BRIEF SCOPE OF WORK
The brief scope of work comprises of, but not limited to, the following:
a. Design, supply, installation and commissioning of Integrated Building Management system
comprising of the following:
i. Building Automation system forHVAC Lower Side (AHUs etc). Electrical System (HT/LT) including DG operation, Vertical Transportation
(Lift Management) system and Water Management System
ii. Integrated building management system including the IBMS software to integrate and monitor
the following services from a central location
Fire Detection & Alarm
Public Address
Access Control
Closed Circuit Surveillance & Digital Video Recording
Lighting ControlWater Management
Fire Fighting
Iii The following system specific to the requirement of the Data centre.:
Gas based Fire Suppression systems.
Water leak detection
Smoke Detection
Ultrasonic Pest Repellent system
-
8/12/2019 07 BMS CheckList
2/13
CHECK LIST FOR BMS
SUB-SECTION-1
INPUT AND OUTPUT SUMMARY FOR BAS.
S l.NO
DESCRIPTION FUNCTI ONS LOCATION
AI A O D
I
D
O
STA
TUS
ALA
RM
CON
TROL
CONTROL/
MONITORING
1 DDC TYPE - A (For chiller) -
Chillers: - AHUROO
M -1
AT
SEC
ON D
FLO
O R.
1
Chiller ON/OFF command. Command from
PC/DDC to the ch il le r
MCC panel.
2 Chiller ON/OFF status. From chiller panel
3 Chiller Auto / Manual status. signal from A/M switch.
4Chiller trip status. signal from potential
free contact.
5Motorized Vavle ON/OFF Command signal from potential
free contact.
6 Motorized Vavle ON/OFF Status
7Immersion type Temp sensor for In
and out
Signal from Immersion
type Temp sensor .
Primary Chilled Water Pumps-
8
Primary Chilled Water pumps ON /
OFF command.
Command from
PC/DDC to the primary
CHW Pumps panel.
9Primary Chilled Water pumps ON /
OFF Status.
Differential pressure
switch.
10Primary Chilled Water pumps Auto /
Manual status.
signal from A/M switch.
11Primary Chilled Water pumps trip
status.
signal from potential
free contact.
12Immersion type Flow switch signal For dry run
status
-
8/12/2019 07 BMS CheckList
3/13
13 Secondary Chilled Water Pumps-
14 Secondary CHW pumps ON / OFF
Command.
Command fromPC/DDC to theMCC panel.
15 Secondary CHW pumps ON / OFFstatus.
Differentialpressure switch.
16 Secondary CHW pumps VFD speed
Control.
Proportional
signal from
DDC to the VFD
17 Secondary CHW pumps VFD speed
feedback.
signal from VFD.
18 Secondary CHW pumps trip status. VFD trip status .
19 Secondary CHW pumps A/M status &
Bypass status.
signal from A/M
switch.
20 Immersion type Flow switch signal for DryRun status
21 Differential pressure Switch across the
supply & return headers.(4 nos Pr
Pump, 3 Nos Sec pump)
Signal from DP
switch for flow.
22 Differential pressure sensor across the
common supply & return headers.
Differential
pressure
sensor.23 CHW flow measurement Pulse O/P from
flow meter.
24 MCC power supply status. Command from
PC/DDC to the
MCC panel.
Total
2 TYPE - B ( For 1 NO AHU with VFD.) -
4Nos
1 AHU ON/OFF Command. 1 * At local control R E
F
D D
CLO
CA
TIO
N
DR
2AHU ON/OFF Status. 1 * At local control
panel
3 AHU Auto/Manual Status 1 * At Auto / Manualswitch
4 Filter status. 1 * DP switch
5RA Temparature status 1 * F r o m
Temparature
7 CHW 2-Way Valve Control. 1 2 Way Valve
-
8/12/2019 07 BMS CheckList
4/13
6 RA Rh status From Rh sensor AWI
NG.
with Actuator
8Fire trip status. From Fire Relay
9
Fire Damper On/Off Status At local control
panel
10VFD speed control. At VFD Panel
11VFD speed refference. At VFD Panel
12VFD trip status. At VFD Panel
13Duct static pressure sensor. Pressure sensor
14VFD Bypass status. At VFD Panel
Total
3 TYPE - C (3 Nos AHU's/CAHU with Starter
) - 2 Nos
1 AHU ON/OFF Command. At local control
panel
REF
DDC
LOCA
TION
DRA
W
ING.
2 AHU ON/OFF Status. At local control
panel
3 AHU Auto/Manual Status At Auto / Manual
switch
4 Filter status. DP switch
5 RA Temparature status F r o m
Temparature
6 RA Rh status From Rh sensor
6 CHW 2-Way Valve Control. 2 Way Valve with
Actuator
7 Fire trip status. From Fire Relay
8 Fire Damper On/Off Status At local control
panel
9 Duct static pressure sensor. Pressure sensor
Total
-
8/12/2019 07 BMS CheckList
5/13
4 TYPE -D(4 Nos CAHU's with Starter )- 1
No
1 AHU ON/OFF Command. At local control
panel
REF
DDC
LOCA
TIONDRA
W
ING.
