ieee_pecon_1569336945_4_
TRANSCRIPT
![Page 1: IEEE_pecon_1569336945_4_](https://reader036.vdocuments.pub/reader036/viewer/2022081805/577d33f61a28ab3a6b8c3857/html5/thumbnails/1.jpg)
8/8/2019 IEEE_pecon_1569336945_4_
http://slidepdf.com/reader/full/ieeepecon15693369454 1/6
Steady State Investigation of Self Excited 3
Phase Induction Generator with Novel
Leading VAR Controller and Mitigation of
Harmonics Using Active Power Filter Vargil Kumar E
Department of EEE, Gudlavalleru
Engineering College, Gudlavalleru,
A.P. 521 356, INDIA
Narasimham PVRLDepartment of EEE, Gudlavalleru
Engineering College, Gudlavalleru,
A.P. 521 356, INDIA
Sarma AVRSDepartment of Electrical Engg.,
Osmania University, Hyderabad,
A.P. 520 001, INDIA
Abstract – Self Excited Induction Generator (SEIG) is
identified as isolated power source, whose terminal voltage
and frequency are controlled by varying speed, excitation
capacitance or load impedance. Since load changes from
time to time, the output parameters mostly are controlledby either speed or by varying excitation capacitance. To
reduce the complexity in analysis, the speed of a prime-
mover driving the induction generator is kept constant. For
proper voltage built-up suitable value of excitation
capacitance is necessary.
This paper presents a method for calculating the
minimum excitation capacitance using the equivalent
circuit approach for analyzing the steady state operation of
SEIG. Change in load impedance forces alteration in the
value of excitation capacitance which is difficult to be
implemented. A novel leading VAR controller (LVARC)
consisting of uncontrolled converter, inverter and a series
LCR resonance circuit, is introduced in between the load
and source to take care of reactive power disparity thereby
feeding the reactive power to the inductive loads andabsorbing reactive power for capacitive loads.
A closed loop operation of SEIG was developed using
Shunt Active Power Filter (SAF) is used for harmonic
elimination.
MATLAB based simulation and experimental results
are presented and compared for VAR controller operated
with linear loads. Simulation study is made for Non-Linear
loads with respect to SAF’s. The simulation results show
the effectiveness of Voltage built-up and harmonic
reduction in Wind based Power Generation.
Key words: SEIG, Leading VAR Controller, Shunt Active Power
Filter (SAF), Harmonics.
I I NTRODUCTION
The depleting Energy resources had made the present
society to rethink about the Power generation procedures
and paved a path for utilizing Non-renewable energy
resources [1]. One such resource is Wind Energy, where
the generated output power varies as the cube of wind
speed shown in Fig.1.
3
2
1ν ρ A pC P = (1)
Where ρ is the air density, ‘C p’ is the power coefficient
and ‘A’ is the rotor swept area and ‘v’ is the wind speed
Basically the wind generation schemes involve
induction generators, not only of its usage in large
numbers but also due to varied modes of operation both
under steady and dynamic states. Increased use of Power
Electronic controllers with such machines makesappropriate modeling and parameter identification
crucial, for both working control strategies and
performance predictions.
Induction Generator (IG) is not able to start on its
own and sustain electrical oscillations. To sustain the
electrical oscillations, reactive magnetization current
should be completely compensated by appropriate
reactive current [2, 3]. It is well known that a suitable
capacitor is compulsory to be connected at the output
terminals of induction machine while working as
generator, which raises a problem in designing the value
of capacitor. This paper confers a simple nevertheless
open methodical procedure to perceive the steady statecondition using the operational equivalent circuit of the
machine [5, 6].
SEIG has to supply both the linear and non-linear
loads. As a result, the reactive power oscillation has to
take place between the source and the load, which
enforces the VAR control, envisaging the usage of
power electronic switching devices and passive energy-
storage-circuit elements inductors or capacitors. These
elements can be used for controlling current harmonics
at the low or medium-voltage distribution levels or for
controlling reactive power, and voltage [7-10].
