mnit_001
TRANSCRIPT
-
7/30/2019 Mnit_001
1/12
1Issue/Rev. 0.2 (1/99)
Bulletin MNIT001
Model 505
January 1, 1999
INVALCO
Installation/Operation Manual
Meter Mounted Rate/Totalizer
Table of ContentsIntroduction................................................................................................................................2
Specifications................................................................................................................................2
Model Number Designation..............................................................................................................................2
Operation..................................................................................................................................2
Intrinsic Safety Considerations............................................................................................................................3
Programming Overview..........................................................................................................................................3
Program Steps.................................................................................................................................................3
Calculation of Rate and Total ..............................................................................................................................4
Total Conversion..............................................................................................................................................4
Filtering................................................................................................................................4
Simplified Setup for Model 505...........................................................................................................................5
Battery Powered Version..................................................................................................................................5
4-20mA Output Version.......................................................................................................................................6
DC Power Version............................................................................................................................................7
Flowmeter Input..............................................................................................................................................7
Installation........................................................................................................................................................9
Intrinsic Safety Connections...........................................................................................................................10
505 Settings for Cubic Meters/Day..........................................................................................................................11
Dimensions..............................................................................................................................................12
FMC INVALCO s Fluid Control s P.O. Box 1377s Stephenville, Texas 76401 s Telephone: 254/968-2181 s FAX 254/968-5709 sToll Free: 800/468-2526
-
7/30/2019 Mnit_001
2/12
2 Issue/Rev. 0.2 (1/99)
Introduction
The Model 505 Rate/Totalizer is designed to acceptfrequency or pulse inputs from a wide range offlowmeters and to display flowrate, a re-settable totaland an accumulated total directly in engineering units.The instrument is compatible with a wide range offlowmeters and a DIP switch on the input board en-ables the circuit to be configured for millivolt signals,reed switches, pulse trains and most other signal types.
Three different versions of the instrument are avail-able:
Battery Powered Version
Loop Powered Version
DC Powered Version with high and low flow alarms
The Model 505 is fully programmable with K-Factors,decimal point positions, filter constants and timebasebeing programmed via the front panel switches.
The instrument is housed in an attractive polycarbon-ate enclosure which is completely watertight and whichenables it to be mounted directly on a flowmeter orwall mounted using a special universal bracket.
Power/Options0 Lithium Battery Powered
1 Loop Powered 4-20mA
3 DC Powered with Alarms
4 DC Powered with input frequencyretransmission
Specifications
General Specifications
Display
Continuously powered LCD
Resettable Total
7 digits, 0.4 (10mm) high, resettable from the front panel
Accumulated Total
7 digits (as above), Not resettable
Rate
4 digits, .33 (8.5mm) high
K-Factor
Programmable, pulses per unit of measure, 0.2 to 29,999
Timebase
Rate displayed in units per second, minute, hour, or day
Frequency Range
0-5000 Hz
Input Signal
Switch settable; Sinewave (20mV P/P min), Pulse, ReedSwitch, others
Physical Specifications
Operating Temperature
0F to 160F (-20C to 70C)
Mounting
Meter mount standard, optional wall mounting kit available
Enclosure
Polycarbonate, meets Nema 4X and IP67 standards;Optional Explosion-proof Cls. 1, Div. 1, Grp C&D
Approvals
Battery operated version/Intrinsically safe to Class 1,Div. 1 Grp C&D; CSA/FM approval applied for;CENELEC Approval: KEMA
Model Number Designation
Model 505T -
Mounting2 Weatherproof Wall Mount Enc.
3 Explosion-proof MMT Enc.
4 Weatherproof MMT Enc.
7 Weatherproof MMT Enc.
with Swivel
Specifications (cont)
Battery Powered Version
Battery Type
Two Lithium Battery packs; Optional NiCad Batter pack(1/2 life-span)
Battery Life
2 to 3 years (dependant on % of time the instrument istotalizing flow)
Loop Powered 4-20mA Output Version
Scale
The 4mA and 20mA points are programmable.
