newton raphson harmonic pf

Upload: trust4josh

Post on 02-Jun-2018

239 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 Newton Raphson Harmonic Pf

    1/126

    ;

    A DETAILED DERIVATION OF

    -. .

    NEWT ON-RAPHSON BASED HARM ONIC POWER FLOW/

    A Thesis Presented to

    The Faculty of the Russ C ollege of Engineering and T echnology

    Ohio University

    In Partial Fulfillment

    of the Requirements for the Degree

    M aster of Science

    David Charles Heidt,

    .--

    i

    June,

    994

  • 8/10/2019 Newton Raphson Harmonic Pf

    2/126

    ACKNOWLEDGMENTS

    The author would like to thank all those who helped to provide the guidance

    needed to complete this thesis including Dr. Herman Hill and Dr. Brian Manhire of Ohio

    University and Dr. Jerry Heydt of Purdue University.

    The author would also like to thank the Electrical and Computer Engineering

    Department at Ohio University for providing the financial support necessary to pursue the

    Master of Science degree.

    Lastly the author would like to thank family and friends who were patient

    supportive and understanding through the many hours of sacrifice.

  • 8/10/2019 Newton Raphson Harmonic Pf

    3/126

    TABLE OF CONTENTS

    Page

    LIST OF TABLES i

    LIST OF FIGURES. . . vii

    LIST OF SYMBOLS

    ......................................................................................................

    .

    ABSTRACT..

    mil

    CHAPTER

    1

    CONTRIBUTIONS OF TH IS THESIS

    .................................................

    CHAPTER CAUSES

    ND

    DETRIMENTAL EFFECTS OF POW ER

    SYSTEM HARMO NICS..

    5

    2 1

    Definitions Related to Harmon ics..

    . 5

    2 2

    The Cause of Harmonics in Power S ystems..

    8

    2 3

    Detrimental Effects of Harmonics on Power System s..

    18

    CHAPTER

    3

    A NEWTON RAPHSON BASED HARMONIC POWER

    FLOW..

    . 22

    3 1

    Introduction..

    22

    3 2

    Solving Nonlinear Algebraic Equations by New ton Raphson

    Methods..

    25

    3 3 A

    Brief Derivation of a Newton Raphson Based Conven tional

    Power Flow..

    33

    3 4 A

    Detailed Derivation of a Newton Raphson Based Harmonic

    Power Flow..

    .

    3

    9

    3 5

    Netw ork M odels for the Newton Raphson based Conventional

    and Harmonic Pow er Flows .............................

    ....

    .. ..

    53

    Introduction..

    53

    Transmission Lines..

    . .

    53

    Transformers.. .

    58

    Generators..

    60

    Induction Motors.. 6

    1

  • 8/10/2019 Newton Raphson Harmonic Pf

    4/126

    ther Conventional Loads 66

    as Discharge Lighting Loads 68

    3 .6 Simplifications to the Newton Raphson Based Harmonic Power

    low Equation Set 72

    CHAPTER 4 DIRECT SOLUTION OF POWER SYSTEM HARMONIC

    OLTAGES 76

    HAPTER EXAMPLES 79

    5.1 Introduction 9

    .2 Example One 90

    .3 Example Two 92

    .4 Example Three 101

    CHAPTER 6 CONCLUSIONS NDFUTURE WORK 103

    .1 Conclusions 103

    .2 Future Work 106

    IST OF REFERENCES 108

    APPENDIX 112

  • 8/10/2019 Newton Raphson Harmonic Pf

    5/126

    LIST OF TABLES

    Table Page

    3 1 Sequence of a Fundamental Frequency Signal and its Harmonics in a

    Completely Balanced Three Phase ac Pow er System 2 4

    3 2 Skin Effect Table 7

    5 1

    Fundamental F requency

    60Hz)

    ystem G enerator Data

    5 2

    Data for the Cond uctors of the

    230 Kv

    Transmission Line o f Figures

    5 2 8 2

    5 3

    Data for the Ground Wires of the

    230Kv

    Transmission Line of Figure

    5 2 8 3

    4

    Impedance Data for the

    230 Kv

    Transmission Line of Figure 5 2

    83

    5

    Per Unit Impedance Data for the

    230 Kv

    Transmission Line of Figure

    5 2

    83

    6

    Data for Polynomial Curve Fits

    9 6

  • 8/10/2019 Newton Raphson Harmonic Pf

    6/126

    LIST OF FIGUR ES

    Figure Page

    2.1.

    Generalized Six-Pulse Converter..

    9

    2.2.

    A Simple Circuit Diagram o f a Fluorescent Lamp Placed in Series with

    an Inductive Ballast..

    12

    2.3.

    Typical B-H Curve used to Describe the Characteristics of the M aterial

    used for a Transformer Core I 5

    2.4.

    n Example of Actual B-H Curves.. I6

    .1 . Geom etrical Interpretation of the Newton-Raphson Me thod..

    .27

    3.2.

    n

    Example of How the Next Approximation to

    x ) =

    can be Far

    Away from the Desired Solution x if Iteration

    xr

    is Close to the

    Minimum of a Function

    x )

    8

    3.3 . Illustration of the Tw o Systems Given by Equation Sets 3.7) and 3.8 ). 30

    3.4 . Single-Line Diagram at Bus

    i

    of a General n-Bus Pow er System 34

    3.5.

    The Equivalent Positive-Sequence-Impedance Diagram of Figure 3.4 .. 34

    3.6.

    General n-Bu s Power System Arranged to Form the Fundamental

    requency Admittance M atrix.

    .36

    3.7.

    Fundamental Frequency Admittance Diagram of a Two-Bu s Power

    ystem.. .3

    6

    3.8.

    Typical ac-Side Line Current Waveform of an ac Current to dc Current

    onverter.. .40

    3.9.

    a) A Bus Containing a G enerator and a Harm onic Producing

    HP)

    Device.

    b) n

    Equivalent Representation of a), Separated into Tw o

    Buses Connected by a Short Circuit SC) 4

  • 8/10/2019 Newton Raphson Harmonic Pf

    7/126

    General n-Bus Power System Arranged to form the

    kth

    Harmonic

    Frequency Admittance Matrix.. 47

    General Representation of a Power System at the

    kth

    Harmonic

    Frequency, with a Harmonic Producing

    HP)

    Load at Bus m.. 48

    a). A General Representation of a Power System at the

    kth

    Harmonic

    Frequency, with a Conventional C) Load at Bus i. b). Equivalent

    Representation of a), with the Conventional Load Modeled as a Series

    -L Combination.. .50

    Pi-Equivalent Model of a Long Transmission Line. 4

    i-Equivalent Model of a Short Transmission Line.

    56

    Power Flow Model of a Transformer 59

    Harmonic Power Flow Model of a Synchronous Machine for the

    kth

    armonic Frequency.. 62

    Per-Phase Fundamental Frequency Equivalent Model for an

    nduction Machine Phase a Shown)

    63

    Harmonic Power Flow Model of an Induction Motor for the kth

    armonic Frequency.. 65

    Suggested Harmonic Power Flow Model of an Unknown Conventional

    oad for the

    kth

    Harmonic Frequency..

    67

    General n-Bus Power System Arranged to form the

    kth

    Harmonic

    Admittance Matrix. Shunt Impedances used to Model Conventional

    Buses at the kth Harmonic Frequency, are Included when Forming

    he

    kth

    Harmonic Frequency Admittance Matrix..

    73

    Representation of a Harmonic Producing Device at Bus

    m,

    as an

    deal Current Source at the

    kth

    Harmonic Frequency.

    77

    Example Two-Bus Power System, with a Generator at Bus One and

    Fluorescent Lighting FL) Load at Bus Two

    ..80

    onfiguration of the 23 Kv Transmission Line in Figure 5 1

    .8 1

    Impedance Diagram of the Power System in Figure 5.1, for

    undamental Frequency

    60Hz )

    Analysis 85

  • 8/10/2019 Newton Raphson Harmonic Pf

    8/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    9/126

    LIST OF SYMBOLS

    In order to eliminate confbsion, frequencies of interest and ite ration numbers will

    be represen ted by superscripts. In addition, bus numbers, phase and phase sequences will

    be represen ted by subscripts. Fo r clarity, the most commonly used superscripts and

    subscripts used in this thesis are explained below. O ther superscripts and subscripts are

    used, but are explained as they are presented.

    superscripts

    1)

    Fundamental frequency.

    3),

    5), 7),

    Harmonic frequencies.

    f)

    The frequency of interest f

    1,

    odd).

    k)

    harmonic frequency k 3, ko dd )

    h) The highest harmonic frequency of interest h

    >

    1,

    h o d )

    r general iteration number.

    subscripts

    i

    conventional nonharmonic producing) bus.

    m harmonic producing) bus.

    j

    conventional or harmonic bus j

    =

    i

    or m) .

    a

    Phase

    a

    b

    Phase b.

    c

    Phase

    c

  • 8/10/2019 Newton Raphson Harmonic Pf

    10/126

    Direct.

    Quadrature.

    n Neutral.

    Fo r this thesis, all power system values shall be expressed in per-unit, instead o f

    conventional SI units. In addition, all currents and voltages are rms values only. The most

    commonly seen variables in this thesis are explained below. Other variables appear in this

    thesis, but are explained as they are presented .

    A voltage.

    A current entering a conventional bus from ground .

    A current entering a harmonic producing) bus to ground.

    Time.

    A hndam ental or harmonic component of a voltage Fourier Series.

    A hndam ental or harmonic component of a current Fourier Series.

    Fundamental angular frequency.

    Angular frequency.

    Active power.

    Reactive power.

