EMC-tested DIN EN ISO 9001 Interference suppression Class B Hyamat V with Movitec Illustration shows variant without acoustic cladding Hyamat r V Type Series Booklet 1953.51-10 Pressure Boosting Units/Fire-fighting Systems with Continuously Variable Speed Adjustment to DIN 1988 Fields of Application F Residential buildings F Department stores F Hospitals F Industry F Office buildings F and other applications F Hotels Fluid Handled Drinking water, utility water, fire-fighting water, cooling water, where there is no chemical and mechanical corrosive action on the sys- tem materials. Operating Data Capacity Q up to 360 m 3 /h, 100 l/s with max. 6 pumps*) Discharge head H up to 160 m Temperature of fluid handled up to 70 o C up to 25 o C to DIN 1988 (DVGW) Ambient temperature up to 40 o C System discharge pressure p d up to 16 bar Inlet pressure p vor up to 10 bar Supply voltage 3/PE, AC 400 V, 50 Hz *) with stand-by pump as peak load pump Materials Pumps Suction/discharge casing stainless steel Hydraulic system stainless steel Mechanical seal to EN 12756 Spring-loaded ring silicon carbide Seat ring hard carbon Elastomer EPDM Hydraulic design Distributor pipe stainless steel Valves copper-base alloy/brass, DVGW-approved Accumulator connection made of stainless steel Membrane approved for drinking water to DIN 4807-5 Drive Electric motor 50 Hz, 2-pole, special KSB model, for three-phase mains. Standard IEC motors can only be used after consultation with KSB. Design Fully automatic pressure boosting package unit, with 2 to 6 vertical high-pressure pumps, with continuously variable speed adjust- ment of one pump for fully electronic control to ensure the required supply pressure, with standard volt-free contact, for general fault indication or indication of the system’s operational availability and live-zero monitoring of the connected sensors. Design and function as per DIN 1988, Part 5. Hyamat V System Equipment (Standard) - 5 - 6 vertical high-pressure centrifugal pumps (standard pumps) Movitec 02/04/10 with oval flange 2 - 6 vertical high-pressure centrifugal pumps (standard pumps) Movitec 18/32/45 with round flange - Hydraulic components made of stainless steel - 1 check valve and shut-off elements for each pump to DIN / DVGW - 1 membrane-type accumulator on the discharge side as control tank (direct flow) to DIN 4807-5, approved for drinking water - Pressure transmitter on the discharge pressure side - Pressure indication via pressure gauge - Steel baseplate powder-coated/epoxy resin-coated - Pump sizes 2, 4 and 10 are fixed to the baseplate on anti-vibration mounts - Pump sizes 18, 32 and 45 are supplied with level-adjustable feet and anti-vibration pads (supplied, but not fitted) - Control cabinet IP 54, EMC interference suppression class B. - With CE certificate. Control Cabinet Equipment (Standard) - Manual-0-automatic selector switch - PLC - LEDs indicating operational availability and fault of the system - Frequency inverter - Transformer for control voltage - Motor protection switch per pump - Fault acknowlegement via reset button - Master switch, lockable (repair switch) - Terminals with identification for all connections - Circuit diagram acc. to VDE, settings for FI and parts list for elec- trical parts - Emergency OFF connection (400 V AC, current max. 6 A) For supplementary equipment and special designs see pages 17 to 19.

Upload: leed-en

Post on 17-Jul-2016

6 views

Category:

Documents


0 download

DESCRIPTION

1

TRANSCRIPT

Page 1: HyamatV Bh En

EMC-tested

DIN EN ISO 9001

Interference suppression Class B

Hyamat V with MovitecIllustration shows variant without acoustic cladding

Hyamat� VType Series Booklet 1953.51-10

Pressure Boosting Units/Fire-fighting Systemswith Continuously Variable Speed Adjustment

to DIN 1988

Fields of Application� Residential buildings � Department stores� Hospitals � Industry� Office buildings � and other applications� Hotels

Fluid HandledDrinking water, utility water, fire-fighting water, cooling water, wherethere is no chemical and mechanical corrosive action on the sys-tem materials.

