ctf878 startup guide
TRANSCRIPT
e imagination at work GE Sensing 1
CTF878 Flowmeter Startup Guide
e imagination at work GE Sensing 2
Principle of Operation
Flow
Channel 1Transmit
Channel 2Transmit
Channel 1Receive
Channel 2Receive
• Continuous wave (CW) acoustic signals are transmitted from the transmit transducers
• Flow eddies modulate the amplitude of each acoustic beam as they pass through
• Electronics console demodulates signals from both receive transducers similar to AM radio
• DSP cross-correlates similar patterns in each demodulated signal to calculate the delay – Tao between these patterns
• The distance between the transducer pairs or Tag Path is divided by Tao to obtain flow velocity
e imagination at work GE Sensing 3
Signal Processing
Carrier UpChannel 1
Carrier DownChannel 2
Modulation UpChannel 1
Modulation DownChannel 2
Tao
e imagination at work GE Sensing 4
Cross-Correlation
Noise
Signal
Cross-Correlation SNR = Signal AmplitudeNoise Amplitude
e imagination at work GE Sensing 5
Obstacles to Flow Measurement
e imagination at work GE Sensing 6
Signal Through Gas• Most of the energy remains in
the pipe wall due to the acoustic impedance (density • SOS) mismatch between the pipe and the gas. A gas with higher density (pressure) provides better Signal Strength
• Signal through gas is attenuated more with longer path length, which is compensated by lowering transducer frequency with a sacrifice in the magnitude of signal modulation
(Caution: Lower transducer frequency is for larger pipes only!)
e imagination at work GE Sensing 7
Short Circuit Noise•Pipe wall conducts acoustic
short circuit or SC through the circumference and heavy wall pipes have more SC due to more acoustic modes generated in the thick wall
•Acoustic signal is also conducted through the pipe wall between the transducers of each path causing cross talk
•Lower frequency transducers generate more SC which excludes their application for smaller pipes
•For these reasons, the dampening material is required for all applications
Gas “Signal”
Short Circuit “Noise”
e imagination at work GE Sensing 8
Liquid on the Pipe Wall• Liquid on the inside or outside surfaces of the pipe is a
major obstacle to CTF878– Amplitude of the acoustic SC signal traveling in the pipe
wall modulates in the presence of a liquid on the wall– SC modulation cannot be distinguished from modulation
caused by flow turbulence
• Dampening material installed outside of the clamping fixture reduces SC modulation due to rain on uninsulated pipes and SC reflected from any nearby circumferential welds
e imagination at work GE Sensing 9
Application VerificationGas type and minimum pressure:– Dry air, oxygen, nitrogen or argon at or above ambient pressure (1 bara, 14.5 psia)– Sweet natural gas at or above 2 bara, 30 psia– Other acoustically conductive gases with density of 0.074 lbs/ft3, 1.185 kg/m3
Transducer frequency:– 0.5 MHz for ANSI (DIN) 3 (75) to 16 (400) pipes – 0.2 MHz for ANSI (DIN) 16 (400) to 24 (600)
Pipes:– ANSI (DIN) 4 (100) to 24 (600)– Non-lined steel (double minimum pressure/density for Duplex), copper and most other
metals– HDPE (High Density Polyethylene), PVC, CPVC and most other non-lined plastic pipes
(fiberglass requires demo)
Velocity Limits:– Bi-directional flow– Between 3.5 ft/s (1.1 m/s) and 150 ft/s (46 m/s)
e imagination at work GE Sensing 10
Installation
e imagination at work GE Sensing 11
Pipe Geometry
20D 10D
Flow
Minimum Straight Run:– 10 to 20 (preferred) diameters upstream– 5 to 10 (preferred) diameters downstream– Minimum of 20 diameters between circumferential welds
P T
e imagination at work GE Sensing 12
Pipe SurveyThickness Variation– Measure the thickness at 5 points
along the axis of the pipe– Maximum variation should be
less than 0.01 in. (0.25 mm)
Pipe Cross-section– Measure the average OD– Measure the thickness at 8 points– Program the meter with the
average thickness value
Transducer Location– Nearest the horizontal plane– Location with the greatest
thickness difference of the opposing walls (W3 and W7 )
– Away from circumferential weld(s) or seam
1 2 3 4 5
W1
W2W8
W4
W3W7
W6
W5
e imagination at work GE Sensing 13
Pipe Preparation Fixture Location– Remove 30 inches (750 mm) of insulation if any– Remove any loose paint and/or rust– Do not alter the curvature of the pipe if using a grinder
Transducer Location– Mark two correctly spaced areas on either side of the
pipe, 4 inches (100 mm) long by 2 inches (50 mm) wide– Grind off paint if it is thick or uneven without altering