    Apparent power.

    Complex power.

    Distortion power.

  • 8/10/2019 Newton Raphson Harmonic Pf

    11/126

    A fundamental f = 1) or harmonic f > 1,

    f

    odd) frequency current entering bus j

    j = i o r m ) from ground into the transmission netwo rk. p = I:)/ '.

    ?

    A hndamental f

    =

    1) or harmonic f > 1 odd) frequency current entering bus j

    j

    =

    i o r

    m

    rom the transmission network to ground .

    =

    gg'/g-

    7'

    A fundamental f = 1) or harmonic f > 1,

    f

    odd) frequency voltage at bus j

    j = i o r m ) y n= yw /q ) .

    Z Impedance. = R + X

    R Resistance.

    X Reactance.

    L Inductance.

    Capacitance.

    Admittance. =

    y g

    =

    g

    + b

    IFfll

    A fundamental f = 1) or harmonic f >

    1,f

    odd) frequency admittance matrix.

    I z ~ I

    A fundamental f = 1) or harmonic f > 1, odd ) frequency impedance matrix.

    IlWI

    A fundamental f = 1) or harmonic f

    >

    1,

    f

    od d) frequency current vector.

    fl I

    A fundamental f = 1) or harmonic f > 1,

    f

    odd) frequency voltage vector

    9

    The total number of harmonic frequencies of interest.

    M

    The total number of harmonic producing ) buses in the pow er system considered.

    Unknown value.

    L Permeability.

    A

    n

    incremental change.

    p.u. Per unit.

    rad. Radians

  • 8/10/2019 Newton Raphson Harmonic Pf

    12/126

    ABSTRACT

    Heidt, David Charles. M . S., Ohio University, June

    1994 A

    Detailed Derivation of a

    New ton-Raphson Based H armonic Pow er Flow. Major Professor: Dr. Herman Hill.

    The ideal electric pow er system contains only elements that genera te, transmit, o r

    receive undistorted hn dam ental frequency voltages and currents. Several devices are

    responsible for introducing harmonics of pure hndam ental frequency waveforms into

    pow er systems. If significant enough in amplitude, these harmonics can have a detrimental

    effect on the performance and life of power system elements.

    A

    tool commonly used to analyze the power system under normal balanced three-

    phase sinusoidal steady -state conditions, is called a pow er flow. How ever, to this date, the

    only power flow s which are readily available in textbook form, assume pure hndam enta l

    frequency voltages and currents throughout the power system.

    It is the primary intent o f this thesis, to tak e an available Newton -Raphson based

    Harmonic Pow er Flow algorithm, and provide a textbook type derivation. This

    algorithm eliminates the assumption of purely sinusoidal voltages and curren ts in a three-

    phase power system operating under normal balanced steady-state conditions.

  • 8/10/2019 Newton Raphson Harmonic Pf

    13/126

    CHAPTER CONTRIBUTIONS OF THIS THESIS

    Chapter two focuses on the cause and detrimental effects of power system

    harmonics. The chapter begins by discussing pertinent definitions related to power system

    harmonics. Several equations in this introductory section and throughout this thesis paper,

    are written in Fourier Series form. The method of Fourier Series is a convenient and

    appropriate way to express the presence of harmonics in a power system.

    The next section of chapter two describes some of the most common sources of

    harmonics in power systems today. Power electronic devices are by far the most

    significant source of harmonics in power systems today, not only because of the nature of

    these devices, but also because of their rapidly growing usage

    [4]

    Several other devices

    such as gas discharge lighting, transformers, and arc furnaces are also significant harmonic

    sources in power systems.

    Chapter two is concluded by describing several of the detrimental effects that

    harmonics can have on power systems. Here it is described how harmonics can cause

    several devices such as relays and computers to misoperate. This section also discusses

    why harmonics can lead to a reduction in the efficiency and life of several other devices

    such as motors and transmission lines. It is also discussed how power system harmonics

    can be amplified significantly depending upon the power system configuration and why

    triplen harmonics i.e., the third harmonic and its integer multiples) represent a special and

    rather complicated problem. Chapter two provides sufficient information as to what power

    system harmonics are, how they originate, and why they cannot be ignored.

    The primary focus of chapter three is to derive a Newton-Raphson based

    Harmonic Power Flow. Chapter three begins by defining both the conventional and

  • 8/10/2019 Newton Raphson Harmonic Pf

    14/126

    harmonic power flows. This introduction describes the differences between conventional

    and harmonic power flows. In addition, this introduction states why a conventional power

    flow cannot be used to obtain information about power system harmonics.

    The next section of chapter three discusses the solution of nonlinear algebraic

    equations by the Newton-Raphson method, along with some of the most common

    problems encountered when using this method. One needs to be aware of how the

    Newton-Raphson method can fail for the problem to be analyzed.

    Chapter three continues by providing the derivation for the Newton-Raphson

    based Conventional Power Flow. These equations are then used to help derive the

    Newton-Raphson based Harmonic Power Flow. This is meant to show that the Newton-

    Raphson based Harmonic Power Flow is a logical extension of the Newton-Raphson

    based Conventional Power Flow. The derivation begins by describing the number of

    equations required for the Newton-Raphson based Harmonic Power Flow and explaining

    briefly how they are obtained. The derivation continues by listing all required equations

    and providing a detailed explanation for the logic behind each equation as they are

    provided. The equation set obtained is derived in a general format, and is to be treated the

    same as any other nonlinear algebraic equation set which is to be solved by the Newton-

    Raphson method. The detailed derivation of the Newton-Raphson based Harmonic Power

    Flow, represents the author s main contribution to knowledge. This derivation is in a much

    more general format than in reference [I] In addition, intricate details provide more

    insight than is available in reference [ I ] To the best of the author s knowledge, reference

    [ I ]

    had provided the best derivation of the Newton-Raphson based Harmonic Power Flow

    to date.

    The following section of chapter three provides network models for the Newton-

    Raphson based Conventional and Harmonic Power Flows. Network models for some of

    the most common power system elements is provided. It is stressed that the hndamental

    frequency power system representation will change for each harmonic frequency of

  • 8/10/2019 Newton Raphson Harmonic Pf

    15/126

    interest. A different admittance matrix is required for each frequency to be examined. The

    equations for modeling one harmonic source (gas discharge lighting) is derived. All

    harmonic producing loads cannot be modeled in the same way however, since the current

    entering each different type of harmonic load will possess a different Fourier Series

    The last section of chapter three discusses possible simplifications to the Newton-

    Raphson based Harmonic Power Flow equation set. Since this derivation is provided in a

    general format, it is possible to model every bus in the power system the same way that

    harmonic producing buses are modeled. In other words, for every bus in the power

    system, the Fourier Series of the current entering each bus could be expressed as a

    hnction of the Fourier Series of the voltage at the respective bus, and of any parameters

    which describe this distorted waveform. The simplifications possible result when this

    approach is used only for harmonic producing busses. The derivation of the Newton-

    Raphson based Harmonic Power Flow provided in this thesis does not assume that a

    simplified approach will always be used, whereas reference [ I ] does.

    Chapter four briefly discusses the most commonly used method for determining

    power system harmonics voltages called the Current Injection Technique. In order to find

    the power system harmonic voltages, this method employs the direct (non-iterative)

    solution of the harmonic frequency admittance matrices. As the voltage distortion levels

    increase throughout the power system, the less effective the Current Injection Technique

    becomes at determining the power system harmonic voltages [I] In addition, the Current

    Injection Technique is generally effective only when the power system is a simple radial

    network [ l 1

    Chapter five provides three examples to help increase the reader s knowledge of

    the Newton-Raphson based Harmonic Power Flow. The same two bus power system is

    analyzed

    in

    all three examples. In addition, the goal is to obtain the same information in all

    three examples. In the first example, the Newton-Raphson based Conventional Power

    Flow is used to obtain the kndamental frequency voltages in the power system. The

  • 8/10/2019 Newton Raphson Harmonic Pf

    16/126

    Current Injection Technique is then used t o determine the harmonic voltages in this power

    system.

    The second exam ple in chapter five uses the Newton-Raph son based Harmonic

    Power Flow to determine the hndamental and harmonic frequency voltages in this same

    power system. For each bus in this example, the Fourier Series of the cu rrent entering the

    bus, is modeled as a hn ct io n o f the Fourier Series of the voltage at this bus, and of any

    parame ters which describe this distorted cu rrent waveform. In this case, harmonic

    frequency admittance matrices include only the admittance information for transmission

    lines and transformers, as is true for the hn dam ent al frequency admittance matrix.

    The last example in chapter five uses the simplified approach which always

    assumed t o be tru e in reference

    [ I ] .

    Therefore, all buses which do not contain harmonic

    sources are treated as an impedance load at harmonic frequencies. In this case, harmonic

    frequency admittance matrices include admittance information for transmission lines,

    transformers, and impedance loads (for nonharmonic producing loads). The hndamental

    frequency admittance matrix, however, still only includes admittance information for

    transmission lines and transformers. C hapter five also represents th e au thor s contribution

    to knowledge. To the best of the author s knowledge, detailed examples on how t o

    perform a Newton-R aphson based Harmonic Pow er Flow are not available.

    Chapter six completes the thesis by listing appropriate conclusions and suggestions

    for future work.

  • 8/10/2019 Newton Raphson Harmonic Pf

    17/126

    CHAPTER

    --

    CAUSES AND DETRIMENTAL EFFECTS OF POWER SYSTEM

    HARMONICS

    2.1 Definitions Related to Harmonics

    Harm onic producing loads have a non-sinusoidal load current that is periodic and

    can be expressed as a Fourier Series. The distorted load current passing through the

    pow er system results in distorted bus voltages that are periodic and can also be expressed

    as a Fourier Series.