Operating DataCapacity Q up to 360 m3/h, 100 l/s with max. 6 pumps*)Discharge head H up to 160 mTemperature of fluid handled up to 70 oC

up to 25 oC to DIN 1988 (DVGW)Ambient temperature up to 40 oCSystem discharge pressure pd up to 16 barInlet pressure pvor up to 10 barSupply voltage 3/PE, AC 400 V, 50 Hz

*) with stand-by pump as peak load pump

MaterialsPumpsSuction/dischargecasing stainless steelHydraulic system stainless steelMechanical seal to EN 12756Spring-loaded ring silicon carbideSeat ring hard carbonElastomer EPDM

Hydraulic designDistributor pipe stainless steelValves copper-base alloy/brass, DVGW-approvedAccumulator connection made of stainless steelMembrane approved for drinking water to DIN 4807-5

DriveElectric motor 50 Hz, 2-pole, special KSB model, for three-phasemains. Standard IEC motors can only be used after consultationwith KSB.

DesignFully automatic pressure boosting package unit, with 2 to 6 verticalhigh-pressure pumps, with continuously variable speed adjust-ment of one pump for fully electronic control to ensure the requiredsupply pressure, with standard volt-free contact, for general faultindication or indication of the system’s operational availability andlive-zero monitoring of the connected sensors.Design and function as per DIN 1988, Part 5.

Hyamat V System Equipment (Standard)- 5 - 6 vertical high-pressure centrifugal pumps (standard pumps)

Movitec 02/04/10 with oval flange2 - 6 vertical high-pressure centrifugal pumps (standard pumps)

Movitec 18/32/45 with round flange- Hydraulic components made of stainless steel- 1 check valve and shut-off elements for each pump to DIN / DVGW- 1 membrane-type accumulator on the discharge side as control

tank (direct flow) to DIN 4807-5, approved for drinking water- Pressure transmitter on the discharge pressure side- Pressure indication via pressure gauge- Steel baseplate powder-coated/epoxy resin-coated- Pump sizes 2, 4 and 10 are fixed to the baseplate on anti-vibration

mounts- Pump sizes 18, 32 and 45 are supplied with level-adjustable feet

and anti-vibration pads (supplied, but not fitted)- Control cabinet IP 54, EMC interference suppression class B.- With CE certificate.

Control Cabinet Equipment (Standard)- Manual-0-automatic selector switch- PLC- LEDs indicating operational availability and fault of the system- Frequency inverter- Transformer for control voltage- Motor protection switch per pump- Fault acknowlegement via reset button- Master switch, lockable (repair switch)- Terminals with identification for all connections- Circuit diagram acc. to VDE, settings for FI and parts list for elec-

trical parts- Emergency OFF connection (400 V AC, current max. 6 A)

For supplementary equipment and special designs see pages 17 to 19.

Page 2: HyamatV Bh En

Hyamat V

2

Standard scope Extended scopecf. supplementary equipment

Hyamat V with control panel Hyamat V with display and keyboard

Settings

Set pressure Potentiometer at the front door Display: set value in plain language

Inlet pressure > 0.5 bar Pressure switch (cf. supplementary equip-ment)

Pressure switch (cf. supplementary equip-ment) or Display: value in plain language (if dry-run-ning protection is effected via pressuretransmitter)

Second set value Activated via volt-free contact or timer Activated via timer in the display and corre-sponding setting

All other values are set at the factory in accordance with the purchase order specificationsfor water supply applications.

Indications Indications via multi-line display (using the return key)

Actual pressure Pressure gauge Pressure gauge and display

Inlet pressure > 0.5 bar Pressure gauge Pressure gauge and display

Operational availability of thesystem

Green lamp Green lamp

General fault indication is trig-gered in the case of:- Pump fault- FI fault- Sensor fault (live-zero)- Lack of water

Red lamp Red lamp and plain language

Operation per pump Display: status indication

Operation hours counter perpump

- Display: operating hours with reset facility

Indication of flow rate - Display: actual value (approximative)

FI operation Function - including operational availabilityof the system

Display: status indication

Indications via volt-free contacts on isolating terminals

Operational availability of thesystem (trouble-free opera-tion of the system)

NO contact NO contact

General fault indication is trig-gered in the case of:- Pump fault- FI fault- Transmitter fault (live-zero)- Lack of water- Power failure

NC contact NC contact

Lack of water NC contact NC contact

FI fault NC contact NC contact

Fault acknowlegement Via reset button Display and keyboard

Miscellaneous

Functional check run Supplementary equipment - via timer Display:may be set to daily or weekly

Manual operation and/oremergency operation

Manual-0-automatic selector switch

Pump change-over Base load pump change-overFunction is triggered via customer-suppliedvolt-free contact or timer (supplementaryequipment)

Display:may be set to daily or weekly

Remote control from control station

- Automatic ON-OFF- Second set value- Emergency OFF- Remote cancellation- Functional check run- Pump change-over- Limitation of number of pumps

