7/26/2019 Dse 705 InstrEng http://slidepdf.com/reader/full/dse-705-instreng 1/2 NOTES : The remote start inputs of all DSE modules can be connected directly to the start/run output (terminal 3) of the 705 ATS controller, providing that the DC supplies are common to each module. Wiring of remote start relay above is shown for connection to an engine controller requiring a battery negative signal to start the set (such as DSE controllers). Modules with different input requirements may need alternative wiring details. If in doubt, consult the manufacturer of your engine control unit. F 2A SSO SSO SSO SSO=Solidstate outputs  = External 'Automotive' or ' Plug-in' type relays 3 1 2 4 5 7 20 21  AuxiliaryOutputs + 89 11 10 12 + Battery F2A + + Start/Run output N L1 L2 L3  Alternator Output Load Mechanical Interlock N L1 L2 L3 Mains / Utility supply 14 SSO Close Gen output + G M Electrical Interlock 13 SSO Close mains output FUSES 2A    R   e   m   o    t   e    S    t   a   r    t Normallyclosed Normally open 16 17 18 19 Close mains relay Close gen relay + * NOTE * Close mains relay must be normally closed to ensure fail safe operation Remote start relay (see note)    N   o    t   c   o   n   n   e   c    t   e    d    N   o    t   c   o   n   n   e   c    t   e    d    N   o    t   c   o   n   n   e   c    t   e    d    N   o    t   c   o   n   n   e   c    t   e    d    C    l   o   s   e    t   o   n   e   u    t   r   a    l   p   o   s    '   n To 'remote start' input of engine controller (see note) 15 6    N   o    t   c   o   n   n   e   c    t   e    d DEEP SEA ELECTRONICS PLC 705 INSTALLATION INSTRUCTIONS Configuration Mode is selected by operation of a small switch on the rear, left-hand edge of the PCB. This is partially hidden to prevent accidental operation. See figs 1 and 2 Fig. 2 Reverse of 705 Fig. 1 Normal Configuration Issue 2 Once Configuration Mode is selected, the ‘Auto’ LED will commence rapid flashing. When in Configuration Mode all normal operation is suspended. The ‘manual on load’ pushbutton can be used to select the LED ‘code’ that corresponds to the required function. The 5 left hand LED’s will form the code. The ‘Manual off load’ pushbutton will allow the user to change the function settings. The 3 right-hand LED’s inform the user of the current setting for the chosen function. When the required setting is displayed, press the ‘Auto’ button to save the selection. The process is repeated for each function change. When configuration is complete, the Configuration Mode Selector Switch should be returned to the ‘Normal’ position.   A key to all configuration options is provided overleaf on the Functions and configuration table. TYPICAL CONNECTIONS Terminals suitable for 0.6mm 2 -1.3mm 2  (22-16 awg) wire. Tightening Torque = 0.8N-m (7lb-in). Dimensions: 165mm x 125mm x 29mm (6.5” x 4.9” x 1.2”) Panel cutout: 149mm x 109mm (5.9” x 4.3”) Mounting Method: 4 x 4.2mm diameter holes suitable for M4 screws.

Upload: asad-iqbal

Post on 01-Mar-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Dse 705 InstrEng

7/26/2019 Dse 705 InstrEng

http://slidepdf.com/reader/full/dse-705-instreng 1/2

NOTES :The remote start inputs of all DSE modules can be connected directly to the start/run output (terminal 3)of the 705 ATS controller, providing that the DC supplies are common to each module.

Wiring of remote start relay above is shown for connection to an engine controller requiring a battery negative signal

to start the set (such as DSE controllers). Modules with different input requirements may need alternative wiring details.If in doubt, consult the manufacturer of your engine control unit.

F 2A

SSOSSOSSO

SSO= Solid state outputs

 = External 'Automotive' or 'Plug-in' type relays

31 2 4 5 7

2021

 Auxiliary Outputs

+

8 9 1110 12

+

Battery

F2A

+ +

Start/Run output

N

L1

L2

L3

 Alternator Output

Load

Mechanical Interlock

N

L1

L2

L3

Mains / Utility supply

14SSO

Close Gen output

+

G M

Electrical Interlock

13SSO

Close mains output

FUSES 2A

   R  e  m  o   t  e   S   t  a  r   t

NormallyclosedNormally open

16 17 18 19

Close mains relayClose gen relay+

*NOTE

* Close mains relay must be normally closedto ensure fail safe operation

Remote start relay(see note)

   N  o   t  c  o  n  n  e  c   t  e   d

   N  o   t  c  o  n  n  e  c   t  e   d

   N  o   t  c  o  n  n  e  c   t  e   d

   N  o   t  c  o  n  n  e  c   t  e   d

   C   l  o  s  e   t  o  n  e  u   t  r  a   l  p  o  s   '  n

To 'remote start' input of engine controller (see note)

15

6

   N  o   t  c  o  n  n  e  c   t  e   d

DEEP SEA ELECTRONICS PLC

705 INSTALLATION INSTRUCTIONS

Configuration Mode is selected by operation of a small switch on the rear, left-hand edge of the PCB. This is partially hidden toprevent accidental operation. See figs 1 and 2 

Fig. 2 Reverse of 705 

Fig. 1

Normal

Configuration

Issue 2

Once Configuration Mode is selected, the ‘Auto’ LED will commence rapid flashing. When in

Configuration Mode all normal operation is suspended.