    All

    frequency terms higher than the hndamental frequency will be

    referred to as the harmonics.

    Fo r this thesis completely balanced pow er systems will be assum ed so that even

    harmonics may be ignored. A property of a completely balanced power system is that even

    harmonic currents and voltages will not exist [20] . For this thesis harmonic frequencies

    shall be assum ed to be odd integer multiples of a

    6 Hz

    kndam ental frequency. By

    definition of a Fourier Series any voltage v t) or current i t) n this balanced power

    system must be an odd function as shown below f 1 odd).

    i t)

    =

    cV in oot P

    Also for this completely balanced power system the active power P and reactive

    power will be defined as follows

    f

    1

    f

    odd).

  • 8/10/2019 Newton Raphson Harmonic Pf

    18/126

    In addition to the above equations the apparent power S is a scalar quantity given

    by equation 2 . 5 ) .Th e root mean square of the voltage and current is defined by equations

    2 . 6 )and 2 . 7 ) espectively f

    1

    odd) .

    Harmonic distortion of a voltage

    v t )

    and a current i t) is defined by equations

    2 . 8 )and 2 . 9 ) espectively f

    1 odd .

    Th e definition of power fac tor is given below.

    In th e special case when

    both

    v t ) and i t ) contain fbndamental frequency

    components only equation 2 . 1 1 )will be valid.

    S2

    p

    Q 2

    2 . 1 1 )

    However when either v t ) or i t ) contains harmonic frequency components

    equation 2 . 1 1 ) s no longer valid. term that is used to account for the discrepancy is

    called the distortion power D as given below.

  • 8/10/2019 Newton Raphson Harmonic Pf

    19/126

    D = /m 2.12)

    The physical origination of in power systems is an extremely controvers ial issue

    [3] and will not be discussed in this thesis The concept of distortion power is mentioned

    here only for the sake of completeness

  • 8/10/2019 Newton Raphson Harmonic Pf

    20/126

    2 . 2 The Cause of Harmonics in Power Systems

    The generation of harmonics in pow er systems today, results from a number of

    major sou rces. However, power electronic devices are by far the most significant sources

    of harmonics

    [4]

    [ 5 ]

    For example, power electronic six-pulse converter devices used as rectifiers (to

    convert ac current to dc current) and a s inverters (to convert dc current to ac current) are

    growing in usage because they are more efficient and economical than conventional

    converter systems such as motor-generator sets [ 6 ] A few of their applications include

    he1 cells and batteries, s tatic var generators, and adjustable-speed drives for motors.

    A generalized six-pulse converter configuration is shown in F igure 2 1 When a

    squa re wave switching scheme is used, each switch changes state only twice for a

    designated switching time period. Whether the converter is used as an inverter or as a

    rectifier, significant ac side harmonics of the hndam ental current will result. Under

    balanced conditions, the characteristic ac side harmonic currents produced by a six-pulse

    converter are k

    = 6b

    b

    =

    1 2 3 . [ 6 ] The magnitude of these harmonics decrease

    inversely proportional to their harmonic order, i.e., = I '/k, where

    I )

    is the

    hndamental frequency current magnitude, and is a harmonic curren t magnitude.

    Uncharacteristic harmonics may also be produced under unbalanced conditions, where the

    magnitudes depend upon the amount of unbalance [ 7 ]

    A switching scheme for the six-pulse converter which is recently becoming more

    popular is called the pulse-width modulated (PWM) scheme. For the PWM scheme, the

    switches change state for a designated switching time period at a higher frequency than the

    squa re wave switching scheme. Basically, the higher the switching frequency, the greate r

    the number of lower order harmonics that can be eliminated. How ever, the PWM scheme

    results in the generation of higher frequency ac side harmonics. These harmonics can be

    even greate r in amplitude than the lower frequency ac side harmonics generated by the

    squa re wave switching scheme. These higher frequency harmonics and their amplitudes

  • 8/10/2019 Newton Raphson Harmonic Pf

    21/126

    Figure 2. 1 . Generalized Six Pulse Converter.

    Source: Boost [8]

    p.273.

  • 8/10/2019 Newton Raphson Harmonic Pf

    22/126

    depend upon the switching frequency of the PWM converter. In addition, a PWM

    converter produces less hndamental frequency current than a converter with a square

    wave switching scheme.

    However, the PWM scheme does have advantages over the square wave switching

    scheme. For example, the main advantage of the PWM scheme is that a large number of

    lower order harmonics can be eliminated. This results in a more sinusoidal ac side

    waveform than a square wave switching inverter can produce. In addition, a square wave

    switching inverter is not capable of regulating the ac output voltage magnitude. Therefore,

    the dc input voltage must be adjusted in order to control the magnitude of the

    inverter-

    output voltage [8]. Since the PWM inverter allows amplitude control of the ac output

    voltage from within the device, this feature can result in a simpler and cheaper power

    inverter [8].

    It should be noted that 12-pulse converters are actually much more common,

    particularly in new designs. One example of where 12-pulse converters are more

    advantageous than 6-pulse converters is in High-Voltage

    DC HVDC)

    transmission

    applications. In order to meet high voltage requirements, and to reduce the number of

    harmonics produced, it is necessary to use 12-pulse converters, instead of 6-pulse

    converters. It is noted that under balanced conditions, the characteristic ac side harmonic

    currents produced by a 12-pulse converter will be = 12b 1 b = 1,2,3,. [6]. The

    magnitudes of the remaining harmonics will be the same as for a six-pulse converter.

    Fuel cells and batteries are highly likely to grow in usage in power systems as

    energy sources during utility peak loading conditions [6]. It is desirable to operate the

    most efficient power generating plants such as nuclear and the newer high-efficiency coal-

    fired plants) at their rated capacity at all times. Due to the time of day and weather

    conditions, the utility load demand will not remain constant. In order to meet peak loading

    conditions, either oil- or gas-fired generators can be used, but are expensive to operate

    because of the high cost of he l.

    n

    alternative is to store the energy generated by the

  • 8/10/2019 Newton Raphson Harmonic Pf

    23/126

    more efficien t pow er generating plants in batteries o r fuel cells during low-load conditions,

    and t o use this surplus during peak-loading conditions. However, since both batteries and

    fuel cells produce a dc voltage, an inverter is required to connect them to the utility

    system.

    converte r system can be designed such that th e ac current can be quickly

    controlled in magnitude and phase leading or lagging) with respect to the ac voltage of

    the device. Such a converter is commonly termed a static var generator, and can be used

    for power factor correction applications [8]. Industrial loads such as arc furnaces can

    cause very rapid changes in power factor . In this case, a fast and efficient static var

    generator would be more desirable to use than a slower conventional power-factor-

    correction capacitor bank.

    Pow er electronic converter devices are commonly used as adjustable-speed drives

    for motors [9]. For instance, a common configuration for an ac m otor drive is made up of

    a rectifier ac to dc) supplying an inverter dc to ac). By controlling the direction of the

    power flow, this adjustable-speed drive configuration can allow precise con trol over the

    motoring and braking of the ac motor [ lo ].

    Gas discharge lighting such as fluorescent, mercury arc, mercury vapor, neon,

    xenon, and high pressure sodium) represent a major source of harmonics, particularly in

    metropolitan areas [ l l ] . In particular, fluorescent lighting may constitute up to twenty-five

    percent o f the total customer load, and may exceed thirty percent [12]. The wide usage of

    fluorescent lamps as compared to other lamp types is due to their high energy efficiency.

    Greater stability in the operation o f conventional

    OHz

    gas discharge lamps is

    provided by an inductive ballast placed in series with the lamp [ l 11. simple circuit

    diagram of a fluorescent lamp placed in series with an inductive ballast is shown in Figure

    2.2, where

    v

    s the ac source supply.

  • 8/10/2019 Newton Raphson Harmonic Pf

    24/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    25/126

    The efficiencyof the lamp can be h rt he r increased twenty to thirty percent by

    using a high frequency electronics solid-state) ballast which converts an incoming 6 Hz

    ac input to a higher frequency in the 25 to

    4 kHz

    ange [6].

    Under balanced conditions, all odd harmonics of the hndam ental ac current are

    produced by a series lamp and ballast combination. The actual m agnitudes of these

    harmonics depends greatly upon the manufacturer models o f both the lamp and ballast

    type. In particular, solid -state ballasts tend to result in higher amplitudes for each of the ac

    current harmonics produced [12]. Depending upon the lamp and ballast combination used,

    a third harmonic ranging from seven to eighty-seven percent of the hndamental ac current

    has been measured [12]. Many other odd harmonics can be also qu ite significant in

    amplitude. Typical third and fifth harmonic currents produced are 21 and percent of the

    fbndamental ac cu rrent respectively [ l 11.

    Even if the harmonics produced by individual lamps are small in amplitude, each of

    the respective harmonics produced by the individual lamps tend t o be in phase and

    additive. This is due to the fact that these harmonics arise from distortion of a 6OHz

    fbndamental current [13].

    Arc fbrnaces, which are most often used for the meltdow n of scrap metals, are a

    source of a number of problems in the power system today. The use of arc fbrnaces is

    expected to increase, since the technology is improving [14].

    In an arc fbm ace, graphite electrodes are lowered into a basin containing scrap

    metal, in order to strike electric arcs between the electrodes and the scrap. The heat

    generated by the electric arcs results in meltdown o f the scrap metal [15].

    Under balanced conditions, typical arc fbrnace third, fifth, seventh, and ninth

    voltage harmonics produced are 20, 10, 6, and 3 percent of the hndamenta l respectively.

