clcp_iom

Upload: leed-en

Post on 07-Aug-2018

212 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/20/2019 CLCP_IOM

    1/44

    Installation

    OperationMaintenance

    Quantum Climate ChangerModel: CLCP

    IND-SVN01A-E4

    0.5 - 27 m3 /s

    (1000 - 58000 CFM)

    TRANE R 

  • 8/20/2019 CLCP_IOM

    2/44

    TRANE R

    Contents

    General InformationNomenclature

    Foreword

    Warranty

    Warning and Caution

    Unit Description

    Name Plates

    Unit Submittals

    Receiving and Handling

    Lifting and Rigging

    Submittal Drawing (VDT)and (HDT)

    InstallationLifting and Rigging Recommendation

    Break Point Joining Method

    Vertical Unit and Final Final Filter Joining Method

    Removing and Inserting Wedge

    Damper Installation

    Duct Connections

    Piping

    Steam Coil Piping

    Refrigerat Coil Piping

    Pulley and Belt

    Wiring/Start-up ProcedureWiring and Start-Up Preparation

    Shipping Bracket Removal Detail

    Delayed Start-Up and Start-Up Procedures

    Sheave Alignment and Fan Belt Tension/Alignment

    Deflection Force Table and Belt Tension Measurement

    MaintenancePeriodic Maintenance Checklist

    Trouble AnalysisTrouble Analysis

    Appendix B-Unit Weight

    Appendix C-Fan Sizes/Arrangements

    Appendix D-Air Filter Sizes x Quantity

    Appendix E-Motor Detail

    Safety Recommendations, Maintenance Contract and Training

    1

    6

      21

    25

    26

    i

  • 8/20/2019 CLCP_IOM

    3/44

    TRANE R

    1

    Model Nomenclature

  • 8/20/2019 CLCP_IOM

    4/44

    TRANE R

    General Information

    Foreword

    These installations, operation and

    maintenance instructions are given as

    a guide to good practice in the

    installation, putting into service,

    operation and maintenance by the

    user, of QCC units. They do not containfull service procedures necessary for

    the continued successful operation of

    this equipment; the services of a

    qualified technician should be

    employed through the medium of a

    maintenance contract with a reputable

    service company.

    Warranty

    Warranty is based on the general terms

    and conditions of the constructor. The

    warranty is void if the equipment is

    repaired or modified without the written

    approval of Trane, if the operating limits

    are exceeded or if the control system

    of the electrical wiring is modified.

    Damage due to misuse, lack of

    maintenance or failure to comply with

    the manufacturer ’s instructions or

    recommendations is not covered by thewarranty obligation. If the user does not

    conform to the rules of chapter

    “Maintenance”, it may entail

    cancellation of warranty and liabilities

    by the constructor.

    Warning and Cautions

    Notice that Warnings and cautions

    appear at appropriate intervals

    throughout this manual. Warning are

    provided to alert installing contractors

    and other personnel to potential

    hazards that could result in personal

    injury or death, while cautions are

    designed to alert personnel to

    conditions that could result in minor

    personal injury or equipment damage.

    Unit Description

    Trane Quantum Climate Changers areCentral Station Air Handlers designed

    for a variety of controlled air application.

    The basic unit consists of a fan,

    heating and/or cooling coils, filters and

    air dampers.

    The Quantum Climate Changer air

    handlers are designed for cooling load

    conditions of 1000-58000 nominal

    CFM. Fans are double width, double

    inlet, centrifugal types with forwardcurved, backward curved, and airfoil

    blade designs.

    To ensure fan stability the unit ships

    with shipping brackets located

    between the fan support frame.

    Removal of bolt and spacer is required,

    prior to fan operation, to insure proper

    vibration isolation.

    Units ship as complete units, sections

    or subassemblies. Each section is

    provided with a nameplate (label)which includes type of section, unit

    serial number, customer tag number

    and unit model number.

    NameplateAll Trane Quantum Climate Changer

    air handlers are identified by a

    multiple-character model number. lts

    use enables owner/operator, installing

    contractors, and service technicians to

    define the operation, components andoptions for a particular unit. Be sure to

    refer to the information printed on the

    unit nameplate (figure1) when ordering

    replacement or requesting service.

    Unit Submittals

    Refer to Figure 2 and 3 for the

    Horizontal Draw Thru (HDT) and

    Vertical Draw Thru (VDT) unit standard

    submittals.

    Figure 1: Typical Unit Nameplate

    Receiving and Handling

    All unit sections are securely fasten to

    skids for shipping and handlingpurpose.

    Upon receipt of the unit(s), inspect for

    damage that may have occurred during

    shipment and any items, which were

    ordered but did not arrive with the unit.

    Complete the following checks:

    1. Visually inspect the exterior unit

    casing and all accessories for any

    dents, punctures or shipping andhandling damage.

    2. Cut all banding (if applicable) loose

    from skid, but do not remove the

    skids.

    3. Check all access doors to confirm

    that they are secured with latches.

    4. Manually rotate the fan wheel to

    ensure free movement of the shaft

    and bearings.

    Inspect the fan housing for any

    foreign objects.5. Inspect the coil(s) for fin damage.

    2

  • 8/20/2019 CLCP_IOM

    5/44

    TRANE R

    lf damage has occurred to the unit

    sections during shipment, the

    following instruction should be

    completed upon receipt .

    1. Report al l claims of shipping

    damage to the delivering carrier

    immediately.2. Make specific notations concerning

    the damage on the freight bill.

