1 3220 Multi Hazard Conventional Suppression Control System P/N 30-32200X-X0X 30-3220.0 Effective: December 2001 FEATURES Microprocessor based Programmable UL & ULC Listed, FM Approved CSFM & MEA Approvals pending Listed for FM-200, FE13 and HALON Clean Agent Suppression Systems. Also for Sprinkler Supervisory, Deluge and Preaction Systems Remote Hazard Control Remote Display Units for Local or Global Repeat Annunciation Completely and easily field programmable 80 character alphanumeric LCD Display 270 event history buffer DESCRIPTION The Fenwal ® 3220 is a microprocessor based program- mable Suppression Control System designed for operation with Conventional Fenwal Ionization and Photoelectric Smoke Detectors. In its simplest configuration, the Fenwal ® 3220 Main Control Panel (MCP) is a single hazard Control Panel that can be field-expanded to be a large 8 hazard Control System with multiple Remote Display Units. Sys- tem expansion is achieved by adding up to 7 Remote Haz- ard Units (1 RHU per added Hazard) and up to 16 Remote Display Units (RDU). The MCP communicates with the RHUs and RDUs on a dual path, Style 7 RS-485 network, monitors their status and displays system wide messages. SYSTEM COMPONENTS MAIN CONTROL PANEL (MCP) MCP Power Supply: The MCP operates on 120/240 Vac 50/60 Hz Power Sup- ply. The Power Supply Unit is rated 4 Amps at 24 Vdc and is provided a Battery Charger to charge a 24 Vdc backup Bat- tery. The Battery may be sized for 24 hour Standby with 5 minutes Alarm or for 90 hour Standby with 10 minutes Alarm depending on the Suppression System. The Power Supply causes an immediate changeover to battery in case of loss of AC input or drop in input voltage. MCP Display Panel: The MCP Display Panel is provided an LCD Display, five status LEDs and a local buzzer It is also provided four Sys- tem Control Buttons and four Menu Control Buttons (see Figure 1). MCP Hazard Block: The MCP controls one Hazard Block and is provided the following Input Circuits: 2 Style B or Style D Initiating Circuits, each of which can support 40 Fenwal Smoke Detectors 1 Style B Manual Release Circuit for N.O. devices 1 Style B Abort Circuit for N.O. devices 1 Style B Supervisory Circuit for N.O. devices 1 Style B or Style D Waterflow Circuit for N.O. devices. The MCP is provided the following Output Circuits: 2 Style Y or Style Z Indicating Appliance Circuits rated 2.5 Amps total at 24 Vdc for polarized A-V signals. 1 Style Y Agent Release Circuit rated 3.4 Amps max at 24 Vdc. The circuit can be configured for Fenwal Initia- tors or Control Head Solenoids for Clean Agent Sys- tems or for FM Group A, B, D, E or G Solenoids for Deluge and Pre-Action Systems. The MCP also provides the following Relay Outputs: 1 Form C System Alarm Relay 1 Form C System Trouble Relay 1 Form C Programmable Relay 5 Form C Programmable Relays (on socket mounted Optional Relay Board) Figure 1. MCP Display Panel CONTROL SUPERVISORY TM SIGNAL TROUBLE SCROLL SCROLL SUP/TBL ALARM RESET SILENCE CONTROLS ALARM POWER ON PANEL MAIN SYSTEM CONTROLS MENU CANCEL ACCEPT SIGNAL SILENCED MCP V1.0 SYSTEM STATUS NORMAL 12:00 4/25/01 ALM00 SUP0 TBL00

Upload: lydat

Post on 09-May-2018

285 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: Conventional Suppression Control System P/N 30 ... - … 3220.pdf · Conventional Suppression Control System P/N 30-32200X ... • Listed for FM-200, ... can support 40 Fenwal Smoke

1

3220 Multi HazardConventional Suppression Control SystemP/N 30-32200X-X0X30-3220.0

Effective: December 2001

FEATURES• Microprocessor based Programmable• UL & ULC Listed, FM Approved• CSFM & MEA Approvals pending• Listed for FM-200, FE13 and HALON Clean Agent