Fig1. Speed and Power Output Characteristic
2010 IEEE International Conference on Power and Energy (PECon2010)., Nov 29 - Dec 1, 2010, Kuala Lumpur, Malaysia
978-1-4244-8945-9/10/$26.00 ©2010 IEEE 495
![Page 2: IEEE_pecon_1569336945_4_](https://reader036.vdocuments.pub/reader036/viewer/2022081805/577d33f61a28ab3a6b8c3857/html5/thumbnails/2.jpg)
8/8/2019 IEEE_pecon_1569336945_4_
http://slidepdf.com/reader/full/ieeepecon15693369454 2/6
In a capacitance excited SEIG, the terminal voltage
and its frequency are dependent on exciting capacitance,
speed and load impedance. The required exciting
capacitance calculation for a load impedance is
estimated through a MATLAB program, by keeping the
prime mover speed as constant.
II THEORY OF PROPOSED VAR CONTROLLER
With the designed capacitance, and constant prime-
mover speed the terminal voltage of IG reaches torequired voltage.
The controller consists of three parts – the front
end uncontrolled rectifier, the SPWM inverter and the
LCR series circuit shown in Fig. 2. The VAR controller
circuit is used in conjunction with the fixed minimum
capacitance, which is permanently connected to the
machine terminals. With increase in load the capacitance
required to sustain the terminal voltage increases, this
increase in the reactive power requirement.
Change in the load current will insist to change
AC/DC/AC resonance circuit current in opposite
direction. The total generator current should be
maintained at the rated current. At any instant of time
AC/DC/AC converter is operated to balance the load
current to maintain the generator current constant. The
variable frequency operation of series resonance LCR
circuit effectively takes care of VAR variation in load,
which is supplied by the VAR controller by operating
the inverter either below or above the resonant
frequency.
Because of proposed VAR controller, the power
factor variation of SEIG is minimized. The mathematical
approach in relation to above discussion is given in the
commencing section.
III MODELING OF PROPOSED VAR CONTROLLER
The advantage in this scheme is that only, fixed
minimum capacitance is needed to be connected to the
SEIG, and also this scheme provides smooth terminal
voltage regulation. The per phase equivalent circuit
given in Fig.3, is taken to derive the expression for
terminal capacitance.
Here core losses are being ignored. For the
minimum capacitance requirement, the machine must
operate at the threshold of saturation. All the parameters
except ‘Xm’ magnetizing reactance are assumed
constant.
The voltage in the loop PQRS can be written as
0=eqloop Z . I (2)
The loop equivalent impedance “Zeq” of SEIG with
proposed controller is given by reducing the circuit
around the loop PQRS
⎥⎥⎥⎥⎥⎥
⎦
⎤
⎢⎢⎢⎢⎢⎢
⎣
⎡
⎥⎥⎦
⎤
⎢⎢⎣
⎡⎥⎦
⎤⎢⎣
⎡+⎟⎟
⎠
⎞⎜⎜⎝
⎛
−
+
⎥⎥⎦
⎤
⎢⎢⎣
⎡
⎟⎟
⎠
⎞
⎜⎜
⎝
⎛ ⎥⎦
⎤⎢⎣
⎡+⎟⎟
⎠
⎞⎜⎜⎝
⎛
+
⎥⎥⎦
⎤
⎢⎢⎣
⎡
⎟⎟ ⎠
⎞
⎜⎜⎝
⎛ −
⎥⎦
⎤
⎢⎣
⎡−+
⎟⎟ ⎠
⎞
⎜⎜⎝
⎛
⎥⎦
⎤
⎢⎣
⎡+
=
mr r
s s
ct csh
lsh
sh
ll
l
jX jX f
R jX
f
R
f
jX
f
jX
jX f
R
jX f
R
eq Z
ν
22
(3) On solving and combining similar terms in eq.3 a
complex equation in terms of terminal capacitive
reactance ‘X ct ’ frequency ‘f’ is achieved.
