mpcc_4_electricaldiagram

Upload: abuzer1981

Post on 02-Jun-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/11/2019 MpCC_4_Electricaldiagram

    1/1686

    This international site

    allows you to access all

    the Merlin Gerin productsin just 2 clicks via

    comprehensive range

    data-sheets, with direct

    links to:

    b complete library:technical documents,

    catalogs, certificates,

    FAQs, brochures

    b selection guides fromthe e-catalog.

    b product discovery sites

    and their Flash

    animations.

    You will also find

    illustrated overviews,

    news to which you can

    subscribe, a discussion

    forum, the list of countrycontacts

    Training allows you to

    acquire the Merlin Gerin

    expertise (installationdesign, work with power

    on, etc.) for increased

    efficiency and a

    guarantee of improved

    customer service.The training catalogue

    includes beginners

    courses in electrical

    distribution, knowledge

    of MV and LV switchgear,

    operation and

    maintenance of

    installations, design of LV

    installations to give but a

    few examples.

  • 8/11/2019 MpCC_4_Electricaldiagram

    2/1687

    Compact NSMasterpact NW

    Electrical diagrams

    Presentation 6

    Functions and characteristics 15

    Dimensions and connection 61

    Compact NS100 to 630 88

    Indication contacts 88

    Motor mechanism (automatic reset) 90

    Motor mechanism (remote reset) 92

    Motor mechanism (local reset) 94

    Early-make contacts 96

    Masterpact NW10 to NW40 DC 97

    Fixed and drawout devices 97

    Communication option 24 V DC external power supply 99

    Installation recommendations 103

    Additional characteristics 121Catalogue numbers and order form 143

    http://mpcc_1_content_presentation.pdf/http://mpcc_2_functionscharact.pdf/http://mpcc_3_dimensionsconnection.pdf/http://mpcc_5_instalrecommand.pdf/http://mpcc_6_additionalcharact.pdf/http://mpcc_7_catalnumber_spareparts.pdf/http://mpcc_7_catalnumber_spareparts.pdf/http://mpcc_6_additionalcharact.pdf/http://mpcc_5_instalrecommand.pdf/http://mpcc_3_dimensionsconnection.pdf/http://mpcc_2_functionscharact.pdf/http://mpcc_1_content_presentation.pdf/
  • 8/11/2019 MpCC_4_Electricaldiagram

    3/1688

    Electrical diagrams Compact NS100 to 630 0Indication contacts

    The diagram is shown with circuits de-energised, all devices open, connected and

    charged and relays in the normal position.

    Compact NS100 to NS250Manually operated circuit breaker

    DB104526

    (1)MN or MX (MN: D1, D4; MX: C1, C2).(2)For the withdrawable and plug-in versions, SDV and OF2 contacts can be installed in thecircuit breaker, but only one can be connected to the automatic auxiliary connectors.

    Circuit breaker with motor mechanism

    DB104597

    SymbolsQ Compact NS100 to 250SD trip indication contactSDE fault indication contactSDV earth-fault indication contactOF ON / OFF indication contactMN undervoltage releaseMX shunt releaseMT motor-mechanism moduleCAO early-break contact of rotary handleCAF early-make contact of rotary handleCE connected-position carriage switchCD disconnected-position carriage switch.

    Colour code for auxiliary wiringRD red

    GN greenBK blackVT violetYE yellowGY greyBL blueOR orangeWH white.

    (1)MN or MX (MN: D1, D4; MX: C1, C2).(2)For the withdrawable and plug-in versions, SDV and OF2 contacts can be installed in thecircuit breaker, but only one can be connected to the automatic auxiliary connectors.(3)Wires supplied, must be connected to ensure correct operation.

    Auxiliary wiring for plug-in / withdrawable circuit breaker

    Automatic auxiliary connectors(wires 0.75 to 2.5 mm2)

    Manual auxiliary connectors(wires 0.75 to 2.5 mm2)

    DB104599

    DB104600

    Fixed part (rear view).

    Fixed part (front view looking into base).

  • 8/11/2019 MpCC_4_Electricaldiagram

    4/1689

    Electrical diagrams Compact NS100 to 630 0Indication contacts

    Compact NS400 to NS630Manually operated circuit breaker

    DB104602

    (1)MN or MX (MN: D1, D4; MX: C1, C2).(2)For the withdrawable and plug-in versions, SDV and OF2 contacts can be installed in thecircuit breaker, but only one can be connected to the automatic auxiliary connectors.(3)Options available with trip unit STR53UE only.