    Unbalanced conditions can lead to significant even harmonics, and additional

    magnification of the odd voltage harmonics [14].

  • 8/10/2019 Newton Raphson Harmonic Pf

    26/126

    It is noted that as the pool of molten metal grows, the arc becomes more stable.

    This in turn results in much steadier currents, with much less distort ion, and less harmonic

    activity.

    The harmonic problem in power systems today is also due to a change in design

    philosophy. In the past, power system devices tended to be underrated or overdesigned.

    Now, in order t o be more competitive, power system devices are more critically designed

    [4] Because o f this design philosophy, iron core devices such as transformers are more

    likely to becom e sa turated.

    The most common curve used to describe the characteristics of the material used

    for a transformer core is the B-H curve as shown in Figure 2 3 [16] Figure 2 4 provides

    an example of some actual B-H curves.

    The

    B-H

    curve represents the relationship between the magnetic field B), and the

    magnetic field strength H).When there is little change in the value of B for large changes

    in H, the transform er is said to be saturated.

    Modern high-voltage transformers with grain oriented steel cores saturate typically

    somewhere above 1 0 to 1 2 imes the rated magnetic flux in the core [17] Magnetic flux

    represents the surface integral of the magnetic field. In general, manufacturer ratings are

    given somewhere around the point of saturation. Operation of the transformer beyond

    these ratings drives the core into satura tion, and resul ts in rapidly increasing levels of

    harmonic currents [ I ]

    It is impractical to design transformers without saturation, and as a consequence,

    harmonic currents produced by a transformer are unavoidable.

    The significant harmonic currents produced by a transformer under balanced

    conditions, are all odd harmonics of the hndamental frequency exciting current. The

    magnitudes of these harmonic currents depends greatly upon the magnitude of the voltage

    at the transform er terminals. However, typical magnitudes for the third, fifth, seventh, and

  • 8/10/2019 Newton Raphson Harmonic Pf

    27/126

    Fig 1-1 0. Hysteresis loop; hysteresis loss is proportional to the loop area shaded).

    Figure

    2.3 .

    Typical

    B H

    Curve used to Describe the Characteristics of the Material used

    for

    a

    Transformer Core.

    Source: Fitzgerald 1161

    p.2

    1

  • 8/10/2019 Newton Raphson Harmonic Pf

    28/126

    10 0 10 20 30 40

    50

    70 90 110130150170

    H turndm

    Fig.

    1-6. 6 -H loops for

    M-5

    grain oriented electrical steel

    0.012

    in thick. Only the

    top

    halves

    of

    the loops are shown here.

    Armco

    I ~ c .

    Figure 2 4 An Example of Actual

    B H

    Curves.

    Source: Fitzgerald [16] p.

    15.

  • 8/10/2019 Newton Raphson Harmonic Pf

    29/126

    ninth harmonic currents produced by a saturated transformer are 50, 20, 5 and 2.6

    percent of the fundamental exciting current respectively [18].

    Even in the absence of other nonlinearities in the power system, transformer

    harmonic currents can reach significant levels [19].

    Transformer harmonics can be of great concern, since transformers are widely used

    in power systems, and play an integral role in power transmission.

    Considerable effort is taken to design rotating machines such that the harmonic

    currents they produce are negligible [16]. Special care is taken to eliminate triplen i.e., the

    third harmonic and its integer multiples) and fifth and seventh harmonics of the

    fundamental frequency exciting current, where other harmonics are taken to be

    insignificant [20].

    Saturation of the stator and rotor teeth can lead to the generation of odd

    harmonics, but these are also generally insignificant in amplitude [21]. For example, rotor

    third harmonics produced under saturated conditions, typically have values lower than one

    percent of the rated stator current 1211.

    Unbalanced operating conditions may also result in odd harmonic voltages at the

    machine terminals of a generator. For example, a third harmonic voltage of magnitude

    greater than six percent of the fundamental can occur. However, these harmonics are

    greatly dependent upon the length of the line that the generator is feeding [22].

  • 8/10/2019 Newton Raphson Harmonic Pf

    30/126

    2 3

    Detrimental Effects of Harmonics

    Harm onics have been linked to a number o f problems in the power system,

    including communication interference. Very often , comm unication lines used for the

    transmission of signals share the same path as power lines used for transmitting and

    distributing electrical energy

    [20]

    Current flowing in the power lines results in m agnetic

    and electric fields which induce currents or voltages) in the nearby communication lines

    [26]

    The interference introduced depends greatly upon the separation distance between

    the power and communication lines which are often closely in parallel with each other),

    and the frequency particularly the harmonics after the fundamental) and magnitude of the

    induced currents voltages)

    [20]

    The inductive reactance of the ac power system composed of generators,

    transmission lines, transformers, etc.) and the capacitive reactance of widely used

    capacitor banks for power factor correction), and insulated cables, produce resonance

    conditions [25] The resonant frequency of an inductive-capacitive LC) circuit occurs

    when the inductive reactance equals the capacitive reactance.

    If the power system appears to be a very low impedance for instance, to a

    harmonic source) at the resonant frequency, then this condition is termed series resonance .

    Likewise, if the system appears to be a very high impedance at the resonant frequency,

    then this condition is termed parallel resonance. In either case, if the resonant frequency of

    the power system happens to be close to one of the frequencies generated by a harmonic

    source in the system, the result may be the flow of high harmonic curren ts or the

    appearance of high harmonic voltages)

    [26]

    Although a system resonance condition does not produce harmonic curren ts or

    voltages, small currents voltages) generated by a harmonic source in the power system

    can be amplified significantly by a resonance condition .

    Since switching the configuration of the capacitor banks for a different power

    factor) changes the capacitive reactance of the system, more than one resonant frequency

  • 8/10/2019 Newton Raphson Harmonic Pf

    31/126

    will exist [27]. In addition, since motor loads appear to be primarily inductive at harmonic

    frequencies, changes in the m otor loads on the system, can result in a shift of the resonant

    frequency [25].

    In a three-phase system, triplen harmonics i.e ., the third harmonic and its integer

    multiples) represen ts a special and rather com plicated problem. The objective here will be

    to keep the discussion as simple as possible, yet to introduce a couple of realistic examples

    of how triplen harmonics cause problems in pow er systems. Therefore, consider the case

    of a wye-connected load, that of a delta-connected load.

    Three-phase power systems are operated under balanced conditions as much as

    possible), where the hndam ental frequency line currents are 120 degrees ou t of phase

    with respect t o each other. For example, in a balanced three-phase system, the

    hndam ental frequency line currents can be:

    I:) I( ) cos Wt)

    I;) I( )

    cos Wt 120)

    I: I ( ) cos 0t 120)

    The third harmonic of the line currents above assumed to be generated by a nonlinear

    device in the power system) would be:

    I:)

    C O S ~ W ~ ) )

    I ( ~ )

    O S ~ W ~ ) )

    I?)

    I ( ~ ) O S ~ W ~1200)) I ( ~ ) O S ~ W ~ ) )

    I;)

    I ( ~ ) O S ~ W ~1200

    1

    I ( ~ ) O S ~ W C ) )

    In a wye-connected load, these third harmonic currents would be in phase and additive in

    the neutral wire. Ideally, it is desired that all currents should be ze ro in the neutral wire. If

    significant enough in amplitude, these third harmonic currents would lead to increased

    heating of the neutral wire, and therefo re shorten its lifespan. The absence of a neutral

    wire will result in circulating triplen harmonic currents in a delta-connected load. Again, if

    significant in amplitude, these third harmonic cu rrents will lead to increased heating of the

    elements in the delta-connected load, and therefore shorten their lifespan.

  • 8/10/2019 Newton Raphson Harmonic Pf

    32/126

    Motors and generators (both induction and synchronous) experience increased

    heating due to iron and copper losses at harmonic frequencies. Harmonics can cause

    rotating machinery to have a pulsating torque output. This results in mechanical

    oscillations which can lead to rotor shaR fatigue and accelerated aging of the shaft and

    connected mechanical parts. In particular, harmonics can cause or enhance phenomena

    called cogging (a refbsal to start smoothly) or crawling (very high slip) in induction

    machines [25]. The net effect of harmonics on rotating machinery is a reduction in both

    efficiency and life.

    The m ajor effects of harmonics on transformers is that current harmonics cause an

    increase in copp er losses and stray flux losses, and voltage harmonics cause an increase in

    iron losses [25 ]. As a result, there will be an increase in transform er heating, which in turn

    can shorten the life of the unit.

    Harmonics flowing through transmission lines (power cables) will lead to

    additional power losses due to the skin effect . As a result, the effective alternating

    current resistance (R,,), will be raised above the direct current resistance (R,,), especially

    for large co nduc tors. Therefore, when the current flowing through the cable contains a

    high harmonic conten t, the equivalent RaC or the cable is raised even higher, which will

    amplifjr the 12Ra, oss as illustrated in equation (2.1 9) . No te that superposition of power is

    valid as long as all terms to be added, are at different frequencies. On the right hand side

    of equation (2.19 ), each successive term is a t a frequency which is an odd integer multiple

    of the first.

    Hot spo ts are created along the cable by maximums of the overall current and voltage

    due to standing wave phenomena. It is at these points, that excessive damage to the cable

    and its insulation can occur [42].

    In order to measure the effective power drawn by industrial loads, watt-hour

    meters a re typically used. Depending upon the type of meter used, and the harmonics

  • 8/10/2019 Newton Raphson Harmonic Pf

    33/126

    present and their magnitudes) in the current and voltage waveforms, a significant

    overestimation or possible underestimation) of the real power drawn by the industrial

    load can take place [30] Therefore, large industrial loads that are significant harmonic

    producers could appear to have a higher or lower) power factor than they actually do.

