amz011

Upload: fahad-khan

Post on 14-Apr-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/30/2019 AMZ011

    1/9

    Battery Problem Feedback Information

    Battery Backup Problem1 Provider Information

    Raised by (Engineer name)FAHAD YOUSAF

    KHANTelephone/Mobile/Fax

    03444459706

    Problem arisen Date 16-7-13Problem reporting

    Date

    17-7-13

    2 Basic Information

    Problem description Battery banks cells found weak

    Problem arisen Country/City Muzafarabad CITY

    Problem battery brand and model Shoto 2V-600Ah

    Date of battery installation

    With generator or not DG

    PAC

    Battery check and accept datePAC

    Quantity of faulty batteries 3 CELLS FOUND ABNORMAL

    3 Background Information

    Problem Arisen BackgroundProject name TP- GLO project

    Operator/Problem arisen city Telenor

    Site name/number ANMZ011

    Power supply system information

    Version, type, batteries quantityZTE

    Site installation date and Runtime N/A

    Peripheral system

  • 7/30/2019 AMZ011

    2/9

    Mains Voltages

    P1-P2 436

    P2-P3 432

    P3-P1 437

    P1-N 248

    P2-N 249

    P3-N 252

    N-G 0.0V

    Daily Power Outage 5 HR

    Daily commercial

    power availability

    16 Hr

    Controller Power

    logs as attachment

    With generator or not

    If has generator, collect the brand, quantity, power, failure

    or not ,ATS failure or not information

    WITH DG

    DG set Brand: N/A

    DG Set Capacity: N/A

    DG Run Time Daily: N/A

    Site Load Information

    Load On P1:5

    Load On P2:4

    Load on P3:3.5

    4 Inquiry of Battery Backup Problem

    Available backup time of batteryh75MINUTES

    Continuous charging time before dischargingh 3HR

    Normal commercial Power availability on site

    per day.

    every day

  • 7/30/2019 AMZ011

    3/9

    5 Spot information feedback

    4.1 Site information feedback

    Feedbac

    k content

    Requisite

    information

    Site ID AMZ011

    Site

    appearance

    Please

    provide the

    whole picture

    of the

    problem site

  • 7/30/2019 AMZ011

    4/9

    Cabinet

    temperatur

    e controller

    informatio

    n

    Please

    provide theCabinet

    temperature

    controller and

    monitor

    systems of

    the problem

    battery site

    Power

    system

    appearance

    Please

    provide the

    whole power

    system

    pictures of

    the problem

    battery site

    PICTURE N/A

  • 7/30/2019 AMZ011

    5/9

    NBBattery

    group

    Please

    provide the

    whole

    pictures of

    group

    problem

    battery

    4.2 Battery information feedback

    Feedback

    content

    Requisite

    information

  • 7/30/2019 AMZ011

    6/9

    Battery

    coding

    Please provide the

    manufacture label of the

    problem battery

    4.3 Battery temperature feedback

    Feedback

    content

    Requisite

    informationGLO DISPLAY FAULTY

    Site cabinet

    temperature

    Please provide the

    indoor temperature

    show

    4.4 Power supply setting feedback

    Feedback

    content

    Requisite

    information

    Power

    system

    model

    Please provide

    the power

    system model

    N/A

    Batterymanaging

    1 Pleaseprovide

  • 7/30/2019 AMZ011

    7/9

    and

    operating

    parameter

    the

    battery

    operating

    parameterof

    PMU(po

    wer

    supply

    unit)

    2 Please

    provide the

    parameter

    below:

    Battery

    capacity set

    value

    Battery bank

    set value

    Set value of

    float-charging

    voltage

    Set value ofboost-charging

    voltage

    Set value of

    charging

    limited current

    Set value of

    bypass

    Set value of

    LLVD(load

    low voltage

    discharge)

    voltage and

    BLVD(battery

    low voltage

    discharge)

    voltage

    N/A

    N/A

    N/A

    47.5

    45.5

  • 7/30/2019 AMZ011

    8/9

    Battery

    managing

    alarm and

    protection

    parameter

    1 Please

    provide the

    batterymanaging

    alarm

    parameter of

    PMU(powe

    r supply unit)

    2 Please

    provide at

    least the

    parameter

    below:

    High

    temperature

    protection

    value of

    battery

    High

    temperature

    alarm value ofbattery

    Over voltage

    alarm value of

    battery

    Over voltage

    protection

    value of

    battery

    4.5 Battery value on the operating

    Feedback

    content

    Requisite

    information

    Voltage of

    battery

    group

    Please provide

    the total voltage

    of battery group

    56.22 V WITHOUT LOAD/ 47.6 WITH LOAD

    Operating

    current

    Charging current

    before battery

    test.

    NOT AVAILABLE

  • 7/30/2019 AMZ011

    9/9

    a) Battery check value on the operating

    WITHOUT LOAD WHILE CHARGIG

    TimeCurrent

    ( A )

    Total voltage

    (V)

    BANKI (V)

    # 1 # 2 # 3 # 4 # 5 # 6 # 7 # 8

    1:00 23.7 IN

    RECTIFIER

    GLO51.5/RECTIFIER

    53.50

    2.44 2.35 2.43 2.15 2.43 2.43 2.44 1.97

    # 9 # 10 # 11 # 12 # 13 # 14 # 15 # 16

    2.44 2.18 2.43 2.44 2.44 2.44 2.43 2.44

    # 17 # 18 # 19 # 20 # 21 # 22 # 23 # 24

    2.44 2.42 2.41 2.17 2.43 2.17 2.17 2.17

    TimeCurrent

    ( A )

    Totalvoltage

    (V)

    BANK

    I (V)

    # 1 # 2 # 3 # 4 # 5 # 6 # 7 # 8

    03:00 4.4 47.10 2.07 2.03 2.04 1.28 2.06 2.05 2.10 0.89

    # 9 # 10 # 11 # 12 # 13 # 14 # 15 # 16

    2.00 1.06 2.05 2.06 2.06 2.06 2.06 2.08

    # 17 # 18 # 19 # 20 # 21 # 22 # 23 # 24

    2.08 2.08 2.08 2.07 2.09 2.10 2.10 2.10