- Automatic ON-OFF- Second set value- Emergency OFF- Remote cancellation- Functional check run- Pump change-over- Limitation of number of pumps

Page 3: HyamatV Bh En

Hyamat V

3

Terminal Connections

Sig

nal,

disc

harg

e pr

essu

re

Sig

nal,

inle

t pre

ssur

e

Rem

ote

canc

ella

tion

Flo

w m

onito

ring,

suct

ion

side

Pre

ssur

e sw

itch,

disc

harg

e pr

essu

re

Em

erge

ncy

OF

F

Operation / fault messageper pump

Optional Optional

Dry-running protection if inlet tank is installed /for suction lift operation

Set

val

ue c

hang

e-ov

er

Aut

omat

ic O

N/O

FF

Lim

itatio

n of

num

ber

of p

umps

Pum

p ch

ange

-ove

r

Fun

ctio

nal c

heck

run

Imm

ersi

on e

lect

rode

s

FI f

ault

FI o

pera

tion

Pre

ssur

e or

floa

t sw

itch,

suct

ion

side

Designation Hyamat V 4 / 1807/ 1,2 - 3,2

Type seriesNumber of pumpsPump sizeNumber of stagesMin. inlet pressure in barMax. effective inlet pressure in bar

FunctionTwo to six pumps are controlled and monitored by a PLC.One pump is connected to a frequency inverter and controlledby the PLC in order to ensure a constant system dischargepressure, deviations of + 0.4 bar being permissible.As the demand increases or decreases, the peak load pumpswill be switched on and off automatically.As soon as the demand increases after one pump has beenswitched off, another pump which has not been in operation be-fore is switched on. After the last pump has been switched off(FI-controlled pump) and the demand increases again, the nextpump in line is switched on and connected to the frequency in-verter.The stand-by pump is also part of the alternating cycle but isswitched on only in case of need.As a standard, the system is switched on automatically depend-ing on the pressure; the actual pressure is measured by an ana-log pressure measuring device (pressure transmitter).The function of this pressure transmitter is monitored (live-zero).As long as the system is in operation, the pumps are switchedon and off depending on the demand (standard setting).In this way it is ensured that the individual pumps operate only

in line with the actual demand. The use of a speed-controlledpump reduces wear as well as the pumps’ switching frequencyin parallel operation.If a duty pump fails, the next pump will be switched on immedi-ately. There will be a general fault indication which can be re-ported via volt-free contacts (e. g. to the control station)If the demand drops towards 0, the system slowly approachesthe switch-off point.Caution!To ensure trouble-free operation of the system, there mustalways be sufficient water on the inlet side.As the system offers different connection possibilities, the con-trol unit is provided with one digital and one analog input allow-ing for the connection of a suitable lack-of-water sensor.This sensor (pressure control device, float switch, flow controldevice etc.; see Accessories) protects the system against dryrunning and in the case of insufficient water supply immediatelyswitches the system off (standard setting).

Manual modeA manual-0-automatic selector switch is available for eachpump installed.In manual mode the pumps are connected directly to themains, independently of the control unit.For this mode of operation no pressure control and nolack-of-water monitoring will be effected.Caution! Please observe the minimum flow rates!In the case of closed consumer installations, the pumpsproduce the max. pressure acc. to the characteristic curve.

CommissioningCommissioning in Germany by specialist KSB staff is effectedagainst extra charge.

Page 4: HyamatV Bh En

DVGW-tested valves

High operating reliabilitythanks to continuous functionalmonitoring of the connected sensors

General fault indicationvia volt-free contact

Corrosion-resistant stainless steel piping

Installation free from solid-bornesound transmissiondue to anti-vibration mounting

Control tank, (accumulator), direct flow,to DIN 4807-5,DVGW-approved

Manual-0-automatic selector switch per pump

Equal distribution of pump operating hoursby automatic pump change-over

Acoustic cladding (supplementary equipment)- Retrofittable and easy to

service- Protects against

contamination- Appealing design- Low-noise operation,

approx. 51-61 dB(A)

Automatic matching to the demandthanks to a continuously speed-controlled base load pump

System Features with Movitec 2, 4 and 10

Reliable, service-friendly shaft seal- Standardised mechanical seal to

EN 12756- High-alloy steel shaft

Low noise,since the flow noise is dampedby water-filled shroud

Movitec Features

Corrosion resistantAll wetted components, hydraulic components and pump shroud aremade of high-alloy stainless steel