    For example, induction watt-hour meters are designed to operate in the presence

    of purely sinusoidal voltage and current waveforms, and are calibrated in this way [3

    11

    The watt-hour meter will indicate the real average) power drawn by sensing the voltage,

    the current, and the phase relation between the voltage and current. However, in the

    presence of harmonics, the true phase relationship between the distorted current and

    voltage waveforms becomes unclear, thus leading to errors in the power readings [32]

    Several other devices are sensitive to the presence of harmonics, such as relays and

    computers. relay is a device which will perform one or more switching actions based on

    the information received from the power system, and is often used in power system

    protection schemes [2] Negative-sequence current relays are oRen used to detect small

    fault currents [33] This negative-sequence overcurrent relay can be used to trip a breaker

    coil to interrupt operation) when the negative-sequence component of the fault current

    exceeds a certain value. The presence of high negative-sequence harmonic currents, may

    cause this relay to operate for a fault current with a negative-sequence component that is

    much lower than the specified value. In a balanced power system, the fiRh harmonic is

    entirely negative-sequence.

    In order to prevent malhnction or damage to a computer, manufacturers typically

    speci@ that the voltage distortion due to harmonics) is to be less than

    5

    percent of the

    hndamental voltage [34]

  • 8/10/2019 Newton Raphson Harmonic Pf

    34/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    35/126

    in this chapter, only power systems operating in a completely balanced three-phase ac

    mode will be considered. If each phase of the three-phase power system contains identical

    fundamental and harmonic voltages and currents, the power system is said to be

    completely balanced [I] property of a completely balanced power system is that even

    harmonic currents and voltages will not exist

    [20]

    With completely balanced conditions

    assumed, a single line admittance impedance) diagram of the power system may be used

    for each harmonic considered, corresponding to the correct sequence given by Table 3 1

    In addition, the admittances impedances) of each single line diagram must be scaled

    according to the harmonic frequency.

    If unbalanced conditions exist, fundamental and harmonic currents can each

    contain positive-, negative-, and zero-sequence components. The method of symmetrical

    components must then be used to simplifL analysis, but will not be considered in this

    thesis.

    For this thesis, buses which do not contain harmonic producing devices will be

    referred to as conventional buses. In addition, buses which do contain harmonic producing

    devices will be referred to as harmonic buses.

  • 8/10/2019 Newton Raphson Harmonic Pf

    36/126

    Table 3.1. Sequence o f a Fundamental Frequency

    Signal

    and its Harmonics in a

    Completely Balanced Three-Phase ac Power System.

    Source: Westinghouse Electric Corporation 1201

    p.759.

    Sequence

    Poai

    tive

    ero

    Negative

    Poeitive

    ero

    Negative

    Poeitive

    Harmonic

    9

    2

    23

    25

    27

    29

    3

    eta

    Harmonic

    6

    7

    9

    3

    5

    17

    Sequence

    Pwi tive

    Zero

    Negative

    Poeitive

    ero

    Negative

    Positive

    Zero

    Negative

  • 8/10/2019 Newton Raphson Harmonic Pf

    37/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    38/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    39/126

    Figure

    3 .1 .

    Geometrical Interpretation of the Newton-Raphson Method.

    Source: Choma [37]

    p.3

    14.

  • 8/10/2019 Newton Raphson Harmonic Pf

    40/126

    Figure 3.2.

    An

    Example of How the Next Approximation to x ) an be Far Away

    From the Desired Solution xs , if Iteration xr is Close to the Minimum o f a Function x ) .

    Source: Choma [37] p.3

    15

  • 8/10/2019 Newton Raphson Harmonic Pf

    41/126

    For two systems, x = C and

    By

    = D , if the elements of A and differ by little, and

    those of

    C

    and D differ by little, then the elements of the solution vectors x and y will

    also differ by litt le if the system is stable. As an example of an unstable system, consider

    the eq uation sets (3.7) and (3.8 ) below.

    x + y = l (3.7a)

    x 1.00001y

    =

    0

    (3.7b)

    x + y = l (3.8a)

    x 0 . 9 99 99 ~ 0 (3 .8b)

    Although these tw o systems above differ by little, the solution set fo r equations

    (3.7) is (x

    =

    100,00 1 and y

    =

    -100,00 0), and the solution set for equations (3.8) is

    ( x = -99,999 and y = 100 ,000 ). Each equation set represents an effort to find a position

    (x ,y ) at which the tw o lines will intersect, as shown in Figure 3.3. Therefore , a slight shift

    of either line, can move the point of intersection quite significantly.

    The above problems with using the Newton-Raphson method a re not necessarily

    separable, and may occur simultaneously.

    Therefore, the Newton-Raphson method for solving nonlinear algebraic equation

    sets is not perfect, and one needs to be aw are of how this method can fail for the problem

    to be analyzed.

    For nonlinear algebraic equa tions with N unknowns as in equation (3.9) below,

    the method of Newton-Raphson may be used to solve the equation set if

    N

    f r

    =

    f (Ar ,Br ...........N r ) = O

    r

    =

    g(Ar B ,

    ............,

    )

    =

    0

  • 8/10/2019 Newton Raphson Harmonic Pf

    42/126

    0 99999~

    Figure

    3 .3 .

    Illustration

    of

    the

    Two

    Systems Given by Equation Sets

    3.7)

    and 3.8).

  • 8/10/2019 Newton Raphson Harmonic Pf

    43/126

    Using these equations, a Jacobian matrix

    I J ) I

    is formed by equation 3.10).

    Numerical values for the partial derivatives are obtained by using the values of the

    unknowns at the rt iteration.

    The error in the unknowns,

    AA

    AB .......

    N is

    found by equation 3.1 1). The

    column matrix on the right side of equation 3.1 I), contains numerical values for equation

    set 3.9) at the rt iteration.

    The next approximation to the roots of equation set 3.9) is obtained from

    equation 3.12).

  • 8/10/2019 Newton Raphson Harmonic Pf

    44/126

    The itera tion process on the unknowns continues until I l E I BI I

    .... and IAN E ~ nless the solution set diverges or the number of iterations has reached

    the maximum number allowed

  • 8/10/2019 Newton Raphson Harmonic Pf

    45/126

    3.3 - A Brief Derivation of a Newton-Raphson Based Conventional Power Flow

    The equations for a Newton-Raphson based Conventional Power Flow or

    Conventional Power Flow) are derived by first observing the hndamental frequency

    current flow at bus

    i

    of a general

    n

    -bus power system. The power system is shown in

    Figure 3.4. According to Table 3.1, only the positive-sequence-impedance diagram is

    required to properly represent this power system, as shown in Figure

    3 5

    Using Kirchhoff s Current Law KCL) at bus i

    ,

    esults in equation 3.13).

    Taking the conjugate of equation 3.13), and multiplying through by the

    hndamental frequency voltage at bus

    i , ~ l )

    ~ ) / 4 ,

    esults in equation 3.14) or its

    equivalent, equation 3.15).

    ~ ( 1 )f z ) ) * ~ ( 1 ) 7 ~ ) ) ~~ ( 1 )? I)*

    3.14)

    -

    (1) - ( 1 )

    S ,

    - Li

    i 3.15)

    The terminology of equation 3.15) is explained below.

    -

    s, )= The hndamental frequency three-phase complex generated power flowing into the

    ith

    bus from the power source s).

    s:) =

    The hndamental frequency three-phase complex power flowing out of the

    ith

    bus

    towards the load buses.

    3;)

    =

    The hndamental frequency three-phase complex power flowing out of ith bus

    towards the transmission network.

    The individual hndamental frequency complex powers of equation 3.15) can be

    resolved into their rectangular components as shown below.

    -

    ( )

    p 1) jQ(1)

    s

    Gi

    Gi

    -

    s;) p 1) Q(

    Li x

    -

    1) - p 1) Q(1)

    Ti -

    Ti

    i

  • 8/10/2019 Newton Raphson Harmonic Pf

    46/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    47/126

    By inspection of equations (3.19, (3.16), (3.17), and (3.18 , equations (3.19) and (3.20)

    are formed.

    P = pi

    ')

    (3.19)

    (1)

    -

    (1)

    Qa

    -

    Qfi

    +

    Q

    (3.20)

    A simple rearrangement of equations (3.19) and (3.20) results in the equations to

    be written at each bus i in an n-bus power system for the Conventional Power Flow. el

    and

    a )

    epresent the net fundamental frequency real and reactive power flows at each bus

    i

    = -

    P ) e)

    P

    =

    (3.2

    1)

    el)

    - ) Q;)

    Q; =

    (3.22)

    Depending upon the bus type, the terms e nd

    Q /

    will be known or unknown

    values in the Conventional Power Flow. Their final values will fall between a prespecified

    minimum and maximum value for each.

    q

  • 8/10/2019 Newton Raphson Harmonic Pf

    48/126

    Fundamental frequency

    positive-sequence

    transmission network

    which only contains

    transformers and

    transmission lines. ll

    loads and generation

    are external.

    Figure 3 .6 .

    General -Bus Power System Arranged to Form the Fundamental Frequency

    Admittance Matrix.

    Source: Gross [2] p.258.

    referen e

    Figure 3.7. A Fundamental Frequency Admittance Diagram o f a Tw o-Bus Power System.

    Source: Gross [2] p.259.

  • 8/10/2019 Newton Raphson Harmonic Pf

    49/126

    Equations 3.23) and 3.24) can be written in matrix form, to obtain equations 3.25),

    3.26), 3.27), and 3.28).

