5/22/2018 DCS Mannual
1/242
OVOVOVOV----215WIN215WIN215WIN215WINOvation 3.1OCR_400)
(Aug.2008)
-
5/22/2018 DCS Mannual
2/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.1
Upon successful completion of this course the student will be able to:
Identify the major components of an Ovation system
Define the Ovation Drop Types Define and Demonstrate Ovation Controller Functions and Capabilities
Describe and Outline the Ovation Fast Ethernet Network
Describe and Demonstrate Ovation Point, Control and Graphics Creation
Describe and Interrogate Ovation Point Types, I/O Modules and Control Algorithms
Demonstrate Basic Operator Functions
Demonstrate Data Retrieval
Describe and Manage Ovation Security
Implement Ovation System Backup
Demonstrate the ability to effectively use Ovation documentation
Course Objectives
-
5/22/2018 DCS Mannual
3/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.2
Module 1: Ovation System Overview
Module 2: Discuss the Hierarchy and Right Click Functions
within the Ovation Developer StudioModule 3: Start with the Ovation Data Acquisition
Module 4: Demonstrate Basic Operator Functions
Module 5: Build & Maintain Ovation Control
Module 6: Understand Typical Ovation Algorithms
Module 7: Ovation Graphic Builder
Module 8: Ovation Data Retrieval
Module 9: Manage Ovation Security
Module 10: Backup Ovation System
-
5/22/2018 DCS Mannual
4/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.3
Module 1: Ovation System Overview
Examine the typical Ovation DCS
Understand the roles of different MMIs
Describe the function of Ovation controller drops
Describe the function of Ovation network
Address the Ovation I/O modules
-
5/22/2018 DCS Mannual
5/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.4
Redundant Controller Pair
-Each with equal capabilityfor control or backup-Scan inputs-Limit check points-Execute control-Send new control values tooutput devices-Multicast points onto theOvation highway
Controller1/51
OVATION NETWORKHigh Speed Ethernet100(Mbps) Megabits / sec.Up to200,000 pointsUp to 254 Drops
Database Software
ServerDB/SS/EWS
OPH
Historian
Operator
WorkstationOWS
Ethernet SwitchEthernet Backup Switch
-
5/22/2018 DCS Mannual
6/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.5
Ovation Operator Workstation (OWS)
The Operator Workstation is the drop that allows us to communicate with plant processesvia the Ovation network and to monitor normal and abnormal plant conditions. The Ovation
Applications links are accessed from:
Ovation Applications folder on the workstation desktop Start menu Icons on the task bar (if configured)
-
5/22/2018 DCS Mannual
7/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.6
OWS Monitoring
Alarm Management Process Graphics Point Information Point Review
Historical Review Trends Viewer Error Log
Interface to Control
Software driven Manual/Auto Stations Control tuning
-
5/22/2018 DCS Mannual
8/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.7
Ovation Engineering Workstation (EWS)
The Engineering Workstation is the drop that allows the engineers or a technician tomake necessary software changes to the Ovation system. This drop contains theOvation Developer Studio software.
The Ovation Developer Studio allows users to:
Configure Ovation dropsAdd or Manage dropsModify alarm configurationsCreate and modify Global Trends (Trend Groups)
Build or change softwarePointsControl SheetsGraphics
Pass software changes to all drops in the system
LoadDownloadReconcile
-
5/22/2018 DCS Mannual
9/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.8
Ovation Developer Studio
Each engineering workstation is also a fully functioning operator workstation.
-
5/22/2018 DCS Mannual
10/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.9
Database Software Server (DB/SS/EWS)
The Database Software Server is the drop that contains the master Oracle database.
Master Database - Contains the majority of Ovation System Data. It is used for
creating, modifying and verifying control strategies and process points. It matches
Ovation system points up with the System IDs (SIDs).
All system graphics and AutoCAD drawing files are stored on the DB/SS.
It also manages the network licenses for the maximum allowable system drops,Developer Studios, Graphics Builders, and Control Builders.
The database server is typically DROP200 and there is only one database server per
Ovation system. It can perform all the functions of an Engineering Workstation and anOperator Workstation.
This drop is routinely backed up and the error log is checked on a regular basis.
-
5/22/2018 DCS Mannual
11/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.10
Domain Controller
With Ovation 2.4 and later releases the Ovation DCS introduces the Domain Controller.
This machine manages security within the domain. A domain is a logical collection of
computers and users on a network that share a common security database. The Domain
Controller can either be a stand alone machine or it can be the Database/Software server.
Functions of the Domain Controller:
Manage Ovation users
Manage password for users
Enforce policies and security for all drops on domain
Prevent unauthorized logins
The domain controller can control security for a single or multiple separate Ovation
systems. This is true whether or not the multiple systems are set up as a multi-networksystem. The Windows Server 2003 operating system runs the Domain controller whether it
is stand alone or tied in with the Database/Software Server.
-
5/22/2018 DCS Mannual
12/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.11
Ovation Process Historian (OPH)
The OPH collects and stores historical data for
Process point values
Alarm history data
Operator events
Sequence of events (SOE) data
System messages
Typically, the OPH is a drop on the Ovation network. Data such as point values, alarm
information, and sequence of events are sent from workstations defined as OPH scanners.These scanner machines collect a predefined set of data and send it to the OPH for
storage. Scanner drops have a binoculars icon in the lower right hand corner of the
screen.
The OPH allows operators to perform historical data retrieval for applications like historical
trends or point reviews.
-
5/22/2018 DCS Mannual
13/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.12
Functions of the OPH
Organize real-time process data
Perform the calculation of summary values
Support on-line storage and off line archival
Successfully respond to any retrieval requests.
Typically, the OPH is packaged with the Crystal Reports software package. This software
provides custom viewing, sorting, and filtering of data that can be output to printers or files
in a variety of formats such as Microsoft Word, Excel, HTML, .csv,and text. These
reports can be executed on demand or at a scheduled time.
-
5/22/2018 DCS Mannual
14/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.13
Ovation Controller Major Functions
Provides alarming and command word processing for originated points Originates and receives process points Adds, deletes, and modifies points off-line Reads I/O modules and converts data to process points
Reads process points and writes data to I/O modules Executes control algorithms Adds, deletes, and modifies control off-line Runs Self-Test Diagnostics Broadcasts point data to the Ovation DCS
The controller both originates and receives process points. Points can either be hardware(wired to the module) or software points (values on a control sheet). Other Ovation dropsobtain point values from the controller.
-
5/22/2018 DCS Mannual
15/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.14
Ovation Controller Features
The Controller in the plant is typically one or more cabinets containing input and output
modules connected to the field devices by wires. These modules monitor each device for
changes in the device's condition. When detecting a change (input), the Controller reads
the change and tells the device (output) to perform an appropriate action as determined bythe controller. This action has been programmed into the Controller by control sheets
(signal diagrams) that are created in the Ovation Control Builder. The Control Builder
sheets consist of algorithms arranged in a logical pattern that define in detail what action to
take when certain events occur in a device.
Up to 32,000 points per controller (4000 direct-wired I/O points)
Scalable flash memory to store operating system, logic, and points
Pentium processor
Automatic failover to Backup Controller
-
5/22/2018 DCS Mannual
16/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.15
Ovation OCR400 Controller
The OCR 400 controller is the newly packaged Ovation controller for use with Ovation 3.0
systems and newer. The picture below shows the primary and backup controller with two
I/O modules on each branch. The interfaces to the controller are located on the top of the
controller as shown below.
-
5/22/2018 DCS Mannual
17/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.16
Processor Module Interface Ports
-
5/22/2018 DCS Mannual
18/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.17
Processor Module Indicator LEDS
P power indicator, green N1N4
each Ethernet port has two indicatorLEDs
first LED: green and flash,
the module is linked with thenetwork on that port. second LED: yellow and flash,
the module is receiving or
transmitting data on that port.