Display (supplementary equipment)- Operating hours counter- Flow rate indicator

Hyamat V

4

Page 5: HyamatV Bh En

High operating reliabilitythanks to continuous functional monitoring of the connected sensors

General fault indicationvia volt-free contact

Corrosion-resistant stainless steel piping

Installation free from solid-bornesound transmissionthanks to anti-vibration mounting

Control tank (accumulator), direct flow,to DIN 4807-5,DVGW-approved

Manual-0-automatic selector switch per pump

Equal distribution of pump operating hoursby automatic pump change-overAcoustic cladding

(supplementary equipment)- Retrofittable and easy to service- Protects against contamination- Appealing design- Low-noise operation

Automatic matching to the demand thanks to a continuously speed-controlled base load pump

System features with Movitec 18, 32 and 45

Reliable, service-friendly shaft seal- Standardised mechanical seal to

EN 12756- High-alloy steel shaft

Low noise,since the flow noise is dampedby water-filled shroud

Movitec Features

Corrosion resistantAll wetted components, hydraulic components and pump shroud aremade of high-alloy stainless steel

Display (supplementary equipment)- Operating hours counter- Flow rate indicator

Hyamat V

5

Page 6: HyamatV Bh En

Set value

Hyamat V

6

Modes of Operation

Cascade: Hyamat K Variable: Hyamat V Other combinations and control modes

Two to six pumps are started up andswitched off by the PLC in line with theactual demand.

A base load pump is continuously con-trolled, with the peak load pumps beingstarted up and switched off in line withthe demand.

Available upon request.(Example: 1 or 2 jockey pumps as lowload pumps)

Standard Pressure Boosting Units Standard Pressure Boosting Units (PBU) 2 / 4 /10 (PBU) 18 / 32 / 45

1 Pump2 Ball valve3 Combined non-return/

shut-off valve4 Pressure gauge5 Pressure transmitter6 Control tank (accumulator)7 Switchgear/control cabinet8 Swing check valve

Modes of Connection

Direct Indirect Indirect

Unpressurised inlet tank at the same orat a higher level

Unpressurised inlet tank at a lower level(suction lift operation) 1)

Inlet pressure monitoring (cf. supplementary equipment or Accessories Booklet)

at pvor > 0.5 bar (min. 1 bar; DIN 1988)- pressure switch- pressure transmitterat pvor < 0.5 bar- flow monitoring

- float switch- set of electrodes and relay- dry-running protection set for

PE inlet tank- flow monitoring

- flow monitoring- float switch- set of electrodes and relay- dry-running protection set for

PE inlet tank

1) non-self-priming pumps; suitable for suction-lift operation (for selection, please consult KSB).

Page 7: HyamatV Bh En

H m PBU discharge head at Qsoll

6 bar

21

characteristic curves andtolerances to ISO 9906

including a stand-by pump to DIN 1988

Pumps per system

without stand-by

pump

Hyamat V

7

Work sheet for selection

Basic data:H = (pE - pvor) � 10 mpE = pvor + (H : 10) bar∆pmax = pE +0.4 barQsoll = PBU capacity at pE m3/hH = PBU discharge head at Qsoll mpE = Start-up pressure for PBU at Qsoll

including inlet pressure pvorpvor = Inlet pressure upstream of PBUH0 = PBU discharge head at Q = 0p0max = PBU discharge pressure at Q = 0 (=H0 + pvor)

Catalogue data always refer to inlet pressure = 0.

Selection exampleRequirementQ = 20 m3/h, pE = 6 bar, pvor = 0

Found solutions to DIN 1988, part 5

1. Hyamat V 6/0408/0

2. Hyamat V 5/0409/0

With any of the two above systems, theset pressure level can be obtained at20 m3/h.

They differ as to the possible inlet pres-sure fluctuations.

If the design point is below the nominalcharacteristic curve, this pressure differ-ence must be deducted from the max. in-let pressure fluctuation.

The exact ∆pvor value can be read directlyin the table: from the design point you gostraight down to the ∆pvor axis of thepumps where you will find the exact value.