2 AHU ON/OFF Status. At local control
panel3 AHU Auto/Manual Status At Auto / Manual
switch
4 Filter status. DP switch
5 RA Temparature status F r o m
Temparature
sensor
6 RA Rh status From Rh sensor
6 CHW 2-Way Valve Control. 2 Way Valve with
Actuator7 Fire trip status. From Fire Relay
8 Fire Damper On/Off Status At local control
panel
9 Duct static pressure sensor. Pressure sensor
Total
5 TYPE -E (22 Nos PAC )- 1 No
1 AHU ON/OFF Command. At local controlpanel
PACROO
M AT
1ST
Total
6 TYPE -F (7 Nos PAC )- 1 No
1 AHU ON/OFF Command. At local control
panel
PAC
ROO
M AT
1ST
Total
-
8/12/2019 07 BMS CheckList
6/13
SUB-SECTION2
I/O SUMMARY
SECTION I: I/O LIST FOR HT/LT ELECTRICAL MONITORING
S.No.
DESCRIPTION DI AI STATUS ALARM CONTROL
LINK LOCATION
SUBSTATIION FUNCTIONS Signalsareto beacquiredfromCircuitBreakers
&Relaysoverserialinterface.ElectricalcontractorshallmakeavailableCBs andrelays
withRS 485port andMODBUSRTUPROTOCOL
SUB-STATIONBLDG-HTROOM
1. 0 11KV SWITCHGEAR SIGNALS(HPCL HT PANEL SIDE)
1. 1 11 KV INCOMING VCB 630A350 MVA
ON/OFF/Auto trip - functions
I n c o m i n g H Tvoltage/current/frequency,power,M VA - Measurements
1.2 MICROPROCESSOR BASEDRELAYS - Trip circuit Un-Healthy
1.3 MANUAL OPERATIONSTATUS -
1.4 11 KV RECEIVING VCB 630A350 MVA
ON/OFF/trip - functions
I n c o m i n g H Tvoltage/current/frequency,power,M VA - Measurements
1.5 MANUAL OPERATIONSTATUSon/off
1.6 MICROPROCESSOR BASEDRELAYS - Trip circuit Un-Healthy
BATTERY CHARGER:
1.7 BATTERY CHARGER - Mainson/ DC supply on/fails
-
8/12/2019 07 BMS CheckList
7/13
1.8 BATTERY VOLTAGE -Measurement
S.No.
DESCRIPTION DI AI STATUS ALARM CONTROL
LINK LOCATION
MAIN POWER CONTROL
CENTER
Signals
areto beacquiredfromCircuitBreakers&Relaysoverserialinterface.Electrical
contractorshallmakeavailableCBs andrelayswithRS 485port andMODBUSRTUPROTOC
OL
SUB-
STATIONBLDG-MPCCROOM
2.0 433 V INCOMING FEEDERSFor TRANSFORMERS
2.1 INCOMING 433 V 3200 AMPSACBS
2.2 ON/OFF/Auto trip - functions
2.3 I n c o m i n g L Tvoltage/current/frequency,power,M VA - Measurements
2.4 MICROPROCESSOR BASEDRELAYS - Trip circuit Un-Healthy
2.5 MANUAL OPERATIONSTATUS
BUSCOUPLER: - 1 NO
2.6 BUS Coupler - On/off/trip
2.7 MANUAL OPERATION STATUS- On/off
DG INCOMER feeders: - 2 NOS
2.8 DG INCOMER - ACBS -On/off/trip
2.9 I n c o m i n g L Tvoltage/current/frequency, KW,kVA - Measurements
3.0 MICROPROCESSOR BASEDRELAYS - Trip circuit Un-Healthy
3.1 MANUAL OPERATIONSTATUS-
4.0 UPS MONITORING
-
8/12/2019 07 BMS CheckList
8/13
1.0 STATUS MONITORING,VOLTAGE, CURRENT, LOAD,BATTERY VOLTAGE ETC6 NOS 200 AND 2 NOS 100KVA UPS - Total around 80soft points
RS 485port andMODBUSR T UPROTOCOL to be
providedby UPSvendor
Groundfloor
U P S
room
S.No.
DESCRIPTION DI AI STATUS ALARM CONTROL
LINK LOCATION
2.0 KW. Voltage, Amps from eachfeeder through DATA Loadmanager meter - Total 28feeder each 5 soft points =140 soft points
* RS 485port andMODBUSR T UPROTOCO L tobeprovidedbyElectricalvendor
ATMETERLEVEL
SUB-STATIONBLDG-MPCC.Thewiringshall betakenoutandterminted at onecommonchamberbyelectricalvendor.