    3. Keep damaged material in the

    same location as received. lt is the

    receiver’s responsibility to provide

    reasonable evidence that damage

    was not incurred after delivery.

    4. Notify the Trane sales

    representative of the damage and

    arrange for repair. Do not attempt to

    repair the unit without consulting thesales representative. TRANE IS

    NOT RESPONSIBLE FOR

    SHIPPING DAMAGE.

    Lifting and Rigging

    Caution: Confirm that factory installed

    (if any) attachment brackets are in

    place and screws tight, before

    rigging.(refer to figure 4, 5 & 6) The unit

    will ship either assembled or assections. Before preparing the unit for

    lifting, estimate the approximate center

    of gravity for lifting safety. Because of

    placement of internal components, the

    unit weight may be unevenly

    distributed, with more weight in the coil

    and fan area. Approximate unit weights

    are given in Appendix B.

    !

      WARNING: DO NOT LIFT THE

    UNIT WITHOUT TEST-LIFT FOR

    BALANCE AND RIGGING. DO NOT

    LIFT THE UNIT ABOVE PERSONNEL.

    FAILURE TO OBSERVE THESE

    WARNINGS MAY RESULT IN

    PERSONAL INJURY, DEATH OR

    EQUIPMENT DAMAGE. (See

    Appendix B for components weight).

    General Information

    !

    Always apply good rigging procedures

    when lifting a unit. Before hoisting the

    unit into position, be sure that a proper

    method of rigging is used, with straps

    or slings and spreader bars for

    protection and safety during lifting.

    Always test-lift the unit to determine

    exact unit balance and stability beforehoisting it to the installation location.

      WARNING:NEVER ASSEMBLE

    OR BOLT SECTIONS OR

    SUBASSEMBLIES TOGETHER

    BEFORE RIGGING. ALWAYS RIG

    SECTIONS OR SUBASSEMBLIES AS

    RECEIVED FROM THE FACTORY.

    3

  • 8/20/2019 CLCP_IOM

    6/44

    TRANE R

    Submittal Drawing

    Horizontal Draw Thru (HDT)

    4

  • 8/20/2019 CLCP_IOM

    7/44

    TRANE R

    Submittal Drawing

    Horizontal Draw Thru (VDT)

    5

  • 8/20/2019 CLCP_IOM

    8/44

    TRANE R

    Lifting and Rigging RecommendationFigure 4

    Move units with Fork-Truck (Forklift)

    Figure 5

    Recommended Rigging Method1

    Figure 6

    Recommended Rigging Method2

    Installation

    6

  • 8/20/2019 CLCP_IOM

    9/44

    TRANE R

    Installation

    7

  • 8/20/2019 CLCP_IOM

    10/44

    TRANE R

    Installation

    8

  • 8/20/2019 CLCP_IOM

    11/44

    TRANE R

    9

    Installation

  • 8/20/2019 CLCP_IOM

    12/44

    TRANE R

    10

    Installation

  • 8/20/2019 CLCP_IOM

    13/44

    TRANE R

    11

    Installation

  • 8/20/2019 CLCP_IOM

    14/44

    TRANE R

    Installation

    12

  • 8/20/2019 CLCP_IOM

    15/44

    TRANE R

    Installation

    13

  • 8/20/2019 CLCP_IOM

    16/44

    TRANE R

    InstallationUnit LocationRecommendations

    Unit handling, LEFT or RIGHT for coil

    connections, drain etc. is expressed

    when facing the airflow thru the coil.

    For dimensional details see the

    standard submittals drawing, Figure 2

    and 3.

    When selecting and preparing the unit

    operating location, consider the

    following;

    1. Consider the weight of the unit.

    Appendix B has a complete listingof all component operating

    weights.

    2. Allow suff icient space for the

    recommended clearances,

    access panel removal, and

    maintenance access. Refer to

    Figure 8.

    3. Coil piping and condensate drain

    requirement must be considered.

    Allow room for proper ductwork and

    electrical connections. Support all

    piping and ductwork independently

    of unit to prevent excess noise and

    vibration.

    Duct Connections

    All air ducts should be installed in

    accordance with the standards of the

    National Fire Protection Association for

    the installation of Air Conditioning and

    Ventilating System other than

    Residence Type (NFPA 90A), and

    Residence Type Warm Air Heating and

    Air Conditioning Systems (90B).

    lnlet and discharge air duct

    connections to the unit should be

    made with a flexible material

    Installation

    minimizing noise and vibration.

    Typically, about three inches is needed

    for this connection to rigid ductwork.

    Ducts should be designed as a

    function of the fan orientation. Duct

    turns and transitions must be made

    carefully to minimize air friction losses.

    Avoid sharp turns and use splitters or

    turning vanes when elbows are

    necessary. Make turns in the same

    direction of rotation as the fan.

    Discharge ductwork should run in a

    straight line, unchanged in size or

    direction, for at least a distance of 1-1/ 

    2-fan diameters (see Appendix C for

    fan diameter).

    Refer to Figure 9 and Figure 10 for

    typical ductwork installation.

    Figure 7

    Unit LEFT or RIGHT Convention

    Figure 8

    Minimum Service Clearance

    14

  • 8/20/2019 CLCP_IOM

    17/44

  • 8/20/2019 CLCP_IOM

    18/44

    TRANE R

    PipingCondensate DrainConnection

    On cooling coil section(s) the drain pan

    should always be connected directly

    to a trap to ensure proper drainage of

    condensate.

