Character i s t i c sne t - l i ne subs ta t i on au tomat i on
Version: setIT V 4.004 17.12.09
The integrated configuration tool setIT was extended with afully graphical dialogue for the assembly of components. Thisfunction allows an even faster integration of substationautomation and telecontrol. It also eases the handling andgives you an quick overview of the systems assembly.
Achieving aims fasterAchieving aims fasterAchieving aims fasterAchieving aims faster
Furthermore setITV4.004 brings extended functionality such as:
Selective linkage to protective equipment
Processing of archives with variable memory depth
Optimised GPRS communication
Integration of the newest series5 devices
High-Speed-Download*
Configuration via USB-Stick*
up to 2 GB of archive memory*Diagnosis via Web-Server*
-
7/30/2019 1Characteristics_setITV4
2/12
* Performance of series5
2009 SAE IT-systems GmbH & Co. KG Characteristics_setITV4.docSubject to modification17.12.2009
Release noteRelease noteRelease noteRelease note ---- Differences to V 3.0Differences to V 3.0Differences to V 3.0Differences to V 3.0
Graphical user interface for configuration of all base systems
visual assembly of serial interfaces and I/Os
Selective coupling of protective equipment
Preprocessing of process data in the process image
Merging addresses of protective equipment into address room and structure of control centre
Processing of archives with variable memory depth
modified memory management with automatic or manual partition
Optimised GPRS communication
IEC 60870-5-104 for VPN-Tunnel with GPRS
Integration of ENET-2 card for optimised TCP/IP timing at GPRS
Optimisation of the symmetric IEC 60870-5-101 driver for GPRS
Complete integration of autarky compact systems and data logger aucolog into telecontrolwith IEC 60870-5-101/-104 protocol
Negative confirmation of commands and desired values with time tag, in the case that therespective time spans have been exceeded.
Validation of set points at coupling of external devices can be activated via status word
Adjustment of idle condition for single-point information and commands
Step position information with validity detection 8 bit or 32 bit
Logging of process data in telecontrol report
Remote diagnose with an external front-end station via switched telephone line, LAN or fieldinterface with IEC -101/-104 protocol or directly via switched telephone line or LAN with PUprotocol UNIP
Integration of series5
net-lineFW-5-BT net-line FW-5-BT with extension cards
net-line FW-50-4 in
housing BGT-S
net-line FW-50
e.g. pure router in BGT-M
net-line FW-50-14 in housing BGT-L
-
7/30/2019 1Characteristics_setITV4
3/12
* Performance of series5
2009 SAE IT-systems GmbH & Co. KG Characteristics_setITV4.doc, Subject to modification 17.12.2009
Further functions for series5 systemsFurther functions for series5 systemsFurther functions for series5 systemsFurther functions for series5 systems****::::
High-speed-download
USBdownload and diagnosevia USB interface
FTPdownload and diagnose via Ethernet LAN
httpStations update via Web page
Hand over of configuration with USB memory stick
Saving operating system, firmware and configuration on USB memory stick
Batch control
Job processing of stick information for each station according to adjustment in setITRead out of status after update
Archive read out over web page and USB memory stick
Dynamic creation of web pages for web server in line with the configuration of process data
Integration of several IEC 60870-5-104 substations over one interface at the master stationPartyline
Support of fast information input < 1 ms with 16IE-5 card by dint of interrupt processing withminimised latencies
Quick LAN connection due to copper or fibre optic switchesSWI1-1: 4* Tx or SWI1-2: Fx + 2 * Tx
Cascading of racks via Ethernet with integrated switch
New rack sizes for larger capacityBGT-S for up to 4, BGT-M for up to 7 and BGT-L for up to 14 I/O cards
Up to 9 communication components4 serial, 2 switch- and max. 3 fieldbus components
NTP-Protocol for time synchronisation according to IEC 61850
Platform for integration of IEC 61850 coupling of protective equipment
-
7/30/2019 1Characteristics_setITV4
4/12
* Performance of series5
2009 SAE IT-systems GmbH & Co. KG Characteristics_setITV4.doc, Subject to modification 17.12.2009
General informationGeneral informationGeneral informationGeneral information
Open & standard communication for
New installation as system solution or component
Extension usually in the field of power system control and industry
Integration of protective equipment via -103 or external components with fieldbus
Quick and easy configuration with setIT
Very fast realisation of your project due to easy handlingMenu, context menus, mouse- and hotkey functions
Learning the ropes quickly be dint of tree structures and well established handling processesfrom the MS Office world (copy/paste, do/undo)
Avoiding faulty entries with dynamic menus and context sensitive entry masks onlyonlyoperative components, options and combinations are selectable
Hand over of mutual configurationssingle-point-of-entry
High flexibility in terms of topologythe telecontrol network is adjustable to almost every existingstructure
Fast modification and extension of installationsTypes of interfaces, protocols, station types
Future proof with modern platform and hardware
Windows based configuration tool with state of the art GUI
setITsupport all characteristics of System-4 and series5 hardware
FW-4, FW-40, FW-10-S4, BGT-4000, FW-5, FW-50 etc.Active advancements, maintenance and optimising
Download and Upload from operating system, system software, configuration and add-on
modules including version control
Saving configuration in access data base
Import and export of configuration with csv file for documentation or further editing with Excel
Recording of system events
Separately loadable system report
Logging of process data changes in telecontrol report
Reports separately loadable as csv-file
Memory management and archive processing
Processing of archives with variable memory depthmodified memory management with automatic or manual partition
Quick ROI due to fair license system
Free 30 days demo-version with optional extension.
