full paper madtharad chakphed

Upload: ursula-johnson

Post on 04-Jun-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/13/2019 Full Paper Madtharad Chakphed

    1/4

    1

    Abstract-- This paper illustrates a procedure to

    design harmonic filters for industrial applications,

    induction furnace load (22 kV, 27 MW, 0.84 PF, and

    voltage distortion 16.15% from harmonics and

    interharmonics). This is essential for eliminating and

    reducing the effects of harmonics in a power system to

    comply with limit of the Kingdom of Thailand (4.0%THDv for 22 kV distribution systems). Off-line steady

    state simulation program, DIgSILENT, is used to

    model loads, to study variation of the harmonics, to

    study the impedance versus frequency, and to evaluate

    the effect of harmonic filter in the system using actual

    recorded data. After the designed harmonic filters are

    placed, the voltage distortion are dramatically reduced

    to be 2.7%.

    Index Terms-- Harmonics, Harmonic Filter Design,

    Induction Furnace

    I. INTRODUCTION

    The increase of harmonics in the power system

    threatens the quality of the electricity supplied to the

    customers. Fundamentally, one needs to control

    harmonics only when they become a problem. When a

    problem occurs, the basic options for controlling

    harmonics are in [1].

    This paper illustrates a procedure to design

    harmonic filters for 27 MW induction furnace with

    voltage distortion from harmonics and interharmonics

    (3.713.4% of THDv and 7.89.0% of Total

    Interharmonic Distortion in voltage (TIDv)). Section

    II presents basic characteristic of harmonic filter. The

    induction furnace load characteristic is presented in

    section III. Section IV shows the criteria to select

    parameter of harmonic filter, section V shows the

    implementation results and conclusion is presented in

    section VI.

    This work was supported by the Provincial Electricity Authority (PEA),

    Thailand.

    II. HARMONIC FILTER

    The harmonic shunt filter works by short-circuiting

    harmonic currents as close to the source of distortion

    as practical. This keeps the currents out of the supply

    system and is the most common type of filtering

    applied because of economics and because it also

    tends to correct the load power factor as well asremove the harmonic current.

    The first step to design filter is computer simulation,

    then hypothetical harmonic filters are placed in the

    model and the response of the power system to the

    filter is examined. If unacceptable results are obtained,

    the location and values of the filter parameters are

    changed until the results are satisfactory.

    III. INDUCTION FURNACE LOAD

    The basic characteristic of the induction furnace load

    is described in [3]. Fig. 1 shows the network

    configuration of this load in PEA transmission and

    distribution system. An induction furnace immediately

    generated customer complaints to 115 kV customer of

    PEA when connected in the same transmission system.

    Complaints included noisy capacitors, capacitor

    failures, flickering lights, UPS alarms, drive trips, and

    other problems. Transformer noise would rise and fall

    several times per second. It affected nearby industrial

    customers and the PEA system.

    IV. FILTER PARAMETER SELECTION CRITERIA

    The major criteria to design harmonic filter is to

    select a suitable capacitor size that results in a

    reasonable PF at fundamental frequency. [4]

    1)Load ParameterLoad:27 MW (max), 22 kV, 0.84 PF (17.44

    MVAr), 13.4% THDv and 9.0 TIDv

    Constrained:THDv less than 4.0% to comply with

    limit of the Kingdom of Thailand, and

    PF higher than 0.95

    Harmonic Filter Design for

    Induction Furnace Load in 22 kV Distribution SystemChakphed Madtharad Mark McGranaghanPEA, Bangkok, Thailand EPRI, Knoxville, TN, USA

    [email protected] [email protected]

  • 8/13/2019 Full Paper Madtharad Chakphed

    2/4

    2

    Fig. 1 Single line diagram

    2)Monitoring Device and LocationDranetz-BMI PowerXplorer PX5 Signature System

    has been used, 256 samples/cycle. It is located at

    22 kV bus inside PEAs substation.