Page 8: HyamatV Bh En

Hyamat V

8

Hyamat V Performance Chart (Complete Overview)

Page 9: HyamatV Bh En

Hyamat V

9

Movitec 2 Movitec 4 n = 2900 1/min

Movitec 10 Movitec 18

Page 10: HyamatV Bh En

Hyamat V

10

Movitec 32 Movitec 45 n = 2900 1/min

Page 11: HyamatV Bh En

Hyamat V

11

Characteristic Curves Movitec 2

pvor = 0 p0 max = 16 barpA = max. switch-off pressure

Characteristic curves andtolerances to ISO 9906

including a stand-by pump to DIN 1988

without stand-by

pump

Pumps per system

Page 12: HyamatV Bh En

Hyamat V

12

Characteristic Curves Movitec 4

pvor = 0 p0 max = 16 barpA = max. switch-off pressure

Characteristic curves andtolerances to ISO 9906

including a stand-by pump to DIN 1988

without stand-by

pump

Pumps per system

Page 13: HyamatV Bh En

Hyamat V

13

Characteristic Curves Movitec 10

pvor = 0 p0 max = 16 barpA = max. switch-off pressure

Characteristic curves andtolerances to ISO 9906

including a stand-by pump to DIN 1988

without stand-by

pump

Pumps per system

Page 14: HyamatV Bh En

Hyamat V

14

Characteristic Curves Movitec 18

pvor = 0 p0 max = 16 barpA = max. switch-off pressure

Characteristic curves andtolerances to ISO 9906

including a stand-by pump to DIN 1988

without stand-by

pump

Pumps per system

Page 15: HyamatV Bh En

Hyamat V

15

Characteristic Curves Movitec 32

pvor = 0 p0 max = 16 barpA = max. switch-off pressure

Characteristic curves andtolerances to ISO 9906

including a stand-by pump to DIN 1988

without stand-by

pump

Pumps per system

Page 16: HyamatV Bh En

Hyamat V

16

Characteristic Curves Movitec 45

pvor = 0 p0 max = 16 barpA = max. switch-off pressure

Characteristic curves andtolerances to ISO 9906

including a stand-by pump to DIN 1988

without stand-by

pump

Pumps per system

Page 17: HyamatV Bh En

Hyamat V

17

Accessories / Supplementary Equipment *) Hyamat VDry-running Protection Equipment

E No. Ident. No.

Dry-running protection (inlet pressure >0.5 bar)pressure switch

Wetted membrane made of neoprene

Retrofit option 1)

E 400 18 040 613

Dry-running protection (inlet pressure >0.5 bar)via pressure transmittercan only be used for variant with display

Wetted components made of 1.4301

Retrofit option 1)

E 410 18 040 614

Dry-running protection (flow monitoring)IFM sensor with tripping electronics

Retrofit option 1) as separateswitchgear

E 201 19 070 923

Set of electrodes and relayRelay fitted in the control cabinetElectrodes with 1.5 m cable and fastening element

(Both ident. nos. are required)

Retrofit option 1)if sufficientspace availablein control cabinet

E 420 00 198 09800 533 947

Weight for adjusting the float switch level

Scope of supply:- Weight with mounting elements

18 040 615

Dry-running protection, float switch1)with H 07 RN-F cable 3x1.5 mm2

for lack-of-water monitoring in combination with areservoir provided by the customer, KTW-approvedCable length 5 m

10 m20 m

Scope of supply:- Float switch with connection cable

11 037 63011 037 63111 037 632

Dry-running protection, float switch 1)with H 07 RN-F cable, 3 x 1.5 mm2, for lack-of-water monitoring in combination with a reservoir provided by the customerCable length 5 m

10 m20 m

Scope of supply:- Float switch with connection cable

11 037 74311 037 74411 037 746

Dry-running protection 5 mwith weight and PG cable gland,. 10 mKTW-approved 20 mSpecial lengths upon request.

19 071 65019 070 39519 071 651

1) As accessory. A trained electrician must effect additional wiring.

Accessories / Supplementary Equipment *) Hyamat V

E No. Ident. No.

Multi-line display,Indications and set values using keyboard

E 511 19 072 450

Ammeter per pump

Voltmeter per system

Always combined

E 340

E 341

*) Accessories (Ident. No.) are included in the scope of supply but not fitted.Supplementary equipment / options (E No.) come fitted to the unit.

76

76

Page 18: HyamatV Bh En

Hyamat V

18

Accessories / Supplementary Equipment *) (continued)

E No. Ident. No.