3.0 DG set - ON/Off status, KW,Amps, Voltage, Frequency
etc through PLC -Approximately - 50 soft point
RS 485port and
MODBUSR T UPROTOCO L tobeprovidedbyElectricalvendor INPLCPANEL
SUB-STATION
BLDG-MPCCROOM
Total
DI = DIGITAL INPUTS AI= ANALOG INPUTS
-
8/12/2019 07 BMS CheckList
9/13
SECTION-II
I/O LIST FOR /LT ELECTRICAL MONITERING
S.No.
DESCRIPTION DI AI STATUSALARM
CONTROL
LINK
4.00433V OUTGOING FEEDERS -On/off/Trip status
LIFT FEEDER- 2NOS
4.10 FIRE HYDRANT PANEL--1 ThorughDDCcontrollers.BMSvendorto providethecontrolleralong withwiring.
Electricalvendor toprovide thenecessaryPotentialfreecontact inthe eachbreakers.The wiringshall betaken out
andterminatedatonecommonchamberbyelectricalvendor
4.20CHILLER NO.1 ,2,3, AND STAND BYFEEDER
4.30 CHILLER PUMPS PANEL - 2 NOS
4.40 WORKSTATION UPS- 2NOS
4.50 APFC PANEL - 2 NOS
4.60 SPARES- 4 NOS
4.70 SUBSTATIION PANEL4.80 EMERGENCY LIGHTING FEEDER
4.90 AC PANELS- 5 NOS
5.00LIGHTING AND POWER FEEDER -2NOS
5.10 UPS FEEDERS- 2NOS
-
8/12/2019 07 BMS CheckList
10/13
SECTION-III
WATER MANAGEMENT SYSTEM I/O LIST
FUNCTIONS
S.No DESCRIPTION AI DO AO STATUS ALARM CONTROL CONTROL/MONITORING
LOCATION
THROUGHDDC.Local displayshall beprovidedindicating waterlevel andpumps status
UG SUMPAREAANDTERRACEOH TANK
1 Pump ON/OFF
2 P u m ptrip,ON/OFF status
3 Linear levels for allthe sumps and tanks
Total
-
8/12/2019 07 BMS CheckList
11/13
SECTION-IV
LIGHTING MANAGEMENT SYSTEM - I/O LIST
SrNo.
DESCRIPTION FUNCTION CONTROL /MONITORINGDI AI DO AO STATU
SALARM CONTROL LOCATI
ON
I LIGHTINGMANAGEMENTSYSTEM -Controller-1
1 External Street Lighting&
ON/OFFContactor
shall beprovided bytheElectricalvendor.ControllojngthroughDDCby BMSvendor
SUBSTATIO
FACADE LIGHTING SUB
Lighting MCCBON/OFF
SUBSTATION
Controller-2 - 6 sets
2 Incomer MCCB switchon/OFF at Ground floor,Second floor LSSB
At floor level,shall beprovided bytheElectricalvendor.Controllojngthrough DDCby BMSvendor
At floorlevel
3 Induvidual circuitON/OFF controlls -Each controller - 20circuits
TOTAL
-
8/12/2019 07 BMS CheckList
12/13
SECTION-V
FIRE FIGHTING PUMPS I/O LIST
FUNCTION
Sr.No DESCRIPTION DI DO AI AO STATUS ALARM CONTROL CONROL/MONITORING
A) HYDRANT andSPRINKLER PUMPS:
Statusmonitoringthrough DDC.Suitablepotential-freecontacts shall be
Made availableby the FireFightingcontractor
1 JOCKEYPUMP: -1 NOS
Pump Trip/ON/OFFStatus
2 HYDRANTPUMP:- 2NOS
Pump TripON/OFF Status
3 SPRINLERPUMPSTANDBYPUMP- 2 NOS
Pump Trip/ON/OFF Status
TOTAL
-
8/12/2019 07 BMS CheckList
13/13
SECTION-VI
I/O LIST FOR LIFTS
FUNCTION CONTROL
/MONITORING
LOCAT
ION
Sr.NO
DISCRIPTION SP DI AI DO AO STATUS
ALARM CONTROL
1 Monitor alarmbell status oflifts
FormonitoringthroughDDG.Potential freecontactsshall be
madeavailable byElevatorssupplier.
L i f tmachine room
2 M o n i t o rFireman'semergencyoperation
status3 Monitor
operation ofelevator in'Attendantmode'
4 Monitor liftu n d e rinspection/testdrive
5 Monitor lift
under fire drive6 Trip Alarm
7 ON/OFF Status
8 FLOOR LEVELStatus(eachlift 3 levels= 2nos x 3 levels)
Total