-
5/22/2018 DCS Mannual
19/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.18
I/O Interface Module Interface Ports
-
5/22/2018 DCS Mannual
20/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.19
I/O Interface Module Indicator LEDS
-
5/22/2018 DCS Mannual
21/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.20
The Ovation Distributed Control System provides modulating control, sequential control,
and data acquisition for a variety of system applications. This system consists of a
configurable mix of functional Input/Output (I/O) modules that communicate on the I/O bus
to the Ovation Controller.
I/O modules provide an interface between the Ovation Controller and the processes in the
plant. Ovation I/O modules are plug-in components with built-in fault tolerance and
diagnostics. They are able to operate on a wide range of signals and perform a multitude of
functions.
The standard modular components are hot swappable and typically consist of the
following:
Base Unit (containing the field terminations)
Electronics module (Emod) -- two slots per Base Unit
Personality module (Pmod) -- two slots per Base UnitThe relay output modular components consist of the following:
Electronics module
Base Unit (containing the field terminations)
Ovation I/O Modules
-
5/22/2018 DCS Mannual
22/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.21
8 Channel Analog Input
8 Channel HART Analog Input
8 Channel TC Input 8 Channel RTD Input
4 Channel Analog Output
16 Channel Digital Input
16 Channel Contact Input
16 Channel Digital Output
2 Channel Pulse Accumulator/Counter
16 Channel Sequence of Events
I/O Modules
-
5/22/2018 DCS Mannual
23/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.22
I/O Card Indicators
Standardized Status Indicating Scheme Redindicates abnormal condition
Green indicates normal condition or status
Power (Green)
Communication (Green)
External Error (Red)
Internal Error (Red)
Channel Status Indicators
Digitals - Green = ON
Analog - Red = Channel Error
P
E
I
1
2
C
-
5/22/2018 DCS Mannual
24/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.23
Addressing The Ovation I/O Modules
Addressing Format: D.N.B.S D = Device number assigned to the PCI card
1. Local Ovation
2. Local Ovation3. Local Q-Line
4. Can be one of the following:
None
Remote Ovation
Remote Q-LineLocal Q-Line
5-9 Third Party devices
N = Node (only used in Remote I/O; 1 through 8).
B = Branch (1 through 8). S = Slot where module is located (1 through 8 for Ovation I/O)
-
5/22/2018 DCS Mannual
25/242
-
5/22/2018 DCS Mannual
26/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.25
A = Address 1.1.4Device 1 Branch 1 Slot 4B = Address 1.4.2 Device 1 Branch 4 Slot 2
C = Address 1.5.3 Device 1 Branch 5 Slot 3
D = Address What is the I/O Address? Why?
-
5/22/2018 DCS Mannual
27/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.26
Controller Cabinet Module Address
Example(1)
Module A address= 1.1.2Module B address= 1.2.4Module C address
= 1.3.6
Controller Cabinet
-
5/22/2018 DCS Mannual
28/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.27
Controller Cabinet Module Address
Example(2)
Module D address= 1.5.6Module E address
= 1.6.1Module F address= 1.8.8
Extended I/O Cabinet
-
5/22/2018 DCS Mannual
29/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.28
Controller Cabinet Module Address
Example(3)Remote Node Cabinet
Module G address= 4.1.1.3Module H address
= 4.1.3.5
Note: Assume the Node is inMAU position 1
-
5/22/2018 DCS Mannual
30/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.29
Installing Ovation I/O modules
-
5/22/2018 DCS Mannual
31/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.30
Guidelines for Replacing, Adding, or
Combining Ovation Modules
Make sure that the replacement module is the exact replacement for the
I/O module, both the Electronic module and the Personality module.
Modules are placed from top to bottom on the left side of a cabinet and
from bottom to top on the right side of a cabinet.
If Relay Output modules are mixed with Standard I/O modules on the
same branch, the Standard I/O module base must ALWAYS start in an
odd-numbered module position on the branch .
Ensure proper Auxiliary voltage is available for all modules contained
within the configuration.
Every I/O branch must be terminated using one of the following:
Left terminator
Right terminator
MAU base module (right or left side)
-
5/22/2018 DCS Mannual
32/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.31
Ovation NetworkThe Ovation network is the 100 Mbps data highway used to allow all the drops and devices
to communicate.
The Ovation highway uses Cisco switches and routers as shown below:
Switches Used to connect drops, other switches, printers, PLCs, and routers
24 ports each designated for certain devices
Many different configurations - Root Switch, Backup root, IP Traffic, Fan-out, etc
Connects devices with CAT5e Ethernet cables or Fiber Ovation ports forced to 100 Mbps/Full Duplex
Diagnostics viewable on switch LEDs
-
5/22/2018 DCS Mannual
33/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.32
Below is an example of a single tier network:
-
5/22/2018 DCS Mannual
34/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.33
Below is an example of two tier network:
The Ovation network is designed so that there are multiple paths for data. Each root and
fan-out switch has a redundant partner so that if any one switch fails network communication
can continue.
-
5/22/2018 DCS Mannual
35/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.34
Module 2: Discuss the Hierarchy and Right Click Functions
within the Ovation Developer Studio
Access the Ovation Developer Studio
Understand Ovation Record Types
Use the right click menu in the Developer Studio to Load
controllers
Understand recommendations when loading controllers
Understand data movement in an Ovation system
-
5/22/2018 DCS Mannual
36/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.35
The Ovation System Database manages all items in the
system
Input, output and calculated points
Control modules Process graphics
System configuration
The Developer Studio was designed in a tree (or system
hierarchy) structure including following folders
Systems Folder
Networks Folder Unit folder
Drops folder
Points Folder
Ovation Developer Studio
-
5/22/2018 DCS Mannual
37/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.36
Resizing Ovation Developer Studio Windows
window RESIZElocations
Hint: Watch for thecursor to change tobars
-
5/22/2018 DCS Mannual
38/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.37
Enables you to establish multiple user security groups.
View Ancillary Label attributes
Configure System defaults. (alarms, trends, diagram colors, etc.)
View, create, delete, modify symbols used in diagrams.
View, create, delete, modify graphics and macros.
Opens Ovation License Manager, License user
details
ConfigureNetwork defaults
View, create, delete, modify graphics and macros
Configure Unit specific defaults
View, create, modify graphics and
macros
Configure Contollerdevices, controllernetworking, etc.View existing point detail in Oracle, Add, delete,modify points.
Define I/O module types, physical locationView existing Control logic. Add, delete, modify
control sheets.
Developer Folders
-
5/22/2018 DCS Mannual
39/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.38
Ovation Record TypesRecord Type Abbr. Monitor status of: Example Name break down
Drop record DU Ovation MMIs & Controllers DROP200, DROP1
Node record RN Power supplies / remote nodes D002P1 Drop2Device1
D001P2N4 Drop1Device2Node 4
Module rec. RM Configured I/O modules D001P1B4L3Drop1PCI1Branch4Slot3
Digital LD Digital points, two possible values (1 or 0), software and hard wired.
Analog LA Points with a range of values. (0-100%, 0-3000 PSIG, etc.)
Packed LP 16 digital bits that are treated as a single point or word.
Long control LC Long Control or Algorithm points are created while building andmodifying control sheets using Ovation Control Builder. See Control Builder Users
Guide for more information on algorithm point names.
Note: There are no standard Emerson Process Control Power & Water Solutions point
names for these record types and therefore, no examples are given.
-
5/22/2018 DCS Mannual
40/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.39
6C-------3 / 53
7B-------2 / 52
8A-------1 / 51
ALARM PRIORITYCHARACTERISTICSCONTROLLER PAIR
Make these common changes and use these guidelines for building
and modifying ALLpoints in class.
-
5/22/2018 DCS Mannual
41/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.40
Drop Load Recommendations
Read all bullets prior to loading controllers.
Use the Developer Studio to perform a consistency check on thecontroller pair prior to actually loading the controllers. Fix all itemsthat are listed that may cause problems during/after the Load.
Use the Developer Studio to perform a Reconcile on the controllerprior to actually loading the controllers. ONLY RECONCILE THECHANGES YOU KNOW ARE VALID. IF YOU ARE NOT SUREASK OTHERS.
Load the controller in control first. DO NOT ASSUME! Use yoursystem status graphic to verify which controller is in control and backup.