Operating hours counter per pump

E 330

Functional check run:Timer for daily functional check run

E 040 18 040 617

Functional check run:Digital timer for weekly programme

E 050 18 040 618

Volt-free individual reporting on isolating terminals E 051

Equipment for monitoring temperature of fluid pumped at hydraulic section for each pump

E 360 19 071 510

Acoustic cladding 2 / 4 / 10 Number of pumps- Protects against contamination 2- Appealing design 3 or 4- Low-noise operation, appr. 51-61 dB(A) 5 or 6

E 120E 121E 122

18 040 61018 040 61118 040 612

Acoustic cladding for Hyamat 18 / 32 / 45 Number of pumpsHyamat 18 up to 5.5 kW 2Hyamat 32 and 45 up to 7.5 kW 3

456

Hyamat 18 up to 7.5 kW 2Hyamat 32 and 45 up to 15.0 kW 3

4- Protects against contamination 5- Appealing design 6- Noise reduction

E 123E 124E 125E 126E 127

E 128E 129E 130E 131E 132

19 071 63319 071 63419 071 63519 071 63619 071 637

19 071 66319 071 66419 071 66519 071 66619 071 667

Telecommunications module, for fault signalling via telephone lines, with battery buffer

E 043 19 072 308

Emergency power connection on second terminal stripExternal activation

E 058

Control cabinet lighting with 230 V socket (for cabinets sized 1000 x 600 x 250 and above)

E 059

Control cabinet heating for special climatic conditions(high air humidity)

E 039

Phase monitoring relay, incl. direction-of-rotation monitoring and phase failure safety device

E 320

Over-voltage protection E 060

Separate control cabinet installation (wall mounting)with connecting switch box and 5 m cablefor pumps and sensors

E 061

*) Accessories (Ident. No.) are included in the scope of supply but not fitted.Supplementary equipment / options (E No.) come fitted to the unit.

36

24

Page 19: HyamatV Bh En

Hyamat V

19

Supplementary Equipment (on request)

Control cabinet equipmentVolt-free individual indications on special isolating terminalsEmergency power connection with automatic activationMotors with PTC resistors and PTC resistor trip device in the control cabinetSwitch position indication for master switch and manual-0-automatic selector switchControl cabinet with cylinder lockSpecial paintingExtra space in control cabinetControl cabinet air-conditioningCommunication via an RS 232C interfaceProfibus / LON bus interface

Indications for control station (on isolating terminals)Operating pressure, analog 4-20 mAOperating pressure, digital, volt-freeInlet pressure, analog 4-20 mAPower input for each pump, analog (e.g signal 0/4-20 mA / 0-10 V)Position of manual-0-automatic selector switch per pump, volt-free

Special designsOther special designs not documented are available upon request, e.g.:

1. Different operating voltage2. Different frequency3. Different connection diameters4. System discharge pressure pd up to 40 bar5. Systems for industry (for example, also for other fluids)6. Systems for suction-lift operation7. System combination with central control system etc.8. Electro-mechanical control units9. Jockey pumps: low-flow operation (on weekends, in case of extremely fluctuating demand etc.)

10. Combined systems (drinking water and fire-fighting systems), booster systems11. Customer-specific special circuit diagrams

Remote control from control stationSetting of basic set value via warning signal (0 - 10 V)

Page 20: HyamatV Bh En

Hyamat V

20

Electrical Performance Data

Hyamat V Rated powerper motor (P2)

Rated currentper motor for

Total rated power requirementHyamat V in kVA

with Movitec 3~400 V Number of pumps (motors)pumps kW A 2 3 4 5 6

0202 0.37 1.4 - - - 5.78 6.800203 0.37 1.4 - - - 5.78 6.800204 0.55 1.5 - - - 6.06 7.150205 0.55 1.5 - - - 6.06 7.150206 0.75 2.1 - - - 7.72 9.220207 0.75 2.1 - - - 7.72 9.220208 1.1 2.9 - - - 10.24 12.300209 1.1 2.9 - - - 10.24 12.300210 1.1 2.9 - - - 10.24 12.300211 1.1 2.9 - - - 10.24 12.300213 1.5 4.4 - - - 14.99 18.090215 1.5 4.4 - - - 14.99 18.09

0402 0.37 1.4 - - - 5.78 6.800403 0.55 1.5 - - - 6.06 7.150404 0.75 2.1 - - - 7.72 9.220405 0.75 2.1 - - - 7.72 9.220406 1.1 2.9 - - - 10.24 12.300407 1.1 2.9 - - - 10.24 12.300408 1.5 4.4 - - - 14.99 18.090409 1.5 4.4 - - - 14.99 18.090410 1.5 4.4 - - - 14.99 18.090411 2.2 6.0 - - - 20.43 24.630413 2.2 6.0 - - - 20.43 24.630415 2.2 6.0 - - - 20.43 24.63

1002 0.75 2.1 - - - 7.72 9.221003 1.1 2.9 - - - 10.24 12.301004 1.5 4.4 - - - 14.99 18.091005 2.2 6.0 - - - 20.43 24.631006 2.2 6.0 - - - 20.43 24.631007 3.0 7.0 - - - 24.40 29.301008 3.0 7.0 - - - 24.40 29.301009 4.0 9.0 - - - 31.44 37.731010 4.0 9.0 - - - 31.44 37.73