Accuracy
0.5% of range
Connection
Two wire
Voltage Input
18 to 28 VDC (16 VDC voltage drop)
Memory Backup
Long life battery
DC Power/Alarm Version
Outputs
Two open collector, fully programmable, High/Low,Low/Low, or High/High contacts based on rate of flow
Switching Power
200mA, 30 VDC Maximum
Voltage Input
12-28 VDC at 8mA Maximum
Memory Backup
Long life battery
Operation
The Model 505 Rate Totalizer will display:
Rate
Resettable Total
Accumulated Total
Both the Rate and Resettable Total are continuouslydisplayed while the Accumulated Total is only displayedwhen the ACCUM TOTAL key is pressed. TheResettable Total can be reset at any time by pressingthe RESET key.
-
7/30/2019 Mnit_001
3/12
3Issue/Rev. 0.2 (1/99)
Operation (cont)
The instrument also has a test mode which can beentered by simultaneously pressing all three front panelkeys. The tests are as follows:
Lo Test - By pressing the ACCUM TOTAL key, thelow alarm output (if installed) will go low. If a 4-20mAoption is installed, the output will go to 4mA.
Hi Test - By pressing the RESET key, the high alarm
output (if installed) will go low. If a 4-20mA option isinstalled, the output will go to 20mA.
Display Test - By pressing the PROGRAM key, allsegments of the display will show.
To exit the test mode, press the ACCUM TOTAL keyand while still holding, simultaneously press the RE-SET and PROGRAM keys.
Intrinsic Safety Considerations
At the date this manual was issued, two versions of theModel 505 were certified for use in hazardous areas toboth CENELEC and Australian Standards.
The versions which have certification are:
Model 505i.20
Model 505i.40
Model 505i.21
Model 505i.41
CENELEC Approval: Kema
SAA Approval: Ex 2003x
Type of Protection: Ex ia
Group: IIB
Temperature Class: T4 at ambient temp. or 60C
When installing in hazardous areas, the instrumentmust be installed according to the guidelines given inthe Intrinsic Safety Connections Section and in accor-dance with standards for wiring and installation in haz-ardous areas.
CSA/FM approval has been applied for and will beoffered as the standard configuration when available.
Programming Overview
The Model 505 is fully programmable with all param-eters being stored in memory.
The Program Mode can be entered in one of two ways:
1. By removing the lower cover strip (i.e. the darkgrey strip along the bottom of the enclosure) andreplacing it after rotating 180. This brings a smallmagnet on the inside of the cover strip in contactwith a reed switch inside the instrument. The pro-gram key is then pressed to enter the ProgramMode.
2. By removing the front section of the enclosurewhich contains the main processor board and bat-teries. Once removed, the PROGRAM key ispressed to enter the Program Mode.
The PROGRAM switch is used to step through theprogram (CAL sequences) and the and keys onthe front panel are used to change and increment theflashing digits.
Up to nineteen CAL steps are accessible, dependingon which options are installed. The CAL number isdisplayed on the lower display and the parameter isdisplayed on the upper display.
Program Steps
Step Comment
CAL 1 Scaling Factor - Whole numbers (K-Factor)
The Scaling Factor is the pulses per unit ofmeasure (i.e. pulses/gallon, pulses/barrel etc.).The Scaling Factor can be programmed in therange of 0.2 to 29,999.
CAL 2 Scaling Factor - Digits to the right of the deci-mal point.
CAL 3 Frequency Divider
This calibrates the Model 505 to a specific
frequency range where:1 = .25 to 500 Hz
2 = .25 to 5KHz
CAL 4 Decimal Point Placement for Rate Display
The flowrate can be displayed with 0, 1, 2, or 3decimal places. Enter number of places.
CAL 5 Timebase for Rate
The Rate can be displayed in units per sec-ond, minute, hour, or day. Enter:
0 = second
1 = minute
2 = hour
3 = day
CAL 6 Filter
Fluctuations in the flowrate can be filtered outso that the Rate and 4-20mA transmission (ifused) are held steady. The filter value is pro-grammed between 1-99 where 1 representsno filtering and 99 is maximum.