Only load the backup controller after you verify proper operation ofthe points and controls.
Drop Load after making a relatively small number of changes DontStockpile.
Make sure you have the authority and permission to Drop Load whenthe unit is in operation.
-
5/22/2018 DCS Mannual
42/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.41
RedundantController
Pair
P
rimary
(Control)
Flash
Disk
RAM
Backup
(Backup)
Flash
Disk
RAM
OperatorWorkStation(s)
OvationLiveDatadisk
Runtimegraphics
andsig
naldiagrams
Trends
PointInformation
PointReview
manyothers
DatabaseSo
ftwareServer
OvationDat
abasedisk
Ovationpoints
Ovationcontroldata
OvationCo
nfigdisk
Ovationsystem
configu
ration
Graphics
Controlsheets(AutoCAD)
muchmore
OvationLiveDatadisk
Runtimegraphics
andsig
naldiagrams
Trends
PointInformation
PointReview
manyothers
DOWNLOAD
ON-LINE
CHANGES
PROPAGATIO
N
DEVELOPER
STUDIO
RECONCILE
LOAD
CONTROL
BUILDER
RECONCILE
MULTICAST
POINTDATA
Ovation Data Movement Diagram :
-
5/22/2018 DCS Mannual
43/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.42
Ovation Developer Studio Right Click Menu
Reference the Developer Studio User Guide for Ovation for more information on right click functions.
-
5/22/2018 DCS Mannual
44/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.43
Module 3: Start with Ovation Data Acquisition
Configure additional Ovation I/O modules
Utilize the Ovation Developer Studio to create and modify
analog points
Utilize the Ovation Developer Studio to create and modify
digital points
Utilize the Ovation Developer Studio to create and modify
packed points
Replace fault Ovation I/O modules
-
5/22/2018 DCS Mannual
45/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.44
Configure additional Ovation I/O modules
1. Insert a New I/O Module using the Ovation Developer
Studio
2. Create a new module point in the Ovation Developer
Studio
3. Build a point using the Ovation Developer Studio
-
5/22/2018 DCS Mannual
46/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.45
1. Inserting a New I/O Module using the Ovation Developer Studio
(General / Nonspecific)
-
5/22/2018 DCS Mannual
47/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.46
a) In the Ovation Developer Studio, drill down through the System Network Unit Drops DropX/Drop5X to the I/O Devicesfolder.
b) Expand the I/O Devices Device? Branch? Slot? to see theOvation Module folder (The ? is dependent upon where the I/O
module is or will be installed). The folder should be read Empty.
c) Right click on the Ovation Module folder and select Insert New
Use the pull down arrow to select the correct module type from the
list. (Use caution because many modules are similar.) Select
Finish.
d) Tabs: Config Tab: Module Record Point Name will populate when
we build a module record; Module Tab: configure as needed. The
Module tab is different for each module type. Analog and Digitaltab fields are grayed out. You cannot modify the grayed out fields.
e) Click OK to save the I/O module configuration.
D fi d C fi A l I M d l
-
5/22/2018 DCS Mannual
48/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.4747
Define and Configure Analog Input Module
4~20mA Analog Input
-
5/22/2018 DCS Mannual
49/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.4848
4~20mA Analog Input
D fi d C fi A l I M d l
-
5/22/2018 DCS Mannual
50/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.4949
Define and Configure Analog Input Module
TC Module
-
5/22/2018 DCS Mannual
51/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.5050
TC Module
D fi d C fi A l I t M d l
-
5/22/2018 DCS Mannual
52/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.5151
Define and Configure Analog Input Module
RTD Module
-
5/22/2018 DCS Mannual
53/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.5252
RTD Module
Define and Configure Analog Output Module
-
5/22/2018 DCS Mannual
54/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.5353
Define and Configure Analog Output Module
4~20mA Analog Output
4 20 A A l O t t
-
5/22/2018 DCS Mannual
55/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.5454
4~20mA Analog Output
Define and Configure Digital Input Module
-
5/22/2018 DCS Mannual
56/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.5555
Define and Configure Digital Input Module
Compact Contact Digital Input
-
5/22/2018 DCS Mannual
57/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.5656
Define and Configure Digital Output Module
-
5/22/2018 DCS Mannual
58/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.5757
Define and Configure Digital Output Module
DOC or DOX Module
DOC or DOX Module
-
5/22/2018 DCS Mannual
59/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.5858
DOC or DOX Module
Define and Configure Digital Input Module
-
5/22/2018 DCS Mannual
60/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.5959
Define and Configure Digital Input Module
SOE Module
2 Inserting a New Module Point (General / Nonspecific)
-
5/22/2018 DCS Mannual
61/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.60
2. Inserting a New Module Point (General / Nonspecific)
-
5/22/2018 DCS Mannual
62/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.61
a) In the Ovation Developer Studio, drill down through the System Network Unit Drops DropX/Drop5X to the Points folder.
b) Expand the Points folder to see the Module Points folder. Right
click on the Module Points folder and select Insert New
c) Give the point a valid Ovation point name and frequency. Click
Finish. Reference the Ovation Developer Studio User Guide for
point name rules.
(A common naming convention for module points is D001P1B1L5
where D001 is the left controller-Drop1, P1 is PCI Device 1, B1 is
branch 1, and L5 is location 5.)
d) Modify the point as necessary. Fields commonly changed are the
description, security, I/O module, and bit information on the display
tab.
e) Click OK to save the point.
3. 1 Insert new Analog points
-
5/22/2018 DCS Mannual
63/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.62
g p
Inserting New Tank level point (Analog Input)
-
5/22/2018 DCS Mannual
64/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.63
(1) Point nameLI1-XXXXXX- your drop numberPoint
DescriptionTank level XXX input signal
CharacteristicsL-------
Security
at least select one security group
Hardware
IO typeOvationIO module (select IO module according to I/O address )
IO channel1IO task index2
Alarm
Prioritiesset alarm priorities
se t g New a eve po t ( a og put)
-
5/22/2018 DCS Mannual
65/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.64
InstrumentationLow sensor0.0038High sensor0.0205Low operating range0High operating range100Field transmitter low value4
Field transmitter high value20Conversion typeLinearConversion coefficient 1-2
Limits
Low alarm limit 110 Low alarm deadband1High alarm limit 190 High alarm deadband2
Display
Engineering unitsINCH
Summary Diagram
50XXMinimum Scale0
Maximum Scale100
Digits Displayed2
These four fields are used to perform conversioncoefficient Calc
(2) Valve position output signalAnalog Output
-
5/22/2018 DCS Mannual
66/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.65
(2) Valve position output signalAnalog Output
Point name LV1-XXXXXX- your drop numberDescriptionvalve-XXX position output signal
CharacteristicsL-------
Security
at least select one security group
Hardware
IO typeOvationIO moduleIO channel1IO task index2
Alarm
Prioritiesset alarm priorities
-
5/22/2018 DCS Mannual
67/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.66
Instrumentation
Bottom output scale0
Top output scale100
Limits
Low alarm limit 110 Low alarm deadband1
High alarm limit 190 High alarm deadband2
Display
Engineering units%
Summary Diagram50XX
Minimum Scale0
Maximum Scale100
Digits Displayed2
(3) Build TC pointTC1-XXXXXX- your drop number
-
5/22/2018 DCS Mannual
68/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.6767
1Build Cold Junction Compensation Point for each TC module: (Ninth Channel point)
CJC1-XXX XXX- your drop number
Hardware
IO typeOvationIO module
IO channel9IO task index(according to TC points task index on this module)
InstrumentationLow sensor-10High sensor100
Field Transmitter TypeblankTransmitter Temperature UnitsCConversion typeX=Y
-
5/22/2018 DCS Mannual
69/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.6868
-
5/22/2018 DCS Mannual
70/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.6969
2) Build TC temperature pointTC1-XXXXXX- your drop number
Point
DescriptionTC xxx temperature point
Characteristics
T-------Security
at least select one security group
Hardware
IO typeOvation
IO moduleIO channel1(1~8)IO task index2
Alarm
Prioritiesset alarm priorities
-
5/22/2018 DCS Mannual
71/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.7070
Instrumentation
Low sensor-0.0205High sensor0.0205Low operating range0High operating range500Field Transmitter TypeTE
Transmitter Temperature UnitsCConversion type5th orderConversion coefficient 1-6(REF-1150)CJ compensation name CJC1-XXXCJC temperature unitsCCJC conversion coefficient 1-2(REF-1150)
Limits
Low alarm limit 1100 Low alarm deadband3
High alarm limit 1400 High alarm deadband5
Display
Engineering unitsC
Summary Diagram50XX
Minimum Scale0 Maximum Scale500
Digits Displayed2
(4) Build RTD pointRTD1-XXXXXX-your drop number
-
5/22/2018 DCS Mannual
72/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.7171
PointDescriptionRTDXXX
CharacteristicsT-------
Security
at least select one security group
Hardware
IO typeOvationIO moduleIO channel1IO task index2
InstrumentationLow sensor118High sensor172Low operating range120High operating range170
Field Transmitter TypeRNTransmitter Temperature UnitsCConversion type5th orderConversion coefficient 1-6Use Ovation Sensor Calibrate. to Cal.
