NOTES :The remote start inputs of all DSE modules can be connected directly to the start/run output (terminal 3)of the 705 ATS controller, providing that the DC supplies are common to each module.
Wiring of remote start relay above is shown for connection to an engine controller requiring a battery negative signal
to start the set (such as DSE controllers). Modules with different input requirements may need alternative wiring details.If in doubt, consult the manufacturer of your engine control unit.
F 2A
SSOSSOSSO
SSO= Solid state outputs
= External 'Automotive' or 'Plug-in' type relays
31 2 4 5 7
2021
Auxiliary Outputs
+
8 9 1110 12
+
Battery
F2A
+ +
Start/Run output
N
L1
L2
L3
Alternator Output
Load
Mechanical Interlock
N
L1
L2
L3
Mains / Utility supply
14SSO
Close Gen output
+
G M
Electrical Interlock
13SSO
Close mains output
FUSES 2A
R e m o t e S t a r t
NormallyclosedNormally open
16 17 18 19
Close mains relayClose gen relay+
*NOTE
* Close mains relay must be normally closedto ensure fail safe operation
Remote start relay(see note)
N o t c o n n e c t e d
N o t c o n n e c t e d
N o t c o n n e c t e d
N o t c o n n e c t e d
C l o s e t o n e u t r a l p o s ' n
To 'remote start' input of engine controller (see note)
15
6
N o t c o n n e c t e d
DEEP SEA ELECTRONICS PLC
705 INSTALLATION INSTRUCTIONS
Configuration Mode is selected by operation of a small switch on the rear, left-hand edge of the PCB. This is partially hidden toprevent accidental operation. See figs 1 and 2
Fig. 2 Reverse of 705
Fig. 1
Normal
Configuration
Issue 2
Once Configuration Mode is selected, the ‘Auto’ LED will commence rapid flashing. When in
Configuration Mode all normal operation is suspended.
The ‘manual on load’ pushbutton can be used to select the LED ‘code’ that corresponds to therequired function. The 5 left hand LED’s will form the code.
The ‘Manual off load’ pushbutton will allow the user to change the function settings. The 3right-hand LED’s inform the user of the current setting for the chosen function.
When the required setting is displayed, press the ‘Auto’ button to save the selection. The process isrepeated for each function change.When configuration is complete, the Configuration Mode Selector Switch should be returned to the‘Normal’ position.
A key to all configuration options is provided overleaf on the Functions and configuration table.
TYPICAL CONNECTIONS
Terminals suitable for 0.6mm2-1.3mm2 (22-16 awg) wire.Tightening Torque = 0.8N-m (7lb-in).
Dimensions:165mm x 125mm x 29mm
(6.5” x 4.9” x 1.2”)
Panel cutout:149mm x 109mm
(5.9” x 4.3”)
Mounting Method:4 x 4.2mm diameter holes
suitable for M4 screws.
![Page 2: Dse 705 InstrEng](https://reader036.vdocuments.pub/reader036/viewer/2022082723/577c791c1a28abe054917c17/html5/thumbnails/2.jpg)
7/26/2019 Dse 705 InstrEng
http://slidepdf.com/reader/full/dse-705-instreng 2/2
Functions and configuration tableFunction Function code Value code Value (Default in bold Italics)
Start Delay ¡ ¡ ¡ l ¡ ¡ ¡ ¡ 0 Seconds
¡ ¡ l 5 Second s
¡ l ¡ 10 Seconds
¡ l l 15 Seconds
l ¡ ¡ 20 Seconds
l ¡ l 30 Secondsl l ¡ 60 Secondsl l l 180 Seconds
Mains (utility) return delay ¡ ¡ ¡ l l ¡ ¡ ¡ 0 Seconds
¡ ¡ l 5 Seconds
¡ l ¡ 10 Seconds
¡ l l 15 Seconds
l ¡ ¡ 20 Seconds
l ¡ l 30 Second s l l ¡ 60 Secondsl l l 180 Seconds
Warming ¡ ¡ l ¡ l ¡ ¡ ¡ 0 Second s
¡ ¡ l 5 Seconds
¡ l ¡ 10 Seconds
¡ l l 15 Seconds
l ¡ ¡ 20 Secondsl ¡ l 30 Secondsl l ¡ 60 Seconds
l l l 180 Seconds
Cooling ¡ ¡ l l ¡ ¡ ¡ ¡ 0 Second s
¡ ¡ l 5 Seconds
¡ l ¡ 10 Seconds
¡ l l 15 Seconds
l ¡ ¡ 20 Seconds
l ¡ l 30 Secondsl l ¡ 60 Seconds
l l l 180 Seconds
Remote start input type ¡ l l l ¡ ¡ ¡ ¡ Remote Start
¡ ¡ l Simulated mains
Remote start function ¡ l l l l ¡ ¡ ¡ Remote start is off load
(Not used when simulated mains is selected) ¡ ¡ l Remote start is on load
Auxiliary Output 1 Function l ¡ ¡ l ¡ ¡ ¡ ¡ Not Used
¡ ¡ l Mains (utility) Fail
¡ l ¡ Generator Available
¡ l l Generator on Load
l ¡ ¡ Mains On Loadl ¡ l System in Auto
l l ¡ Close to Neutral position
Auxiliary Output 2 Function l ¡ ¡ l l ¡ ¡ ¡ Not Used
¡ ¡ l Mains (uti l i ty ) Fail
¡ l ¡ Generator Available
¡ l l Generator on Loadl ¡ ¡ Mains On Loadl ¡ l System in Autol l ¡ Close to Neutral position
Mains (utility) Under Voltage l ¡ l ¡ ¡ ¡ ¡ ¡ 60V / 70V¡ ¡ l 70V / 80V
¡ l ¡ 80V / 90V
¡ l l 90V / 100V
l ¡ ¡ 120V / 140V
l ¡ l 140V / 160Vl l ¡ 160V / 180V
l l l 180V /200V
Deep Sea Electronics Plc.Highfield House, Hunmanby Industrial Estate,
North Yorkshire. YO14 0PH. ENGLANDTel +44 (0)1723 890099.Fax +44 (0)1723 893303.
Email - [email protected] - www.deepseaplc.com
Deep Sea Electronics inc.5301 E. State St. – Suite 202
Rockford, Illinois 61108. U.S.A.Phone +1 (815) 316-8706Fax +1 (815) 316-8708
Email – [email protected] – www.deepseausa.com