    Caution:  Failure to provide adequate

    condensate piping may result in water

    damage to the equipment or building.

    lmportant:  The applicable "rule of

    thumb" for amount of condensate may

    as high as 6 lbs/hr/ton for units serving

    Coil Piping and Connection

    General Coil Piping Recommendation

    Refer to Figure 12 for typical cooling

    and heating coil piping.

    Proper installation, piping and trapping

    is necessary to assure satisfactory

    heating/cooling coil operation and to

    prevent operational damage. Waterinlet and outlet connections protrude

    through the coil section side panel.

    Follow standard piping practices when

    piping to the coil. Note the following:

    Installation

    areas with high latent heat.

    Male-threaded, BSPT 1 1/2"

    condensate drain connection is

    provided on one side of the coil

    section. The main drain lines and trap

    must be the same size as the drain

    connection.

    Pitch the connection line horizontal or

    downward toward an open drain and

    install a plugged tee to facilitate

    cleaning. Condensate lines should not

    be connected to a closed drain. This

    is to avoid the possibility of drawing

    sewer gasses into the unit.

    Drain traps must be primed. lf they are

    not, the trap is essentially non-existent

    and the drain pan will likely overflow.

    Make sure the drain pan connection

    openings are unobstructed. Trap the

    drain line as shown in Figure 11 for

    section with negative static pressure.

    When more than one section has a

    drain pan, trap each section

    individually. Do not connect all drains

    to a common drain line with only one

    trap. Use the following drain

    connection recommendations.

    Figure 11

    Drain Trap for Draw-Thru UnitsFigure 12

    Typical Piping for Water Coil

    AV - Automatic or

      manual air vent

    MV - Magnetic valve

    GV - Gate valve

    1. Support all piping independently of

    the coils.

    2. Provide swing joints or flexible

    fittings in all connections that are

    adjacent heating coils in order to

    absorb thermal expansion and

    contraction strains.

    3. When attaching piping to the coil

    header, make the connection only

    tight enough to prevent leaks, the

    maximum recommended torque is200ft-lbs.

    4. Teflon tape or teflon piping

    compound should not be used

    because of its high lubricity, teflon

    makes it easier to tighten the pipe

    to the header joint past the point

    where an effective seal is created,

    thus damage to the coil could result.

    5. "White Zinc" compound is

    recommended, instead.

    Caution: Use "Back-up Wrench" when

    attaching piping to coils with copper

    headers. Do not use brass fitttings or

    brass pipe connectors. Brass distorts

    easily and causes connection leaks.

    16

  • 8/20/2019 CLCP_IOM

    19/44

    TRANE R

    Installation

    Steam Coil PipingType A, AA Steam Coils

    These are for central system,

    industrial and process application with

    one row, opposite-end connections.

    Maximum standard operating limits:

    Copper tubes: 100 psig and 400oF

    Type AA coils feeds alternate tubes.

    Refer to Figure 13 for typical steam coil

    piping.

    Caution: Condensate must flow freely

    from coil at all times to prevent physical

    coil damage from water hammer,

    unequal thermal stresses, freeze-up

    and/or corrosion.

    Complete the following

    recommendations to prevent coil

    damage.

    1. lnstall a 1/2 inch, 15 degree swing

    check vacuum breaker in the

    unused condensate return

    tapping as close as possible to the

    coil.

    2. Vent the vacuum breaker line to the

    atmosphere or connect it to the

    return main at the discharge side of

    the steam trap.

    Note: Vacuum breaker relief is

    mandatory when the coil is controlled

    by a modulating steam supply or a two-

    position (ON-OFF) automatic steam

    supply valve.

    3. Run the return pipe at the full size of

    the steam trap connection except

    for the short nipple screwed directly

    into the coil condensate connection.

    Do not bush or reduce the coil return

    tapping size.4. Proper steam trap selection and

    installation is necessary for

    satisfactory coil performance and

    service life. For installation, use the

    following steps:

    • Select trap based on maximum

    possible condensate rate.

    • Locate the steam trap discharge

    at least 12 inches below the

    condensate return tapping, this

    provides sufficient hydrostatic

    head pressure to overcome traplosses and assure complete

    condensate removal.

    • Float and thermostatic traps are

    recommended because of gravity

    drain and continuos discharge

    operation.

    • Use float and thermostatic traps

    are recommended because of

    gravity drain and continuos

    discharge operation.

    Use float and thermostatic trapswith atmospheric pressure gravity

    condensate return, with automatic

    control or where the possibility of

    low-pressure supply steam exists.

    • Use bucket traps ONLY when the

    supply steams in unmodulated

    and 25 psig or higher.

    • Always install strainers as close

    as possible to the inlet side of the

    trap.

    5.

    6.

    Caution: Always open the steam

    supply control valve slowly to

    prevent possible coil damage.

    7.

    8.

    9.

    10. Do not drain the steam mains or

    take-off through the coils. Drain the

    mains ahead of the coils through

    a steam trap to the return line.

    11. Overhead return require 1 psig of

    pressure at the steam trap

    discharge for each 2 - feet

    elevation to assure continuouscondensate removal.

    Do not modulate Type A, AA coils.

    Use two position (ON-OFF) steamsupply controls.

    Use a V-port modulating valve to

    obtain gradual modulating action.

    Do not modulate systems withoverhead or pressurized returns

    unless the condensate is drained

    by gravity to a receiver (vented to

    the atmosphere) and returned to

    the main by a condensate pump.

    At start-up on units with fresh air

    dampers, slowly turn the steam on

    full at least 10 minutes before

    opening the fresh air.

    Pitch all supply and return steam

    piping down minimum of 1-inchper 10 feet in the direction of flow.