-
5/22/2018 DCS Mannual
73/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.7272
120 OHM - Nickel RTDManufacturer: Minco Products (No. S4-60)
Alpha = .0081
Deg. F Deg. C Ohms32.0
57.0
81.0
104.0
127.0158.0
0.0
13.89
27.22
40.00
52.7870.0
120.0
130.01
139.95
149.79
159.99170.17
Temperature Range Information
Minco S4 - 60Nickel 120 OHMS AT 0 Deg. C
redwhite
white
Westinghouse Part No. 774A759H01
red
white
white
RN = Nickel RDT
RC = Copper RDT
RP = Platinum RDT
1 O S C lib t St t All P O ti
Cal. Conversion Coefficient on-line using Sensor Calibrate
-
5/22/2018 DCS Mannual
74/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.7373
1. Open Sensor Calibrate. Start All Programs Ovation
Ovation Utilities Sensor Calibrate.
2. SensorCalibration window
point name: RTD1-XXX (press enter key)
Note1. Before enter point name, point must be loaded into Controller
2. Define proper Conversion type
3.Sensor Calibrate will remove the point from scan, causing BAD
quality, as well as put the point into calibrate mode.
Take any precautions necessary to prevent problems!
3. Enter the information as listed in the table below
TRAINING RTD DATA
ACTUAL FIELD READING(OHMS )
EXPECTED VALUES
F C
120.0 32.0 0.0130.01 57.0 13.9
139.95 81.0 27.2
149.79 104.0 40.0
159.99 127.0 52.8
170.17 158.0 70.0
-
5/22/2018 DCS Mannual
75/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.7474
Step2
step3
4 Click Calc Coeff button
-
5/22/2018 DCS Mannual
76/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.7575
4. Click Calc Coeffbutton
5. Select Plot Point Tabconfirm curve6. If ok, go back to Sensor Calibration Tabclick Store Coeffbutton
Then new Coeff. will be Stored into Controller;
7. File Exit (Notewhen exit, point go back to on scan status automatically
8. Reconcile Conversion Coefficients into the Ovation Database
Launch on Developer Studio
System Network Unit Drops Controller#
right click Reconcile select point name rtd1 OK
-
5/22/2018 DCS Mannual
77/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.7676
Cal. Conversion Coefficient off-line using Coefficient Calc
-
5/22/2018 DCS Mannual
78/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.7777
3.2 Insert new Digital points
-
5/22/2018 DCS Mannual
79/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.78
(1) Pump Feedback Signal pointDI1-XXXXXX- your drop number
Point
-
5/22/2018 DCS Mannual
80/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.79
Point
DescriptionPump XXX Feedback Signal
CharacteristicsA-------
Config
Status checking typeAlarm on Zero
Security
at least select one security group
AlarmPrioritiesset alarm priorities
HardwareIO typeOvationIO moduleIO channel1IO task index2
Display
Set descriptionRUNReset descriptionSTOPSummary Diagram50XX
(2) Pump open/close command pointDO1-XXXXXX- your drop#
-
5/22/2018 DCS Mannual
81/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.80
Point
Descriptionpump open command point
CharacteristicsA-------
Config
Status checking type No Status CheckingSecurity
at least select one security group
Hardware
IO typeOvationIO moduleIO channel1IO task index2
DisplaySet descriptionOPEN
Reset descriptionblankSummary Diagram50XX
3.3 Control Application for Packed Point
-
5/22/2018 DCS Mannual
82/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.8181
Output of a PACK16 algorithm is apacked point. Each bit representsthe status of a digital input point.The PBPT output of controlalgorithms are packed points.
Common Uses of Packed Points
-
5/22/2018 DCS Mannual
83/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.8282
Mode words for control algorithms
Status feedback for motors, pumps, valves, etc
Permissive for starting, stopping, and controlling field
devices
Packed Point in the Ovation Developer Studio
-
5/22/2018 DCS Mannual
84/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.8383
Packed Point in Point Information
-
5/22/2018 DCS Mannual
85/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.8484
1. In the Ovation Developer Studio, drill down through the System Network Unit Drops
Packed Point Exercise: (LP1-XXX
-
5/22/2018 DCS Mannual
86/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.8585
DropX/Drop5X to the Points folder.2. Expand the Points folder to see the Packed Points folder. Right Click to insert new packed point.
3. Type point name LP1-XXX in your controller. Frequency is S;
4. Define the point, if needed, as noted in the table below
BIT #BIT
DESCRIPTION SETDESCRIPTION
RESETDESCRIPTION
0 MRE Output Signal TRUE FALSE
1 Xmtr Malfunction Alarm TRUE FALSE
2 Inhibit Control DevCheck MRE TRUE FALSE3 Xmtr A Quality Alarm TRUE FALSE
4 Xmtr B Quality Alarm TRUE FALSE
5 Mode Select Made by TMOD TRUE FALSE
6 Xmtr Alarm Dev Signal TRUE FALSE
7 Average Mode TRUE FALSE
8 Lower Mode TRUE FALSE
9 Higher Mode TRUE FALSE
10 Xmtr A Mode TRUE FALSE
11 Xmtr B Mode TRUE FALSE
Replace Fault Ovation I/O modules
-
5/22/2018 DCS Mannual
87/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.86
1. Find fault card hardware address on Point Information window
2. According to the application of channel points on fault I/O card, Make proper action
to ensure the safety of system control
3. Enter the channel point name in the Point Information Window one by one, thenmake the following operation:
a) Force the Quality to Good
b) Scan off the point
4. Pull out the fault I/O cardplug in the new I/O card with the same type
5. Release all points one by one on Point Information Window
a) Scan on the point
b) Test mode off the point
6. Recover whole control system
Module 4: Demonstrate Basic Operator Functions
D t t d E l i h b i d i i i
-
5/22/2018 DCS Mannual
88/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.87
Demonstrate and Explain the basic data acquisition operator
functions
Monitor Point Information and Point Review details
Understand the Alarm functions of Ovation system
Implement a Digital and Analog Trend
Use Point Viewer to list points
Monitor the Ovation Error log for errors and warnings
OPERATOR TO CONTROLLER INTERFACE
-
5/22/2018 DCS Mannual
89/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.88
Operator
Station
Hi-Speed Ethernet Highway
PROCESS( Power plants, Blast Furnaces, Waste Treatment plants,etc.)
RedundantController
Pair
Ethernet Switch #1 Ethernet Switch #2
OVATION APPLICATIONS FOLDER
-
5/22/2018 DCS Mannual
90/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.89
Ovation Point Information
Point Information is the Ovation application used to bring up information on any individual
-
5/22/2018 DCS Mannual
91/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.90
Point Information is the Ovation application used to bring up information on any individualpoint. Information is presented in a tabular fashion.
