proposal skripsi- syarbaini nur
TRANSCRIPT
JURUSAN TEKNIK ELEKTRO
FAKULTAS TEKNOLOGI INDUSTRI
UNIVERSITAS BUNG HATTA
PROPOSAL SKRIPSI
Nama : SYARBAINI NUR
No. BP : 0910017111058
Peminatan :
Judul Skripsi : INVESTIGASI PENYEBAB KENAIKAN SUHU PADA
TERMINASI KABEL OKONITE DENGAN PEMANFAATAN
KAMERA INFRAMERAH (THERMACAM)
Pembimbing 1 :
Pembimbing 2 :
Dilaksanakan :
Duri, 25 April 2010
Di Usulkan Oleh,
( SYARBAINI NUR )
Mengetahui :
Pembimbing I,
--------------------
Mengetahui :
Pembimbing II,
--------------------
Koordinator Skripsi,
----------------------
1. INVESTIGASI PENYEBAB KENAIKAN SUHU PADA TERMINASI KABEL
OKONITE DENGAN PEMANFAATAN KAMERA INFRAMERAH
(THERMACAM)
2. ABSTRAK
Dalam dunia industri, salah satu jenis industrial fault yang sering terjadi adalah
munculnya Hot Spot (titik panas) pada instalasi listrik yang menjadi penghubung antar
konduktor, baik itu antara kabel ke busbar, kabel ke kabel, ataupun kabel ke terminal
lainnya, dll. Gejala pemanasan yang terjadi ini bisa di sebabkan berbagai jenis
permasalahan, dan umumnya suatu peralatan memasuki tahapan mengeluarkan panas
yang berlebihan sebelum kerusakan phisik muncul. Kerusakan phisik yang terjadi ini
bisa berupa kerusakan pada isolator kabel, kerusakan sambungan, ketidakseimbangan
arus, atau bahkan bisa mengakibatkan terjadinya arc flash yang dapat menjadi pemicu
terjadinya kebakaran. Untuk membantu mengurangi terjadinya kasus seperti tersebut
penulis bermaksud untuk mempelajari penyebab yang mungkin menjadi sumber
pemicu munculnya hotspot. Dengan memanfaatkan teknologi infrared thermography
penulis mencoba menyingkap hal-hal yang memiliki potensi sebagai penyebab
munculnya hotspot yang terjadi. Dengan harapan hal ini bisa membantu kehandalan
instalasi listrik pada dunia industri, membantu menunjukkan pada dunia kelistrikan
akan hal-hal yang patut diperhitungkan dalam menjaga kehandalan suatu fasilitas
kelistrikan, sehingga instalasi listrik yang dipergunakan memiliki tingkat keamanan
dan kehandalan yang lebih baik, mengurangi terjadinya breakdown, dan cost saving
yang optimal.
Index Term : Hotspot, ThermaCam, Terminasi
3. LATAR BELAKANG
Pemakaian konduktor listrik adalah mutlak dalam dunia industri. Baik itu berupa
kabel, kawat, busbar, batangan atau bahkan pelat logam. Saat transmisi listrik,
konduktor yang di gunakan menanggung dua jenis beban, yaitu beban arus yang
melewatinya dan beban panas sebagai akibat negatif dari besarnya arus listrik yang
lewat. Banyak cara yang di tempuh dalam dunia industri untuk menekan efek negatif
arus listrik yang berupa panas ini. Baik dengan memilih material yang memiliki daya
tahan panas tinggi, ataupun dengan menggunakan mesin pendingin seperti Air
conditioner, dll. Namun hotspot tetap bisa muncul dalam operasionalnya.
Gbr 1. Salah satu kasus hotspot pada terminasi kontaktor
Seperti halnya industri lainnya, PT. Chevron Pacific Indonesia juga mengahadapi
tantangan yang sama, pada instalasi listrik yang di pergunakan. Terutama pada instalasi
listrik 3-Phasa. Karena secara umum beban untuk listrik 3-phasa lebih besar dari pada
beban listrik yang 1-phasa., sehingga konsumsi arusnya juga besar. Sebagai
kompensasinya tentu saja panas yang muncul akan lebih tinggi. Sebagai efek dari
terjadinya hotspot tersebut, sebagian dari kabel tersebut mengalami kerusakan pada
isolatornya. Kerusakan terbanyak terjadi pada isolator ujung-ujung kabel, dan berawal
dari titik-titik terminasi kabel. Bahkan ada kabel yang terbakar habis bersamaan
dengan melelehnya terminasinya, karena hotspot yang terjadi sangatlah tinggi. Untuk
meminimalisasi munculnya kasus-kasus seperti ini, maka penulis mencoba untuk
menganalisa penyebab kegagalan awal pada terminasi kabel yang menjadi faktor
penyebab kenaikan suhu pada terminsasi instalasi listrik yang di pergunakan.
4. DEFINISI MASALAH
Studi pengkajian skripsi diarahkan pada permasalahan:
1. Mengamati kondisi yang menjadi penyebab kenaikan suhu pada terminasi kabel.
2. Mengamati kondisi hotspot yang terjadi dan menganalisa penyebabnya dengan
memanfaatkan kamera inframerah.