    3)Fundamental Frequency Reactive PowerCompensation

    The reactive power, compQ , to improve the PF of 27

    MW load from 0.84 to be 0.96 can be given by

    ( ) ( )1 127 tan cos 0.84 tan cos 0.96 9.57compQ MVAr = = (1)

    The number of filter branches can be selected basedon the percentage of the harmonic components of

    voltage and current. It may also, be necessary to place

    filters elsewhere in the system to reduce resonance

    problems (series or parallel), if any.

    At the tuning frequency rh , the capacitive and

    inductive components of the filter become equal. That

    is

    C Cr L r

    r L

    X Xh X Then h

    h X= = (2)

    To design harmonic filter, LX was normally defined interm of percentage of CX . That is

    r L 2

    L r

    100 100h Then %X

    % X h= = (3)

    The parameters CX and LX are the fundamental

    frequency capacitive and inductive components of a

    single tuned filter, respectively. Ifcomp

    Qis the total

    reactive power generated by the filter, the critical or

    rated reactive power ( crQ ) at fundamental frequency

    can be given by

    Event #286at 12/05/2007 07:55:19.800

    Pre-trigger

    Event Details/Waveforms

    07:55:19.805

    12/05/2007

    Wednesday

    07 :5 5: 19. 810 07:5 5: 19. 815 07 :5 5: 19. 820

    -1000

    -500

    0

    500

    1000

    Amps

    A I BI CI

    (a)Harmonic current waveform

    Event #286at 12/05/200707:55:19.800

    Pre-trigger

    Event Details/Waveforms

    07:55:19.805

    12/05/2007

    Wednesday

    07 :5 5: 19 .8 10 07 :5 5: 19 .8 15 07 :5 5: 19 .8 20

    -20000

    -10000

    0

    10000

    20000

    Vo

    lts

    AV BV CV

    (b) Harmonic voltage waveform

    Fig. 2 Monitoring result for designing harmonic filter.

    2

    crLcr comp

    s

    V100 %X Q Q

    100 V

    =

    (4)

    where sV is bus voltage of filter, and

    crV is critical or rated voltage of capacitor.

    The next step is to decide if how many harmonic

    filter banks should be used. In this step the impedance

    versus frequency analysis (frequency scan) and

    harmonic load pattern have to be considered.

    The three-phase power converter of induction

    furnace in this case is a 12-pulse current-source. The

    monitoring results and harmonic spectrum in Fig. 2

    shows that the characteristic harmonics in the ac-sideline currents are the 11th

    , 13th

    , 23th

    , 25th

    , etc with some

    non characteristic 2nd

    , 5th

    and 7th

    and also

    interharmonic.

    Since the magnitude of harmonic and interharmonic

    currents decreases as the harmonic order increases, a

    damped or high pass filter is recommended to screen

    out a broad range of higher order harmonics. The

    parameters of these filters can be obtained similar to

    the single tuned filter except the value of the

    resistance which can be obtained as where quality

    factor ( QF) has a low value. [4]

  • 8/13/2019 Full Paper Madtharad Chakphed

    3/4

    3

    30.2020.2010.200.20 [-]

    80.00

    60.00

    40.00

    20.00

    0.00

    -20.00

    CSI 22 kV: Network Impedance, Line-Ground A in Ohm

    CSI 22 kV: Network Impedance, Line-Ground A in Ohm

    CSI 22 kV: Network Impedance, Line-Ground A in Ohm

    With Filter 11 and 13

    Without Filter

    4.98459.180 Ohm

    5.04810.298 Ohm

    5.04829.460 Ohm

    With Filter 5,11 and 13

    DIgSILENT

    Fig. 3 Frequency scans at 22 kV bus in customer side.

    Fig. 3 shows frequency scans at 22 kV bus in

    customer side, the black line shows frequency scan inexisting case (without harmonic filter). While the blue

    line represents frequency scan in case of using

    harmonic high pass filter just only in significant

    characteristic harmonic orders (11th

    and 13th

    ).The blue line in Fig. 3 show parallel resonance at

    harmonic order 5th, harmonic order at parallel

    resonance frequency would be magnified about 6

    times of normal value. As a result, harmonic high pass

    filter order 5 has to be added to shift the resonance

    frequency and/or lower the impedance at resonance

    frequency (red dotted line).