    AV - Automatic or manual air ventGV - Gate valveVB - Vacuum breakerOV - Automatic two-position control valve

    17

    Figure 13

    Typical Piping for Steam Coil

    MV - Magnetic valveFT - Float and thermostatic steam trapST - Strainer

  • 8/20/2019 CLCP_IOM

    20/44

    TRANE R

    Refrigerant Coil Piping

    1. Type FD coils have been dehydrated

    and sealed with 10-20 psig dry

    nitrogen holding charge.

    2. Refer to the "Trane Refrigeration

    Manual" for refrigeration-piping

    practices, which must follow.

    Caution:   To avoid equipment

    malfunction, use care when brazing or

    soldering so that distributor tubing is

    not restricted or blocked. To braze

    Thermostatic Expansion Valves (TXV)

    Figure 14

    Typical Piping for Refrigerant Coil

    avoid direct flame (figure 15) to the valve

    body and avoid excessive heat on

    diaphragm. As an extra precaution. a

    wet cloth may be around the body and

    element during brazing operation.

    Figure 15

    Solder Technique

    Note: Flame should heat away from

    TXV element

    18

    Installation

  • 8/20/2019 CLCP_IOM

    21/44

    TRANE R

    Installation

    Pulley and Belt

    Proper installation techniques will

    assure that you get full service life and

    minimum down time from your belt

    drives.

    1. Turn machine OFF and lock out

    power source.2. Remove belt guard, loosen motor

    mounts and shorten center distance

    between pulleys. Remove old belts.

    3. lnspect. Repair or replace drives

    components.

    • Clean oil, grease and debris from

    pulleys, remove rust with wire

    brush.

    • lnspect and replace damage

    pulleys. Get your moneys worth

    from a new set of belts by checkingand replacing worn or damaged

    pulleys. ln the long run,

    replacement pulley cost will more than

    be recovered in increased belt life,

    reduced downtime, and lower

    maintenance expenses.

    Check following:

    a) Worn groove sidewalls, "Dishing"

    should not exceed 1/32" for

    individual belts. With a banded belt,

    dishing should not exceed 1/64".

    When a banded belt rides too low

    in worn pulley grooves the tie bandcan be cut by the flanges between

    the grooves.

    b) Shiny pulley groove bottoms. This

    is a sure sign that the belt has

    bottomed out. The resulting

    slippage shortens belt life.

    c) Wobbling and/or damaged pulleys.

    Generally caused by improper

    pulley or bushing installation,

    wobbling and/or damaged pulleys

    can unbalance a drive, wear out

    belt rapidly, and damage bearingsand bend shafts.

    Check and repair worn bearings and

    bent shafts.

    4. Select replacement belts.

    Replace all belts on a drive with a new

    matched set from UNI-DRIVE.

    a) Do not mix old and new belts on a

    drive. A new belt will ride higher in

    the pulley groove and operate at a

    higher tension than an old belt.Running them together will

    damaged the new belt as it cannot

    carry its share of the load.

    b) Do not mix belt from different make,

    because dimensions and

    constructions will vary running such

    "Mis-Matched" belts will not give full

    service life.

    c) Replace with correct type and cross

    section belt. Matched SPA section

    belt with SPA section pulleys. Do notput a SPA belt section on a SPB

    section pulley. Also dimensionally

    similar belts can have very different

    horsepower rating.

    5. lnstall new belts

    • Loosen the drive take up and place

    the new belts on the pulley. Press

    the belts with your hand to position

    the slack of each belt on the same

    side of the drive. lf the slack is ondifferent sides. start up loads can

    break belt tensile cords.

    • Do not pry or force belts onto the

    pulleys. This can break the load

    carrying tensile cords of the belt

    and the belts will break or turn over

    shortly after installation.

    • Take up sleck until belts fit snugly.

    6. Check pulley alignment.

    • Place a straight edge or taut string

    across pulleys faces to correctalignment.

    • Check parallel position of shafts

    and correct alignment or grooves.

    • Note: Mount pulleys as close to

    bearing as possible.

    19

  • 8/20/2019 CLCP_IOM

    22/44

    TRANE R

    Installation

    20

    7. Tension Belts.

    • Ideal tension for a UNI belt is the

    lowest tension at which a belt will

    not slip under peak load.

    • Tension belts, replace belt guard

    run the drive for 15 minutes and

    apply full load. Retighten slopping

    or squeaking belt.• Retention after 24 to 48 hrs.

    running, when belt will be

    completely seated into grooves.

    • Do not use belt dressing. If the

    belt slips, tighten and/or check for

    worn pulley grooves.

    Note:  Store belts in a cool, dry place

    out of direct sunlight.

    Types of sheave and shaft misalignment

    Horizonal Angular

    Vertical Angular

    Parrallel

    Align with straightedge along

    sheave faces

  • 8/20/2019 CLCP_IOM

    23/44

    TRANE R

    Wiring/Start-Up Procedure

    21

    Shipping Bracket Removal Detail

  • 8/20/2019 CLCP_IOM

    24/44

    TRANE R

    Wiring/Start-Up Procedure

    1. Check fan hub setscrews; sheave

    setscrews and bearing setscrews

    for proper torques. Fan sheaves

    should be tight and aligned. See

    Maintenance section for alignment.

    2. Check the piping and valves for

    leaks. Open and close the valves to

    check for proper operation. Drainline should be open.