CAL 7 Decimal Point for Total Display
The totals can be displayed with 0, 1, or 2decimal places.
CAL 8 Total Conversion Factor - Whole Numbers
CAL 9 Total Conversion Factor - Digits to the rightof the decimal point.
The Total Conversion Factor enables the rateto be displayed in one engineering unit andthe totals to be displayed in another engineer-ing unit.
Set to 1.000 if totals and rate are in the sameengineering unit.
CAL 10 Low Alarm - Whole Numbers
A A
-
7/30/2019 Mnit_001
4/12
4 Issue/Rev. 0.2 (1/99)
Program Steps (cont)
Step Comment
CAL 11 Low Alarm - Digits to the right of the deci-mal point.
CAL 10 to CAL 13 are displayed regardless ofwhether the high and low alarms are installed.If the high and low alarms are not installed,these parameters can be ignored.
CAL 12 High Alarm - Whole numbersCAL 13 High Alarm - Digits to the right of the deci-
mal point.
CAL 12 and 13 program the flowrate abovewhich the high alarm relay will close. Thevalue can be programmed in the range 0 to49,999.9999.
CAL 14 4mA Output Value - Whole numbers
CAL 15 4mA Output Value - Digits to the right ofthe decimal point.
CAL 14 and 15 represent the flowrate at which4mA will be output (only displayed on the LoopPowered version.)
CAL 16 20mA Output Value - Whole numbers
CAL 17 20mA Output Value - Digits to the right ofthe decimal point.
CAL 16 and 17 represent the flow rate at whichthe output will reach 20mA.
CAL 18 Identification Number
Not currently used.
CAL 19 Communication Parameter
Not currently used.
Calculation of Rate and Total
The flowrate, R, is calculated as follows:
R =
where: f is the input frequency in Hz.
H is the timebase of rate and is 1 for seconds,60 for minutes, 3600 for hours and 86,400for days.
S is the Scaling Factor.
The Scaling Factor, S, is equal to the K-Factor of theflowmeter expressed in pulses per unit volume.
The user programs the Scaling Factor and selects thetimebase during the Programming procedure.
Total Conversion
The Total Conversion feature enables the rate to bedisplayed in one engineering unit (i.e. gallons/minute)and the totals to be displayed in another engineeringunit (i.e. barrels).
fx H
S
The Scaling Factor is always programmed in the unitrelating to Rate, and the Total Conversion constant isa division factor which can be used to convert thetotals to the different unit. The Total Conversion fac-tor affects the resettable and accumulated totals andis limited between 0.01 and 2000.
For example:
If the Rate is required in gallons per minute:
1. The Scaling Factor would be programmed as
pulses per gallon.2. The timebase would be programmed as minutes.
If the Totals are required in barrels:
3. The Total Conversion Factor is programmed as42 (there are 42 gallons in a barrel). All totals willnow totalize in barrels.
Some common units are given below together with theTotal Conversion constant which should be pro-grammed.
Rate* Totals TOTCON
Gallons (US)/ Barrels (oil) 42.000
Liters/ Kiloliters 1000ml/ Liters 1000
Mgallons/ Acre-feet 0.32587
* Units per second, minute, hour or day. The timebaseis programmed separately during Programming.
Filtering (Dampening)
Frequency fluctuations caused by pulsating flow througha flowmeter, often makes the Rate impossible to readwith any precision.
The Flow Computer has a digital filter which will aver-
age out these fluctuations and enable the Rate to beread to four digit accuracy. The ability to select asuitable filtering level means that highly accurate andstable readings can be obtained without excessivelag. When the Rate is retransmitted via the 4-20mAoutput, the filtering will also average out any fluctua-tions on the output.
The diagram below shows a pulsating signal input to-gether with the effect of filtering.