1802 2.2 6.0 6.81 11.01 15.22 19.43 23.631803 3.0 7.0 8.50 13.40 18.30 23.20 28.101804 4.0 9.0 11.09 17.37 23.66 29.94 36.231805 5.5 11.8 14.53 22.75 30.98 39.20 47.431806 5.5 11.8 14.53 22.75 30.98 39.20 47.431807 7.5 14.3 21.46 31.41 41.37 51.33 61.291808 7.5 14.3 21.46 31.41 41.37 51.33 61.291810 11.0 26.6 35.78 54.26 72.74 91.22 109.70

3202 4.0 9.0 12.59 18.87 25.16 31.44 37.733203 5.5 11.8 17.53 25.75 33.98 42.20 50.433204 7.5 14.3 21.46 31.41 41.37 51.33 61.293205 11.0 26.6 35.78 54.26 72.74 91.22 109.703206 11.0 26.6 35.78 54.26 72.74 91.22 109.703207 15.0 31.7 45.01 67.02 89.04 111.05 133.063208 15.0 31.7 45.01 67.02 89.04 111.05 133.06

4502-1 5.5 11.8 17.53 25.75 33.98 42.20 50.434502 7.5 14.3 21.46 31.41 41.37 51.33 61.294503-1 11.0 26.6 29.98 48.46 66.94 85.42 103.904503 11.0 26.6 29.98 48.46 66.94 85.42 103.904504-1 11.0 26.6 35.78 54.26 72.74 91.22 109.704504 15.0 31.7 45.01 67.02 89.04 111.05 133.064505-1 15.0 31.7 45.01 67.02 89.04 111.05 133.064505 18.5 40.5 55.11 83.22 111.33 139.44 167.554506-1 18.5 40.5 55.11 83.22 111.33 139.44 167.554506 22.0 44.5 62.48 93.36 124.24 155.12 186.00

Page 21: HyamatV Bh En

Hyamat V

21

Weight of units in kg (approx.)

Hyamat V Number of stages02 03 04 05 06 07 08 09 10 11 13 15

5/02../. 219 229 234 244 249 274 279 279 299 299 304 3496/02../. 239 251 257 269 275 305 311 311 335 335 341 395

5/04../. 219 229 234 239 249 249 279 279 284 299 304 3096/04../. 239 251 257 263 275 275 311 311 317 335 341 347

5/10../. 259 269 299 319 319 369 374 409 409 - - -6/10../. 287 299 335 359 359 419 425 467 467 - - -

2/18../. 292 314 334 383 385 395 397 - 553 - - -3/18../. 381 414 444 512 515 530 533 - 757 - - -4/18../. 499 543 583 671 675 695 699 - 991 - - -5/18../. 598 653 703 845 850 875 880 - 1240 - - -6/18../. 777 843 903 1069 1075 1105 1111 - 1544 - - -

2/32../. 387 438 452 614 618 702 706 - - - - -3/32../. 526 597 618 851 857 963 969 - - - - -4/32../. 714 806 834 1138 1146 1274 1282 - - - - -5/32../. 853 1000 1035 1410 1420 1575 1585 - - - - -6/32../. 1057 1229 1271 1722 1734 1911 1923 - - - - -

2/45../. 454 618 700 794 872 - - - - - - -3/45../. 646 882 985 1106 1223 - - - - - - -4/45../. 833 1141 1265 1413 1569 - - - - - - -5/45../. 1095 1475 1625 1800 1995 - - - - - - -6/45../. 1297 1754 1925 2117 2351 - - - - - - -

Noise characteristics of units with Movitec 2 / 4 / 10 pumps

Hyamat V with pumps

without acoustic cladding with acoustic cladding

Movitec 2 60 - 65 dB(A) 51 - 56 dB(A)

Movitec 4 60 - 67 dB(A) 51 - 56 dB(A)

Movitec 10 65 - 69 dB(A) 56 - 61 dB(A)

Noise characteristics of units with Movitec 18 / 32 / 45 pumps upon request.