⎥⎥⎥⎥⎥
⎦
⎤
⎢⎢⎢⎢⎢
⎣
⎡
−+
+−
+
+
−−++++−
−++−
=
4v)E j(f 3 E
2 jE 1v)E (f
f
2 jfB1 B
+
ct X 11 fA )10 Act X 9(A2
jf )8 Act X 7 (A3
f 6 A4
jf 5 A5
f
)4 A3 jfA2 A2
f 1 A3
jf ( ct X
eq Z
(4)
Under steady state self excitation the loop current is not
zero,( 0≠loop I ), so equivalent impedance is assumed
to be zero [6]. The real and imaginary parts of ‘Z eq’ are
zeros. From eq. 4 separating the real and imaginary parts
of the terminal capacitance ‘ X ct ’ are obtained as
11102
93
84
75
62
53
44
35
26
17
fM M f M f M f M f
M f M f M f M f M f M f
real ct X
++++
+++++
= (5)
982
73
64
52
43
34
25
16
fI I f I f I f
I f I f I f I f I f
imag ct X +++
++++
=
(6)
The terminal capacitance is to be calculated it should
simultaneously satisfy both eq.5 and eq.6. is obtained by
equating both of them, resulting in a 11 th order equation
in ‘ f ’.
93
84
75
66
57
48
39
210
111
J f J f J f J f J f J f J f J f J f ctl X ++++++++=
(7)
Fi .2 Pro osed VAR controller with SEIG
Fig. 3 Equivalent circuit of SEIG with proposed controller.
496
![Page 3: IEEE_pecon_1569336945_4_](https://reader036.vdocuments.pub/reader036/viewer/2022081805/577d33f61a28ab3a6b8c3857/html5/thumbnails/3.jpg)
8/8/2019 IEEE_pecon_1569336945_4_
http://slidepdf.com/reader/full/ieeepecon15693369454 3/6
The solution of the eq.7 is tedious and lengthy a
MATLAB m-file program was written and solved. By
conducting suitable tests, and using the basic equations
of induction machine the proposed VAR controller is
designed, and open loop operation is being assessed for
linear loads and nonlinear loads, by verifying the
theoretical and experimental results and are presented in
section VIII.
Operation of LVARC happened to an open loopsystem is effective with respect to linear, but coming to
nonlinear loads the harmonic current are not properly
taken care because of presence of fast acting nonlinear
switching devices (as shown in Fig.13, Fig. 18 can be
compared). So a closed loop system based on shunt
active power filter is designed, the discussion follows.
IV CLOSED LOOP SAF DESIGN FOR SEIG
When SEIG supplies a non-linear load, the load
draws a fundamental component of current and harmonic
current from the generation systems, which are to be
properly controlled. The shunt APF can compensate the
harmonic current by continuously tracking the changesin harmonic content. APF’s consists of a voltage fed
converter with a PWM current controller and an active
filter controller that realizes an almost instantaneous
control algorithm shown in Fig.4.
The SAF works in a closed loop manner,
continuously sensing the load current and calculating the
instantaneous values of the compensating current
reference I c* for the PWM converter. In an ideal case,
the PWM converter may be considered as a linear power amplifier, where the compensating current I c tracks
correctly its reference I c*.
V MATHEMATICAL MODELING OF SAF-SEIG
The source voltages in all the three phases are
combined with currents, are converted to Vα ,Vβ , and Iα
,Iβ by using Clarke Transformation. These space vectors
are easily transformed into a three coordinates as follows
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
⎥⎥
⎦
⎤
⎢⎢
⎣
⎡ −
=
⎥⎥⎦
⎤
⎢⎢⎣
⎡
cvb
v
av
23
1/2
23
1/2
0
1
3
2
β v
αv
(9)
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
⎥⎥
⎦
⎤
⎢⎢
⎣
⎡ −
=
⎥⎥
⎦
⎤
⎢⎢
⎣
⎡
cibi
ai
23
1/2
23
1/2
0
1
3
2
β i
αi
The conventional instantaneous power on the three phase
circuit can be defined by using ‘p-q’ theory as
β β α α .iv.iv += p (10)
Instantaneous reactive power is defined by
αββα .iv.ivq += (11)
The conventional instantaneous power, ‘p’ and the
Instantaneous imaginary power ‘q’, are expressed by
⎥⎥⎦
⎤
⎢⎢⎣
⎡
⎥⎥
⎦
⎤
⎢⎢
⎣
⎡
−=⎥
⎦
⎤⎢⎣
⎡
β
α
α β
β α
i
i
vv
vv
q
p
(12)After determining the active and reactive power signals,
they are smoothened by passing through a low pass
filter. Later they are converted back to three phase
reference currents and made available for comparison
with actual currents. Both are fed to Hysteresis Current
Controller (HCC) where the firing angle corresponding
to the difference of the two signals is generated and fed
to Inverter shown in Fig. 5.
