    AEGIS- Vacuum Circuit Breaker Ring Main Unit

  • 8/3/2019 Aegis Brochure[1]

    2/6

    Aegis Vacuum Circuit Breaker Ring Main UnitDesigned for secondary distribution networks up to 24kV, and rated currents up to 630A, the Aegis range of vacuum circuit

    breaker ring main units (RMU) provides a comprehensive series of solutions which lend itself to numerous applications for

    utilities, compact secondary substations, mining and commercial buildings. It is available for both indoor and outdoor

    environments protected against the harshest of conditions without the need for additional housings.

    Used at the secondary distribution level primarily for distribution of power and for the protection of local transformers.

    It is suitable for heavy duty operation with a long service life and virtually zero maintenance. It can be used either as a

    freestanding unit or installed in compact mini-substations and kiosks.

    Benefits Front accessed cable box suitable for disconnectable

    cable terminations

    Fully interlocked for safe operation

    Maintenance free

    Easy to install

    Simple operation

    Suitable for mini substation

    Configured for future automation applications

    Climate-independent

    Proven technology

    No Kiosk required

    Cost effective

    Key features 12kV, 17.5kV and 24kV versions

    Compact one tank solution

    Intuitive mimic diagram

    Vacuum interrupters for circuit breakers

    Pre-wired for motor actuation and

    remote indication

    Integral cable testing from front of the unit

    Common stainless steel switching chamber

    Hermetically sealed switching chamber

    DIN 400 C-bushings as standard on all circuits

    Indoor and outdoor application

    Superior electrical performance - in excess

    of IEC requirements

    Transformer over current protection for phase

    to phase faults

  • 8/3/2019 Aegis Brochure[1]

    3/6

    1 Lifting lugs

    2 Sealed tank

    3 Switch blades

    4 Vacuum interrupters

    5 Internal arc vent

    6 Primary earth point

    7 Fully interlocked test access cover

    8 Cable test terminals

    9 Pressure gauge

    10 Facia and mimic

    11 Circuit breaker or ring switch operation

    12 Cable termination

    13 Cable box

  • 8/3/2019 Aegis Brochure[1]

    4/6

    DesignThe Aegis ring main unit is available with up to 4 functionsin one common tank. It can be configured with vacuum circuit

    breaker units or a combination of vacuum circuit breakers

    and fault-make load break switches.

    Stainless Steel Gas Enclosure

    Highest quality stainless steel switching enclosure.

    Housing

    Fully treated, to resist weather and pollution attacks. Outdoor

    units are provided with a hinged, weatherproof and lockable

    cover.

    Circuit Breaker

    Comprises 3 vacuum interrupters for fault-make, fault-break

    rating.

    Switches

    Switching available via single break 3 position switches

    providing ON, OFF and EARTH positions.

    Operation

    Operated via manually independent mechanisms mounted

    external to the gas enclosure, status is clearly identified

    through mimic diagram on front panel.

    Test Facilities

    Fully interlocked test facilities are provided in accordance

    with IEC62271 requirements, standard on ring switch, optional

    on circuit breaker.

    Interlocks

    Positive, intuitive, clear and simple safety interlocks are

    incorporated on all switch positions to prevent mal-operation.

    Padlocks

    All switch and selector positions can be padlocked to prevent

    unauthorised access

    Options Circuit Breaker ProtectionCircuit breaker protection can be achieved via ring core

    current transformers in combination with Time Limit Fuse or

    a range of protection relays.

    Cable Boxes

    Internal arc tested cable boxes are available for IEC 62271

    specifications. Interlocked cable boxes are also provided

    as options.

    Automation

    Pre-wired for automation. Rotary actuators can be easily and

    rapidly fitted on site whilst the unit is in service no access

    is required to the internal workings of the Aegis.

    Remote Trip Coil

    Push to trip

    Earth Fault Indicator

    Safety Hermetically sealed, touch safe units ensures maximum

    operator safety.

    Mimic diagram representation minimising language issues.

    Voltage Presence Indicator System (VPIS) clearly identifies

    when circuit is isolated from supply.

    Quality ISO 9000 quality systems approved.

    Proven technology.

    FMEA (failure mode evaluation analysis) designed.

  • 8/3/2019 Aegis Brochure[1]

    5/6

    Typical Schematic Line Diagram

    Typical Configurations and Dimensions

    3-way 4-way

    3-way 4-way

  • 8/3/2019 Aegis Brochure[1]

    6/6

    Technical Data(ratings in brackets are optional)

    LS00001 AEGIS 04 2010 (1000) 7642

    www.lucyswitchgear.com

    Rated Voltage 12kV 17.5kV 24kV

    Frequency 50Hz 50/60Hz 50Hz

    Impulse Withstand Voltage 75 kVp 95kVp 125kVp

    Normal Current

    Ring Switches 630A 400A 400A

    Circuit breaker 250A(630A) 200A 250A(400A)

    Short Circuit Peak making Current

    Ring Switches 50kA 54.6kA 40kA

    Circuit Breaker 50kA 54.6kA 40kA

    Short Circuit breaking Current

    Circuit Breaker 20kA 21kA 16kA

    Short Time Current

    Ring Switches 20kA for 3 sec 21kA for 1 sec 16kA for 3 sec

    Circuit Breaker 20kA for 3 sec 21kA for 1sec 16kA for 3 sec

    Earth Switch Peak Making Current

    Ring Switches 50kAp 54.6kAp 40kAp

    Circuit Breaker 7.9kAp(50kAp) 54.6kAp 7.9kAp(40kAp)

    Internal Arc Rating

    Freestanding 20kA 1sec 21kA 1sec 16kA 1sec

    Substation 20kA 1sec 21kA 1sec 16kA 1sec

    Optional Cable Boxes internal Arc Rating 20kA 1 sec 21kA 1sec 16kA 1sec

    Gas Pressure

    Min Operating Pressure 0 Bar 0 Bar 0.4 Bar

    IP Rating IP4X(IP54W option) IP4X(IP54W option) IP4X(IP54W option)

    Testing Standards

    IEC 60265-1

    IEC 62271-100

    IEC 62271-102

    IEC 62271-200

    12kV 17.5kV 24kV

    cy Switchgear

    owland Road, Thame,

    xfordshire, OX9 3UJ, UK

    l: +44 (0)1844 267267

    x: +44 (0)1844 267223

    mail: [email protected]

    Lucy Middle East

    PO Box 17335, Jebel Ali,

    Dubai, United Arab Emirates

    tel: +9714 812 9999

    fax: +9714 812 9900

    email: [email protected]

    The Saudi Lucy Company Ltd

    PO Box 834, Al-Khobar,

    31952, Saudi Arabia

    tel: +966 3 8823057

    fax:+ 966 3 8822553

    email: [email protected]

    Lucy South Africa

    Suite 22, Fourways Business

    Centre, Design Quarter, Nicole

    Grove Office Park, Leslie Road,

    Fourways 2005, South Africa

    tel: +27 (0)11 5133415

    tel: +27 (0)11 5133000

    fax: +27 (0)86 6783418

    email: [email protected]

    Lucy Asia Pacific Sdn Bhd

    Suite 32-01-92, 32nd Floor, Wisma Keck

    Seng, 203 Jalan Bukit Bintang, 55100

    Kuala Lumpur, Malaysia

    tel: +603 2116 5640

    fax: +603 2116 5647

    email: [email protected]