Single user license, multi user license and company license
-
7/30/2019 1Characteristics_setITV4
5/12
* Performance of series5
2009 SAE IT-systems GmbH & Co. KG Characteristics_setITV4.doc, Subject to modification 17.12.2009
CommunicationCommunicationCommunicationCommunication
Communication according to standard protocols.
IEC 60870-5-101 Serial coupling with dedicated line
IEC 60870-5-102 Routing of data from remote meter reading
IEC 60870-5-103 Coupling of protective equipment
IEC 60870-5-104 Coupling with TCP-IP /LANSelective coupling of protective equipment via IEC 60870-5-103
Preprocessing of process data in the process image
Merging addresses of protective equipment into the address room and structure of the controlcentre
Rapid coupling to control centreswith IEC 60870-5-10x protocols supporting ProCoS, PSI, STS/BTC, SAT, ids, ABB, repas ...
OPC server supported
Handover of station names, names of process points and parameter in namespace of OPC
Supervision name semantic respectively automatic conversion with underliningsupport of redundant OPC-Server
Free cross-connection in network
free linkage of information inputs to the outputs of the network
overall cross-connection by dint of control centre or router
Structured station- and object addressing in up to 6 levels
Switched telephone line & remote diagnostics via telephone line
switchable login procedure name, password
Translation form IEC 60870-5-101 to IEC 60870-5-104 by router
On site integration of PLC functions with codeIT
Optimised GPRS communication
GPRS with VPN Tunnel directly over IEC 60870-5-104
Optimisation of the symmetric IEC 60870-5-101 driver for GPRS
-
7/30/2019 1Characteristics_setITV4
6/12
* Performance of series5
2009 SAE IT-systems GmbH & Co. KG Characteristics_setITV4.doc, Subject to modification 17.12.2009
Integration & AdaptionIntegration & AdaptionIntegration & AdaptionIntegration & Adaption
flexible types of communication are supported:
direct coupling to control system point-to-point or LAN mode
Star coupling point-to-point mode to router
LAN Industrial Ethernet, TCP/IP, pulse code modulation
Partyline Networks and loop lines multipointvariable structures in complex networks and cascading
at subordinated networks routers are the connection to controlcentre or telecontrol knot
Dial up connection via analogue link, ISDN or GSM
with switchable protection against remote access
Multiple link to control centres
Filtering of data points with transmission lists for a selective transmission to control system
Transformable address structures for a separate structure of the secondary control system
Time synchronisation via DCF and GPS receiver
Flexible fieldbus coupling and gateways for the implementation of external devices
Profibus-DP master/slave
Modbus RTU master/slave
Modbus RTU master/slave
MPI 3964R/RK512
Free allocation of external devices/components
external components are integrated as station objects
process data are allocated with free declaration of LEDs
process data of external devices are provided just like system-own process data
Complete integration of autarky compact systems and data logger aucolog into telecontrolwith IEC 60870-5-101/-104 protocol
Integration of autarky objects in interconnected systems
-
7/30/2019 1Characteristics_setITV4
7/12
* Performance of series5
2009 SAE IT-systems GmbH & Co. KG Characteristics_setITV4.doc, Subject to modification 17.12.2009
Additional functions in the section of interconnected systems andAdditional functions in the section of interconnected systems andAdditional functions in the section of interconnected systems andAdditional functions in the section of interconnected systems and
subsubsubsubstation automationstation automationstation automationstation automation
Command termination;via EVU special cards with 1 of n monitoring
Single- and double commands 1,5 and 2 pole
Adjustable for each command: post command lag time, suppression of imperfection, couplingresistance
measuring circuit test from 10 to 20 k
Cascading of several racks with IEC profileAdministration of of up to nine racks at only one station address
1 of n monitoring of several racksAt cascaded systems large command groups can be assembled. The EVU-X cards loops the interlocksignals of the 1 of n monitoring to the implemented racks.
