Data Mutx = 5.61 kNm H tebal = 500 mm Mulx = 5.61 kNm D' = 70 mm Muty = 5.61 kNm Dimensi = 16 mm Muly = 5.61 kNm Fc = 22 Mpa Fy = 390 Mpa dx = 422 mm dy = 406 mm Atas X b = 3000 dx = 422 Mn Mu 5.61 ø 0.8 = 7.0125 Rn Mn b * dx 2 3000 422 = 0.01312583 m fy 0.85 * fc 0.85 22 = 20.855615 Rasio Tulangan ρ min = 1.4 Fy = 1.4 390 = 0.00358974 ρb = 0.85 fc 600 + fy = 0.85 22 600 + 390 = 0.02470085 Perhitugan Pilecap 0.85 600 390 β 600 fy = = 390 = = = = 7.0125

Upload: ivanbean

Post on 16-Nov-2015

217 views

Category:

Documents


4 download

DESCRIPTION

perhitngan pilecap

TRANSCRIPT

  • Data

    Mutx = 5.61 kNm H tebal = 500 mmMulx = 5.61 kNm D' = 70 mmMuty = 5.61 kNm Dimensi = 16 mmMuly = 5.61 kNm

    Fc = 22 MpaFy = 390 Mpa

    dx = 422 mmdy = 406 mm

    Atas Xb = 3000 dx = 422

    Mn Mu 5.61 0.8

    = 7.0125

    Rn Mn b * dx2 3000 422

    = 0.01312583

    m fy 0.85 * fc 0.85 22

    = 20.855615

    Rasio Tulangan min = 1.4

    Fy

    = 1.4390

    = 0.00358974

    b = 0.85 fc600 + fy

    = 0.85 22600 + 390

    = 0.02470085

    Perhitugan Pilecap

    0.85 600390

    600fy

    = = 390

    = =

    = =7.0125

  • max = 0.75 x b= 0.75 x 0.024701= 0.01852564

    aktual = 1 2 m Rnm

    = 1 2 20.85561 0.0131320.855615

    = 3.3668E-05

    0.00358974

    As perlu = pakai b dx= 0.00358974 3000 422= 4544.61538

    Jarak Antar TulanganS 0.25 d2 b

    0.25 3.14 16 3000

    = 132.658091 125 mm

    Kontrol Terhadap Kapasitas Momen > As perlu

    0.25 d2 b > 4544.615 mm

    0.25 3.14 16 3000 > 4544.615 mm

    > 4544.615 mm

    a As ada x fy0.85 fc b

    4823.04 x 3900.85 22 3000

    = 33.5291551 mm

    Mn a2

    33.529162

    = 762241994 mm= 762.241994 kNm

    = 4823.04 390 422 -

    =

    =

    = As ada fy dx -

    1254823.04 ok aman

    maka jarak antar tulangan

    As ada

    s

    =As perlu

    = 4544.62

    390

    maka pakai adalah min

    fy

    1 - 1 -

    1 - 1 -

  • Mn > Mu / 762.242 > 7.0125

    Bawah Xb = 1000 ( diambil per 1 m ) dy = 406

    Mn Mu 5.61 0.8

    = 7.0125

    Rn Mn b * dx2 1000 406

    = 0.04254228

    m fy 0.85 * fc 0.85 22

    = 20.855615

    Rasio Tulangan min = 1.4

    Fy

    = 1.4390

    = 0.00358974

    b = 0.85 fc600 + fy

    = 0.85 22600 + 390

    = 0.02470085

    max = 0.75 x b= 0.75 x 0.024701= 0.01852564

    aktual = 1 2 m Rnm

    = 1 2 20.85561 0.04254

    fy

    1 - 1 -

    1 - 1 -

    0.85 600390

    600fy

    = = 390

    = =

    = =7.0125

    ok aman

  • 20.855615

    = 0.00010921

    0.00358974

    As perlu = pakai b dx= 0.00358974 1000 406= 1457.4359

    Jarak Antar TulanganS 0.25 d2 b

    0.25 3.14 16 1000

    = 137.885996 125 mm

    Kontrol Terhadap Kapasitas Momen > As perlu

    0.25 d2 b > 1457.436 mm

    0.25 3.14 16 1000 > 1457.436 mm

    > 1457.436 mm

    a As ada x fy0.85 fc b

    1607.68 x 3900.85 22 1000

    = 33.5291551 mm

    Mn a2

    33.529162