    Every entry of the matrix

    IF

    is in the general form of 7;:

    y F / a :

    Equation 3.18) may now be written in terms of the transmission current j:); ,

    which was formed when creating 1F' 1

    Equation 3.18) above may be separated into its rectangular components, as shown

    below.

  • 8/10/2019 Newton Raphson Harmonic Pf

    50/126

    Q:)

    = vl) y ~in(8')q at)

    Therefo re, the nonlinear algebraic equations that are to be written at each bus i in

    the C onventional Pow er Flow, and solved using the New ton-Raphson technique, are

    formed by rewriting equations (3.21) and (3.2 3) as shown below.

    The above two equa tions describe the real and reactive power cond itions at each

    bus

    i

    in the power system. They will be referred to as the real and reactive pow er

    mismatch equations.

    The known and unknown variables in equations (3.3 1) and (3.32) depend upon the

    bus type. As stated before,

    e'

    nd

    Q;)

    are always prespecified numerical values at every

    bus in the pow er system.

    t

    the swing (or slack bus), the hndamental frequency voltage is

    assumed to be ql)1/@ p.u . as a reference, while

    e

    and

    Q

    are the unknowns.

    How ever, equations (3.31) and (3.32) do not need to be w ritten at the slack bus, since

    there are no restrictions placed upon e and Q: and ql)nd 4 re known. At all load

    buses, both E)nd

    Q;)

    are known and usually zero for each, while vl'nd 8'' re

    unknown . Lastly, at gen erator (voltage-controlled) buses, P

  • 8/10/2019 Newton Raphson Harmonic Pf

    51/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    52/126

    Figure 3 8 Typical ac Side Line Current Waveform of an ac Current to dc C urrent

    Converter.

    Source: Mohan [ 6 ] p.57.

  • 8/10/2019 Newton Raphson Harmonic Pf

    53/126

    However, the following derivation will show that conventional and harmonic buses

    are basically treated the same way in the Harmonic Pow er Flow, even though the difficulty

    of their bus models may not be the same. The goal here is to make this point as obvious as

    possible for two reasons. First, once the simplified conventional bus model is understood ,

    the more detailed harmonic bus models will be easier to understand . Second, it will be

    easier to understand how improved conventional bus models may be incorporated into the

    Harmonic Power Flow.

    Following this derivation, simplifications to the Harmonic Pow er F low equation

    set will be discussed. These simplifications are possible only when the simplified

    conventional bus model as discussed above is used.

    In order to solve for the hndam enta l frequency unknowns in an

    n

    -bus power

    system, 2 n 1) equa tions are required. Like the Conventional Power Flow, there is no

    need to solve for any hnd am enta l frequency unknowns at the slack bus, since ql and q

    are know n, and because there a re no restrictions placed upon el nd

    Q: .

    Also,

    2 n) q )

    equa tions are required to solve for every harmonic unknown in an

    n -bus pow er system, when

    q

    harmonic frequencies are of interest. For this thesis, all

    frequencies of interest greater than the hn dam ental, are referred to as the harmonics.

    Up to two equations may be required to solve for the p arameters which are used to

    describe the distorted current waveform entering each harmonic producing bus m .

    Therefore, for

    M

    harmonic buses, up to

    2 M )

    additional equations may be required fo r

    the Harm onic Power Flow. Therefore, the total number of equ ations which may be

    required to solve for all of the unknowns in the Harmonic Power Flow is

    2 n

    1

    2 n ) q ) 2 M ) .

    brief description of the Harmonic Power Flow equations is now given, before

    explaining them in further detail.

    First, 2 n 1) equations are provided by describing the real and reactive power

    condition s at each bus in the power system, as a Fourier Series. Like the Conventional

  • 8/10/2019 Newton Raphson Harmonic Pf

    54/126

    Pow er Flow, these equations will be referred to as the real and reactive power mismatch

    equa tions in the Harmonic Pow er Flow. These equations will allow complex power

    generated and load) to be specified at each bus in the power system, exactly as was

    desired with the Conventional Pow er F low.

    As will be shown, a convenient way to obtain the additional 2 n) q) 2 M )

    equations required for the Harmonic Power Flow is to apply Kirchhoff s current law

    KCL) at every bus in the power system.

    Applying KCL at every bus in the power system for each harmonic frequency of

    interes t, will result in n) q) equations. Separating each of these equations into its real and

    imaginary components, results in 2 n) q) equations for the Harmonic Pow er Flow. These

    equa tions will be referred to as the harmonic frequency real and imaginary current

    mismatch equations.

    Lastly, 2 M ) equations are obtained from the real and imaginary components of

    the fundamental frequency KCL equation formed at each harmonic bus. These equations

    will be referred to as the fundamental frequency real and imaginary current mismatch

    equations.

    Like the Conventional Power Flow, the real and reactive power mismatch

    equations will be formulated such that all complex power will be treated as either

    generation, transmission, or load complex power. A lthough these equations will contain

    the hndamental and all harmonic frequency components, generated complex power will

    be assumed to contain no harmonic components. Generators synchronous machines) are

    generally not considered to be significant harmonic producing devices, and are therefore

    not m odeled as harmonic sources in the Harmonic Power Flow [I] .

    Genera tors and harmonic devices both fulfill important, yet different roles in the

    Harmonic Power Flow. Therefore, unnecessary complications may be avoided , if

    generators and harmonic devices are placed at different buses in the power system

    impedance diagrams. In addition, it will generally be easier if different types of harmonic

  • 8/10/2019 Newton Raphson Harmonic Pf

    55/126

    devices are placed at separa te buses. For example, a gas discharge lighting load is not

    treated the same as an ac current to dc current converter, in the Harmonic Power Flow.

    When necessary, a single bus may be separated into two buses connected by a short circuit

    (or a very small impedance). Figure 3.9 provides a simple example of how a single bus

    containing a genera tor and a harmonic producing device, can be separated into two buses

    connected by a short circuit.

    The refore , the general form of the real and reactive power mismatch equations at

    every harmonic bus m are given by equations (3.33 ) and (3.34). The letter h refers to the

    highest harmonic to be considered in the Harmonic Pow er Flow, and the letter

    represents the frequency of interest (fbndamental or harmonic).

    In add ition, the general form of the real and reactive power mismatch equations at

    every conventional bus are given by equations (3.35 ) and (3.36).

    Only odd terms appear in equations (3.33) through (3.36) above, since even

    harmonics do not exist in a completely balanced pow er system. Therefore,

    1f

    odd

    The slack bus in the Harmonic Pow er Flow is treated essentially the same as for

    the Conventional Pow er Flow. The hndamental frequency voltage is assumed to be

    V

    =

    l / g p u

    as a reference, while

    El

    nd

    Qz

    are the unknowns. How ever,

    equations(3.35) and (3.36 ) do not need to be w ritten at the slack bus, since there a re no

    restrictions placed upon

    and Q and v nd 4 )re known.

  • 8/10/2019 Newton Raphson Harmonic Pf

    56/126

    Figure 3 9 a)

    A

    Bus Containing a Generator and a Harmonic Producing@Pevice. b)

    An

    Equivalent Representation of a), Separated into Two Buses Connected by a Short

    Circuit SC).

  • 8/10/2019 Newton Raphson Harmonic Pf

    57/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    58/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    59/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    60/126

    Figure 3 . 1

    1

    A General Representation of a Power System at the kt Harmonic

    Frequency, with a Harmonic Producing HP) Load at Bus

    m .

  • 8/10/2019 Newton Raphson Harmonic Pf

    61/126

    for this thesis.

    As stated before, conventional buses can be modeled exactly the same way as

    harmonic buses are modeled in the Harmonic Power Flow. This approach, however is

    generally not used, in order to simplifjr the Harmonic Power Flow. Instead, each

    conventional bus is modeled as a complex power demand at the hndamental frequency,

    and is modeled as an impedance (that has a linear voltage-current characteristic) at the

    harmonic frequencies. At each harmonic frequency, a different impedance is used to

    model the device(s) at the conventional bus. These harmonic impedances are easily

    estimated, and are discussed for several conventional devices in this thesis. Therefore, it is

    easy to obtain the harmonic currents entering a conventional bus, and to obtain the

    harmonic complex power drawn by a conventional bus.

    For example, Figure 3.12(a), shows a general representation of a power system at

    the kt harmonic frequency, with a conventional

    (C)

    load at bus i The current

    ZEI? g E / p j * , represents the

    kt

    harmonic current entering the conventional load at bus

    i The kt harmonic voltage at bus i is represented as y ' ~ ( ~ / 4 ~ ) .ssuming that the

    kt harmonic impedance model at conventional bus i is a series

    R-L

    combination as in

    Figure 3.12(b), the current g: is found by Ohm s law to give equation (3.43).

    g

    y ( k )

    (3.43)

    R + j 2 @

    By substitution of equation (3.43) into

    f

    I , at the

    kt

    harmonic frequency, the

    harmonic complex load power for the conventional load of Figure 3.12(b) is given by

    equations (3.44) and (3.45).

  • 8/10/2019 Newton Raphson Harmonic Pf

    62/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    63/126

    The additional 2 n ) q ) 2 M ) equations required for the Harmonic Pow er Flow,

    are conveniently obtained by applying KCL at every bus in the power system. As stated

    before, applying KCL at every bus for each harmonic frequency of interest, will give

    n) q) equations . Separa ting each of these equations into its real and imaginary

    components, results in 2 n) q) equations for the Harmonic Pow er Flow. These equations

    are referred t o as the harmonic frequency real and imaginary curren t mismatch equations.