    Circuit breaker with motor mechanism

    DB104604

    SymbolsQ Compact NS100 to 250SD trip indication contactSDE fault indication contactSDV earth-fault indication contactOF ON / OFF indication contactMN undervoltage releaseMX shunt releaseMT motor-mechanism moduleCAO early-break contact of rotary handleCAF early-make contact of rotary handleCE connected-position carriage switchCD disconnected-position carriage switch.

    Colour code for auxiliary wiring

    RD redGN greenBK blackVT violetYE yellowGY greyBL blueOR orangeWH white.

    (1)MN or MX (MN: D1, D4; MX: C1, C2).(2)For the withdrawable and plug-in versions, SDV and OF2 contacts can be installed in thecircuit breaker, but only one can be connected to the automatic auxiliary connectors.(3)Options available with trip unit STR53UE only.(4)Wires supplied, must be connected to ensure correct operation.

    Auxiliary wiring for plug-in / withdrawable circuit breaker

    Automatic auxiliary connectors(wires 0.75 to 2.5 mm2)

    Manual auxiliary connectors(wires 0.75 to 2.5 mm2)

    DB104605

    DB104606

    Fixed part (front view looking into base).

    Fixed part (rear view).

  • 8/11/2019 MpCC_4_Electricaldiagram

    5/1690

    Electrical diagrams Compact NS100 to 630 0Motor mechanism (automatic reset)

    The diagram is shown with circuits de-energised, all devices open, connected and

    charged and relays in the normal position.

    Following tripping due to an electrical fault,reset must be carried out locally andmanually.

    Automatic reset with MN

    DB104608

    (1)Wires supplied, must be connected to ensure correct operation.(2)The tripping order must lock out the closing order.

    Automatic reset with MX

    SymbolsQ Compact NS100 to 630SDE fault indication contactMT motor-mechanism moduleF1 breaker for protection of motor-mechanism module

    circuitsH1 lamp signalling an electrical faultH2 lamp signalling motor mechanism in manual positionF closing orderO opening order

    (must be > 150 ms).

    Colour code for auxiliary wiringRD redGN greenBK blackBL blueOR orangeWH white.

    DB104610

    (1)Wires supplied, must be connected to ensure correct operation.(2)The tripping order must lock out the closing order.

    orders must not

    be simultaneous

  • 8/11/2019 MpCC_4_Electricaldiagram

    6/1691

    Electrical diagrams Compact NS100 to 630 0Motor mechanism (automatic reset)

    Automatic reset without auxiliary

    DB104612

    (1)Wires supplied, must be connected to ensure correct operation.

    Control via switch or relayWith MN/MX

    Controlled by switch Controlled by relay

    DB104614

    DB104616

    Without auxiliary

    Controlled by switch Controlled by relay

    DB104617

    DB104618

  • 8/11/2019 MpCC_4_Electricaldiagram

    7/1692

    Electrical diagrams Compact NS100 to 630 0Motor mechanism (remote reset)

    The diagram is shown with circuits de-energised, all devices open, connected and

    charged and relays in the normal position.

    Following tripping due to an electrical fault,reset must be carried out locally andmanually.

    Remote reset with MN

    DB104620

    (1)Wires supplied, must be connected to ensure correct operation.(2)Connect SDE terminal 81 to auxiliary-connector terminal 84.(3)The tripping order must lock out the closing order.

    Remote reset with MX

    SymbolsQ Compact NS100 to 630SDE fault indication contactMN undervoltage releaseMX shunt releaseMT motor-mechanism moduleF1 breaker for protection of motor-mechanism module

    circuits and MN/MXH2 lamp signalling motor mechanism in manual positionR reset order

    (must be > 150 ms)F closing orderO opening order

    (must be > 150 ms,has priority over F order).

    Colour code for auxiliary wiringRD redGN greenBK blackBL blueOR orangeWH white.

    DB104622

    (1)Wires supplied, must be connected to ensure correct operation.(2)Connect SDE terminal 81 to auxiliary-connector terminal 84.(3)The tripping order must lock out the closing order.

    orders must notbe simultaneous

  • 8/11/2019 MpCC_4_Electricaldiagram

    8/1693

    Electrical diagrams Compact NS100 630 0Motor mechanism (remote reset)

    Remote reset without auxiliary

    DB104624

    (1)Wires supplied, must be connected to ensure correct

    operation.(2)Connect SDE terminal 81 to auxiliary-connector terminal 84.