Ways to bring up information on an individual point:
1. Type the point name in the white text box and press ENTER
2. (1.) Click on the Search button
(2.) Select the Network, Unit or Drop
(3.) Choose your point
(4.) Click Apply or Hit ENTER or Double Click
3. Right click on Graphic, Trend, Alarm, or Point Review
4. Drag and drop from Graphic, Trend, Alarm, or Point Review
Points can be filtered so that only interested points in appear in the list. Filtering can be
based on any one or combination of the following:
Point Name *
Point Alias *
Description *
Record Type
Frequency
Point Information Search Window
-
5/22/2018 DCS Mannual
92/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.91
Use the left window to
define the level you want to
search. Searches can be done at
the Drop, Unit, or Network
level.
Use the right window, via the
Filter pull down menu on the
Find Points window, to narrow
the search using wild cards
and/or pull down options.
* = Point Information multi-
character wild card
? = Point Information single
character wild card
Point Info TabDescriptionAbbreviationRecord Field
The following table shows common record fields of interest to operator (1)
-
5/22/2018 DCS Mannual
93/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.92
HardwareDisplays a points volts or amperageFVCard Value
AlarmFirst Character in Characteristic Field (Plant Area)AYDestination
AlarmDigital Point that when Set will Remove AlarmCheck from Current Point Loaded in Point InfoCXAlarm Cutout
AlarmAlarm Status Checking for Digital Point (state pointwill alarm)ARStatus Checking
ModeDisplays the analog valueSNSensor Calibration
Value/StatusInformation About the Point3WThird Status Word
Value/StatusInformation About the Point2WSecond Status Word
Value/StatusInformation About the Point1WFirst Status Word
PointDrop in which the Point is LocatedDOOriginating Drop
PointPlant Specific Information Regarding Point LocationKRCharacteristics
PointType of Point (Analog, Digital, Packed, Module,etc.)RTRecord Type
AllCurrent Value of an Analog PointAVAnalog Value
AllUnits of Measurement For the PointEUEngineering Units
All30 Character Description of the PointEDPoint Description
All16 Character Name of Process PointPNPoint Name
The following table shows common record fields of interest to operator (2)
Point Info TabDescriptionAbbreviationRecord Field
-
5/22/2018 DCS Mannual
94/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.93
DisplayDescription of a Digital Point = 0RSReset State Description
DisplayDescription of a Digital Point = 1STSet State Description
LimitsHigh Incremental Alarm ValueZIHigh Inc Alarm Limit
LimitsLow Incremental Alarm ValueZMLow Inc Alarm Limit
LimitsFirst High Alarm LimitHLHigh Alarm Limit #1
LimitsFirst Low Alarm LimitLLLow Alarm Limit #1
LimitsDeadband for High AlarmsDBHigh Alarm Deadband
LimitsDeadband for Low AlarmsDJLow Alarm Deadband
InstrumentationHighest Volts/Amps Allowed on CardHSSensor High Limit
InstrumentationLowest Volts/Amps Allowed on CardLSSensor Low Limit
InstrumentationHighest Value the Point Should Reach (Default Highon Trend)TVMax Scale Value
InstrumentationLowest Value the Point Should Reach (Default Lowon Trend)BVMinimum Scale Value
Point Info TabDescriptionAbbreviationRecord Field
For more information on each record field and record type, refer to the Ovation RecordTypes Manual (REF_1140).
Quality
Quality of a process point is generated by the controller based on the operational readiness
of a process point The one letter abbreviation of the current quality of the point is shown
-
5/22/2018 DCS Mannual
95/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.94
of a process point. The one letter abbreviation of the current quality of the point is shown
following the English description. It is also shown in the Quality row on the Value/Status
tab. The following table describes each of the five possible qualities.
N/ABit 15 = 1
The point is not being updated, the drop that broadcasts the point is probably offthe network
Timed Out
1 1Off Scan, Out of Sensor Limits, out of Reasonability Limits, Power Bad on a Digitalpoint, Bad Card, Algorithm Propagation, or Test Mode on
Bad
1 0Out of Engineering Limits, Over-range on AI module, some special algorithm,Algorithm Propagation, or Test Mode on
Poor
0 1Forced or Entered Value, Algorithm Propagation, or Test Mode onFair
0 0On Scan, within Sensor Limits, within Engineering and Reasonability Limits, PowerOk or Test Mode on
Good
1W9 8
DescriptionQuality
Ovation Point Review
Point Review allows the Ovation user to see the current status and checking
-
5/22/2018 DCS Mannual
96/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.95
Point Review allows the Ovation user to see the current status and checking
configuration for points. The user can specify the parameters they want to search and
then have the Point Review tool help them find points meeting the specified criteria. Once
the search is complete, the user has the option of modifying attributes on any or all points.
You can base a review on point characteristics that define plant areas, or other user-
defined sorting criteria such as equipment or subsystems.
In addition to characteristics and point groups, a review can also be based on status
conditions, such as points in alarm, points for which scan has been disabled, or points in
sensor alarms.Point Review is a very important operator tool. It is suggested at a shift turnover
because is can quickly identify unexpected plant status. Results of a point review can be
changed from Review Modify Point Attributes window.
2
1 Point Review Window
-
5/22/2018 DCS Mannual
97/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.96
Point Review Filters Window
Common filter search items, as shown below, are Alarm Check Removed, Limit Check Removed,Scan Removed Test Mode and Entered Values
-
5/22/2018 DCS Mannual
98/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.97
Scan Removed, Test Mode, and Entered Values.
3
4
Point Review Modify Attributes Window
58
-
5/22/2018 DCS Mannual
99/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.98
7
8
9
Using Point Review (see screen captures from previous pages)
1. Open Point Review.
-
5/22/2018 DCS Mannual
100/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.99
p
2. Select the Filter button on the toolbar.
3. Check the items you want to search for (see example on p. 15)
4. Click OK.5. Click the GO button on the toolbar. After the search is complete, points meeting any of the
search criteria will be on the screen.
6. NOTE: Proceed only if you are sure of your actions.
7. Select any points you wish to modify attributes.
8. Click the MODIFY POINT ATTRIBUTES button on the toolbar.
9. Select attributes you want to modify on ALL selected points. Click OK
10. The Point Review window will update status as point attributes are changed
Point Viewer
The Point Viewer allows you to view all points in the system database. Points can bedisplayed by network unit or drop Operators can filter points for specific characteristics
-
5/22/2018 DCS Mannual
101/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.100
displayed by network, unit or drop. Operators can filter points for specific characteristics,
such as record type, characteristics, and point frequency. By selecting specific filters, a
review contains points with only the desired attributes.
The following diagram shows a point view of all the points in DROP3.
The main purpose of this application is to print out lists of point within the database.
Ovation Alarm SystemThe Ovation Alarm System is the application for detecting and displaying abnormal plant
conditions such as:
-
5/22/2018 DCS Mannual
102/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.101
conditions such as:
Points out of range
Drop time outs
Digital state changes
Points getting better
Points getting worse
Module errors
Alarms are sent to:
Workstation alarm window
Historian (if configured to)
Alarm printerThe alarms history buffer will retain last 15000 alarms. Older alarms are stored on the
historian such as an OPH.
Alarm Status
The alarm status of the point is displayed in the Alarm Type column.Analog Points:
-
5/22/2018 DCS Mannual
103/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.102
Analog Points:
Analog points have up to 5 high and 5 low alarm limits
HIGH1 HIGH4 and a HUD (High User Defined)
LOW1 LOW4 and a LUD (Low User Defined)
Incremental Alarms (HI WRS, HI BET, LOW WRS, LOW BET)
Digital Points:
Digital points can be configured to alarm 5 different ways
Alarm on 1
Alarm on 0
Alarm on 1 0 transition
Alarm on 0 1 transition
State change (1 0 or 0 1)
State change type alarms are listed in the History view only.
Any point that has returned from its alarm state to normal will be listed as RETURN. This
indicates that the point is no longer in alarm.
Other Common Types of Alarms:
SENSOR - Data exceeded the sensor limits of device.
HI WRS - Highest defined alarm (i.e. HIGH4) has been reached and the points value is
-
5/22/2018 DCS Mannual
104/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.103
getting further from normal.
