1 …6 Karl Dungs, Inc 3890 Pheasant Ridge Dr. NE, Suite 150, Blaine, MN 55449 U.S.A. Phone: (763) 582-1700 Fax: (763) 582-1799 E-mail: [email protected] Enclosure Rating NEMA Type 4 Maximum Operating Pressure 7 PSI (500 mbar) Ambient / Fluid Temperature Versions -2, -3, -5, & -6; -40°F to +140°F; (-40°C to +60°C) Version -8; -20°F to +140°F; (-30°C to +60°C) Materials in contact with Gas Housing: aluminum & steel; Diaphragm: NBR-based rubber Approvals UL Listed: File #. MH 16628 CSA Certified: File # 201527 FM Approved: Report J.I. 1Y9A9.AF Commonwealth of Massachusetts Approved Product Approval code G3-0106-191 GAO-A2, GMH-A2, and GML-A2 Gas Pressure Switch Installation Instructions SPECIFICATIONS High/low ventless gas pressure switch (SPDT) with automatic or manual reset. Includes visual indication of switch position. Mounts directly to various ports on the SV, DMV and MB series valves and FRI series regulators. Gxx_A2 Installation Manual - P/N 80111 - Ed. 04/10 Gases Dry, natural gas, propane, butane; other noncorrosive gases. Suitable for up to 0.1% by volume, dry H 2 S. A “dry” gas has a dew point lower than +15 °F and its relative humidity is less than 60 %. Switch action GAO: high/low limit, NC breaks on rise, automatic reset GMH: high limit, NC breaks on rise, manual reset GML: low limit, NO breaks on fall, manual reset Switch Type and Contact Rating SPDT; 10 A res., 8 FLA, 48 LRA @120 Vac; 1A @ 12-48Vdc. Vent Limiter Incorporates a vent limiter as per UL 353 and limits the escape of gas less than 1.0 CFH of natural gas at 7 PSI if internal switch diaphragm rupture. Electrical Connection 1/2” NPT conduit connection via screw terminals ATTENTION • Read these instructions carefully. • Failure to follow them and/or improper installation may cause explosion, property damage and injuries. • Installation must be done with the supervision of a licensed burner technician. • Check the ratings in the specifications to make sure that they are suitable for your application. • Never perform work if gas pressure or power is applied, or in the presence of an open flame. • Ensure that the switch is not subjected to vibration during operation. • Once installed, perform a complete checkout including leak testing. • Label all wires prior to disconnection when servicing. Wiring errors can cause improper and dangerous operation • Verify proper operation after servicing. • The system must be installed, used, and maintaned to meet all applicable national and local code requirements such as but not limited to NFPA 85, NFPA 86, UL 795, CSD-1, ANSI Z83.4, ANSI Z83.18, ANSI Z21.13, and CSA B149.3.

Upload: nguyenquynh

Post on 18-Apr-2018

222 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: SPECIFICATIONS - gti-altronic.com · Maximum Operating Pressure ... • Use an accurate pressure gauge connected upstream from the switch to measure the actual pressure. • Replace

1 …6

Karl Dungs, Inc3890 Pheasant Ridge Dr. NE, Suite 150, Blaine, MN 55449 U.S.A.

Phone: (763) 582-1700 Fax: (763) 582-1799 E-mail: [email protected]

Enclosure Rating NEMA Type 4Maximum Operating Pressure 7 PSI (500 mbar) Ambient / Fluid Temperature Versions -2, -3, -5, & -6; -40°F to +140°F; (-40°C to +60°C) Version -8; -20°F to +140°F; (-30°C to +60°C) Materials in contact with Gas Housing: aluminum & steel; Diaphragm: NBR-based rubberApprovals UL Listed: File #. MH 16628 CSA Certified: File # 201527 FM Approved: Report J.I. 1Y9A9.AF CommonwealthofMassachusettsApprovedProductApprovalcodeG3-0106-191

GAO-A2,GMH-A2,andGML-A2GasPressureSwitchInstallationInstructions

SPECIFICATIONSHigh/low ventless gas pressure switch (SPDT) with automatic or manual reset. Includes visual indication of switch position. Mounts directly to various ports on the SV, DMV and MB series valves and FRI series regulators.

