Bus 1 is the

    slack bus. The generator on bus 2 is generating at unity power factor, and the another on

    bus 3 is operated under voltage control. The load is all on bus 4.

    We have:1

    U 1.02 and3

    U 1.05. The power of generator 2 is 90 MW andthe

    power of generator 3 is 70MW. The load powers are P + j Q = 300 + j80 (MVA). Theparameters of transmission lines are showed in below table:

    R X Y/2

    Line 1 0.11 0.3 0

    Line 2 0.10 0.25 0

    Line 3 0.09 0.2 0

    Line 4 0.08 0.35 0

    Line 5 0.07 0.3 0

    Line 6 0.06 0.25 0

    Line 7 0.05 0.2 0Line 8 0.12 0.27 0

    Calculate the bus voltages and line currents by Power system toolbox andPowerWorld Simulator (25 pts.)

    Open the line 7. Calculate again the bus voltages and line currents. (20 pts) Compare the results and show your conclusion. (10 pts.) Calculate symmetric fault in bus 6 and bus 5 by Power system toolbox. (25 pts.)