HI BET - Highest defined alarm (i.e. HIGH4) has been reached but the points value is
getting closer from normal.
TIMEOUT - Point has timed out, meaning it is expected but not received.
Alarm Priority
All alarms have a priority assigned to it. There are eight total priorities available in theOvation system. The priority value is displayed in the AP column.
1 - Highest, most crucial alarm8 - Lowest, least crucial alarm
Priorities Are Color Coded (Default)
1. Red
2. Magenta3 Yellow
-
5/22/2018 DCS Mannual
105/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.104
Points will change to the alarm status RETURN if the point has returned from an alarmstate. By default, all returns are green.User defined alarms can have a priority associated with them. However, once any other
limit has been reached, the higher priority will supersede.
3. Yellow4. White5. Purple6. Tan
7. Brown8. Slate Blue
Alarming Dead Band
If security allows, the operator has the ability to alter the alarm dead band. Dead bandsare set up to limit nuisance alarms. By creating a dead band a point will stay in alarm untilthe value has returned to normal past the dead band value. The altering of dead bands
and alarm limits is performed in the Point Information Ovation application.
Typical Alarm Configuration
The number of alarm limits is determined when the point is built. Alarm limits can be added
or removed; however, this function would be done at an Engineering Workstation.
-
5/22/2018 DCS Mannual
106/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.105
Operators, security allowing, can alter dead bands, change the alarm limit, and take points
off alarm check. These functions are all performed in the Point Information Ovation
application.
The following table is a typical setup for an analog point. In this example, four HIGH and
four LOW are defined along with an incremental alarm.
Acknowledging and Resetting Alarms
An Alarm or a Return can be acknowledged, if the operator has permission.
-
5/22/2018 DCS Mannual
107/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.106
An Alarm Return can be reset if:
The Return has been acknowledged AND
The alarm point has remained normal AND
The operator has permission to do so.
Alarms can be acknowledged and reset individually, by groups of points, or by page.
Drop alarms can be acknowledged and MUST be cleared through the System Status display.
the Base Alarm Window
-
5/22/2018 DCS Mannual
108/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.107
Trend Display SystemThe Trend application enables you to display data samples collected for live points on the
Ovation Network in graphical or tabular trends. Six hundred data samples display for every
-
5/22/2018 DCS Mannual
109/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.108
collection interval. Trend data such as point names, scale limits, and collection intervals
must be specified. Notes about Trends:
Analog and Digital points can be trended
Permanent Trends are available through Trend Groups or locally saved trends
Trend Groups - Predefined trends built in Developer Studio
Saved Trends - Saved on local machine or on network drive by operator
Right Click will bring up the point menu
600 Samples per point displayed on each trend
8 points per Trend Group
Unlimited points per user defined trend
Multiple trend windows can be open simultaneously
Points can be dragged and dropped into trend from Graphics, Point Review, andAlarms
Right click on a trend brings up cursor
Historical trends will access data from historian for specified time period
Trend Chart View
-
5/22/2018 DCS Mannual
110/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.109
Trend Tabular View && Trend Both View
-
5/22/2018 DCS Mannual
111/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.110
TREND MENUS
-
5/22/2018 DCS Mannual
112/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.111
TREND TOOLBAR
-
5/22/2018 DCS Mannual
113/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.112
New
Points
Properties
Groups
Stop
Help
Chart Zoom
Chart Reset View
Tabular
Chart
Both
Print
Creating Trends
-
5/22/2018 DCS Mannual
114/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.113
Configuring Trends
-
5/22/2018 DCS Mannual
115/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.114
Ovation Error Log
The OvationError.log file contains error, warning, and informational messages generated bythe various Ovation services and applications. The Ovation Error Log Viewer reads theOvationError.log file and displays the information in a list-oriented display. This is a
-
5/22/2018 DCS Mannual
116/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.
115
technicians screen more than an operators. In general, it is of little interest to the operator.
1: Monitor Existing Control Schemes
Module 5: Building & Maintaining Ovation Control
-
5/22/2018 DCS Mannual
117/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.
116
2: Tune and Calibrate Existing Control
3: Modify Existing Control Sheets using Developer Studio
4: Use Miscellaneous Developer Studio Functions
Control Diagrams
The two types of control flow are analog and digital.
-
5/22/2018 DCS Mannual
118/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.
117
Analog Control - Inputs top outputs bottomLogic (digital) - Inputs left outputs right
Accessing Real Time Functional Diagrams
Using the Point Menu:1.In a process or monitor graphic, place the mouse pointer over a points value.2.Right click to access the point menu:
-
5/22/2018 DCS Mannual
119/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.
118
3. Select Signal Diagram from the point menu.
Using the Application Menu:
1.From the applications menu:2.Left click on the Signal Diagramtab to access the CBViewer program:
3. The CBViewer will launch and open without a control sheet. Select the in the Sheet
Browser section and expand, select and expand, select Drop and expand, select Task and expand,which will show all the configured control sheets. Select the control sheet you desire. CBViewer will open and
display the sheet in real time.
-
5/22/2018 DCS Mannual
120/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.
119
Understanding colors for Algorithms
Analog algorithms Green - algorithm is tracking.
Orange Red algorithm is in manual mode
-
5/22/2018 DCS Mannual
121/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.
120120
Orange Red - algorithm is in manual mode.
Cyan (blue green) - algorithm is in local mode.
Purple - algorithm has reached its low limit. Magenta - algorithm has reached its high limit.
Gold - algorithm is off scan.
Digital algorithms
Red - output is high
White - output is low
Cyan - output is calculated by the application, notfeedback from the Controller.
Analog Signals
Hot Pink - Point is in alarm. Yellow - Point is off scan.
Light Red (tomato) - Analog value has changed by a value greater than 1
Understanding colors for Signals
-
5/22/2018 DCS Mannual
122/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.
121121
Light Red (tomato) - Analog value has changed by a value greater than 1since the last time the value changed.
Light Green (spring green) - Analog value has changes by a value less than -
1 since the last time the value changed. White - no change in the analog value.
Digital Signals
Yellow - Point is off scan - False
Orange - Point is off scan - True
Orange Red - Point is in Alarm - False
Orange - Point is in Alarm - True
White - No change - False
Red - No change True
Packed Signals Magenta - Point is in alarm
Blue - Point is stable
Orange - Point is off scan
Green - Point has changed
Tuning and Calibrating Existing Control
ACCESS the properties summary window for algorithms
EXPLAIN the restrictions that may be imposed by System Security settings
-
5/22/2018 DCS Mannual
123/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.
122122
N e es c o s y be posed by Sys e Secu y se gs
on the ability to tune a control diagram
EXPLAIN where the physical control process is executed and the impact on
plant operations due to various component failures
MODIFY tuning parameters in an operating control sheet
DESCRIBE the purpose of each tuning parameter in the following
algorithms:
- SETPOINT - HIGHMON
- PID - ONDELAY
- MASTATION
EXPLAIN how tuning changes are saved by the system.
Exercise: Tune PID parameters
1. Access PID LogicSignal Diagram Sheet Browser select PID control sheet- double click
-
5/22/2018 DCS Mannual
124/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.123123
2. Select PID algorithm Properties Summary tune parameters (INTG, PGAIN, DGAIN, DRAT)then click Commitbutton
1
-
5/22/2018 DCS Mannual
125/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.124124
2
3
3. Reconcile tuned parameters into the Ovation DatabaseLaunch on Developer Studio-select desired controller
right click select Reconcile select tuned algorithms- ok
4. Launch on Developer Studio, open the control sheetdisplay Update Tuning parameters window automatically
Select the tuned parameters to Reconcile, to ensure the consistency between CB file and Oracle database ;
-
5/22/2018 DCS Mannual
126/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.125125
Opening an Existing Control Sheet1. Open the Ovation Developer Studio.
2. Drill down into the Systems folder in the Hardware Root.3. Drill down into the Network folder.4. Drill down into the desired Unit folder.5. Drill down into the desired Controller Drop folder.