Gxx

_A2

Inst

alla

tion

Man

ual-

P/N

801

11-

Ed.0

4/10

Gases Dry, natural gas, propane, butane; other noncorrosive gases. Suitableforupto0.1%byvolume,dryH2S. A “dry” gas has a dew point lower than +15 °F and its relative humidity is less than 60 %.Switch action GAO: high/low limit, NC breaks on rise, automatic reset GMH: high limit, NC breaks on rise, manual reset GML: low limit, NO breaks on fall, manual resetSwitch Type and Contact Rating SPDT; 10 A res., 8 FLA, 48 LRA @120 Vac; 1A @ 12-48Vdc.Vent Limiter IncorporatesaventlimiterasperUL353andlimitstheescapeofgaslessthan1.0CFHofnaturalgasat7PSIifinternalswitchdiaphragmrupture.Electrical Connection 1/2” NPT conduit connection via screw terminals

ATTENTION•Readtheseinstructionscarefully.•Failuretofollowthemand/orimproperinstallationmaycauseexplosion,propertydamageandinjuries.•Installationmustbedonewiththesupervisionofalicensedburnertechnician.•Checktheratingsinthespecificationstomakesurethattheyaresuitableforyourapplication.•Neverperformworkifgaspressureorpowerisapplied,orinthepresenceofanopenflame.•Ensurethattheswitchisnotsubjectedtovibrationduringoperation.

•Onceinstalled,performacompletecheckoutincluding leak testing.•Labelallwirespriortodisconnectionwhenservicing.Wiringerrorscancauseimproperanddangerousoperation•Verifyproperoperationafterservicing.•Thesystemmustbeinstalled,used,andmaintanedtomeetallapplicablenationalandlocalcoderequirementssuchasbutnotlimitedtoNFPA85,NFPA86,UL795,CSD-1,ANSIZ83.4,ANSIZ83.18,ANSIZ21.13,andCSAB149.3.

Page 2: SPECIFICATIONS - gti-altronic.com · Maximum Operating Pressure ... • Use an accurate pressure gauge connected upstream from the switch to measure the actual pressure. • Replace

2…6

MOUNTING

WiringProcedureRemovetheclearcoverfromtheswitch.•Use14or16AWGwireratedforatleast75°C•Routethewiresthroughtheconduitconnector.•Installaconduitplugatsomepointintheconduitrun•betweentheswitchandclosestpanelthatcontainsswitchingcontactsorothersparkingdevices(seeNFPA86requirementsaboutpotentialrisksofgasleakingdownconduit).Connectthewiringtotheappropriatescrewterminals.•

CAUTION:Allwiringmustcomplywithlocalelec-trical codes, ordinances and regulations.

WIRING

CAUTION:Donotexceedtheswitchratingsgiveninthespecificationsandontheswitch.

RecommendedMountingProcedureRemovetheclearcoveroftheswitchinordertore-•movethethreadformingsocketheadscrews.VerifythattheO-ringandthegroove,inwhichtheO-•oringisplaced,arecleanandfreeofnotchesorburrs.PlacetheO-ringintothegrooveonthebackofthe•pressureswitch.Thisislocatedontheflatesideofthealuminum housing.Usinga3mmhexwrench,removetheG1/8plugfrom•theportonwhichtheswitchistobemounted.Thiswillbeeitheraflange,thesideoftheFRIregulator,oraG1/8portofDungssafetyshutoffvalve.Mounttheswitchontotheportusingthethread-form-•ingsocketheadscrews.TheO-ringcanslideduringthemountingprocess,so•itisrecommendedthatastheswitchispressedontotheport,visuallyverifythattheO-ringremainsinthegroove.Tightenthescrewsbutdonotexceed22lb-in.Perform•aleaktesttoverifythatnoleakageoccursaroundtheo-ring.

GAOLoworHighGasSwitch(Operatingstateshownasahighlimit). Aspressurerisesabovesetpoint,1NCopens,2NOcloses,NeonlightON (fault). As pressure falls below set point, switch resets: 1 NC closesand2NOopens.

GMH High Gas Switch (Operating state shown) As pressure rises abovesetpoint,2NOcloses,1NCopens,andNeonlightON(fault),switchtripsandlocksout.

GMLLowGasSwitch(Operatingstateshown)Aspressurefallsabovesetpoint,2NOopens,1NCcloses,NeonlightON(fault),switchtripsandlocksout.