the pipe curvature– Polish with fine sand paper
e imagination at work GE Sensing 14
Dampening Installation Wrapping DMP-1 (Maximum Temperature 150 ºF, 65 ºC)– Warm up the DMP-1 if the pipe surface is below 45 ºF (7 ºC) – Apply the DMP-1 starting at the bottom– Align it parallel to the axis of the pipe– Pull DMP-1 while wrapping, taking care to minimize air pockets by
pressing it and sliding back and forth with the free hand
Removing DMP-1 from Transducer Locations– Temporarily install the clamping fixture with the yokes correctly
spaced– Install the transducers without any couplant and mark their locations– Remove the transducers and cut off the dampening material from
marked locations
e imagination at work GE Sensing 15
High Temp. Dampening Installation
Safety Equipment and Precautions– Wear high temperature gloves and goggles – Use hardhat to avoid head injuries and burns from overhead pipes– The area must have good ventilation because of fumes and
smoke during installation
Installing the Pipe Dampening Jacket (PDJ)– Orient the PDJ to allow clearance for transducers and junction
boxes– Remove the paper liner from the inside of the PDJ– Wrap the PDJ around the pipe with the fasteners close to the
bottom– Place a metal bucket and a drop cloth under the PDJ to collect the
hot fluid runoff
e imagination at work GE Sensing 16
Final Installation Clamping Fixture– Replace any plastic parts with metal versions for high temperature– Adjust the transducer yoke positions to correct spacing– Align fixture correctly during installation by maintaining equal distance
between pipe brackets on top and bottom and placing yokes over transducer openings
Transducers– Screw the transducers into the junction boxes and verify the
orientation – Apply a thin layer of couplant to the whole face of each transducer– CPL-01/CPL-04 for temporary normal/high temperature installations– CPL-16 for permanent normal and high temperature installations– Allow the CPL-16 to “skin” on the pipe for 15 minutes before fully
tightening the transducer hold down bolts and locking nuts
e imagination at work GE Sensing 17
System Wiring Wiring the Preamplifier(s)– Connect the preamplifier cable in the junction box to the
Channel 1 receive or upstream transducer of the upstream path– The Channel 1 Transmit cable from the flowmeter should be
connected to the downstream transducer of the upstream path– Repeat connections for the Channel 2 (downstream path)
transmit and receive cables
Wiring the Flowmeter– If used, wire the pressure and temperature transducers to the
Analog/RTD inputs– Hook up the Analog or Frequency output and Alarms, if required– Verify that the power source is not energized and connect the
power to the CTF878 flowmeter
e imagination at work GE Sensing 18
Wiring Diagram
Flow
P
T
Ch. 1 TX
Ch. 2 TXCh. 2 RX Ch. 1 RX
Preamplifiers (1080) installed on receiving transducersTransducer Spacing = X1 – X2
X1
X2
Tag Path
DigiFlow CTF878
g
e imagination at work GE Sensing 19
Flowmeter Programming
DigiFlow CTF878
g
e imagination at work GE Sensing 20
Pipe and Transducer Parameters• Transducer Selection
– Number 312/310 for 0.2/0.5 MHz up to 266°F (130 °C)– Number 318 for 0.2 MHz up to 350°F (176°C)– Number 307 for 0.5 MHz up to 450°F (232°C)– Wedge temperature is an average of ambient and gas temperatures
• Pipe Properties– Select the pipe material from the list– Program OD and wall thickness measured in “Pipe Survey”
• Gas Properties– Select the type of Fluid being measured– Use Sonicware™ or the NIST website for Kinematic Viscosity
• Transducer Spacing– Physical transducer spacing for each path must be the same as calculated by the
CTF878– Up to 0.25 inch (6.4 mm) difference from calculated spacing is allowed
• Tag Path– Tag Path or the distance between paths must be the same as calculated by the
CTF878– Based on pipe ID with minimum 5-inches (125 mm) and maximum 10-inches (250
mm)
e imagination at work GE Sensing 21
Standard/Normal Flow Parameters
• Enabling Analog/RTD Inputs– Enable Analog inputs in the “Analog I/O” menu
• Temperature Input– Program correct “Base” temperature (check with customer)– Measure the “Fixed” temperature as close as possible to the
measurement location and under the insulation, if used– Program “Active” temperature input with appropriate limits
for the probe
• Pressure Input– Program correct “Base” pressure (check with customer)– “Fixed” pressure must be obtained from a probe as close as
possible to the measurement location without pressure drops (elbows, tees, valves or reducers) in between