Page 22: HyamatV Bh En

Control cabinet doorhinged to the left

Acoustic cladding (supplementary equipment)

Suction side

Dischargeside

Hyamat V

22

Dimensions of Hyamat V with Movitec 2, 4 and 10

Dimension Table (in mm)

Number of pumps 5 / 6

with Movitec 2 and 4 10

B 770 860

B1 630 735

H1 115 145

L 1770

L1 1645

DN external thread R 2 1/2 (DN 65)

Painting:Baseplate RAL 5002Control cabinet RAL 7032

Page 23: HyamatV Bh En

Acoustic cladding (supplementary equipment)

see control cabinetsControl cabinet doorhinged to the left

Plan view

Suction side

Discharge side

Hyamat V

23

Dimensions of Hyamat V with Movitec 18 and 32

Movitec 18/.. and 32/..

Number ofpumps

2 3 4 5 6 Pump

B 1085 1085 1085 1085 1238 18/..

1105 1105 1255 1255 1255 32/..

B1 865 865 865 865 953 18/..

885 885 970 970 970 32/..

B2 405 405 405 405 448 18/..

415 415 458 458 458 32/..

B3 460 460 460 460 505 18/..

470 470 515 515 515 32/..

L1 886 1296 1706 2116 2526

L2 - - 820 820 1230

L3 820 1230 820 1230 1230

L4 820 1230 1640 2050 2460

DN 100 100 100 100 150 18/..

DN 150 150 32/..

H1 287 287 287 287 287 18/..

302 302 302 302 302 32/..

Flanges drilled to EN 1092-1 PN 16

Page 24: HyamatV Bh En

Acoustic cladding (supplementary equipment)

see control cabinetsControl cabinet doorhinged to the left

Plan view

Discharge side

Suctionside

Hyamat V

24

Dimensions of Hyamat V with Movitec 45

Movitec 45Number of pumps 2 3 4 5 6

B 1060 1175 1175 1280 1280

B1 840 890 890 940 940

B2 350 375 375 400 400

B3 490 515 515 540 540

L1 886 1296 1706 2116 2526

L2 - - 820 820 1230

L3 820 1230 820 1230 1230

L4 820 1230 1640 2050 2460

DN 100 150 150 200 200

H1 302 302 302 302 302

Flanges drilled to EN 1092-1 PN 16

Page 25: HyamatV Bh En

Control cabinet doorhinged on the left

Control cabinet doorhinged on the left

+

Transfer control unit Full-length cabinet

Control cabinet doorhinged on the left Control cabinet door

hinged on the left

Hyamat V

25

Control Cabinet Dimensions1000 x 600 x 250 1200 x 800 x 300

Hyamat Rated power Design

V 2 - V 6 up to 4 kW StandardTimerVolt-free reportingOperating hours counterManual-0-automatic selectorswitchPTC thermistor analysisTemperature monitoringAmmeter and voltmeter

Hyamat Rated power Design

V 2 - V 4 5.5 to 11 kW *) StandardTimerVolt-free reportingOperating hours counterManual-0-automatic selectorswitchPTC thermistor analysisTemperature monitoringAmmeter and voltmeter

*) with Movitec 4504-1 full-length cabinet (see below)

Control cabinet consisting of:Transfer Control Unit and Full-length Cabinet (1800 x 800 x 400 mm) and 5 m Connection Cable

Transfer control unit with terminal strip for all pumps and sen-sors. In combination with separately installed control cabinet.

Hyamat Rated power Design

V 5 - V 6 5.5 to 7.5 kW StandardTiV 2 - V 4 15 kWTimerVolt-free reporting

V 2 - V 3 18.5 to 22 kWVolt-free reportingOperating hours counterManual-0-automatic selectorswitchPTC thermistor analysisTemperature monitoringAmmeter and voltmeter

Page 26: HyamatV Bh En

+

Transfer control unit Full-length cabinet

Control cabinet doorhinged on the left

Control cabinet doorhinged on the left

Control cabinet doorhinged on the right

Hyamat V

26

Control cabinet consisting of:Transfer Control Unit and Full-length Cabinet (1800 x 1200 x 400 mm) and 5 m Connection Cable

Transfer control unit with terminal strip for all pumps and sensors. In combination with separately installed switchgears and control cabinet.

Hyamat Rated power Design

V 5 - V 6 11 to 15 kW StandardVolt-free reporting

V 4 - V 6 18.5 to 22 kWVolt-free reportingManual-0-automatic selector switchOperating hours counterPTC thermistor analysisTemperature monitoringAmmeter and voltmeter

Page 27: HyamatV Bh En

Hyamat V

27

Page 28: HyamatV Bh En

1953

.51-

10

/ 1.

11.2

004

Sub

ject

to te

chni

cal m

odifi

catio

n w

ithou

t prio

r no

tice.

Hyamat V