    4)Capacitor, Inductor, and Resistor of each banksTo decide if how much reactive power in each banks

    should be used, harmonic pattern have to be taken into

    account. The harmonic orders 11th

    and 13th

    are

    dominant harmonic components and filter order 5th

    is

    mainly used to shift the resonance frequency. Then

    reactive power for harmonic high pass filter order 11th

    and 13th

    are 4.0 MVAr, and 2.0 MVAr for order 5th

    .

    The design of the filter bank may result in an iterative

    process to optimize the capacitor bank size and filterthe unwanted harmonics [5].

    For any banks of harmonic high pass filter, crQ can

    be calculated using equation (4). For filter bank order

    5th

    , if sV is 22 kV, crV is 32.32 kV, and

    compQ is 2.0 then

    crQ would be 4.317 MVAr. In the same manner, if the

    tuning frequencyr

    h is 10.9 and crV is 38.80 kV then

    crQ would be 12.435 MVAr.

    If the value of reactive power to be supplied by the

    filter ( crQ ) is known, the capacitive component of

    wye-connection can be given by

    2

    50

    6

    50

    ( )

    10( )

    2

    crC Hz

    cr

    C Hz

    VX

    Q

    C FfX

    =

    =

    (5)

    The value of inductive reactance can then becalculated using equation (6).

    50

    3

    50

    ( ) ( )

    10( ) ( ) 2

    2

    C Hz

    L Tuned C Tuned

    r

    L Tuned

    L Hz

    XX X

    h

    XL mH Then X fL

    f

    = =

    = =

    (6)

    The value of parallel resistance can then be calculated

    using equation (7).

    50( )

    r L HzR h X QF = (7)

    where QFis the quality factor of the filter.

    5)Evaluate filter duty requirementsEvaluation of filter duty requirements typically

    involves capacitor bank and also inductor/resistor

    duties. These duties include peak voltage, current,

    kVAr produced, and rms voltage.Ref. [6-7] is used as

    the limiting standard to evaluate these duties.

    Table 1 summarizes the parameter of each harmonic

    high pass filter banks.

    Table 1Summarize the parameter of harmonic filter.

    ItemsHarmonic filter order

    5th 11th 13th

    rh 4.5 10.9 12.8

    QF 4.0 4.0 4.0

    L%X 4.94 0.84 0.61

    compQ 2.0 4.0 4.0

    sV 22.0 22.0 22.0

    crV 32.32 38.80 32.49

    crQ 4.317 12.435 8.723

    50 ( )C HzX 254.5289 122.0827 121.7518( )C F 12.5058 26.0733 26.1442

    ( )L TunedX 56.5620 11.2003 9.5119

    ( )L mH 40.0094 3.2708 2.3654

    50 ( )L HzX 12.5693 1.0275 0.7431( )R 226.2480 44.8010 38.0474

    V. IMPLEMENTATION RESULTS

    Table 2 shows monitoring result comparing with

    simulation result which the values are not far away

    from each others.

  • 8/13/2019 Full Paper Madtharad Chakphed

    4/4

    4

    Table 2Monitoring & simulation results at 22 kV bus

    Items

    Monitoring results

    (before/after)

    Simulation results

    (before/after)

    A B C A B C

    TIDi

    5.25/

    1.51

    5.33/

    1.48

    5.28/

    1.33

    THDi

    7.47/

    4.77

    8.17/

    6.56

    7.50/

    4.61

    Current

    Distortion

    9.37/

    5.00

    9.87/

    6.73

    9.21/

    4.80

    9.44/

    6.90

    9.94/

    6.54

    9.27/

    6.27

    TIDv

    8.91/

    0.60

    9.03/

    0.61

    8.73/

    0.62

    THDv

    11.81

    /2.49

    13.39

    /2.68

    12.20

    /2.25

    Voltage

    Distortion

    14.79

    /2.57

    16.15

    /2.75

    15.00

    /2.33

    14.52/

    2.45

    15.06/

    2.49

    13.90/

    2.36

    1.0 3.0 5.0 7.0 9.0 11. 13. 15. 17. 19. 21. 23. 25. [-][-]

    30.00

    20.00

    10.00

    0.00

    Induction Furnace: Phase Current A in A

    115/22 kV: Phase Current A/LV-Side in A

    11.00026.052 A

    11.0003.363 A

    13.00026.497 A

    13.000

    2.557 A

    4.0006.977 A

    4.00019.639 A

    DIgSILENT

    Fig. 4 Harmonic current spectrum of before (red line)

    and after (green line) the filters are placed.