-
7/30/2019 Mnit_001
5/12
5Issue/Rev. 0.2 (1/99)
As a guideline to the degree of filtering to be used, thefollowing table shows the response to a step change ininput. The value, CAL 6, is the filter constant which isprogrammed during the Programming routine. Thetimes for the display value to reach 90% and 99% offull swing are given in seconds, for different values ofCAL 6.
CAL 6 Value 90% 99%
1 0 0
2 1 2
4 2 4
6 3 6
10 5 11
15 8 17
20 11 22
25 14 28
35 20 40
45 25 51
60 34 69
75 43 86
90 52 103
99 57 113
Table 1. Response to a step Input (in seconds).
Note that if CAL 6 is set to 01 there is no filtering of theinput signal.
Example:
A flowmeter produces 208.538 pulses per Gallon andhas a maximum output frequency on 1200Hz. It isrequired to display the flowrate in Gal/min with 1 deci-mal point and the total in Gallons with no decimals. A4-20mA output is installed and 4mA is to represent 0GPM and 20mA is to represent 500 GPM. The instru-ment is then programmed as follows:
CAL 1 208 Scaling Factor (Whole Numbers)
CAL 2 5380 Scaling Factor (Dec imals)
CAL 3 1 Frequency Divider
CAL 4 1 Rate Decimal Position
CAL 5 1 Timebase
CAL 6 01 Filter Disabled
CAL 7 0 Total Decimal Position
CAL 8 0001 Total Conversion (set to 1.0000)
CAL 9 0000 Total Conversion (decimals)
CAL 10 00000 Low Alarm (not installed)
CAL 11 0000 Low Alarm (not instal led)
CAL 12 00000 High Alarm (not installed)CAL 13 0000 High Alarm (not installed)
CAL 14 00000 4mA Output Value (Whole No.'s)
CAL 15 0000 4mA Output Value (Decimals)
CAL 16 00500 20mA Output Value (Whole No.'s)
CAL 17 0000 20mA Output Value (Decimals)
Simplified Setup for Model 505
1. Insert screwdriver blade under end of dark graystrip at bottom of 505 and pry up. Remove stripand swap is end for end. Reinstall.
2. Press Program key. Unit will go into calibration mode.
3. See Chart below.
4. Remove gray strip at bottom of 505. Swap it endfor end. Reinstall. Unit will go into OperationalMode. Unit is ready.
Battery Powered Version
The battery powered version of the Model 505 is de-
signed for operation in the field without external powersources. Lithium batteries provide sufficient power tooperate the instruments for up to 3 years and the op-erator is warned of a low power condition by a mes-sage on the LCD display.
New batteries can be purchased through INVALCO orour distributors and replaced in the field. There aretwo battery packs in each instrument and care must betaken to replace only one pack at a time so that thereis always power connected to the memory. Failure todo so may result in loss of setup parameters.
CAL 1 Enter Meter K-Factor. Press Program Key
CAL 2 Does K-Factor have numbers after the decimal?decimal? If so, enter them. If not, enter 0000.
Press Program key.
CAL 3 Set to 10 for 2" and smaller meter.
Set to 1 for 3" and larger meters.
CAL 4 Do you want Flow Rate to be displayed with
decimals? If no, enter 0. If yes, enter 1, 2, or
3 for number of decimal places to be s hown.
Press Program key.
CAL 5 Will Rate to be in secs., min., hrs., or days?
0 - sec.
1 - min.
2 - hr.3 - day
CAL 6 Enter a number from 1 to 99 to smooth out flow
rate reading fluctuations. 1 is m inimum and 99
max. Press Program key.
CAL 7 Do you want total to read out in decimals? If no,
enter 0. If yes, enter 1 or 2 for the number
decimal places desired. Press Program key.
CAL 8 Do you want the total readout to be in gallons?
If so, set to 1. If you want total to be in barrels,
set to 42. Press Program key.
CAL 9 Set to 0. Press Program key.
CAL 10 Set to 0. Press Program key.CAL 11 Set to 0. Press Program key.