    Lastly, 2 M ) equations are obtained from the real and imaginary components of

    the hndam ental frequency KCL equation formed at each harmonic bus. These equations

    are referred to as the hndam ental frequency real and imaginary current mismatch

    equations.

    By observation of Figure 3.1 1, application of KCL at a harmonic bus m for any

    frequency of interest hndam ental or harmonic), results in equation 3.46), where

    1,

    and is odd ordered.

    Also, by observation of Figure 3.12 a), application of KCL at a conventional bus

    i

    or any harmonic frequency of interest, gives equation 3.47), where

    k

    3, and

    k

    is

    odd ordered.

    The current

    j

    i

    or m) is simply a KCL equation that is written at every bus

    in the power system, using nodal analysis. These KCL equations are then used to produce

    the hndamental f I), or harmonic f

    >

    1, odd frequency admittance matrix

    /PI

    Therefore, equations 3.46) and 3.47) can be written as equations 3.48) and 3.49)

    respectively. Again,

    1

    k 3 and and k are odd ordered.

  • 8/10/2019 Newton Raphson Harmonic Pf

    64/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    65/126

    3.5 Network Models for the Newton-Raphson Based Conventional and Harmonic Power

    Flows

    Introduction

    This section describes how to model a power system elements for the New ton-

    Raphson based Conventional and Harmonic Power Flow s. The power system transmission

    network composed of transmission lines and transformers, must be modeled a t the

    fundamental and harmonic frequencies. Harmonic frequency shunt impedance models, for

    the most common conventional loads, such as synchronous machines and induction

    motors is presented here.

    The harmonic load m odel for a gas discharge lighting load is discussed. All

    harmonic devices cannot be modeled in the same way, how ever, since the current entering

    each different type of harmonic load will possess a different Fourier Series.

    For the Conventional Pow er Flow, all impedances are positive-sequence.

    However, for the H armonic Power Flow, harmonic impedances may be positive-,

    negative-, o r zero-sequence, depending upon the harmonic fi-equency. The harmonic

    frequencies presented in Table 3.1 , apply to all power system netw ork and device

    impedances discussed here.

    Transmission Lines

    For the H armonic Power Flow, three-phase transmission lines are modeled by a

    single-phase pi-equivalent with the correct phase sequence, for both the fundam ental and

    harmonic frequencies. This model is also used for the Conventional Power Flow . The most

    important factors to be considered for the pi-equivalent model in Figure 3.13, are line

    length and skin effect. The long line pi-equivalent model in Figure 3.13 is recomm ended

    for distances longer than five percent of the wavelength of the highest harmonic of

    interest[2] Knowing that c/f where c is the speed of light c

    3.00

    x

    lo

    mls ) , and

  • 8/10/2019 Newton Raphson Harmonic Pf

    66/126

    z,

    sinh(@) ohms

    RC Series resistance per unit length.

    ~ Series inductance per unit length.

    d :Shunt capacitance per unit length

    @:shunt conductance per unit length.

    d:

    Length of the transmission line.

    Figure 3; 13. Pi-Equivalent Model o a Long Transmission Line.

    Source: Grady El], p.24.

  • 8/10/2019 Newton Raphson Harmonic Pf

    67/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    68/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    69/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    70/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    71/126

    Figure 3 1 5 Power Flow Model of a Transformer.

    Source: Grady

    [I]

    p 30

  • 8/10/2019 Newton Raphson Harmonic Pf

    72/126

    based Harmonic Pow er Flow.

    s suggested by Figure 3.15, tap changing transform ers must be used when

    necessary, such as for modeling phase shift. For either wye-delta or delta-wye

    connections, the high voltage side leads the low voltage side by thirty degrees for the

    positive-sequence networks. Likewise, for the negative-sequence network, high voltage

    side lags the low voltage side by thirty degrees. The zero-sequence ne twork will introduce

    no phase shift.

    Generators

    For each harmonic frequency, an acceptable model for a synchronous generator is

    to directly scale the hndamental frequency negative-sequence inductance reactance of the

    generator with frequency [I ]. The resistive component of the hndam ental frequency

    negative-sequence impedance is generally much smaller in comparison to th e reactive

    com ponent. In addition, in the absence of elaborate information, the resistive component is

    assumed to remain constant for all harmonic frequencies, and negligible.

    Negative-sequence hndam ental frequency stator currents rotate at twice

    synchronous speed, as seen from the rotor. The resultant flux is forced into paths o f low

    permeability, which do not link any rotor circuitry. These paths a re characterized by the

    direct and quadrature subtransient inductances

    L;

    and L: respectively. By definition, the

    hndam ental frequency negative-sequence reactance of a synchronous machine is given by

    equation 3.55) [20]

    x: [(xi) ' (x;) ']/2

    3.55)

    where:

    (xi)' Direct axis subtransient reactance

    (xi) '

    Quadrature axis subtransient reactance

  • 8/10/2019 Newton Raphson Harmonic Pf

    73/126

    Then, by observation of equation (3.59, the findamental frequency negative-

    sequence inductance of a synchronous machine is given by equation (3.56). This is the

    inductance met by findamental frequency negative-sequence currents flowing into the

    stator winding of a synchronous machine.

    iq [(L; ) ' (~:) ']/2

    (3.56)

    When harmonic currents flow from the network into the stator windings of a

    synchronous generator, they also create a flux rotating at multiples of synchronous speed,

    where the direction may be the same or in opposition to the rotor s direction of rotation

    [38]. In addition, these fluxes are also forced into paths characterized by the subtransient

    inductances. Therefore, the average inductance which appears to be met not only by

    negative-sequence fbndamental frequency stator currents, but also by harmonic frequency

    stator currents is given by equation (3.56) [I].

    Then, the reactance used to model the synchronous machine as in Figure 3.16, for

    the

    kth

    harmonic frequency is given by equation

    3.57),

    where

    k

    is the harmonic frequency

    of interest, and

    x )

    is given by equation (3.55).

    x

    q

    (3.57)

    Induction Motors

    The induction machine is one of the most commonly used motor loads in power

    systems today. An adequate harmonic frequency model of the induction machine is the

    same one proposed for the synchronous machine [ l]. However, if the direct axis and

    quadrature axis subtransient reactances are unknown, then a harmonic impedance model

    can be obtained, based on the per-phase fbndamental frequency model shown in Figure

    3.17 [I]

    The magnetizing inductance L, is generally ignored, since it is large in comparison

    with the other terms.

  • 8/10/2019 Newton Raphson Harmonic Pf

    74/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    75/126

    ST

    =The per

    ph se

    fundamental frequency stator voltage.

    Tz =The per

    ph se

    fundamental frequency stator current.

    r, =The resistance of the stator winding.

    L =The leakage inductance of the stator winding.

    L =The magnetizing inductance

    L =Th e leakage inductance of the rotor winding.

    r, =The resistance of the rotor winding.

    s =The slip = a, o r / @ ,

    w =The angular frequency in radians per second.

    Figure

    3 17

    A

    Per-Phase Fundamental Frequency Equivalent Model for an Induction

    Machine Phase a Shown).

    Source: Grady [ I ] p.33.

  • 8/10/2019 Newton Raphson Harmonic Pf

    76/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    77/126

    Figure

    3 18

    Harmonic Power Flow Model o f an Induction Motor for the

    k h

    Harmonic

    Frequency

    Source: Grady

    [I] p 36

  • 8/10/2019 Newton Raphson Harmonic Pf

    78/126

    Other Conventional Loads

    It is difficult to represent many conventional load buses at harmonic frequencies,

    since their exact composition is usually unknown. It is suggested, that in the absence of

    specific information, a conventional load bus must be modeled as a shunt resistor in

    parallel with an inductor or a capacitor [I] . The resistance and the reactance can be

    determined by the hndamental frequency active and reactive power demand of the

    conventional load. Therefore, the values of R ~ nd LS~, are obtained from equations

    3.62), and 3.63) below, and are used in the Harmonic Power Flow model of Figure

    3.19. Note that if

    Qz

    is negative, then a capacitance

    c

    should be used instead of an

    inductance

    LS~,;.

    In the absence of elaborate information, the hndamental frequency resistance is

    assumed to remain constant for all harmonic frequencies

    [I] .

    The hndamental frequency

    reactance is scaled directly with frequency.

    Therefore, the impedance used to model an unknown conventional load at all

    harmonic frequencies is given by equations 3.64) and 3.65) below.

    ~ f R L 3.64)

    lo d

    L

    kX l) 3.65)

  • 8/10/2019 Newton Raphson Harmonic Pf

    79/126

    Figure 3.19 . Suggested Power Flow M odel of an Unknown Conventional Load for the

    kt Harmon ic Frequency

    Source: Grady

    [I] p.37.

  • 8/10/2019 Newton Raphson Harmonic Pf

    80/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    81/126

    were taken. The term B in equation (3.6 8) is simply a scaling variable which is

    multiplied across the entire equation.

    The Fourier Series expansions for odd powers of voltage is completely given by

    equation (3.69 ). No te that equation (3.69) is simply a shortcut method o f raising equation

    (3.67) to an odd power, and expanding and rearranging this equation to a form suitable for

    the Harmonic Power Flow.

    (3.69)

    The terms

    L

    and

    A

    are given by equations (3 .70 ) and (3.71) respectively.

    AL

    =

    8i2

    .

    ..............+did (3.71)

    Since even harmonics are not considered here, the values of A A 2 ....... A d and h are

    odd integers only. In addition, since -h

    Ld

    h , negative values of

    Ld

    are converted to

    positive values via the trigonom etric identities below.

    cos(x) = cos(-x), and in(x) = sin(-x)

    (3.72)

    After directly substituting equation (3.69) into equation (3.68) and expanding,

    equation (3.68) will assume the form given by equation (3.73 ). No te that all harmonic

    terms greater than

    h

    are simply ignored.