    Caution:  The use of untreated or

    improperly treated water in unit coils

    may cause scaling, erosion,

    corrosion, algae, slime or other

    equipment damage. Consult a

    qualified water treatment specialist to

    determine if water treatment is

    required. The Trane Company

    assumes no responsibility forequipment damage caused by

    untreated or improperly treated water.

    3. Check that the air filter is in place.

    4. Remove all foreign material from the

    drain pan. Check the drain pan.

    Check the drain pan and

    condensate line to make sure they

    are not obstructed.

    5. Close and secure all unit access

    doors. Check that the latches aretight.

    Delayed Start-Up

    lf installation and start-up do not occur

    immediately after delivery, take the

    following precautions:

    a) Protect equipment in an area not

    exposed to excessive heat and

    humidity.

    b) Take special care to protectelectrical components.

    c) Periodically, manually turn all

    moving parts to avoid any possibility

    of jamming or blocking.

    d) For long stocking periods, remove

    electrical equipment and store in a

    dry atmosphere.

    e) Verify the motor lubrication before

    start-up and follow the motor

    manufacturer recommendations.

    f) lt should be noted that the bearings

    are prelubricated. lt is howeverpossible that start-up will be noisy

    until the grease is evenly

    distributed.

    Start-Up Procedures

    After completing all items under

    “preparation”  the unit may be started.

    The following checks and adjustments

    should be made during initial start-up:

    1. Bump-start unit and observe the fanwheel for proper rotation. As

    indicated by indicated by rotation

    arrow located on fan housing.

    2. Measure the motor voltage and

    amperage on all phases to ensure

    proper operation The readings

    should fall within the range given

    on the motor nameplate. Never

    overload the motor.

    3. Maximum allowable voltage

    imbalance is two percent. Voltageimbalance can cause motor

    overheating and failure. Voltage

    unbalance is calculated as follows:

    The difference of the bracketed value

    in the numerator of the equation are

    absolute values. Disregard whether

    they are positive or negative when

    adding the values.

    lf the fan speed is changed more than

    5% from the original designed rpm, or

    if parts such as shaft, fan wheels,

    bearings, or other drive componentsare replaced, the unit vibration should

    be checked. Do not exceed max. fan

    RPM.

    Pay particular attention to any vibration,

    noise or overheating of the fan

    bearings and motor (bearings may run

    warm during break in)

    Note: During break in period, bearing

    temperature may be 1500

    F and 1600

    F.For normal running, bearing

    temperature is 900F to 1000F.

    Excessive Vibration-must be corrected

    to prevent bearing and shaft damage.

    The trouble shooting section details

    the common causes for vibration.

    Determining fan FPM - can be

    determine by using a strobe-type

    tachometer, or revolution counter.

    Sheave Alignment

    Align the fan and motor sheaves by

    using a straight edge as shown in the

    Figure 16.

    The straightedge must be long

    enough to span the distance between

    the outside edges of the sheaves.

    When the sheaves are aligned, the

    straightedge will touch booth sheavesat points A through D.

    (L avg -L1)+(L avg-L2 )+(L avg-L3) x100 = %unbalance

    2 x L avg

    L avg = Average line voltage of lines

    L1, L2 and L3

    L1 = Line 1 voltage

    L2 = Line 2 voltage

    L3 = Line 3 voltage

    22

  • 8/20/2019 CLCP_IOM

    25/44

    TRANE R

    Wiring/Start-Up Procedure

    Figure 16

    Sheave Alignment

    Fan Belt Tension/Alignment

    Note: Fan belt tension should be

    checked at least twice during the first

    day of operation, since there is a rapid

    decrease in tension until belts are run

    in.

    Proper belt tensioning is required to

    ensure maximum bearing and drive

    component life and is based on fan

    brake horsepower requirement.

    Belt Tension Measurement

    Check the belt tension as follows:

    Measure the span length of the drive

    (in mm). With a belt tensioner at the

    center of the span. apply a force K

    (perpendicular to the span) large

    enough to deflect the belt 15mm per 1

    meter of span. Refer to figure 17.

    DEFLECTION = SPAN X 15/1000mm

    The deflection force for the belt should

    be within the minimum and maximum

    force shown in the Table A. When the

    tension drops to the minimum value,

    readjust to the maximum value.

    To measure belt tension, use a belt

    tensioner as shown in Figure 18.

    Determine actual deflection by

    depressing one belt with the belt

    tensioner and measuring the

    deflection relative to the other belts or

    to belt line. Adjust the belt tension tothe correct force (Newton) and tighten

    all setscrews to the proper torques.

    Figure 17

    Belt Tension Measurement

    23

  • 8/20/2019 CLCP_IOM

    26/44

    TRANE R

    24

    Wiring/Start-Up Procedure

    Table A

    Deflection Force Table

    Figure 18

    Belt Tension Measurement

  • 8/20/2019 CLCP_IOM

    27/44

    TRANE R

    Maintenance

    Periodic MaintenanceChecklist

    The following checklist describes the

    suggested maintenance schedule to

    maintain proper operation of the unit.

    Detailed procedures for owner-

    operator maintenance checks aregiven after this checklist.

    Warning: Disconnect electrical power

    and allow rotating parts to stop before

    servicing the unit. Exercise caution if

    unit must be on for test or maintenance

    procedures. Failure to do so may result

    in injury or death from electrical shock

    or moving parts.

    Warning: Disconnect electrical powerprior to access into fan or ductwork.

    Even when locked out electrically, fans

    may cause injury or damage if the

    impeller is subject to "windmilling". The

    impeller should be secured to

    physically restrict rotational movement

    can cause severe personal injury or

    death.