-
5/22/2018 DCS Mannual
127/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.126
5. Drill down into the desired Controller Drop folder.6. Drill down into the Control Tasks folder.7. Drill down into the desired Control Task.
8. Double click the desired sheet from the workpad (bottom) pane.
9. Control Builder will launch. Wait
10. The control sheet is loaded.
Ovation Control Builder Menus
The File Tab: The Edit Tab:
-
5/22/2018 DCS Mannual
128/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.127
Ovation Control Builder Menus
The View Tab: The Draw Tab:
-
5/22/2018 DCS Mannual
129/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.128
The Tools Tab:
Add control algorithm
Add l iBuild control signal
Move selected items
deleteSave file
Zoom window view Draw algorithm value
Ovation Control Builder Toolbars
-
5/22/2018 DCS Mannual
130/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.129129
Add control pinBuild control signaldelete
Open file
Standard Algorithms
I/O Algorithms
Creating a New PID Analog Control Sheet
1. Open the Ovation Developer Studio.
2. Drill down into the Systems folder in
the Hardware Root.
ill d i h k f ld
-
5/22/2018 DCS Mannual
131/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.130130
3. Drill down into the Network folder.
4. Drill down into the Unit folder.
5. Drill down into the desired Controller
Drop folder.
6. Drill down into the Control Tasks folder.
7. Right Click on the desired Control Task.
8. Choose Insert New.
9. The New Control Sheets window will appear:10. Supply an appropriate Sheet Name (maximum 38 characters), Sheet Number
(maximum 3 characters).
-
5/22/2018 DCS Mannual
132/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.131131
11. Control Builder will launch. WAITa Control Builder canvas will initialize
with a blank screen.
12. Build an analog control scheme that uses the some basic elements of analog
control: PID, SETPOINT, MASTATION and MAMODE algorithms.
Add analog input, PID, SETPOINT, MASTATION and FIELD algorithms.
Connect the algorithms with signal lines.
Edit the algorithms to use the PA10X(where X is your assigned number) foran input and a M10X(where X is your assigned number) for an output.
13. Using Control Builder, select the Floppy Disk
icon after making changes to a controlsheet. This will:
A. Saves the control sheet drawing (.svg) file
-
5/22/2018 DCS Mannual
133/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.132132
B. Saves all control related database changes
into Oracle
C. Saves the control sheet drawing for MMI
Control Builder Directories & FilesDatabase/Software ServerMaster Diagrams(.svg):
Control Builder is configured for the Signal DiagramFolder to be at the System level:Drive :\Ovdata$\\on-line\
Control Sheet(.svg):Drive :\OvptSvr\\\\ControlFunctionsOn-Line Graphics Files (.svg) CBViewerDrive :\Ovation\CrtlBldr\On-Line
14. Using the Developer Studio, perform a Drop Load to the controller by right-
clicking on the desired controller drop folder then selecting Load.
For redundant controllers, load the drop which is currently in Control Mode first
(use the System Status diagram to determine), then load the drop currently in Backup
-
5/22/2018 DCS Mannual
134/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.133133
( y g ), p y p
Mode. This step will load all of the pending Oracle database changes into the controller.
15. Using Developer Studio, Download the graphic files to Ovation Stations by right-
clicking on the folder for the desired Unit then selecting Download and picking the
Workstation-type drops only.
Alternately, right-click on the folder for an individual Workstation then select
Download. This will place copies of the updated .svg files in the appropriate path foraccess via the Control Signal Diagram windows (C:\Ovation\MMI\CrtlBldr\On-Line)
16. Test your circuit. Does if perform as you expect? Is it Direct or Indirect control?
Tune the PID for an error dead band that ensures the process will stabilize.
Modifying Existing Control Schemes Using Developer Studio
1. Update Database and Control files to reflect online tuning changes made to
controllers (Reconcile, Audit Sheet)
2 Open an existing control sheet in the Developer Studio
-
5/22/2018 DCS Mannual
135/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.134
2. Open an existing control sheet in the Developer Studio
3. Use the pan and zoom functions to view specific areas of a sheet
4. Modify existing control sheets using the Control Builder
-ADD or DELETE sheet inputs and outputs
-ADD, MODIFY or DELETE algorithms
-ADD or DELETE algorithm parameters, point and signal tags
-MOVE individual algorithms-ADD or DELETE and MOVE pins
-ADD, MODIFY, MOVE or DELETE notes on a sheet
-MODIFY the Title Block data
5. Save and Implement changes made to control sheets
6. Update the real time functional diagrams displayed in the Process Diagram
windows to properly reflect the changes made to control
Exercise: Page Connectors Objective:
Build an analog control scheme thatincludes page connectors and a tieback simulation.
-
5/22/2018 DCS Mannual
136/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.135135
Steps:1. Open the PID analog control sheet in
your controller.
2. Use an analog output connector instead
of the FIELD algorithm, and dummypoint names for the analog inputconnector and the output connector.
3. Save, Load and Download.
4. Create another new control sheet in your controller.
5. Create an analog control scheme that includes ananalog input, LEADLAG, GAINBIAS and analogoutput algorithms. Use the dummy point name usedin the output of the MASTATION in the previous
-
5/22/2018 DCS Mannual
137/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.136136
in the output of the MASTATION in the previoussheet as the output of the analog input for this sheet,
and the output of the analog output on the previoussheet as the output of the GAINBIAS on this sheet.This will create the tie back:
6. Save.
7. Reopen the previous control sheet and Save.
8. Load to the controller and Download to MMI.9. Test the page connectors do they work as expected?
Using Miscellaneous Developer Studio Functions
EXPORT and IMPORT full and partial control sheets using theLibrary functions
BUILD and USE a control macro
-
5/22/2018 DCS Mannual
138/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.137137
BUILD and USE a control macro
RECOGNIZE the impact of algorithm and control sheet execution
order
MODIFY the execution order of algorithms within a control sheet
and of multiple control sheets within a control task area
DESCRIBE and DEMONSTRATE the control options
Export control logic to a library
1. Open a control sheet and use the cursor to select the portion of the drawing that you want to export to a library;
2. File Menu
-
5/22/2018 DCS Mannual
139/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.138138
3. Define the path
and enter a name for the file
4. Select the Savebutton
5. Left-click to select an insert point.
Import a library into a control sheet
1. Open a control sheet, File Menu :
-
5/22/2018 DCS Mannual
140/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.139139
2. Find the desired library file and press the Openbutton;
Note: if there are point names that may be duplicated, a dialog box appears, select Yes;
3. A Point Edit dialog box appears, make the necessary changes
to the points and select OK to commit the changes.
-
5/22/2018 DCS Mannual
141/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.140140
4. Use the cursor to position the control elements;
Create a new Control Macro1. Open a Macro work sheet in Control Builder.
From the main Control Builder window, pull down the File menu and select New. Pull right andchoose Control Macro from the menu that displays.
-
5/22/2018 DCS Mannual
142/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.141141
2. Build a simple circuit that has two digital inputs, a FLIPFLOP, an ONDELAY, a NOT gate
and a digital output algorithm.
-
5/22/2018 DCS Mannual
143/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.142142
Note1. The following algorithms are not recommended for use in macros: KEYBOARD
MASTAION, XMA2, 2XSELECT, MEDIANSEL,SETPOINT, Other Macros;
2. You must create a ControlMacros folder under your System folder to store all your macros.
This step is only performed once, but you must complete it before you create any macros. Under
the System folder, create a folder called ControlMacros.
Location: c:\OvPtSvr\\ControlMacros
It must be defined as one word, with no spaces, and a capital "M" -- ControlMacros.
DO NOT create the ControlMacros directory under a Drop folder. It must be under theSystem folder.
3. Do not define points in Macros;
3. Define Input/Output Pin
(1) Click on the input/output connector
Solution one
-
5/22/2018 DCS Mannual
144/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.143143
(2) At the Input Mnemonic field,enter a name for the input.At the Function Description field,enter a description for the input.
Empty! Do not define point name in macros.