The ‘manual on load’ pushbutton can be used to select the LED ‘code’ that corresponds to therequired function. The 5 left hand LED’s will form the code.

The ‘Manual off load’ pushbutton will allow the user to change the function settings. The 3right-hand LED’s inform the user of the current setting for the chosen function.

When the required setting is displayed, press the ‘Auto’ button to save the selection. The process isrepeated for each function change.When configuration is complete, the Configuration Mode Selector Switch should be returned to the‘Normal’ position.

  A key to all configuration options is provided overleaf on the Functions and configuration table.

TYPICAL CONNECTIONS

Terminals suitable for 0.6mm2-1.3mm2 (22-16 awg) wire.Tightening Torque = 0.8N-m (7lb-in).

Dimensions:165mm x 125mm x 29mm

(6.5” x 4.9” x 1.2”)

Panel cutout:149mm x 109mm

(5.9” x 4.3”)

Mounting Method:4 x 4.2mm diameter holes

suitable for M4 screws.

Page 2: Dse 705 InstrEng

7/26/2019 Dse 705 InstrEng

http://slidepdf.com/reader/full/dse-705-instreng 2/2

Functions and configuration tableFunction Function code Value code Value (Default in bold Italics)

Start Delay   ¡ ¡ ¡   l   ¡ ¡ ¡ ¡ 0 Seconds

¡ ¡   l 5 Second s 

¡   l   ¡ 10 Seconds

¡   l l 15 Seconds

l   ¡ ¡ 20 Seconds

l   ¡   l 30 Secondsl l   ¡ 60 Secondsl l l 180 Seconds

Mains (utility) return delay   ¡ ¡ ¡   l l   ¡ ¡ ¡ 0 Seconds

¡ ¡   l 5 Seconds

¡   l   ¡ 10 Seconds

¡   l l 15 Seconds

l   ¡ ¡ 20 Seconds

l   ¡   l 30 Second s l l   ¡ 60 Secondsl l l 180 Seconds

Warming   ¡ ¡   l   ¡   l   ¡ ¡ ¡ 0 Second s 

¡ ¡   l 5 Seconds

¡   l   ¡ 10 Seconds

¡   l l 15 Seconds

l   ¡ ¡ 20 Secondsl   ¡   l 30 Secondsl l   ¡ 60 Seconds

l l l 180 Seconds

Cooling   ¡ ¡   l l   ¡ ¡ ¡ ¡ 0 Second s 

¡ ¡   l 5 Seconds

¡   l   ¡ 10 Seconds

¡   l l 15 Seconds

l   ¡ ¡ 20 Seconds

l   ¡   l 30 Secondsl l   ¡ 60 Seconds

l l l 180 Seconds

Remote start input type   ¡   l l l   ¡ ¡ ¡ ¡ Remote Start 

¡ ¡   l Simulated mains

Remote start function   ¡   l l l l   ¡ ¡ ¡ Remote start is off load

(Not used when simulated mains is selected)   ¡ ¡   l Remote start is on load 

 Auxiliary Output 1 Function   l   ¡ ¡   l   ¡ ¡ ¡ ¡ Not Used

¡ ¡   l Mains (utility) Fail

¡   l   ¡ Generator Available

¡   l l Generator on Load

l   ¡ ¡ Mains On Loadl   ¡   l System in Auto 

l l   ¡ Close to Neutral position

 Auxiliary Output 2 Function   l   ¡ ¡   l l   ¡ ¡ ¡ Not Used

¡ ¡   l Mains (uti l i ty ) Fail 

¡   l   ¡ Generator Available

¡   l l Generator on Loadl   ¡ ¡ Mains On Loadl   ¡   l System in Autol l   ¡ Close to Neutral position

Mains (utility) Under Voltage   l   ¡   l   ¡ ¡ ¡ ¡ ¡ 60V / 70V¡ ¡   l 70V / 80V

¡   l   ¡ 80V / 90V

¡   l l 90V / 100V

l   ¡ ¡ 120V / 140V

l   ¡   l 140V / 160Vl l   ¡ 160V / 180V

l l l 180V /200V 

Deep Sea Electronics Plc.Highfield House, Hunmanby Industrial Estate,

North Yorkshire. YO14 0PH. ENGLANDTel +44 (0)1723 890099.Fax +44 (0)1723 893303.

Email - [email protected] - www.deepseaplc.com

Deep Sea Electronics inc.5301 E. State St. – Suite 202

Rockford, Illinois 61108. U.S.A.Phone +1 (815) 316-8706Fax +1 (815) 316-8708

Email – [email protected] – www.deepseausa.com