CAL 12 Set to 0. Press Program key.
CAL 13 Set to 0. Press Program key.
-
7/30/2019 Mnit_001
6/12
6 Issue/Rev. 0.2 (1/99)
4-20mA Output Version
The 4-20mA output provides a two wire retransmissionof the flowrate. Both the 4mA and 20mA points arefully programmable so that the output can span acrossthe entire operating range or, alternatively, across asmall section of the operating range.
The response rate of the output is very fast, makingthe instrument suitable as a frequency to current con-verter in closed loop systems where a fast response isnormally required.
The instrument draws its operating power from the 4-20mA loop and uses a Lithium Battery for memorybackup.
Specification:
Digital to Analog Converter
10 bit
Accuracy
0.5% of Span
Voltage Drop across terminals 7 & 8
16 VDC max.
Response (4mA to 20mA)
0.5 seconds
Maximum Voltage across Output
28 VDC
Since the 4-20mA output is designed to provide powerto the Model 505, it is not isolated from the input.Hence, all sensors must be self powering (such asreed switches and coils). If external power is requiredto power the sensor (i.e. Namur switches, Hall Effectsensors or opto-sensors), the power supply deliveringthe external power must be isolated from the 4-20mA
loop supply.
Typical Connection
Magnetic Pick-upMagnetic Pick-upMagnetic Pick-upMagnetic Pick-upMagnetic Pick-upor Reed Switchor Reed Switchor Reed Switchor Reed Switchor Reed Switch
Model 505Model 505Model 505Model 505Model 505
ReceivingReceivingReceivingReceivingReceiving
InstrumentInstrumentInstrumentInstrumentInstrument
SupplySupplySupplySupplySupply
LoadLoadLoadLoadLoad
77777
88888
Connection to a Sensor requiring External Power
SupplySupplySupplySupplySupply
LoadLoadLoadLoadLoad
Model 505Model 505Model 505Model 505Model 505
77777
8888833333
44444
RF or Half EffectRF or Half EffectRF or Half EffectRF or Half EffectRF or Half Effect
Pick-upPick-upPick-upPick-upPick-up
Isolated SupplyIsolated SupplyIsolated SupplyIsolated SupplyIsolated Supply33333
+VDC+VDC+VDC+VDC+VDC
GN DGN DGN DGN DGN D
Model 505Model 505Model 505Model 505Model 505
SupplySupplySupplySupplySupply
LoadLoadLoadLoadLoad
ReceivingReceivingReceivingReceivingReceivingInstrumentInstrumentInstrumentInstrumentInstrument
ReceivingReceivingReceivingReceivingReceiving
InstrumentInstrumentInstrumentInstrumentInstrument
RF or Half EffectRF or Half EffectRF or Half EffectRF or Half EffectRF or Half EffectPick-upPick-upPick-upPick-upPick-up
33333
+VDC+VDC+VDC+VDC+VDC
0 VDC0 VDC0 VDC0 VDC0 VDC
33333
4444477777
88888
+++++
-----
+++++
-----
+++++
-----
-
7/30/2019 Mnit_001
7/12
7Issue/Rev. 0.2 (1/99)
DC Power Version
The DC Power version will operate from an externalpower source between 12-28 VDC and draws no morethan 8mA.
The instrument uses a Lithium battery for memorybackup capable of maintaining memory for long peri-ods.
Open collector outputs are also provided for high and
low flowrate alarms. They can sink up to 200mA andcan be used to power external relays, lights or audiblealarms. The outputs are internally protected againstvoltage spikes caused by relays and coils.
Both outputs are separately isolated via opto isolators.
The switching points can be programmed during thesetup mode and the low flow alarm will switch on when-ever the flowrate drops below the programmed flowrate.Similarly, the high alarm switches on whenever theflow exceeds the high setpoint.
Specification for Alarm Output
Maximum Current (sink)
200mAMaximum Voltage
30VDC
Voltage across Output when in the On state
2.0VDC
Isolation
Both outputs are separately isolated.