    After 48 Hours Operation

    [*] Belts have acquired theirpermanent stretch. Readjust but do not

    overtighten(Ref. Start-Up Procedures

    section in this manual).

    Weekly

    [*] Observe unit weekly for any change

    in running condition and any unusual

    noise.

    Every Month

    [*] Check air filters. Clean or replace ifclogged or dirty. Coat permanent filters

    with oil after cleaning. Change bag

    filters when pressure drop is 1-inch

    W.G.

    Every Three to Six Months

    [*] Check greasing on fan and motor.

    [*] Align fan and motor sheaves

    (pulley). Tighten sheaves setscrews to

    the proper torque.

    [*] Check and adjust fan belt tension.

    [*] Tighten electrical connection.

    [*] lnspect coils for dirt build-up or coil

    freeze up

    Every Year

    [*] lnspect the unit casing for corrosion.

    lf damage is found, clean and repaint

    the surface with a rust-resistant primer

    and vinyl chlorinated lacquer.

    [*] Clean the fan wheels and fan shaft.

    Remove rust with emery cloth and

    apply a coat of LPS#3 or an equivalent.

    [*] lnspect the condensate drain pan

    and drain line, remove sludge or

    foreign materials that might obstruct

    proper drainage. Remove obstacles.

    [*] Check damper linkages, set-screws

    and blade adjustment for proper

    damper operation.

    [*] lnspect the control and power box

    wiring for secure connections and

    insulation.

    [*] Rotate the fan wheel and check for

    obstruction in the fan housing. The

    wheel should not rub on the fan

    housing. Adjust the center if necessary

    and tighten wheel setscrews to the

    proper torque.

    [*] Check condition of gasketing and

    insulation around unit, door and

    damper.

    [*] Examine flex connections for cracks

    or leaks. Repair or replace damage

    material.

    25

  • 8/20/2019 CLCP_IOM

    28/44

  • 8/20/2019 CLCP_IOM

    29/44

    TRANE R

    Trouble Analysis

    27

  • 8/20/2019 CLCP_IOM

    30/44

    TRANE R

    Trouble Analysis

    Maintenance Procedures

    Warning: Disconnect electrical power

    source before sevicing the unit or

    connecting electrical wires. Failure to

    do so may result in personal injury or

    death from electrical shocks or

    entanglement in moving.

    Air Filters

    Appendix D provides filter size, type and

    quantity. To replace throwaway filters,

    install new filters with the directional

    arrows pointing in direction of airflow.

    To clean permanent filters wash under

    a stream of water to remove dirt and

    lint. Remove oil filter (aluminum or

    grease filter) with a wash of mild alkalisolution. Rinse in clean, hot water and

    allow to dry. Coat both sides of the filter

    by immersing or spraying it with Air

    Maze Filter Lote W or equivalent. Allow

    to drain and dry for about 12 hours.

    Fan Bearings Lubrication

    Fan bearings are permanently sealed

    and lubricated. Do not attempt to

    lubricate bearings.

    Fan Motors

    lnspect periodically for excessive

    vibration or temperature. Operating

    conditions will vary the frequency of

    inspection and lubrication. Contact the

    motor manufacturer or Trane for

    lubrication instruction. Most smaller

    frame motors comes without oil tubes

    or grease nipple where the bearingsare permanently sealed.

    The motors with double shielded

    bearings are lubricated for life and

    cannot be relubricated.

    W.E motors up to 132 frame and TECO

    and Brook Hansen motors up to 180

    frame comes with sealed for life

    bearings, while motors above this

    range, have open bearings with "flush

    through" re-greasing facilities.

    To re-lubricate the motor, complete the

    following:

    1.Turn the motor off. Make sure it

    cannot accidentally restart.

    2. Remove the relief plug and clean out

    any hardened grease.

    3. Add fresh grease through the fitting

    with low pressure grease gun.

    4. Run the motor for few minutes to

    expel any excess grease through

    the relief vent.

    5. Stop the motor and replace the relief

    plug.

    Table1Motor Greasing lntervals

    Standard condition: 8 hour operation

    per day with rated or light loading in a

    clean and low vibration environment.

    Severe condition: 24 hour operation per

    day with rated/light loading or in a dirty/ 

    dusty environment or where the motor

    is subject to vibration/light shock

    loading.

    Grease Type:

    TECO/Brook Hansen motor - Use

    Esso Unirex Lithium N3 grease.

    W.E motor - Use Shell Alvania R3.

    Coil Cleaning

    Steam, hot water and chilled watercoils should be kept clean to maintain

    maximum performance. lf fins become

    dirty, clean with steam and detergent,

    hot water spray and detergent, or one

    of the commercially available chemical

    coil cleaners. Rinse coils throughly

    after cleaning.

    Warning: Follow all directions provided

    with chemical cleaners to avoid

    personal injury and/or coil damage.Commercially available chemical

    cleaners may contain caustic or

    hazardous agents.

    WARNING: DISCONNECT POWER

    SOURCE FOR MOTOR

    LUBRICATION. FAILURE TO DO SO

    MAY RESULT IN INJURY OR DEATH

    FROM ELECTRIAL SHOCK OR

    MOVING PARTS.

    !

    28

  • 8/20/2019 CLCP_IOM

    31/44

    TRANE R

    29

    Trouble Analysis

    Refrigerant coils should be kept clean

    to maintain maximum performance. lf

    fins become dirty, clean with cold water

    and detergent or one of the

    commercially available chemicals coil

    cleaners. Rinse coils thoroughly after

    cleaning.