    Control via switch or relayWith MN/MX

    Controlled by switch Controlled by relay

    DB104626

    DB104628

    Without auxiliary

    Controlled by switch Controlled by relay

    DB104629

    DB104630

  • 8/11/2019 MpCC_4_Electricaldiagram

    9/1694

    Electrical diagrams Compact NS100 630 0Motor mechanism (local reset)

    The diagram is shown with circuits de-energised, all devices open, connected and

    charged and relays in the normal position.

    Following tripping due to an electrical fault,reset must be carried out locally andmanually.

    Local reset with MN

    DB104632

    (1) (2)Required to ensure correct indication of an electrical fault.

    Local reset with MX

    SymbolsQ Compact NS100 to 630SDE fault indication contactMN undervoltage releaseMX hunt releaseMT motor-mechanism moduleF1 breaker for protection of motor-mechanism module

    circuits and MN/MXH1 lamp signalling an electrical faultH2 lamp signalling motor mechanism in manual positionF closing orderO opening order

    (must be > 150 ms,

    has priority over F order).

    Colour code for auxiliary wiringRD redGN greenBK blackBL blueOR orangeWH white.

    DB104634

    (1) (2)Required to ensure correct indication of an electrical fault.

    orders must notbe simultaneous

  • 8/11/2019 MpCC_4_Electricaldiagram

    10/1695

    Electrical diagrams Compact NS100 630 0Motor mechanism (local reset)

    Local reset without auxiliary

    DB1046

    36

    (1) (2)Required to ensure correct indication of an electrical fault.

    Control via switch or relayWith MN/MX

    Controlled by switch Controlled by relay

    DB104638

    DB104640

    Without auxiliary

    Controlled by switch Controlled by relay

    DB104641

    DB104642

  • 8/11/2019 MpCC_4_Electricaldiagram

    11/1696

    Electrical diagrams Compact NS100 630 0Early-make contacts

    The diagram is shown with circuits de-energised, all devices open, connected and

    charged and relays in the normal position.

    Following tripping due to an electrical fault,reset must be carried out locally andmanually.

    With MN

    DB104644

    (1)Independent auxiliary source.

    With MN + SD

    SymbolsQ Compact NSSD trip indication contactMN undervoltage releaseCAF early-make contact of rotary handle

    XI terminal block for CAF wiring(must be ordered).

    Colour code for auxiliary wiringRD redGN greenBK blackBL blueWH white.

    DB104646

    (1)Independent auxiliary source.

  • 8/11/2019 MpCC_4_Electricaldiagram

    12/1697

    Electrical diagrams Masterpact NW10 to NW40 DC 0Fixed and drawout devices

    The diagram is shown with circuits de-energised, all devices open, connected and

    charged and relays in the normal position.

    Version C Version D Remote operation

    E90098

    E90100

    DB105058

    Version E

    E90099

    Control unit Remote operation

    Terminal block marking Com: E1-E6 communication SDE2 / Res SDE1 MN / MX2 MX1 XF PF MCH

    E5 E6 184 / K2 84 D2 / C12 C2 A2 254 B2

    E3 E4 182 82 C3 A3 252 B3

    E1 E2 181 / K1 81 D1 / C11 C1 A1 251 B1

    SDE2: fault-trip indication contact

    orRes: remote reset

    SDE1: fault-trip indication contact (supplied as standard)

    MN: undervoltage release

    orMX2: shunt release

    MX1: shunt release (standard or communicating)

    XF: closing release (standard or communicating)

    PF: ready-to-close contactMCH: electric motor

    Note:When communicating MX or XF releases are used, the third wire (C3,A3) mustbe connected even if the communication module is not installed.

  • 8/11/2019 MpCC_4_Electricaldiagram

    13/16

  • 8/11/2019 MpCC_4_Electricaldiagram

    14/1699

    Electrical diagrams Masterpact NW10 to NW40 DC 0Communication option24 V DC external power supply

    Connection of the communications option

    DB104887

    The communications bus requires its own 24 V DC power source (E1, E2).

    (1) Drawout device equipped with Modbus chassis COM module.(2)Drawout device equipped with Digipact chassis COM module.

  • 8/11/2019 MpCC_4_Electricaldiagram

    15/16100

    Electrical diagrams Masterpact NW10 to NW40 DC 0Communication option24 V DC external power supply

    Examples using the COM communications option

    Communicating switchboardThis configuration provides remote display and control of Masterpacts equipped withthe Modbus or Digipact COM module. The Digipact bus can be combined with the

    Modbus bus.