Typical Connections
Flowmeter Input
The Model 505 has an input conditioning circuit whichwill accept signals from most pulse or frequency pro-ducing flowmeters. A six position DIL switch on therear panel enables the input circuit to be configured fordifferent signal types.
The input will interface directly to:
Turbine Flowmeters
Open Collector OutputsReed Switches
Logic Signals
Two Wire Proximity Switches
For pulse or logic type signals, the input switchingthreshold is 1.3 volts. Accordingly, the input signalmust have a low voltage of less than 1.2 volts and ahigh voltage of greater than 1.4 volts.
Separate input terminals are provided for the coil inputso that high inductance values can be handled, whilemaintaining the intrinsic safety of the system. For acoil, the minimum input voltage is 20mV P-P.
All inputs are protected for over voltage up to 25 volts.The following are examples of interconnection to vari-ous signal outputs, and a circuit diagram of the input isalso provided.
-
7/30/2019 Mnit_001
8/12
8 Issue/Rev. 0.2 (1/99)
Flowmeter Input (cont)
1. Squarewave, CMOS or Pulse
2. Open-Collector with 100K ohm internal pullup re-sistor.
3. Reed Switch - Battery Powered with 100K ohminternal pullup resistor.
Note: For a switch or reed input with contact bounce,S4 can be switched on. This will eliminate the effectof switch bounce, while limiting the input frequency to200 Hz.
Note: If a 4-20mA output is installed, the supply to theProximity Switch must be isolated, as detailed in theVersion Section.
4. Reed Switch - External DC Power with 10K ohmpullup resistor.
5. Coils (Magnetic Pick-up)
6. Namur Proximity Switch
Note: For a switch or reed input with contact bounce,S4 can switched on. This will eliminate the effect ofswitch bounce, while limiting the input frequency to200Hz.
Switch SettingsSwitch Settings
Switching ThresholdVoltage is 1.3 volts.
e.g. Millivolt signalfrom turbine orpaddlewheel (20V P-P minimum)
Use shielded cable
e.g. Positive displace-ment flowmeters withreed switch outputs.
-
7/30/2019 Mnit_001
9/12
9Issue/Rev. 0.2 (1/99)
Installation
Wall Mounting
A wall mounting bracket is supplied with each instru-ment. The bracket should be attached to the wall usinground head screws (do not use counter sunk screws).The bracket is mounted with the tray section at thebottom. The instrument is then attached to the bracket atthe bottom with two screws (see diagram below).
Removing the Front Panel
The front of the instrument is removed as follows:
1. Remove both the top and bottom cover strips (i.e.the dark plastic strips on the front) by levering ascrewdriver under one end.
2. Undo the seven screws retaining the front. Notethat the screws should not be removed from thefront panel as they are retained by O-rings.
3. Pull the front panel free from the housing.
Replacing the front panel of the instrument is the reverseprocedure. However, ensure that the front panel is alignedat both connector points before tightening the screws.
The Main Electronics
The front section of the housing contains the micro-processor, batteries and display.
When replacing the Lithium battery packs, only onebattery pack should be replaced at a time so that thereis always one pack connected to power the memory.
NiCad batteries should not require replacement, butthey may need to be charged for a short period beforethey will provide effective backup to the memory.
It is also possible to adjust the display contrast via asmall potentiometer on the board. The DISPLAY CON-TRAST control is shown below and this can be ad-
justed for optimum contrast.
Adjacent to this control is a RESET switch which canbe used to reset the microprocessor. Note that press-ing this button will reset all Setup Parameters and setall totals to zero.
Terminal Designations
All Versions1 Coil Input
2 Coil Input
3 Pulse Input (+)
4 Pulse Input (-)
4-20mA Output
7 4-20mA (-)
8 4-20mA (+)
DC Power Versions
7 DC Power 0V8 DC Power +12 to 28 VDC
9 Low Alarm (+)
10 Low Alarm (-)
11 High Alarm (+)
12 High Alarm (-)
-
7/30/2019 Mnit_001
10/12
10 Issue/Rev. 0.2 (1/99)
Intrinsic Safety Connections
When installing the Model 505i in hazardous areas,the wiring and installation must comply with appropri-ate installation standards.
