dd95a83ad01
TRANSCRIPT
-
8/14/2019 DD95A83Ad01
1/2
Continuous Gas Supply
Dangerous gases enter the line system with negative pressure by de-fault. At least two gas containers are needed for a continuous gas sup-ply. Once the rst gas container is empty the C 7522 vacuum changeover switch automatically switches to the second gas container. It facili-tates an uninterrupted supply.
Vacuum change over switches are used in swimming pools, water works,for water purication processes and in the most diverse applications.
Automated and informative
The C 7522 can be used for chlorine gas, hydrogen chloride, carbon di-
oxide or sulphur dioxide. The most diverse connections are available forthe line system. The C 7522 switches between two gas supplies withoutintervention from personnel and with the utmost reliability.
When too much negative pressure is attained due to the low pressurein one of the empty gas container batteries. Fitted with a visual displaymonitor for the current operating condition, the option to switch manu-ally, a manometer to report negative pressure in the line system and arelay circuit for the transfer of the units condition, all these featuresmake the C 7522 an ideal and reliable partner.
Compact and compatible
The switching time of the C 7522 comes to approx. 25 seconds. Mount-ed on a wall plate, means that the C 7522 can be installed everywhere.Both actuators permit manual intervention in the event of an emergency.
After an automatic changeover, the C 7522 later switches for a briefemptying of the residue, thus guaranteeing that the gas container iscompletely empty. Both gas container batteries can be used at the sametime if there is a high need, on a short-term basis, for the media con-veyed. In the event of an emergency, both valves can be closed.
In short
Plate mounted design Emptying of residues Peak mode Manual control Empty status signal Malfunction alert
Product Information Electrical Vacuum Change Over C 7522
Technical data
Output with chlorine gas up to 100 kg/hr
Connections DN 25/ PN 16, PVC-bondedsocket joint d32
Voltage supply 230 V AC, 50/60 Hz
Engine ball valves 2, DN 25, with manual control
Contact vacuum gauge NG 63, -1...0 bar
Control Position indicator and relayfor the empty and malfunction signal
-
8/14/2019 DD95A83Ad01
2/2
Product Information Electrical Vacuum Change Over C 7522
Model variant
Product Description Order no.
Electrical vacuum change over C 7522 2 motor ball valves DN 25/ d32i, with emergency manual control Contact vacuum gauge -10 bar Microprocessor-controlled switch control, manually activated
and all statuses displayed through LED Emptying of residue by periodic changeovers
22400011
Dimensional gure
All dimensions in mm
P I - 2 2 4 0 5 - 0
2 - V
0 2 I
C o p y r i g h t 1 0
. 2 0 0 8 b y L u t z - J
e s c o
G m b H
S u b j e c t t o t e c h n i c a l c h a n g e s
Accessories
Description Order no.
Connection set for hose 8/123 adaptor from 1 1/2a to hoseclamp connection 8/12 mm
35793
Connection set for hose 12/163 adaptor from 1 1/2a to hoseclamp connection 12/16 mm
35794
Connection set for hose 8/12 und 12/162 adaptor from 1 1/2a to hoseclamp connection 8/12 mm1 adaptor from 1 1/2a to hoseclamp connection 12/16 mm
91899
Gasket/seal set for 1 ball valve 35984
600q
7O
156~
80~
2 8 0
550q
476~
1 9 2
~
Lutz-Jesco GmbH P.O. Box 10 01 6430891 Wedemark
Phone: +49 5130 5802-0Fax: +49 5130 580268
E-mail: [email protected]: www.lutz-jesco.de
24h-Hotline:+49 5130 580280