    Spring 2002 ELCT 553 Synchronous generator:

    Operation

    1

    Synchronous Generators:Operation

    We consider:isolated generator

    generator connected in parallelwith a large system

    two generators connected inparallel

  • 7/29/2019 -Syngenoperatn

    2/16

    Spring 2002 ELCT 553 Synchronous generator:

    Operation

    2

    Isolated generator

    Control prime mover throttle

    to control speedspeed governor measures

    speed and uses a control loopto regulate it to generate 60 Hz(for example)

    average load power met (up tothe system limits)

  • 7/29/2019 -Syngenoperatn

    3/16

    Spring 2002 ELCT 553 Synchronous generator:

    Operation

    3

    Control exciter to controlterminal voltage

    voltage regulator measuresarmature voltage and uses a

    control loop to regulate it togenerate at rated voltage

    the reactive power needs of theload are met (up to systemlimits)

  • 7/29/2019 -Syngenoperatn

    4/16

    Spring 2002 ELCT 553 Synchronous generator:

    Operation

    4

    VAjXS IA Load

    EA

    IA

    VA

    EA

    jXSIA

  • 7/29/2019 -Syngenoperatn

    5/16

    Spring 2002 ELCT 553 Synchronous generator:

    Operation

    5

    EA

    IA

    XSIA

    VAdq g

    EAsin(d)=XSIAcos(q)

    q

    EAcos(d)-VA=XSIAsin(q)

    S

    AAA

    S

    AA

    X

    )V-)cos((E3VAA

    X

    )sin(E3V

    AA

    )sin(IV3Q

    )cos(I3VP

    d

    d

    =q=

    =q=

  • 7/29/2019 -Syngenoperatn

    6/16

    Spring 2002 ELCT 553 Synchronous generator:

    Operation

    6

    Since the speed and |VA| areregulated:

    Load average power (P) increasescause increased values ofd(caused by increased powerinput)

    Load reactive power (Q) increases

    cause |EA| to increase (byincreased field current)

  • 7/29/2019 -Syngenoperatn

    7/16

    Spring 2002 ELCT 553 Synchronous generator:

    Operation

    7

    EA

    IA

    XSIA

    VA

    d

    q

    g

    Increase P at constant Q

  • 7/29/2019 -Syngenoperatn

    8/16

    Spring 2002 ELCT 553 Synchronous generator:

    Operation

    8

    EA

    IA

    XSIA

    VA

    dq

    g

    Increase Q at constant P

  • 7/29/2019 -Syngenoperatn

    9/16

    Spring 2002 ELCT 553 Synchronous generator:

    Operation

    9

    EA

    IA

    XSIA

    VAdq g

    Increase |S| at constant pf

  • 7/29/2019 -Syngenoperatn

    10/16

    Spring 2002 ELCT 553 Synchronous generator:

    Operation

    10

    Generator in parallel with alarge system

    Infinite bus = generator withinfinite inertia and zero internal

    reactance = ideal ac voltagesource

    approximate representation of alarge power system

  • 7/29/2019 -Syngenoperatn

    11/16

    Spring 2002 ELCT 553 Synchronous generator:

    Operation

    11

    Governor characteristicf

    [Hz]

    fnl

    sp=-DP/Df

    P

    [kW]

  • 7/29/2019 -Syngenoperatn

    12/16

    Spring 2002 ELCT 553 Synchronous generator:

    Operation

    12

    genbusf[Hz]

    load

    fnl

    PB [kW] PB1 PG1 PG [kW]Pload

  • 7/29/2019 -Syngenoperatn

    13/16

    Spring 2002 ELCT 553 Synchronous generator:

    Operation

    13

    f

    [Hz]

    fnl

    PG2PB2

    Pload

    PG1

    Raise

    Pload

    PB1PB [kW] PG [kW]

  • 7/29/2019 -Syngenoperatn

    14/16

    Spring 2002 ELCT 553 Synchronous generator:

    Operation

    14

    Two generators in parallel

    f [Hz]

    f

    P2

    Pload

    P1P1 [kW] P2 [kW]

  • 7/29/2019 -Syngenoperatn

    15/16

    Spring 2002 ELCT 553 Synchronous generator:

    Operation

    15

    Same load, raise unit 2, f increases,

    load shifts from 1 to 2

    f [Hz]

    f

    P2

    Raise

    Pload

    P1P1 [kW] P2 [kW]

  • 7/29/2019 -Syngenoperatn

    16/16

    Spring 2002 ELCT 553 Synchronous generator:

    Operation

    16

    Excitation system

    characteristicVT [kV]

    Vnl

    sq=-DQ/DV

    Q

    [kVAr]