    Event #1 at 06/14/2008 09:35:39.800

    Snapshot

    Event Details/Waveforms

    09:35:39.800

    06/14/2008

    Saturday

    0 9:3 5: 39. 805 0 9:3 5: 39 .8 10 09 :3 5: 39 .8 15 0 9:3 5: 39. 820

    -750

    -500

    -250

    0

    250

    500

    750

    Amps

    A I B I C I

    (a)Harmonic current waveform

    Event #1 at 06/14/2008 09:35:39.800

    Snapshot

    Event Details/Waveforms

    09:35:39.800

    06/14/2008

    Saturday

    0 9:3 5: 39 .8 05 0 9: 35 :3 9. 81 0 0 9:3 5: 39 .8 15 09 :3 5: 39 .8 20

    -15000

    -10000

    -5000

    0

    5000

    10000

    15000

    Volts

    A V B V C V

    (b)Harmonic voltage waveform

    Fig. 5 Monitoring result after the filter are placed.

    Total RMS: 462.54 A

    DC Level: -1.60 A

    F un damen ta l(H1 ) R MS : 4 98 .7 6 A

    Total Harmonic Distortion THD: 23.84 A (Even: 10.54 A, Odd: 21.39 A)

    THD H10 H20 H30 H40 H50

    0

    5

    10

    15

    20

    25

    Amps

    A IHarm

    (c) Harmonic current spectrum (Fig.5 cont.)

    From simulation (Fig. 4) and monitoring (Fig. 5)

    results we have found that, designed harmonic filtercan dramatically improve voltage distortion.

    VI. CONCLUSION

    The procedure to design harmonic filters for

    induction furnace load using actual recorded data has

    been presented. The results of harmonic high pass

    filters are dramatically reduced voltage distortion on

    the 22 kV bus; 3.713.4% to be 1.02.7% of THDv

    and 7.89.0% to be 0.22.0% of TIDv. In addition the

    filters also reduced flickering (1.8 to be 0.6 of Pst) and

    improved plant PF (0.84 lagging to be 0.99).

    VII. REFERENCES

    [1] R.C. Dugan, M. McGranaghan, S. Santoso, and H.W. Beaty,"Electrical Power System Quality, Second Edition,"

    McGraw-Hill

    [2] J. C. Das, "Passive FiltersPotentialities and Limitations,"IEEE Trans. Industry Applications, VOL. 40, pp.232-241,

    Jan/Feb 2004. 126821

    [3] R.C. Dugan, Sr. Conrad, and L.E., Sr., "Impact of InductionFurnace Interharmonics on Distribution Systems," The IEEE

    Transmission and Distribution Conference, New Orleans,

    LA, USA, Apr. 1999. 756150

    [4] Elham B. Makram,E. V. Subramaniam,, Adly A. Girgis, andRay Catoe, "Harmonic Filter Design Using Actual Recorded

    Data,"IEEE Trans. Industrial Application, vol. 29, pp. 1176-

    1183, Nov. 1993. 259730

    [5] D. Andrews, M.T. Bishop, and J.F. Witte, "HarmonicMeasurements, Analysis, and Power Factor Correction in a

    Modern Steel Manufacturing Facility," IEEE Trans.

    Industrial Application, vol. 32, pp. 617-624, May/June 1996.

    502174

    [6] IEEE Standard 18-1992,IEEE Standard for Shunt PowerCapacitors.

    [7] IEEE Standard 1531TM-2003,IEEE Guide for Applicationand Specification of Harmonic Filters.