Solution twouse the Control Builder Macro Interface Editor window
Make the desired change. When finish, select OK to
Commit the changes;
-
5/22/2018 DCS Mannual
145/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.144144
Commit the changes;
4. Add Macro Parameter function
-
5/22/2018 DCS Mannual
146/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.145145
(1) Right-click on the desiredalgorithm (for example:flipflop algorithm) and selectAdd Macro Parameter .
(2) Go to the Property Editor and define: Source -- original name of the parameter as defined forthe algorithm.
Interface Parameter Name -- new name given to theparameter as displayed when the macro is used. Theinterface parameter name should be four to six characters in length. Description -- new description for the parameter. Descriptions should be less than 31characters in length.
5. Save the macro to the ControlMacros directory. When you save the macro, it is automatically
audited. Any errors result in the macro not being saved.
-
5/22/2018 DCS Mannual
147/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.146146
C:\OvPtSver\\ControlMacro\TEST2.svg
6. create a symbol for the macro
(1) Open Control Builder File Menu New Algorithm Symbol CONTROL MACROS TEST2(macro name)
-
5/22/2018 DCS Mannual
148/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.147147
(2) Use Draw toolba r(rectangle) to create the symbol
(3) Select Algorithm-function layer, define the symbol name on the symbol;
Modify symbol color
-
5/22/2018 DCS Mannual
149/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.148148
(4) Add desired control pin;
7. Save the Symbol;
-
5/22/2018 DCS Mannual
150/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.149149
The new symbol is saved to a Symbols folderthat the Control Builder automatically createdunder the System folder;
To add a macro to a control sheet:
1. Add Algorithm toolbar icon,Expand the Control Macros folder and
select the symbol you created for your macro.Place the macro on the sheet at the
desired location.
-
5/22/2018 DCS Mannual
151/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.150150
2. Build any additional control logic into your sheet.3. Save the control function.4. Loading sheets in a Controller and Downloading MMIs.5. Access a signal diagram to test the function of macro.
To modify a macro:
1. Open Control Build - File menu - OPEN:
-
5/22/2018 DCS Mannual
152/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.151151
2. Find the macro (.svg file) in the Control Macro directory, and open it in theControl Builder.3. Edit the macro as desired. You can use the Property Editor to edit parameter values or thedrawing canvas to edit graphic entities.
4. Save the macro.
CAUTION!Any modificationmade to a macro may haveadverse effects on the sheets
-
5/22/2018 DCS Mannual
153/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.152152
containing the macro.Reload those sheets into theController and test your controlbefore you add them to yourOvation system.
To display macros in signal diagrams:
1. Access a signal diagram and display a sheet that contains a macro.
-
5/22/2018 DCS Mannual
154/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.153153
Macro parameters
Macro
2. Right-click on the macro. Select Explode Macro from the pop-up menu.
-
5/22/2018 DCS Mannual
155/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.154154
3. Another window appears that displays all the internal components of the macro. In this wayyou can observe the macro's performance in the online environment. The signal diagram allowsyou to toggle back and forth between a sheet and the macro.
Modify the execution order of algorithms within a control sheet
4 Use the up or down arrow icons on the Object Browser to move;
-
5/22/2018 DCS Mannual
156/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.155155
1 Select algorithm folder
2 Select ordering type: manual
3 Select the algorithm which
you want to change the order
1 Open Control Builder window;
2 Tool Menu Order Sheets3. Open icon, select the directory where the sheets
Reside and press the OK button;
Order control sheets within a control task area
-
5/22/2018 DCS Mannual
157/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.156156
4. Select Drop and Control Task window appears;
5. Select a control task area and select the OK button;
6 Select the sheet(s);
7 Move the selected sheet(s);
8 When finish ordering sheets, select the OK button to save the new sheet order;
Exercise: Execution Order
Objective:Build a control scheme and alter the sheets execution order to demonstrate its effect.
1. Build the following control scheme using the default execution order:2. Save, Load, Download and test the logic.
-
5/22/2018 DCS Mannual
158/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.157157
3. Reopen the control sheet and alter its execution order to match the order show below:
4. Save, Load, Download and test the logic. Does it perform as expected, and if not why not?
-
5/22/2018 DCS Mannual
159/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.158158
Backup CB files
1. Use the export operation to backup control function files : *.svg
1From the main control builder window, pull down Tools Menu> operations>Export operationor launch on Developer Studioselect any controller, any control task area, right click to selectcontrol options export operation
2Export operation window appearsselect control function files which you want to export
3Select Next button, Configure operation window appears, Enter the destination which you want to save, append
-
5/22/2018 DCS Mannual
160/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.159159
, g p pp , y , pp
Extra information to the exported file and select the type of file: SVG
4Select the Next button, Confirmation window appears, after Verifying the information, press Next to export
5Completed window appearsshowing the status of the export
2. Backup CB Macro files
copy ControlMacros folder from the path: OvPtSvr\\ControlMacros
3. Backup CB symbol files
copy symbols folder from the path: OvPtSvr\\symbolsor OvPtSvr\\\symbols
-
5/22/2018 DCS Mannual
161/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.160160
-
5/22/2018 DCS Mannual
162/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.161161
Restore CB files
1. Restore CB macro files
1copy CB macro files back to the existing Ovation system
The path is: OvPtSvr\\ControlMacros
2compile these restored CB macro files
Go to OvPtSvr\\ControlMacros folderopen anyone macro file, CB window appears,
-
5/22/2018 DCS Mannual
163/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.162162
select Tools menu >operations>Compile
select these restored CB macro files to compile
2. Restore CB symbol files
copy CB symbol files back to the existing Ovation system;
The path is: OvPtSvr\\symbols
or OvPtSvr\\\symbols
3. Use import operation to restore Control function files: *.svg
1From the main control builder window, pull down Tools Menu -> operations -> import operationor launch on Developer Studioselect any controller, any control task area, right click to select
control options import operation
2The Import Operation window appears, at the Data Directory section, use Browse to select the folder which
you backup;
Restore CB files (Cont.)
-
5/22/2018 DCS Mannual
164/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.163163
you backup;
3From the directory structure displayed on the window, select the CB files which you want to import;
4Select the Next button, the Configure operation window appearsUse the Browse button to enter the
Destination of the import, The path is: OvPtSvr\\\\ControlFunctions
5Enter a drop number, these sheets are imported to this drop ID;
Enter a task number, these sheets are imported to this task ID;
Enter a Base sheet number here if you want to change the actual sheet number;
6If desired, enter the full path name of the point map file to use;
7If desired, select the create undefined point to create all undefined user points that are found on the
compiled sheet;
8Select the Next button, confirmation window appears, after verifying, select Run button to import;
9check the Completed window
-
5/22/2018 DCS Mannual
165/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.164164
-
5/22/2018 DCS Mannual
166/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.165165
DESCRIBE the functions of the following basic logic (digital) and modulating(analog) algorithms used in typical control strategies:
Module 6: Typical Ovation Algorithms
- SETPOINT- KEYBOARD- AND
-
5/22/2018 DCS Mannual
167/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.166
- 2XSELECT- OFFDELAY
- FIELD- TRANSFER- ONDELAY
- MAMODE- FUNCTION- FLIPFLOP
- MASTATION- LOWMON- NOT
- PID- HIGHMON- OR
FLIPFLOP
-
5/22/2018 DCS Mannual
168/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.167
?
? --- TYPE=SET, ?=1TYPE=RESET, ?=0
S = Output remains in the same or previous state.
HIGHMON IF IN1 > HISPTHEN OUT = TRUE
ELSE
IF IN1 < (HISP - HIDB)
THEN OUT = FALSE
-
5/22/2018 DCS Mannual
169/242
Emerson Process Management Power & Water Solutions Co., Ltd. All rights reserved.168
LOWMON
HIGHLOWMON
IF IN1 < LOSPTHEN OUT = TRUE
ELSE
IF IN1 > (LOSP + LODB)
THEN OUT = FALSE
IF IN1 > HISP OR IN1 < LOSP
THEN OUT = TRUE
ELSE
IF IN1 < (HISP - HIDB) AND IN1 > (LOSP + LODB)
THEN OUT = FALSE
ONDELAY
-
5/22/2018 DCS Mannual