    From equation (3.73), the terms gZVrnd

    g2A

    re directly substituted into

    equations (3.50a), and (3.50b ) respectively.

    Tw o suggested methods are given by equations (3.74) and (3 .7 9 , which can be

    used to initialize the fbndamental and harmonic voltage magnitudes at each bus in the

    power system, in the absence of a better method. For both initialization methods, the angle

  • 8/10/2019 Newton Raphson Harmonic Pf

    82/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    83/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    84/126

    3 6

    Simplifications to the Newton-Raphson Based Harmonic Power F low Equation Set

    As stated in the previous section, since nonlinear components are the source of

    harmonics in pow er systems, it is of great importance in the Harm onic Power Flow, to

    accurately model the nonlinear relationship between the current and voltage waveforms at

    each bus containing a harmonic device. For this purpose, it is convenient to express

    distorted voltages and currents as Fourier Series. For the H armonic Power Flow, the

    Fourier Series of the current entering a harmonic bus is expressed as a function of the

    Fourier Series of the voltage at this bus, and of any parameters which describe this

    distorted current waveform.

    Conventional buses can be modeled exactly the same way as harmonic buses are

    modeled in the Harmonic Power Flow. This approach, however is generally not used, in

    order t o simplify the Harmonic Power Flow. Instead, each conventional bus is modeled as

    a complex power demand at the hndamental frequency, and is modeled as an impedance

    that has a linear voltage-current characteristic) at the harmonic frequencies. At each

    harmonic frequency, a different impedance is used to model the dev ice s) at the

    conventiona l bus. This is the approach which is assumed in reference [I].

    In the previous section, the Harmonic Pow er Flow was derived in a general

    format. Therefore, both harmonic and conventional buses were approached in the same

    way . However, when the simplified modeling approach discussed above) is used for

    conventiona l buses, two basic simplifications can be made when forming the Harmonic

    Pow er Flow equation set. These simplifications result when the kt harmonic power

    system impedance diagram is arranged according to Figure 3 .20 instead of Figure 3 o),

    when forming the kt harmonic frequency admittance matrix i.e.,

    lY(* I

    Although

    simplified, the resulting equation set will be equivalent to the set formed by following the

    previous section. Note that no information is lost as a result of these simplifications.

    Rather, the same information is simply restated in a different way.

  • 8/10/2019 Newton Raphson Harmonic Pf

    85/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    86/126

    First, at every conventional bus modeled as a shunt impedance for each harmonic

    frequency, as in Figure 3.12), the real and reactive power mismatch equations only need to

    be written with fbndamental frequency components. Therefore, equations 3.3 5), 3.36),

    3.39), and 3.40) are combined to give equations 3.81) and 3.82) below.

    In addition, by forming the

    kt

    harmonic frequency admittance matrix according to

    Figure 3.20, the currents i ) and g: of Figure 3.12 and equation 3.47), are both

    automatically included in the

    K L

    equations which are written. Therefore, the harmonic

    frequency real and imaginary current mismatch equations to be written at each

    conventional bus modeled as a shunt impedance for each harmonic frequency), are also

    simplified. Hence, equations 3.5 1a) and 3.5 1b) are rewritten as equations 3.83) and

    3.84) respectively, where k

    3,

    and k is odd ordered.

    F)y k)in(a ) y

    Note that all other equations discussed in the previous section, will remain

    unchanged.

    In the Examples chapter, the equations discussed in the previous section are used

    to form the Harmonic Power Flow equation set, for a two bus power system. Then, this

    equation set is again formed, using the two simplifications discussed in this section. It will

    be shown that both equations sets have an identical solution set.

    Although it may be then concluded that the two equation sets are equivalent, it is

    very possible that they may converge at a different rate. In addition, depending upon the

  • 8/10/2019 Newton Raphson Harmonic Pf

    87/126

    initial conditions the two equation sets may converge to a different solution set. However

    no attemp t will be made by the au thor of this thesis to prove this hypothesis.

  • 8/10/2019 Newton Raphson Harmonic Pf

    88/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    89/126

    us - k)

    1

    Figure 4 1 Representation o f

    a

    Harmonic Producing Device

    at

    Bus m as an Ideal Current

    Source at

    the

    kth Harmonic Frequency.

  • 8/10/2019 Newton Raphson Harmonic Pf

    90/126

    In the examples chapter the Current Injection Technique is used to find the third harmonic

    voltages in a two bus pow er system with a gas discharge lighting load.

    Project IEEE-5 19 [25] states that the assumption which permits the Current

    Injection Technique to be used is that the pow er system voltages are not distor ted.

    However Project IEEE-5 19 also states that the Current Injection Technique is generally

    accurate if the voltage distortion levels in the pow er system are less than ten percen t.

    Basically as the voltage distortion levels in the power system increase the less effective

    the Current Injection Technique becomes at modeling the relationship between harmonic

    voltages and currents in the power system.

    The purpose of this chapter was not meant to be a comparison between the

    Harmonic Pow er Flow and the Current Injection Technique. Rather the idea was to

    present a simple method which can be used in place of the Harmonic Power Flow in

    certain instances. Very often a simplified solution is adequate in simple radial netw orks.

    However this is usually not the case in nonradial netw orks or when the magnitudes of

    power system harmonic voltages are significant [I].

  • 8/10/2019 Newton Raphson Harmonic Pf

    91/126

    CHAPTER 5

    EXAMPLES

    5 1 Introduction

    The example system under consideration is as shown in Figure 5.1 . The complex

    pow er generated at bus one is carried over a one half mile,

    230Kv

    transmission line, to a

    large fluorescent lighting load drawing

    6MW

    and

    OMVARS

    at bus tw o. Fo r simplicity, it

    will be assum ed that the presence of the fluorescent lighting load will only introduce third

    harmonic currents and voltages into the power system.

    It is noted that this exam ple pow er system is not entirely realistic. The au thor of

    this thesis constructed this example power system based on readily available information.

    In addition, simplicity was desired in ord er to keep the examples manageable. However,

    the solution methods presented in the examples are correct.

    For all impedance data, the system base values are given below in equation 5.1).

    The generato r data of Table 5.1 is supplied in per-unit form on the system bases

    chosen.

    The configuration of the

    230Kv

    transmission line is as shown in Figure 5.2. No te

    that due to lack of information, some dimensions had t o be approximated. In Tables 5.2

    and 5.3 , the data for the transmission line conductors and ground wires is given. Using

    Tables 5 .2 and 5.3, and the equations in the Appendix, the necessary impedance data for

    the

    230Kv

    transmission line was obtained, and is given in Table 5.4. Because the

  • 8/10/2019 Newton Raphson Harmonic Pf

    92/126

    Figure

    5.1.

    Example Two-Bus Power System,

    with

    a Generator at Bus One and a

    Fluorescent Lighting FL) Load at Bus Two.

    ur 2 ur generaor3 8Kv

    Rotor

    s3+ ,4 VL , ~ f r a t s a f r a t 4 Q- Q* H

    MVA) kV)

    kg)

    (Hz) Mvar) Mvar) Type Poles s)

    Salient

    0 5 mile - 230Kv transmission line

    X d

    XL

    Xi

    X

    i X i X

    X Xm

    R,

    R, R

    impedance

    data

    in on generator

    ratings)

    j 0 0 2 ~

    Table

    5 .1 .

    Fundamental Frequency

    60Hz

    System Generator Data.

    Source: Gross

    [2], p.251.

  • 8/10/2019 Newton Raphson Harmonic Pf

    93/126

    Figure

    5 2

    Configuration of the 23 Kv Transmission Line in Figure

    5 1

    Source: Westinghouse Electric Corporation [20] p 590

  • 8/10/2019 Newton Raphson Harmonic Pf

    94/126

  • 8/10/2019 Newton Raphson Harmonic Pf

    95/126

    Electrical characteristics of overhead ground wires

    Part

    A :

    Alumoweld strand

    Table 5 .3. Data for the Ground Wires of the

    23 Kv

    Transmission Line of Figure 5.2 .

    Source: Gonen [41]

    p.658.

    I

    freauencv positive-sequence impedance

    I

    zero-sequence impedance I

    Strand

    A W G )

    NO. 10

    Table

    5.4.

    Impedance Data for the

    23 Kv

    Transmission Line of Figure 5 2

    60 Hz

    reactance

    for -lt rad iw

    Induct~ve Capac~tive

    n / m l

    Mn.

    mi

    0.777 0.1

    392

    frequency I positive-sequence impedance I zero-sequence impedance

    60

    Hz

    geometric

    mean radius

    it

    0.001650

    Res~stancc.Rim1

    Small currents

    25C 25C

    oc 60Hz

    8 870 8 870

    Table 5 .5 . Per-Unit Impedance Data for the 230

    Kv

    Transmission Line o f Figure 5 .2 .

    75 of cap.

    75C 75C

    oc 60

    Z

    10.440 10.670

    Hz)

    6 0

    per unit

    0.043415 + 0.258128

    per

    unit

    0.082514 + 0.507372

  • 8/10/2019 Newton Raphson Harmonic Pf

    96/126

    transmission line of Figure 5.1 is only one half mile in length, and the highest harmonic

    i.e., current or voltage) of interest is the third, the short transmission line equations of

    Chapter 3 can be used, with shunt capacitance ignored. The transmission line data of Table

    5.4 is converted to per-unit, by using the chosen system base values, and is given in Table

    5.5.

    As an example, the 60Hz posi