– Program “Active” pressure input with appropriate limits for the probe
e imagination at work GE Sensing 22
Error Limits• Diagnostic Parameters
– SNR Min. sets Low SNR Error (E8) trigger point, default is 10
– Carrier Limits set Carrier Under (E4) and Over (E5) trigger points, defaults are 75 mV and 1200 mV
– DMod Limits set Modulation Under (E6) and Over (E7) trigger points, defaults are 75 mV and 1500 mV
• Flow Parameters– Velocity Limits set Velocity Range Error (E9) trigger point
which should be programmed to application maximum and minimum
– Acceleration Limit sets Acceleration Error (E10) trigger point, decrease if flow will not change a lot and increase otherwise to improve response
e imagination at work GE Sensing 23
Signal Setup Parameters• Signal Menu
– Reverse Flow should be checked to reverse the flow reading – Zero Cutoff is the lowest measured velocity, lower values will be
displayed as zero– Velocity Averaging is the number of readings that are averaged
together, the greater the number, the slower the response– Errors Allowed sets the number of errors that is allowed before an error
message is displayed, the default is 2• AGC/MGC Menu
– Gain control should always be set to AGC or automatic, manual control or MGC is used for diagnosis of problems
– Carrier set point limits HFHI and HFLO for AGC should be set to 1000 mV and 200 mV
– Modulation or low frequency set point LFSP should be set to 590 mV• Cross-Correlation (CC) Averaging
– CCorr Average should be set to 75%, increase to improve SNR for low flow
• Low Pass (LP) Filter– Electrical (Elec.) System should be set to the frequency of the AC power
system
e imagination at work GE Sensing 24
Calibrating Analog I/O• Calibrate Analog Output(s) for Data or Input
Calibration– Connect DMM or Calibrator to the Output being calibrated– Select “Main Board (0)” or Slot # corresponding to the Analog
Output option card in the “Calibrate/Test” submenu from the “Service menu”
– Calibrate upper and lower limits then repeat for the other output(s)• Calibrate Analog Input(s)
– Connect a Calibrator or Analog Output A to Input (A)– Select the appropriate Slot number– Select the appropriate Analog Input in the “Calibrate/Test” submenu
from the “Service menu”– Calibrate upper and lower limits then repeat for the other input(s)
• Calibrate RTD Input(s)– Connect RTD Calibrator to the appropriate RTD Input on the Option
Card– Select the appropriate Slot # and Input in the “Calibrate/Test”
submenu– Calibrate upper and lower limits for each RTD Input used
e imagination at work GE Sensing 25
Operation Verification and Troubleshooting
e imagination at work GE Sensing 26
Signal Verification• Cross-Correlation SNR (CC SNR)
– CC SNR should be greater than 10– If not, the flow is too low
• Carrier Amplitude and Gain– Carrier Amplitude should be between 75 mV and 1200 mV– If Carrier Gain is close to –6 dB and Amplitude is high, the carrier may
be saturated – remove the preamplifiers and disable preamplifier power– If Carrier Amplitude is below 75 mV and Gain is 31 dB, the carrier is too
weak, add preamplifiers or use 0.2 MHz transducers and receiver card
• Modulation (Mod) Amplitude and Gain– Mod Amplitude should be between 75 mV and 1500 mV– If Mod Amplitude is below 75 mV and Gain is 31.5 dB, the Carrier is
weak– If Mod Amplitude is above 1500 mV and Gain is –16.5 dB, there is
inadequate straight run upstream or high liquid content in the gas
e imagination at work GE Sensing 27
Flow Measurement Verification
• Delay (Tau)– Tau should be stable and reasonable– Unstable Tao could be caused by low CC SNR
• Velocity/Volumetric Accuracy– Check the physical Tag Spacing and programmed setting
consistency– Check the Temperature and Pressure settings or probe parameters– Check whether there is enough straight run of pipe and no
disturbances upstream
• Sanity Check– Reverse the transducer cables between channels – Verify that Tau and velocity/volumetric are negative with the same
magnitude– The sum of Carrier and Demodulation gains for Channel 1 should be
equal to Channel 2, which indicates that the cross-talk is cancelled out
e imagination at work GE Sensing 28
Troubleshooting Flow ChartCARRIER UNDER (E4) CARRIER OVER (E5) MOD UNDER (E6) MOD OVER (E7)
XDCR SPACING?
COUPLANT?
GAS DENSITY LOW?
ADD PREAMPS
CHANGE TO 0.2 MHz
DAMPENING?
CHANGE TO 0.5 MHz
TAG PATH?
COUPLANT?
LOW VELOCITY?
CHANGE TO 0.5 MHz
REMOVE PREAMPS
CHANGE TO 0.2 MHz
LIQUID CONTENT?
LOW SNR (E8)
CARRIER GAIN < 0?
MOD GAIN < 0?
STRAIGHT RUN?
DAMPENING?
REMOVE PREAMPS
YesNo
YesNo
LOW VELOCITY?