The inverter is enabled to act as a filter and the use of
inductive and capacitive elements can be vanished out,thereby reducing the cost involved on them (as in case of
LVARC). And this filter design promises the closed loop
control and provides better efficient harmonic
elimination, which is validated by simulation results.
VI SIMULATION METHODOLOGY
The required capacitance value (C = 105.2 µFd) of
SEIG has been calculated from the steady state
Fig. 4 Block Diagram of APF
Fig. 5 A Three phase, Three-wire, Current Compensation SAF
497
![Page 4: IEEE_pecon_1569336945_4_](https://reader036.vdocuments.pub/reader036/viewer/2022081805/577d33f61a28ab3a6b8c3857/html5/thumbnails/4.jpg)
8/8/2019 IEEE_pecon_1569336945_4_
http://slidepdf.com/reader/full/ieeepecon15693369454 4/6
equivalent circuit, using MATLAB m-file program by
solving a 11th order equation in ‘X ct ’ , and simulation of
SEIG with proposed VAR controller and the closed loop
operation with SAF is being done using simpower
systems block-set of MATLAB/Simulink. The Simulink
models of SEIG with LVARC and SAF is shown in
Fig.6, Fig.7 and results of LVARC are presented in Fig.8
to Fig.10 for linear loads and Fig. 11 to Fig. 12 for
Nonlinear loads. The results of SAF with Non-linear loads are presented in Fig. 16 for Voltage built-up;
variation of voltage, current in Fig. 17; and Pulse
Generation using current controller in Fig. 18.
VII R ESULTS
A 3-φ, 3 KVA, 415V, 7A alternator is connected
across R-L load, and a drop of about 45V is calculated to
be controlled. For convenience the voltage waveform in
the graphs from 8 to 11 are scaled by 5, in order to get a
better view of voltages and currents.
0.56 0.57 0.58 0.59 0.6 0.61 0.62
-10
0
10
S o u r c e
O u t p u t
0.56 0.57 0.58 0.59 0.6 0.61 0.62
-10
0
10
C o n t r o l l e r
O u t p u t
0.56 0.57 0.58 0.59 0.6 0.61 0.62
-10
0
10
Time in Seconds
L o a d
O u t p u t
0.56 0.57 0.58 0.59 0.6 0.61
-5
0
5
S o u r c e
O u t p u t
0.57 0.58 0.59 0.6 0.61 0.62
-10
0
10
C o n t r o l l e r
O u t p u t
0.56 0.57 0.58 0.59 0.6 0.61 0.62-10
-5
05
Time in Seconds
L o a d
O u t p u t
0.56 0.57 0.58 0.59 0.6 0.61
-5
0
5
S o u r c e
O u t p u t
0.57 0.58 0.59 0.6 0.61 0.62
-5
0
5
C o n t r o l l e r
O u t p u t
0.56 0.57 0.58 0.59 0.6 0.61 0.62-10
-5
0
5
Time in Seconds
L o a d
O u t p u t
0.6 0.61 0.62 0.63 0.64 0.65 0.66 0.67 0.68 0.69 0.7
-5
0
5
S o u r c e O u t p u t
0.6 0.61 0.62 0.63 0.64 0.65 0.66 0.67 0.68 0.69 0.7
-5
0
5
C o n t r o
l l e r O u t p u t
0.6 0.61 0.62 0.63 0.64 0.65 0.66 0.67 0.68 0.69 0.7
-5
0
5
Time in Seconds
L o a d O u t p u t
Fig. 10 Leading VAR Control of proposed Controller
Fig. 8 Lagging VAR Control of proposed Controller
Fi . 9 In- haseVAR Control of ro osed Controller simulation
Fig. 7 Simulation of SEIG with Active Power Filter and HysteresisCurrent Controller with non-linear Load
Fig. 11 Leading VAR Control of proposed Controller with
Nonlinear Loads
Fig. 6 Simulation of SEIG with proposed VAR controller
498