3. Menentukan parameter-parameter penyebab kenaikan suhu pada terminasi kabel .
5. BATASAN MASALAH
Dalam pengerjaan skripsi ini permasalahan akan dibatasi pada hal:
Terminasi kabel yang dipilih adalah terminasi kabel listrik 3-phasa yang memiliki
tegangan operasional 460 V s/d 500 V.
Tidak membahas tentang pengaruh kimiawi terhadap terminasi.
6. METODA PENELITIAN
Langkah-langkah dalam penelitian yang akan dilakukan penulis meliputi:
Studi literatur
Studi Literatur yang dilakukan, disini penulis mencoba mengumpulkan data
tentang kabel yang digunakan yaitu jenis OKONITE khusus untuk Tray Aplication.
Data yang dikumpulkan akan mengarah ke arah kemampuan kabel sebagai
penghantar arus, dan kemampuan isolatornya sebagai pembatas tegangan tembus
dan suhu.
Hal lain yang akan di pelajari penulis mengarah ke kamera inframerah
(ThermaCam) yang di gunakan. Prinsip dasar ThermaCam, parameter-parameter
penting yang mempengaruhi pemakaian ThermaCam, dan batasan kemampuannya.
Pengumpulan dan Pengolahan Data:
Penulis akan mengumpulkan data kasus-kasus munculnya hotspot yang terjadi pada
instalasi listrik yang digunakan, khususnya mengarah hotspot yang muncul pada
terminasi kabel OKONITE yang digunakan. Metode Instalasi yang di terapkan
dilapangan, untuk spesifikasi unit yang sama, akan dilihat metode instalasi yang
diterapkan.
Data yang ada ini akan dikelompokkan berdasarkan beban yang dipakai, area
tempat pengambilan data, dan persamaan instalasi yang diterapkan.
Experimen Pengamatan
Pada tahapan ini penulis melakukan riset apa saja yang menjadi titik awal
munculnya hotspot yang terjadi berdasarkan data yang di ambil. Penulis juga
melakukan perbaikan terhadap kejadian hotspot yang muncul, untuk melihat
apakah kasus yang sama akan berulang lagi atau tidak. Hasil percobaan, perbaikan,
dan pengamatan ini akan menjadi masukan bagi penulis untuk mendata parameter-
parametr apa saja yang menjadi penyebab hotspot pada terminasi kabel, parameter-
parameter pendukung yang menjadi pemicu kemungkinan terjadinya tingkat
kerusakan yang lebih tinggi, dan parameter-parametr luar yang mungkin menjadi
katalis terjadinya hotspot tersebut.
Pengamatan yang dilakukan penulis ruang lingkupnya meliputi kondisi lingkungan,
jenis beban yang digunakan, teknik instalasi yang diterapkan, dan hal-hal lain yang
mungkin menjadi faktor penyebab munculnya hotspot tersebut.
Data yang sudah ada akan diolah dengan bantuan software khusus yang menjadi
alat pendukung utama dalam menganalisa kasus yang terjadi.
7. TINJAUAN PUSTAKA
Pada penelitian ini penulis telah memeriksa beberapa tulisan yang memiliki
hubungan dengan pengamatan yang penulis lakukan, antara lain:
A. Haas1* and J. Kindersberger1 (DETERMINATION OF AGEING OF
POLYMERIC INSULATING MATERIALS BY THERMAL ANALYSIS
METHODS) 1 Lehrstuhl für Hochspannungs- und Anlagentechnik, TU München,
Germany. *Email: [email protected]
Abstract:
In this paper Differential Scanning Calorimetry (DSC) and Thermogravimetrical
Analysis (TGA) are used to evaluate different kinds of ageing phenomena in
polymeric insulating materials. Specimen of different polymer insulating materials
(cross-linked Polyolefin, ETFE and silicone rubber) with a defined preconditioning
are subject to a DSC and a TGA, identifying parameters such as glass transition,
melting temperature and degree of cross-linking and crystallisation. The samples
subsequently undergo a certain treatment in form of thermal ageing or storage in
hot salty water and by voltage stress. In the following, another analysis is being
performed. Differences in the measured curves of new and aged samples give
information about modifications in the polymer due to ageing. By the applied
methods it is possible to identify physical ageing such as inclusion of water and
chemical ageing such as cracking of polymer chains.
Zdena Benešová, Martin Škopek, Bohuš Ulrych and Ivo Doležel, Member, IEEE
( Investigation of Electric Stress of Insulation of a Three-Phase Power Cable
with Respecting its Heating by Passing Currents )
Abstract –
The paper is aimed at determination of the electric stress of insulation of a three-
phase cable and check of its dielectric strength. The task is formulated as a
combined electro-thermal problem. The steady-state temperature field is calculated
from the Joule losses produced by the currents passing through the conductors and
other metal parts of the cable. Solution to the problem is carried out numerically,
by means of the FEM-based programs. The theoretical analysis is supplemented by
an illustrative example and discussion of the results.