Suppression Systems. Also for SprinklerSupervisory, Deluge and Preaction Systems

• Remote Hazard Control• Remote Display Units for Local or Global Repeat

Annunciation• Completely and easily field programmable• 80 character alphanumeric LCD Display• 270 event history bufferDESCRIPTIONThe Fenwal® 3220 is a microprocessor based program-mable Suppression Control System designed for operationwith Conventional Fenwal Ionization and PhotoelectricSmoke Detectors. In its simplest configuration, the Fenwal®3220 Main Control Panel (MCP) is a single hazard ControlPanel that can be field-expanded to be a large 8 hazardControl System with multiple Remote Display Units. Sys-tem expansion is achieved by adding up to 7 Remote Haz-ard Units (1 RHU per added Hazard) and up to 16 RemoteDisplay Units (RDU). The MCP communicates with theRHUs and RDUs on a dual path, Style 7 RS-485 network,monitors their status and displays system wide messages.

SYSTEM COMPONENTSMAIN CONTROL PANEL (MCP)MCP Power Supply:The MCP operates on 120/240 Vac 50/60 Hz Power Sup-ply. The Power Supply Unit is rated 4 Amps at 24 Vdc and isprovided a Battery Charger to charge a 24 Vdc backup Bat-tery. The Battery may be sized for 24 hour Standby with 5minutes Alarm or for 90 hour Standby with 10 minutes Alarmdepending on the Suppression System. The Power Supplycauses an immediate changeover to battery in case of lossof AC input or drop in input voltage.

MCP Display Panel:The MCP Display Panel is provided an LCD Display, fivestatus LEDs and a local buzzer It is also provided four Sys-tem Control Buttons and four Menu Control Buttons (seeFigure 1).

MCP Hazard Block:The MCP controls one Hazard Block and is provided thefollowing Input Circuits:• 2 Style B or Style D Initiating Circuits, each of which

can support 40 Fenwal Smoke Detectors• 1 Style B Manual Release Circuit for N.O. devices

• 1 Style B Abort Circuit for N.O. devices• 1 Style B Supervisory Circuit for N.O. devices• 1 Style B or Style D Waterflow Circuit for N.O. devices.The MCP is provided the following Output Circuits:• 2 Style Y or Style Z Indicating Appliance Circuits rated

2.5 Amps total at 24 Vdc for polarized A-V signals.• 1 Style Y Agent Release Circuit rated 3.4 Amps max at

24 Vdc. The circuit can be configured for Fenwal Initia-tors or Control Head Solenoids for Clean Agent Sys-tems or for FM Group A, B, D, E or G Solenoids forDeluge and Pre-Action Systems.

The MCP also provides the following Relay Outputs:• 1 Form C System Alarm Relay• 1 Form C System Trouble Relay• 1 Form C Programmable Relay• 5 Form C Programmable Relays (on socket mounted

Optional Relay Board)

Figure 1. MCP Display Panel

CONTROL

SUPERVISORYR

TM

SIGNALTROUBLESCROLL

SCROLL

SUP/TBL

ALARM

RESET

SILENCE

CONTROLS

ALARMPOWER ONPANEL

MAIN

SYSTEM

CONTROLSMENU

CANCEL ACCEPT

SIGNAL

SILENCED

MCP V1.0SYSTEM STATUS NORMAL

12:00 4/25/01ALM00 SUP0 TBL00

Page 2: Conventional Suppression Control System P/N 30 ... - … 3220.pdf · Conventional Suppression Control System P/N 30-32200X ... • Listed for FM-200, ... can support 40 Fenwal Smoke

2

MCP Programming:All programming is done via the MCP keypad. When theSystem is initialized, the MCP downloads the Operating Con-figuration to the RHUs and RDUs.

MCP Enclosure:The MCP enclosure is rated NEMA 1 for indoor use. It isconstructed of 18 gauge steel, painted Fenwal beige andkept closed by a steel door with a key-lock. All operator in-terface switches and indicators are located behind the lockedcover. The enclosure is large enough to house two 12 Ah 12Vdc batteries for backup supply. Battery Enclosures areavailable for larger capacity batteries. Optional dead-frontenclosures are also available for use in Canada.