    Warning: Never use steam or hot water

    to clean a refrigerant coil. Dangerous

    pressures may be built up by improper

    application of heat resulting in

    equipment damage or personal injury.

    Coil Winterization

    Provisions must be made to drain

    those

    coils that are not in use when subjected

    to freezing temperatures.

    Caution: Failure to properly drain and

    vent coils when not in use during

    freezing temperatures may result in

    coil freeze-up damage. Drain and vent

    hardware provided by installing

    contractor.

    To drain these coils, blow out the coils

    with compressed air, fill and drain the

    tubes with full-strength ethylene glycol

    several times, and then drain the coilas completely as possible.

    Trouble Analysis

    Use the tables in this section to assist

    in identifying the cause or causes of a

    malfunction in Modular Climate

    Changer operation. The column

    header RECOMMENDED ACTION will

    suggest repair procedures.

    Note: These tables are intended as a

    diagnostic aid only. For detailed repair

    procedures, contact your local Trane

    Service Company.

      WARNING:  DISCONNECT

    ELECTRICAL POWER PRIOR TO

    ACCESS INTO A FAN OR

    DUCTWORK. EVEN WHEN

    LOCKED OUT ELECTRICALLY,

    FANS MAY CAUSE INJURY ORDAMAGE IF THE IMPELLER

    SHOULD BE SECURED TO

    PHYSICALLY RESTRICT

    ROTATIONAL MOVEMENT FAILURE

    TO SECURE IMPELLER CAN

    CAUSE SEVERE PERSONAL

    INJURY OR DEATH.

    !  WARNING:  DISCONNECTELECTRICAL POWER SOURCE

    AND ALLOW ALL ROTATING

    EQUIPMENT TO STOP

    COMPLETELY BEFORE

    INSPECTING OR SERVICING THE

    UNIT. FAILURE TO DO SO MAYRESULT IN PERSONAL INJURY OR

    DEATH FROM ELECTRICAL SHOCK

    OR MOVING PARTS.

    !

  • 8/20/2019 CLCP_IOM

    32/44

    TRANE R

    30

    Trouble Analysis

    Pulley and Belt

  • 8/20/2019 CLCP_IOM

    33/44

    TRANE R

    Appendix B

    HDT - Unit Weight

    31

    50mm Casing

    HDT Unit Weight (kg) _ Fan and Coil Sections (without motor weight)

    25mm Casing

    Motor Weight (kg)

    1. Coil weight is the operating weight.

  • 8/20/2019 CLCP_IOM

    34/44

    TRANE R

    Appendix B

    HDT - Unit Weight

    32

    HDT Unit Weight (kg) - Fan + Coil + Filter Sections (without motor weight)

    50mm Casing

    25mm Casing

    Motor Weight (kg)

    1. Coil weight is the operating weight.

    2. Filter weight include filter media.

  • 8/20/2019 CLCP_IOM

    35/44

    TRANE R

    Appendix B

    HDT - Unit Weight

    33

    HDT Unit Weight (k g) - Fan + Coil + Filter and Mixing Sections (without motor weight)

    50mm Casing

    25mm Casing

    Motor Weight (kg)

    Note:1. Coil weight is the operating weight.

    2. Filter weight includes filter media.

  • 8/20/2019 CLCP_IOM

    36/44

    TRANE R

    Appendix B

    VDT - Unit Weight

    34

    Note:1. Coil weight is the operating weight.

    VDT Unit Weight (kg) - Fan and Coil Sections (without motor weight)

    50mm Casing

    25mm Casing

    Motor Weight (k g)

  • 8/20/2019 CLCP_IOM

    37/44

    TRANE R

    Appendix B

    VDT - Unit Weight

    35

    Motor Weight (kg)

    50mm Casing

    VDT Unit Weight (kg) _ Fan + Coil + Filter Sections (without motor weight)

    25mm Casing

    Note:1. Coil weight is the operating weight.2. Filter weight includes filter media.