The approval uses entity parameters on the input forconnections to the flowmeter, and an associated ap-paratus type approval for the 4-20mA output. The 4-20mA output must, therefore, only be connected as
shown on the following page, to barriers with the speci-fied parameters.
The Model 505i will connect directly to a turbineflowmeters or paddlewheel with a certified I S coil orother certified I S sensors which produce a pulse out-put, provided they do not exceed the following inputparameters:
Ui = 24V
Ii = 20mA
Pi = 320mW
The maximum allowed capacitance and inductance ofthe pulser or coil, including cabling is:
Cext = 60uF
Lext = 1.5H
The internal capacitance and inductance of the Model505 seen on the input are negligibly small and themaximum voltage and current produced by the Model505 on its inputs (terminals 1 to 4) are:
Uo = 10.0 volts (open circuit)
Io = 9.0mA (short circuit)Devices such as reed switches, which can be classedas Simple Apparatus as defined in the CENELECstandard EN50020, can be connected to the Model505 without certification.
Intrinsically Safe Operation
Typical Wiring Diagram for 4-20mA Current Loop
Typical Wiring Diagram for Namur Proximity Detector*Note: Base units, battery powered, are entity approved intrinsically safe without the need for barriers. Only when outside power is applied are certified I.S. Barriersneeded.
-
7/30/2019 Mnit_001
11/12
11Issue/Rev. 0.2 (1/99)
505 Settings for Cubic Meters/Day
If the K-Factor is above 29,999 pulses per cubic meter, then the time base can be shifted to allow the 505 todisplay rate in cubic meters per day. (M3/DAY and a corrected total for cubic meters (M3).
Conversions:
1 gpm = 3.785 lpm
1 lpm = 1.44 M3/DAY
1 Day = 1440 Minutes
Shifted K = K-Factor (P/G) / (1.44 * 3.785) = K-Factor / 5.4504
Enter the K-Factor in P/GAL:
Equivalent K-Factor (P/L) =
Shifted K-Factor =
Set the 505 for Minutes
Set Total Conversion to 1440 MIN/DAY
The 505 will now display rate in M3/DAY and Total M3.
The alarms and 4-20mA should be set in M3/DAY.
Sample:
1 Meter K = 873 P/GAL
Shifted K-Factor = 160.1717 (CAL01 = 00160 and CAL 2 = 1717)
Set the 505 for Minutes (CAL 05 = 1 for Minutes)
Set Total Conversion to 1440 MIN/DAY (CAL 08 = 1440)
924
244.12153
169.5288 (CAL 01 & CAL 02)
(CAL 05 = 1 FOR MINUTES)
(CAL 08 = 1440)
-
7/30/2019 Mnit_001
12/12
12 Issue/Rev. 0.2 (1/99)
The specifications contained herein are subject to change without notice and any user of said specifications should verify from the manufacturer that the specifications arecurrently in effect. Otherwise, the manufacturer assumes no responsibility for the use of specifications which may have been changed and are no longer in effect.
FMC INVALCO Fluid Control P.O. Box 1377, Stephenville, TX 76401, Phone: 254/968-2181, FAX: 254/968-5709, Toll Free: 800/468-2526
Printed in U.S.A. 1/99 FMC INVALCO All rights reserved. Issue/Rev. 0.2 (1/99)
Dimensions
Inches (mm)
Standard Weatherproof Meter Mount Connection(Wall Mount Enclosure - Ignore Mounting Stem)
Optional Swivel Mount Connection(Weatherproof Enclosure Only)
Explosion-proof Meter Mount ConnectionNote: Dimensions - Inches to the nearest tenth (millimeters to the nearest whole mm), each independently dimensioned from respectiveengineering drawings.