Wiringterminalillustration

Page 3: SPECIFICATIONS - gti-altronic.com · Maximum Operating Pressure ... • Use an accurate pressure gauge connected upstream from the switch to measure the actual pressure. • Replace

3 … 6

AnnuallychecktheswitchforproperoperationSetPointCalibrationThesetpointdialoftheGAOandGMHisfactorycalibrat-edwithincreasingpressure(GML:decreasingpressure).Duetohysteresis,theGAOswitchwillactuateataslightlylowerpointasthepressuredecreases.AdjustingtheSetPoint•Removetheclearcoverfromtheswitch.•Turnthedialuntilthedesiredtrippressureisoppositethewhitearrow(mark)ontheyellowdialface.•Afteradjustingthesetpointfornormaloperationchecktoseethatthegaspressureswitchoperatesasintended.•Useanaccuratepressuregaugeconnectedupstreamfromtheswitchtomeasuretheactualpressure.•Replacetheclearcover.

OPERATIONANDADJUSTMENTAutomaticResetTheNCcontactoftheGAObreakswhenpressurerisesabovethesetpoint.Itmakesautomaticallywhenpressurereturnstothenormaloperatinglevel.ManualResetTheNCcontactoftheGMHbreakswhenpressurerisesabovethesetpoint.TheNOcontactoftheGMLbreakswhenpressurefallsbelowthesetpoint.Neitheroftheswitcheswillreturntotheirformerpositionautomatically.Toreset,waituntilthepressurereturnstothenormaloperat-inglevel.Thenpressandreleasetheclearcoverovertheredresetbuttoninthecenteroftheyellowdialface;itisnotnecessarytoremovethecover.TheneonlightindicatesafaultconditionfortheGMLandGMHseriesandfortheGAOserieswhenusedasahighgaslimit.Theleadforthelightwiredtoterminal#2ontheGAOseriesshouldbewiredtoterminal#1whenusedasalowgaslimit.

Page 4: SPECIFICATIONS - gti-altronic.com · Maximum Operating Pressure ... • Use an accurate pressure gauge connected upstream from the switch to measure the actual pressure. • Replace

4 … 6

MAINTENANCEANDTESTINGAnnuallychecktheswitchforproperoperation

LowGasPressureSwitch:First,connectametercapableofreading+/-0ohmsto•theNOandCOMcontacts,andverifythattheNOandCOMcontactsaremade.Measuretheresistance,andiftheresistanceismorethan1ohm,removeswitchfromservice.ismorethan1ohm.(Seeterminalillustrationbelowforguidance).Then,verifythatthelowgaspressureswitchwillchange•statewhenalowgasconditionissensedbyconnect-ingametercapableorreading+/-0ohmstotheNCandCOMcontactsandthenbycausingtheswitchtogointoafaultcondition.Oncethefaultoccurs,Measurethe resistance, and if the resistance is more than 1 ohm, removeswitchfromservice.ismorethan1ohm.Tocausethefault,performoneofthetwoprocedures:•

Turnthepressureswitchsetpointcounterclockwise1. untiltheswitchtrips.Depressurizethevolumeofgasthelowgaspressure2. switchissensing.ForFRI/6regulators,thiscanbedonebyopeningthesidetapontheoppositivesideoftheFRI/6regulator.ForDMVandMBCsafetyshutoffvalves,thiscanbedoneopeningtheport1pressuretap.ForSVvalves,openport1oftheupstreamvalve.

Allowtheburnertogothroughastartupsequence,and•thenverifythattheburnerfaultsandisnotallowedtolightoff.Closealltesttaps(ports)andopenupstreamballvalve.•Whenfinished,closeallpressuretestpointsused,and•thenopentheupstreamballvalveSLOWLYtoallowgaspressuretograduallybleedintothesystem.

CAUTION:Openingtheupstreamballvalvetoofastcanpermanentlydamagetheregulator.