  • 8/20/2019 CLCP_IOM

    38/44

    TRANE R

    Appendix C-

    Fans and Arrangement

    36

    Fan Size and Diameter

  • 8/20/2019 CLCP_IOM

    39/44

  • 8/20/2019 CLCP_IOM

    40/44

    TRANE R

    Appendix D-

    Filter and Quantity

    38

    Filter Dimension and Arrangement

    High Capacity Filter

  • 8/20/2019 CLCP_IOM

    41/44

    TRANE R

    Appendix D-

    Filter and Quantity

    39

    Filter Dimension and Arrangement

    Final Filter

  • 8/20/2019 CLCP_IOM

    42/44

    TRANE R

    Appendix E-

    Motor Detail

    40

    OUTPUT

    HP

    0.25

    0.5

    0.75

    11.5

    2

    3

    4

    5

    5.5

    7.5

    10

    15

    20

    25

    30

    4050

    60

    75

    100

    Kw

    0.18

    0.37

    0.55

    0.751.1

    1.5

    2.2

    3

    3.7

    4

    5.5

    7.5

    11

    15

    18.5

    22

    3037

    45

    55

    75

    FULL LOAD

    63.5

    67.0

    71.5

    74.074.0

    76.5

    81.0

    83.5

    84.5

    85.0

    86.0

    88.0

    89.5

    90.0

    91.0

    91.5

    92.592.5

    92.5

    93.5

    94.0

    0.75 LOAD

    63.0

    65.0

    70.5

    73.074.0

    77.0

    80.5

    83.0

    84

    84.5

    85.0

    88.0

    89.0

    90.0

    91.5

    91.5

    92.592.5

    92.5

    93.0

    94.0

    0.5 LOAD

    58.0

    59.0

    65

    69.070.0

    74.0

    78.5

    80.5

    82.5

    83.0

    83.5

    86.5

    88.0

    88.5

    91.0

    91.5

    92.092.0

    92.0

    91.5

    93.0

    FULL LOAD

    70.0

    70.0

    74.0

    77.079.0

    81.0

    82.5

    82.0

    83.5

    82.0

    82.5

    85.0

    86.5

    86.0

    86.0

    86.5

    86.585.0

    85.5

    89.0

    93.5

    0.75 LOAD

    61.0

    60.0

    65.0

    68.071.0

    73.5

    76.0

    75.5

    76.5

    77.0

    76.0

    80.0

    82.5

    81.5

    83.0

    83.5

    84.081.5

    83.5

    87.5

    94.0

    0.5 LOAD

    49.0

    48.0

    52.0

    54.058.5

    61.0

    63.0

    63.0

    65.0

    65.0

    64.0

    70.0

    74.0

    73.0

    78.0

    76.5

    77.075.5

    77.0

    83.0

    92.5

    SPEED

    (RPM)

    1350

    1390

    1405

    14001400

    1405

    1425

    1430

    1440

    1440

    1445

    1450

    1465

    1460

    1455

    1460

    14701475

    1470

    1475

    1475

    EFFICIENCY (%)FRAME

    NO.

    63

    71

    80

    8090S

    90L

    100L

    100L

    112M

    112M

    132S

    132M

    160M

    160L

    180MC

    180LC

    200LC225SC

    225MC

    250SC

    250MC

    POWER FACTOR (%)

    FULL LOAD

    CURRENT (AMP)

    FULL LOAD

    CURRENT (AMP)

    LOCKED - ROTOR

    TORQUE, Tf

    (kg.m)

    0.134

    1

    1.61

    1.99

    2.91

    3.66

    5.08

    6.62

    8.03

    8.95

    12

    15.2

    22

    29.3

    36.2

    42.9

    56.672.1

    86

    102

    129

    LOCKED

    ROTOR (%)

    260

    265

    260

    260210

    220

    250

    330

    220

    250

    240

    275

    235

    240

    200

    215

    230200

    190

    200

    180

    380 V

    0.64

    1.11

    1.47

    1.822.66

    3.35

    4.66

    6.06

    7.35

    8.19

    11

    13.9

    20.1

    26.8

    33.2

    39.3

    51.966

    78.7

    93.5

    119

    415V

    0.59

    0.261

    0.387

    0.5180.778

    1.033

    1.528

    2.03

    2.523

    2.772

    3.767

    5.006

    7.432

    9.943

    12.47

    14.91

    19.7524.61

    29.63

    39.91

    49.21

    380 V

    2.6

    5.3

    8.4

    1116

    21

    34

    49

    63

    63

    79

    111

    153

    205

    226

    284

    400453

    511

    684

    979

    415V

    2.4

    4.8

    7.7

    1014

    19

    31

    45

    58

    58

    72

    101

    140

    188

    207

    260

    366414

    467

    627

    896

    Three-Phase Squirrel - Cage (Standard Induction Motors) 50Hz Totally Enclosed Fan Cooled (TEFC) Horizontal Foot

    Mounting, 4 Poles

  • 8/20/2019 CLCP_IOM

    43/44

    TRANE R

    Safety Recommendations

    To avoid accidents and damage, the

    following recommendations should be

    observed during maintenance and

    service visits:

    1. Disconnect the main supply beforeany servicing on the unit.

    2. Service work on the refrigeration

    system and the electrical system

    should be carride out only by

    qualified and experienced

    personnel.

    Maintenance Contract

    lt is strongly recommended that you

    sign a maintenance contract with yourlocal Service Agency. This contract

    provides regular maintenance of your

    installation by a specialist in our

    equipment. Regular maintenance

    ensures that any malfunction is

    detected and corrected in good time

    and minimizes the possibility that

    serious damage will occur. Finally,

    regular maintenance ensures the

    maximum operating life of your

    equipment. We would remind you thatfailure to respect these installation and

    maintenance instructions may result

    in immediate cancellation of the

    warranty.

    The manufacturer has a policy of 

    continuous product improvement, and 

    reserves the right to alter any details of 

    the products at any time without notice.

    This publication is a general guide to 

    install, use and properly maintain our 

    products. The information given may 

    be different from the specification for a 

    particular country or for a specific order.

    ln this event. Please refer to your 

    nearest office.

    ln no event shall Trane be liable for 

    any incldental or consequential 

    damages resulting from the use,

    misuse or inability to use the product.

    Training

    The equipment described in this

    manual is the result of many years

    of research and cont inuous

    development. To assist you in

    obtaining the best use of i t and

    maintaining it in perfect operating

    condition over a long period of time,

    the manufacturer has at your

    disposal a refr igerat ion and air

    conditioning service school. The

    pr incipal aim of this is to give

    operators and technicians a better

    knowledge of the equipment they

    are using, or that is under their

    charge. Emphasis is particularly

    give to the importance of periodic

    checks on the uni t operat ing

    parameters as well as on preventive

    maintenance. which reduces the

    cost of owning the unit by avoiding

    serious and costly breakdown.

    For additional information, contact:

    Distirbutor / Installer stamp

    41

  • 8/20/2019 CLCP_IOM

    44/44

    Literature Order NumberTRANE 

    IND-SVN01A-E4 (December 2006)