    = 244048742 mm= 244.048742 kNm

    Mn > Mu / 244.0487 > 7.0125 ok aman

    = 1607.68 390 406 -

    =

    =

    = As ada fy dx -

    1251607.68 ok aman

    maka jarak antar tulangan

    As ada

    s

    =As perlu

    = 1457.44

    390

    maka pakai adalah min

    1 - 1 -

  • Data

    Mutx = 5.61 kNm H tebal = 500 mmMulx = 5.61 kNm D' = 70 mmMuty = 5.61 kNm Dimensi = 12 mmMuly = 5.61 kNm

    Fc = 22 MpaFy = 390 Mpa

    dx = 422 mmdy = 410 mm

    Atas Yb = 3000 dx = 422

    Mn Mu 5.61 0.8

    = 7.0125

    Rn Mn b * dx2 3000 422

    = 0.01312583

    m fy 0.85 * fc 0.85 22

    = 20.855615

    Rasio Tulangan min = 1.4

    Fy

    = 1.4390

    = 0.00358974

    b = 0.85 fc600 + fy

    = 0.85 22600 + 390

    = 0.02470085

    0.85 600390

    600fy

    7.0125

    = = 390

    = =

    = =

  • max = 0.75 x b= 0.75 x 0.024701= 0.01852564

    aktual = 1 2 m Rnm

    = 1 2 20.85561 0.01320.855615

    = 3.3668E-05

    0.00358974

    As perlu = pakai b dx= 0.00358974 3000 422= 4544.61538

    Jarak Antar TulanganS 0.25 d2 b

    0.25 3.14 16 3000

    = 132.658091 125 mm

    Kontrol Terhadap Kapasitas Momen > As perlu

    0.25 d2 b > 4544.615 mm

    0.25 3.14 16 3000 > 4544.615 mm

    > 4544.615 mm

    a As ada x fy0.85 fc b

    4823.04 x 3900.85 22 3000

    = 33.5291551 mm

    Mn a2

    33.529162

    = 762241994 mm= 762.241994 kNm

    4823.04 390 422 -

    As ada fy dx -

    =

    =

    =

    =

    1254823.04 ok aman

    maka jarak antar tulangan

    As ada

    s

    =As perlu

    = 4544.62

    1 - 390

    maka pakai adalah min

    1 - fy

    1 -

    1 -

  • Mn > Mu / 762.24 > 7.0125

    Bawah Yb = 1000 ( diambil per 1 m ) dy = 406

    Mn Mu 5.61 0.8

    = 7.0125

    Rn Mn b * dx2 1000 406

    = 0.04254228

    m fy 0.85 * fc 0.85 22

    = 20.855615

    Rasio Tulangan min = 1.4

    Fy

    = 1.4390

    = 0.00358974

    b = 0.85 fc600 + fy

    = 0.85 22600 + 390

    = 0.02470085

    max = 0.75 x b= 0.75 x 0.024701= 0.01852564

    aktual = 1 2 m Rnm

    = 1 2 20.85561 0.0431 -

    1 - fy

    1 -

    1 -

    0.85 600390

    600fy

    7.0125

    = = 390

    = =

    = =

    ok aman

  • 20.855615

    = 0.00010921

    0.00358974

    As perlu = pakai b dx= 0.00358974 1000 406= 1457.4359

    Jarak Antar TulanganS 0.25 d2 b

    0.25 3.14 16 1000

    = 137.885996 125 mm

    Kontrol Terhadap Kapasitas Momen > As perlu

    0.25 d2 b > 1457.436 mm

    0.25 3.14 16 1000 > 1457.436 mm

    > 1457.436 mm

    a As ada x fy0.85 fc b

    1607.68 x 3900.85 22 1000

    = 33.5291551 mm

    Mn a2

    33.529162

    = 244048742 mm= 244.048742 kNm

    Mn > Mu / 244.05 > 7.0125

    1607.68 390 406 -

    ok aman

    As ada fy dx -

    =

    =

    =

    =

    1251607.68 ok aman

    maka jarak antar tulangan

    As ada

    s

    =As perlu

    = 1457.44

    1 - 390

    maka pakai adalah min

    1 -