HighGasPressureSwitch:First,connectametercapableofreading+/-0ohmsto•theNCandCOMcontacts,andverifythattheNCandMeasure the resistance, and if the resistance is more than1ohm,removeswitchfromservice.ismorethan1ohm. Then,verifythatthehighgaspressureswitchwill•changestatewhenahighgasconditionissensedbyconnectingametercapableorreading+/-0ohmstotheNOandCOMcontactsandthenbycausingtheswitchtogointoafaultcondition.Tocausethefault,performoneofthetwoprocedures:•

Turnthepressureswitchsetpointclockwiseuntilthe1. switchtrips.Pressurizethevolumeofgasthehighgaspres-2. sureswitchissensing.Thiscanbedonebyclosingthedownstreamballvalve,openingport3taponaDMVandMBCsafetyshutoffvalves,orport2or3ofthedownstreamSVvalve,andthenusingapumptopressurizethetestchamber.

MeasuretheresistanceacrosstheNOandCOM•contacts.Iftheresistanceismorethan1ohm,removeswitchfromservice.Allowtheburnertogothroughastartupsequence,and•thenverifythattheburnerfaultsandisnotallowedtolightoff.Whenfinished,closealltesttaps(ports)andopenthe•dowmstreamballvalve.

NOTE:Aresistanceofmorethan1ohmindicatesthattheswitchcontactsarestartingtoeithercorrodeorcarbonize.

TerminalIllustration

Donotsimilatefaultconditionswhiletheburnerisfiring.

Page 5: SPECIFICATIONS - gti-altronic.com · Maximum Operating Pressure ... • Use an accurate pressure gauge connected upstream from the switch to measure the actual pressure. • Replace

5 … 6

LocationModelseriesGAO-A2-4,GMH-A2-4,andGML-A2-4canbemounteddirectlytovariousportsonaDUNGSvalve.Thepressureswitchshouldbemountedinlocationsmeetingtherequirementsoftheapplicablecode.Ordermountingkit214-975forDMVport3mountandMBCport3mounting,andkit225-047formountingswitchverticallyonavalveflange.

MOUNTINGTOSAFTYVALVES

2016 12 8

4

pBr

2

3

1 1

4 455

3

3

2

2

1

1

54

2016 12 8

4

pBr

A2mountingoptionsDMV701-703Dualmodularvalve

A2mountingoptionsSV1010,SV1012,SV1015,andSV1020seriessafetyvalve

Pressuretap

1 2 3 4 5

Mountingpossible? yesyesyesnoyes

A2mountingoptionsSV 1005 and SV 1007 series safetyvalve

Pressuretap 1 2 3 4 5

Mountingpossible? yesyesyes,with#214-975yes,horizontalyes,verticalwith#225-047yes,horizontalyes,verticalwith#225-047

Pressuretap

1 2 3 4

Mountingpossible? noyesnono

A2mountingoptionsMBCseriesmultifunctionalcontrol

Pressuretap

1 2 3 4 5

Mountingpossible?yesyesyes,with#214-975yes,horizontalyes,verticalwith#225-047yes,horizontalyes,verticalwith#225-047

Page 6: SPECIFICATIONS - gti-altronic.com · Maximum Operating Pressure ... • Use an accurate pressure gauge connected upstream from the switch to measure the actual pressure. • Replace

6 … 6

REPLACEMENTPARTS

Replacementcover(screwsnotincluded) Screwforreplacementcover

PG11-1/2”NPTconduitadapter

120VACneonlight

24VAC/VDClight(orange)

DINconnector(femaleplug)

MaleplugforDINconnector

Mountingscrewkit

M20-1/2”NPTAdapter

Port3adapter

Adapterwith1/4”NPTthreadedcon-nectionandpressuretapforverticallymountingpressureswitchonaSV,DMV,orMBCflange.

228-732(forGAOswitches)and233-113(forGMHandGMLswitches)

237-675

220-566

244-156 for orange 248-240 for green

244-157

210-318

219-659 (forGAOswitches)and227-644 (forGMHandGMLswitches)

226-188(includeso-ringandtwoM4threadformingscrews)

240-671

214-975(forMBC1000-4000seriesandDMV701-703series)

225-047

A2mountingoptionsFRIgaspressureregulator

Pressuretap

1 2 3

M o u n t i n gpossible?yesyesyes

MOUNTINGTOSAFTYVALVESorFRIREGULATORA2mountingoptionsDMV525,5040-5125/11dualmodularvalve

Pressuretap

1 2 3 4 5 6

Mountingpossible?yesyesyesyesnono