![Page 5: IEEE_pecon_1569336945_4_](https://reader036.vdocuments.pub/reader036/viewer/2022081805/577d33f61a28ab3a6b8c3857/html5/thumbnails/5.jpg)
8/8/2019 IEEE_pecon_1569336945_4_
http://slidepdf.com/reader/full/ieeepecon15693369454 5/6
0.6 0.62 0.64 0.66 0.68 0.7 0.72 0.74
-5
0
5
V o l t a g e o f P h a s e ' a '
o f L V A R C
0.6 0.62 0.64 0.66 0.68 0.7 0.72 0.74
-5
0
5
Time in Seconds
C u r r e n t i n p h a
s e ' a '
o f L V A R C
VIII POWER QUALITY A NALYZER R ESULT The observed phasors are obtained using the
FLUKE power quality analyzer and are given in Fig.13
to Fig.15. The variable impedance effect of the LCR
series circuit with the change in inverter output
frequency was observed. 0.6 0.62 0.64 0.66 0.68 0.7
-4
-2
0
2
4
V o l t a g e
i n
p h a s e
' a ' o f S A F
0.6 0.62 0.64 0.66 0.68 0.7
-4
-2
0
2
4
Time in Seconds
C
u r r e n t i n
p h a s e
' a ' o f S A F
0.6 0.62 0.64 0.66 0.68 0.7
-2
0
2
C
u r r e n t i n
' A ' p h a s e
0.6 0.62 0.64 0.66 0.68 0.7
-4-202
D i s t o t e d
C u r r e n t
0.6 0.62 0.64 0.66 0.68 0.7
-202
E r r o r
C u r r e n t
0.6 0.62 0.64 0.66 0.68 0.7
0
0.5
1
Time in Seconds
H y s t e r e s i s
P u l e s e s
IX CONCLUSION
It can be accomplished that the minimum
excitation capacitance calculated from the design
equations was found to be 105.2µF, which aided proper
Fig. 14 Lagging effect at frequencies greater than
resonant fre uenc
Fig. 18 Waveforms of Reference currents, Controller Current, Error
current and H steresis ulse Generation
Fig. 16 Voltage built-up in all the three phases of SEIG-SAF
Fig. 17 Stator Voltages and currents in phase ‘A’ of SAFwith non linear loads.
Fig. 15 Leading effect at frequencies greater than
resonant frequency
Fig. 12 Stator Voltages currents in phase ‘A’ of
LVARC with non linear loads
Fig. 13 UPF effect at frequencies equal to resonant
499
![Page 6: IEEE_pecon_1569336945_4_](https://reader036.vdocuments.pub/reader036/viewer/2022081805/577d33f61a28ab3a6b8c3857/html5/thumbnails/6.jpg)
8/8/2019 IEEE_pecon_1569336945_4_
http://slidepdf.com/reader/full/ieeepecon15693369454 6/6
voltage built-up in an SEIG. The novel LVARC
introduced between SEIG and load has taken care of the
reactive power disparity by providing a reactive power
ranging from 10% to 40% of the rated capacity on an
average, feeding linear and non-linear loads. An
improvement in the voltage magnitude and power factor
is possible by changing the operating frequency of the
inverter in multiples of 50Hz, and the by varying LCR
component ratings above and below 35mH and 291 µF.The shunt active power filter with the aid of
hysteresis current controller had taken care of the uneven
distortion in current thereby smooth voltage
characteristic at the output is achieved in comparison
with LVARC technique. The Shunt active power filter
eliminated the harmonics by enabling the inverter to act
as a filter, fading away the usage of inductors and
capacitors, reducing the cost involved on them.
The simulation and experimental results proves
the effectiveness of VAR controller, and Shunt Active
Power Filter in Wind based Power System.