12 Ah 12 Vdc

Battery

J4

J5

TB6

TB7

TB4

TB1 TB2 P1&P2 TB3 TB5

J1

W200

W104 W101

W109

W108

ISP RES

SW90

CPU RES

SW1

WATERFLO

W ++

SUP'V

+

ABORT

+

Man

Rel +

DETECTOR

2 + +

DETECTOR

1 ++R-

24V DC

OUT +R+

24V

IN +

AC MAINS

INPUTL ENN L

NO

C

NC

A

M

L

NO

C

NC

T

L

B

NO

C

NC

V

R

F

+

SOUNDER

1

+

STOP V

++

SOUNDER

2

+ +

RELEASE

+A

CHANNEL

1

BAB A

CHANNEL

2

BAB

BATTERY

+

INTERNALSOUNDER

LCD

CONTRAST

VR1

- + - +

12 Ah 12 Vdc

Battery

MENU

CONTROLS

CANCEL ACCEPT

SILENCE

RESET

MAIN

CONTROL

PANEL

SUPERVISORY TROUBLE SILENCED

POWERON

ALARM

ALARM

SCROLL

TROUBLESCROLL

SYSTEMCONTROLSTM

MCP V 1.0SYSTEM STATUS NORMAL

12:00

01-30-01

Figure 3. Internal View

SYSTEM COMPONENTSREMOTE HAZARD UNIT (RHU)RHU Power Supply:The RHU Power Supply Unit is exactly the same as that ofthe MCP.

RHU Display Panel:The optional RHU Display can operate either in local orglobal mode. It is provided the same features as the MCPwith the exception of the Menu Controls (see Figure 4).

SILENCE

UNIT

SUPERVISORYR

SIGNALTROUBLE

ALARMPOWER ON

SCROLLSUP/TBL

REMOTEHAZARD

TM

SYSTEMCONTROLS

SCROLLALARM

RESET

SIGNAL

SILENCED

RHU # 1 V 1.0

LOCAL STATUS NORMAL

12:00 4-25-01

ALM00 SUP0 TBL00

Figure 4. Remote Hazard Unit Display Panel

RHU Hazard Block:Each RHU also controls one Hazard Block and is providedthe same Input and Output Circuits as the MCP with theexception of the three System Relays. The Optional RelayBoard (ORB) can also be mounted to the RHU.

RHU # 1w/ Display

RDU # 1 for MCP

RDU # 2 for RHU # 1

Main Control Panel

RHU # 2w/o Display

Two independant Style 7RS-485 Data Pairs. Max.length 4,000 ft. each.

120/240

Vac

24 Vdc

24 Vdc

24 Vdc

RDU # 4 for RHU # 2

RDU # 3 for RHU # 2

RHU # 2

RDU # 5 for

120/240

Vac

120/240Vac

Note: The system must comprise 1 MCP.

To expand, add up to 7 RHUs andup to 16 RDUs to the network.

