Kurzschluß- und Nennstromberechnung für HS-Anlagen
Grid
Sk" [MVA] 300 0.01 Project Test
Un [kV] 11 0 Date 1993-09-30
x [%/MVA] 0.3667 11000 Rev.: 1
Transf/Motor
Sn [MVA] 2 0.01 Summe 30 0.01 0.01
uk od. xd" [%] 6.25 0 14 14
Ia/In 5
x [%/MVA] 3.125 0 0.6667 1400 1400
Cable
Rk [Ohm/km) 0 0 0 0
xk [Ohm/km] 0 0 0 0
Lk [m] 0 0 0 0
x [%/MVA] 0 0 0 0
CB
I [A] 2782 14
Incoming Sum Sum Incomings
x [%/MVA] 3.4917 11000 0.6667 1400 1400
SS Sk" [MVA] 32 0 165 0 0 196.67 Sk" [MVA]
Un[kV] Ik" [kA] 44 0 230 0 0 274 Ik" [kA]
0.415
CB
I [A] 1 3478 6956
Cable
Rk [Ohm/km) 0.125 0 0
xk [Ohm/km] 0.085 0 0
Lk [m] 150 0 0
x [%/MVA] 13.166 0 0
Transf
Sn [MVA] 0.001 2.5 5
uk [%] 0 8 8
x [%/MVA] 0 3.2 1.6
Cable
Rk [Ohm/km) 0 0 0
xk [Ohm/km] 0 0 0
Lk [m] 0 0 0
x [%/MVA] 0 0 0
CB
I [A] 1 2092 875
Busbar
x [%/MVA] 13.166 3.2 1.6
Sk" [MVA] 8.3552 34.375 68.75
Ik" [kA] 12.06 28.763 12.028
SS Un[kV] 0.4 SS Un[kV] 0.69 SS Un[kV] 3.3
M G G
Remarks: Calculation acc.. VDE 0103 and ABB- Handbook (%/MVA-Methode)