APPENDIX
By performing various tests on a 3φ squirrel cage
induction machine possessing a rating of 3.7KW, 415V,
50Hz the stator resistance and inductances were found
to be 0.057, and 0.001 p.u., and Rotor 0.04 and 0.001
p.u., and magnetizing reactance of 1.93 p.u. is preferred.
Expansion of various terms used in the equation are
given below
lshl ll sh
lshll
cshl
lshll lshl
ll shlshl
lshll
X R X R A
X X A X R A
X X R R A
X R X R A
X X A
+=
=
=
+=
+=
+=
6
5
4
3
2
1
csh
shl
cshl
lshll
cshll shl
X A
R R A
X R A
X X A
X X R R A
=
+=
=
+=
+=
11
10
9
8
7
)(
)(*
14366
135
3512344
33113
322
311
vQQM
QM QQvQM
QQM
vQM
QM
+−=
=
−+=
+=
−=
=
)(
)(*
170511
5516045410
0353159
02528
517
QQM
QQQvQM
QQQM
vQQM
QM
+−=
−−−=
++=
+=
=
255
2442414
40233
2239382
37211
)(*
)(*
Q I
QQvQ I
QQ I
QQvQ I
QQ I
=
−+=
−=
−+−=
−=
)(*
)(*
29099
28088
59582707517
5626066
QQv I
QQ I
QQQQvQ I
QQQ I
−=
−=
+++−=
++=
J1=(M1I6-M7I1)
J2=M1I7+M2I6-(M8I1+M7I2)
J3=M1I8+M2I7+M3I6-(M9I1+M8I2-M7I3)
J4=M1I9+M2I8+M3I7+M4I6-(M8I3+M9I2+M10I1+M7I4)
J5=M2I9+M3I8+M4I7+M5I6-
(M8I4+M9I3+M10I2+M11I1+M7I5)
J6=M3I9++M4I8+M5I7+M6I6-(M8I5+M9I4+M10I3+M11I2)
J7=M4I9+M5I8+M6I7-(M9I5+M10I4+M11I3)
J8=M5I9+M6I8-(M10I5+M11I4)
J9=M6I9-M11I5
R EFERENCES
1. Iulian Munteanu • Antoneta Iuliana Bratcu, Nicolaos-Antonio
Cutululis • Emil Ceang “Optimal control of Wind EnergySystems” , Springer Edn., 2007.
2. P.Vas, Electrical Machines and Drives – A Space Vector Approach, Oxford: Clarendon Press, 1992..
3. R.Rabinovici, “Autonomous excitation of induction generators”,
IEEE transactions on Mag., v.34, pp. 664-670, May 1998.
4. G.R.Slemon, Electric Machines and Drives, Reading, MA:
Addison-Wesley Publishing Company, Inc., 1992.5. Kh. Al Jabari and Alolah “ Limits on the performance of the Three
Phase Self-excited Induction Generators”, IEEE Transaction on
energy Conversion, vol.,5, No.2, Page 350-356,June 1990.
6. Kh. Al Jabari and Alolah, “Capacitance requirement for Self-excited Induction Generator”, IEE Proceeding, Vol.137, pt. C,
No.3, Page 154-159,May 1990. 7. S. Singaravelu, S. Velusami, “Capacitive VAR requirements for
wind driven self-excited induction generators”, Energy
Conversionand Management 48 (2007) 1367–1382.
8. Hirofumi Akagi, Yoshihira Kanazawa, and Akira Nabae.:
‘Instantaneous Reactive Power Compensators Comprising Switching Devices without Energy Storage Components’ , IEEE
Transactions on Industry Applications, Vol. IA-20, No. 3,
June1984.9. Jayant K. Chatterjee, B.Venkatsa Perumal, and Naveen Reddy
Gopu “Analysis of Operation of a Self Excited InductionGenerator with Generalized Impedance Controller”, IEEETrans. Power App. Sys., vol.22 No.2, pp. 307-315, 2006.
10. Bhim Singh, S.S. Murthy, and Sushma Gupta, “Analysis and Design of Electronic Load Controller for Self-Excited InductionGenerators”, IEEE Trans. On Energy Conversioon, Vol.21,
No.1, Page 285-294, March 2006.
500