SILENCE

UNIT

SUPERVISORYR

SIGNALTROUBLE

ALARMPOWER ON

SCROLLSUP/TBL

REMOTEHAZARD

TM

SYSTEMCONTROLS

SCROLLALARM

RESET

SIGNAL

SILENCED

RHU # 1 V 1.0

LOCAL STATUS NORMAL

12:00 4-25-01

ALM00 SUP0 TBL00

SYSTEMCONTROLS

ALARMSCROLL

SUP/TBLSCROOL

RDU #1 V 1.0SYSTEM STATUS NORMAL

12:00 04-25-01ALM00 SUP0 TBL00

R

TM

REMOTE DISPLAY UNIT

POWER

CONTROL

SUPERVISORYR

TM

SIGNALTROUBLESCROLL

SCROLL

SUP/TBL

ALARM

RESET

SILENCE

CONTROLS

ALARMPOWER ONPANEL

MAIN

SYSTEM

CONTROLSMENU

CANCEL ACCEPT

SIGNAL

SILENCED

MCP V1.0SYSTEM STATUS NORMAL

12:00 4/25/01ALM00 SUP0 TBL00

SYSTEMCONTROLS

ALARMSCROLL

SUP/TBLSCROOL

RDU #1 V 1.0SYSTEM STATUS NORMAL

12:00 04-25-01ALM00 SUP0 TBL00

R

TM

REMOTE DISPLAY UNIT

POWER

SYSTEMCONTROLS

ALARMSCROLL

SUP/TBLSCROOL

RDU #1 V 1.0SYSTEM STATUS NORMAL

12:00 04-25-01ALM00 SUP0 TBL00

R

TM

REMOTE DISPLAY UNIT

POWER

SYSTEMCONTROLS

ALARMSCROLL

SUP/TBLSCROOL

RDU #1 V 1.0SYSTEM STATUS NORMAL

12:00 04-25-01ALM00 SUP0 TBL00

R

TM

REMOTE DISPLAY UNIT

POWER

SYSTEMCONTROLS

ALARMSCROLL

SUP/TBLSCROOL

RDU #1 V 1.0SYSTEM STATUS NORMAL

12:00 04-25-01ALM00 SUP0 TBL00

R

TM

REMOTE DISPLAY UNIT

POWER

Figure 2. Typcial System Block Diagram

Page 3: Conventional Suppression Control System P/N 30 ... - … 3220.pdf · Conventional Suppression Control System P/N 30-32200X ... • Listed for FM-200, ... can support 40 Fenwal Smoke

3

RHU Programming:The RHU receives its Operating Configuration from the MCP.

RHU Enclosure:The RHU Enclosure when using the Optional Display Panelis very similar to that of the MCP. In the case that this optionis not selected, the RHU Enclosure has no viewing window.

SYSTEM COMPONENTSREMOTE DISPLAY UNIT (RDU)RDU Power Supply:The RDU operates on 24 Vdc Power received either fromthe MCP, its associated RHU or any other UL Listed source.

RDU Display Panel:The RDU is a Display only unit and can be programmed tooperate either in local or global mode. In local mode, it mim-ics the Display of the MCP or the RHU to which it is as-signed whereas in global mode, it mimics the display of theMCP. The RDU Display Panel provides one LCD Display,one Status LED and System Controls (see Figure 6.)

RDU Hazard Block:RDUs may be used to accept one Manual Release and oneAbort input from the local protected zone to which its asso-ciated MCP/RHU is assigned.

RDU Backbox:The RDU Backbox is constructed of 18 gauge steel, paintedFenwal beige and kept closed by the Display Panel frontplate.

SYSTEM LOGSThe Fenwal® 3220 Control System is provided an EventLog and Configuration Log, both of which reside in the MainControl Panel. The Event Log is a compilation of all Alarm,Trouble, Supervisory and Event messages stored in non-volatile memory. Up to a maximum of 270 events can bestored at any given time. The occurrence of a new eventbeyond the maximum capacity erases the earliest event.

MENU STRUCTUREThe Main Menu of the Fenwal® 3220 Control System con-sists of the following items as shown on the tree structurein Figure 7. Specific functions are password protected tolimit access to authorized personnel only.

Figure 5. Hazard Block Inputs and Outputs

Detection Circuit # 1Style B or D

Detection Circuit # 2Style B or DSmoke and

Heat Detectors

Waterflow InputStyle B or D

Sprinkler System

Pull Station

Manual Release

AbortStyle B

Abort Station

Supervisory Signal

Release Circuit

Auxiliary Power 124 Vdc 24 Vdc

(Not resettable)Auxiliary Power 2

Inputs from

field devices

Outputs

RS485Port

RS-485 Data Highway

Clean Agent Control Head

Deluge System Solenoid

To Remote Display Units

To and from other

System Units

Form C Alarm Relay

Form C Trouble Relay

Form C Prog. Relay

Auxiliary Functions- Equipment Shutdown- Repeat Annunciation- DACT (MCP only)

Main Control Panel and Remote Hazard Units

PUSH

PULL

FIRE FIRE

PUSH / HOLD

SUPPRESSIONSYSTEM ABORT

Style B

Style B

5 Form C Prog. Relayson Option Relay Board

Indicating Circuit # 1

Style Y or Z

Indicating Circuit # 2

Style Y or ZAudible and VisualIndicating Devices

All relays except those on ORBare applicable to the MCP only.