Process image in telecontrol router
Telecontrol router are able forward the data of subordinated stationsdefault value generation at control commandsControl commands can be set to an individual default status in the case of disturbed communicationor system start.
Rapid acquisition of measurands (max. 1 kHz pulses)with the intelligent counter card CNT-1
Logging of measurands with external pulse inputs at the deviceTime synchronised logging is available due to external control signals.
Binary step position information, BCD and 32 bit
Step position information can be directly linked with 32 bit.
Intuit configuration with setIT
-
7/30/2019 1Characteristics_setITV4
8/12
* Performance of series5
2009 SAE IT-systems GmbH & Co. KG Characteristics_setITV4.doc, Subject to modification 17.12.2009
Cascaded stations for large capacities
-
7/30/2019 1Characteristics_setITV4
9/12
* Performance of series5
2009 SAE IT-systems GmbH & Co. KG Characteristics_setITV4.doc, Subject to modification 17.12.2009
SecuritySecuritySecuritySecurity
Redundancy functions
Support of redundant control centre
Twinned master stations easily settablewatchdog monitors the functions of the master stations and autarky switches hot/standby mode
Quick loop line over baseband modem or WT96 as daisy-chainSecurity at short-circuit, line interruption and station- or modem breakdown
Redundancy of switched telephone linePreferred interface, alternative numbers, prioritisation
System informationprovide station status and internal error messages as binary single-point information
Combining system information to group indicationLogical linkage without PLC layer
Cross-connection of system informationSystem information may be handed over as output information to any station
System history logs all station internal processes
Archiving of reports in the case of communication error
Default value generation at outputs in the case of communication error
Management of system- and configuration version
Optical marker for new system- / configuration versions after generating
Control of station and version access prior to download
Twinned master stations in hot/standby operation
-
7/30/2019 1Characteristics_setITV4
10/12
* Performance of series5
2009 SAE IT-systems GmbH & Co. KG Characteristics_setITV4.doc, Subject to modification 17.12.2009
Support at diagnostics & project planningSupport at diagnostics & project planningSupport at diagnostics & project planningSupport at diagnostics & project planning
Comprehensive diagnostics and help functions are already integrated
Online help provides a complete manualcontext sensitive forwarding to information with F1, search function
Indication of connection status
of interconnected station and process data states scaled or in plain textQuick correction of configuration errors
Link to entry masks during generating
Extended diagnostics with integrated telegram analyser (optionally)
Recording of data transmission and receiving in substation is possible without additional devices
Trigger functionsStart/stop or marking of character strings
Logging as csv- file in a revolving archive
Memory management of csv-files
HTML export for an easy transfer of the recording
Chronometry and indication of receiving errors
Online switching of view
Data flow analysis
Exchange and distribution of station's/router's data
Follow up of the router's information paths
Extended help at installation
Analysis of coverage
New value message
Report for documentation printable or as pdf-file
List for quick overview of prior indications
Integrated interface monitor (optionally)
-
7/30/2019 1Characteristics_setITV4
11/12
* Performance of series5
2009 SAE IT-systems GmbH & Co. KG Characteristics_setITV4.doc, Subject to modification 17.12.2009
Types of communicationTypes of communicationTypes of communicationTypes of communication
Modes
point-to-point
Partyline
Star operation
Loop modeConcentrator connection & routing
Transmission routes
Dedicated lines
LAN networks
Dial-up links
Radio communication networks (in development)
GSM - Transmission
GPRS if the provider complies with the requirements
Cause of transmission
Spontaneous atchanges or reaching limit values
Cyclic
queried by GA
in background
transmission of integrated totals inside the intervalspontaneously and synchronous, from 12 s to8 hours
Integration and communication of telecontrol and substation automation to control centre
-
7/30/2019 1Characteristics_setITV4
12/12
2009 SAE IT-systems GmbH & Co. KG Subject to modification 17.12.2009
Supported types of process dataSupported types of process dataSupported types of process dataSupported types of process data
Inputs
Single-point information
Single-point information
Step position information 7/8/32 bit, binary, BCD
Measured values 8/12/16/32 bit
Integrated total inputs 16/32 bit
System information
Group indication with logical connection
Cumulative values equally spaced interval values from 1 to 60min
Checkback definition command termination with DSO card
Outputs
Single commands
Double commands
Regulating step command
Set points 8/12/16/32 bit
Integrated total outputs 16/32 bit
Cross-connection & etc.
Single point information in control direction
Double information in control direction
System information in control direction
Measurand in command direction
Integrated total cross-connection 16/32 bitInterval data, Interval-/ alarm-/ operation archive
setIT's easy structure of and configuation