FENWAL

Style Y

AG

EN

TR

EL

EA

SIN

GL

OG

IC

Clean Agent Initiators

Figure 6. Remote Display Unit Display Panel

SYSTEMCONTROLS

ALARMSCROLL

SUP/TBLSCROLL

RDU #1 V 1.0SYSTEM STATUS NORMAL

12:00 04-25-01ALM00 SUP0 TBL00

R

TM

REMOTE DISPLAY UNIT

POWER

Page 4: Conventional Suppression Control System P/N 30 ... - … 3220.pdf · Conventional Suppression Control System P/N 30-32200X ... • Listed for FM-200, ... can support 40 Fenwal Smoke

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes no re-sponsibility for the product's suitability for a particular application. The product must be properlyapplied to work correctly.If you need more information on this product, or if you have a particular problem or question, contactKIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.comProtection Systems

R

Figure 7. Menu Structure

TECHNICAL INFORMATIONMAIN CONTROL PANEL (MCP)Input Supply: 120/240 Vac 50/60 HzCurrent Draw: 3.0 Amps @ 120 Vac

1.4 Amps @ 240 VacOutput Rating: 4.0 Amps @ 24 VdcBattery Charger Output: 3.5 Amps max @ 27.3 VdcAux. Power Output: 0.5 Amp max @ 24 VdcQuantity per System: 1Enclosure Rating: NEMA 1Enclosure Material: 18 gauge steel, painted beigeDimensions (WxDxH): 15.5” x 5.0” x 15.5”

(393.7mm x 127mm x 393.7mm)Ambient Temperature: 32°F to 120°F (0°C to 49°C) max.Relative Humidity: 93% non-condensing max.

TECHNICAL INFORMATIONREMOTE HAZARD UNITS (RHU)Input Supply: 120/240 Vac 50/60 HzCurrent Draw: 3.0 Amps @ 120 Vac

1.4 Amps @ 240 VacOutput Rating: 4.0 Amps @ 24 VdcBattery Charger Output: 3.5 Amps max @ 27.3 VdcAux. Power Output: 0.5 Amp max @ 24 VdcQuantity per System: Maximum 7Enclosure Rating: NEMA 1Enclosure Material: 18 gauge steel, painted beigeDimensions (WxDxH): 15.5” x 5.0” x 15.5”

(393.7mm x 127mm x 393.7mm)Ambient Temperature: 32°F to 120°F (0°C to 49°C) max.Relative Humidity: 93% non-condensing max.

30-3220.0 12/01 Kidde-Fenwal Inc. Printed in USA

TECHNICAL INFORMATIONREMOTE DISPLAY UNITS (RDU)Input Supply: 24 Vdc (nominal)Quantity per System: Maximum 16Backbox Rating: NEMA 1Backbox Material: 18 gauge steel, painted beigeDimensions (WxDxH): 8.0” x 2.25 x 4.45”

(203.2mm x 57.1mm x 113.0mm)Ambient Temperature: 32°F to 120°F (0°C to 49°C) max.Relative Humidity: 93% non-condensing max.

ORDERING INFORMATION

������� ������ �

������������������� ���������������

��������

������������������� ���������������

��������

�������������� �� �������� �������������

������������ �!

������������� "�� �� �������� �������������

������������ �!

#������������� �� �������� �������������

������������ �!

������������� ��!�� ������ �!� �������������

$������������ �%�&����%�������� �&���������

'(��#�$#���)���� %��*+�������,�+��-�!.��

�����"/����

)(��#�$#���)���� %��*+�������,�+'�-�!.��

�����"/����

�����#�����$0��� %��*+�������,�+��-�!.��

�����"/����

����(���������� � �"��1� ���2���� %���������

� ���� %��*+�������,�+��

������$$���)� �"*���� ����3�&4� �5�� � ��

����"!

For design, installation, configuration and additional order-ing information, refer to the Fenwal® 3220 EngineeringManual P/N 06-235976-001.