I. INTRODUCTION
Transmission of the electric energy by power cables results in growth of their
temperature, which can negatively affect quality of their insulation and cause za
substantial decrease of its lifetime [3]. The reason consists in two antagonistic
trends: the tendency of transmitting currents as high as possible and, on the other
hand, to prevent the temperature rise of the cable from exceeding the admissible
value. Operation accompanied by such undesirable effects may occur at long-term
- load of the cable by the nominal current or voltage,
- overload of the cable by higher currents or voltages (that must not, however,
exceed certain values given as multiples of the nominal load).
Quantitative answers to different questions associated with these problems may be
obtained from suitable experiments or - much more operatively and (based on the
contemporary theoretical knowledge) substantially reliably - from the computer
modelling. This possibility is also used in the presented paper that deals with the
numerical solution of the electric stress of insulation of a three-phase cable NYFY
1 kV [1] in both above cases of the long-term load. Its resultant values are then
compared with the dielectric strength of the insulation, which is a function of the
temperature (that depends on the operation regime of the cable, particularly on the
passing currents).
The solution starts from formulation of the particular technical problem and its
mathematical model, that is given by equations describing the
- steady state temperature field distribution within the cross-section of the cable,
- time-dependent distribution of the electric field.
The model is then solved by the FEM-based professional program QuickField [2]
supplemented by special user programs.
Except for the methodology of computation the paper presents the most important
results of a typical illustrative example and discussion of its results. Discussed are
also possibilities of further possible improvements of the described algorithm
consisting in its hard-coupled formulation, that would enable to respect continuous
variations of the electric resistance of the cable in dependence on its temperature
rise.
8. RENCANA PENELITIAN
Pada Rencana penelitian ini, penulis akan meneliti secara langsung kesesuaian
dilapangan di bandingkan dengan teori berikut:
In the present study the performance of low-voltage polymer-insulated cables for
application in harsh environmental conditions is investigated. Temperatures up to
423 K (150°C) and saline water immersion may occur during application. The
range of applied AC and DC voltage is up to 1 kV. For the given environmental
conditions no knowledge of the specific ageing of the insulating materials is
available. Therefore, the ageing of the polymeric insulation due to the expected
stresses is investigated in detail in this study. The focus is set on the ageing
mechanism effecting the polymer structure and chemistry, since these are the cause
for any decrease in the electric performance. In future investigations, the detected
phenomena of polymer ageing will be compared to the electric performance of the
aged cables.
2. AGEING MECHANISM
Ageing can be classified in two groups: Physical ageing is a reversible, temporary
reduction of properties which disappears with the removal of the influencing factor
(defined as degradation [1]). On the contrary, chemical ageing causes an
irreversible, permanent reduction of properties (defined as deterioration [1]).
Regardless of the formal definition the term degradation is commonly used for all
kinds of ageing mechanism and shall thus be used in the same way in this study.
2.1. Chemical Ageing
All chemical ageing phenomena involve a chemical polymer reaction whereas.
Chemical ageing can be initiated by temperature alone, by water or other fluids, by
particle and ultraviolet radiation and some more [4]. In the following we will
concentrate on the phenomena most characteristic in the present investigation.
Thermal degradation follows the free radicals mechanism, initiated by oxygen or
oxidative contamination in the material [10] or other stresses [4]. Depending on
the polymer the thermal activation of reactions can lead to [10]:
depolymerisation of the main chain starting at the end of the chain
statistical chain break, which may result in
depolymerisation from resolving ends
radical transfer and disproportionation
stabilisation of fragments
break of side groups
inter-chain condensation and splitting of small molecules
Usually this type of degradation results in mainly the monomer and a mix of
oligomeres, cycled or linear, and a variety of by-products. The main reaction, the
free radicals mechanism, can be characterised by steps of initiation, radical
preserving reactions and radical recombinations [5].
The path taken through the numerous possibilities of reactions is highly dependent
on ambient conditions and the polymer itself. Oxidative reaction is equally a
degradation process based on free radicals, which consists of steps of initiation,
propagation and termination. The mechanism depends on peroxy radicals [5]. Like
simple thermal degradation, oxidative reactions may lead to breaking of the main
chain as well as crosslinking between chains. This generally results in the
monomer itself, additionally various oxidative compounds can be formed this way
Some additive materials are capable of catalyzing an oxidative reaction of
polymers, such being copper and copper oxide [9].
Hydrolysis is, unlike thermal or oxidative degradation, an ion reaction, leading to
random scissions of macromolecules. It may not occur in all kinds of polymers.
Most vulnerable to hydrolysis attacks are ester linkages [4], which appear
especially in Polyester and epoxy resin, but also in some silicone rubber
compounds. The dependence of this reaction on the presence of vulnerable linkages
in the polymer gives the varying sensitivity of polymers to this reaction.
Hydrolysis in theory is a reversible reaction [6]. In practice the reverse reaction
requires diffusion of large macromolecules which may slow the back esterification
to an insignificant level [7].
2.2. Physical Ageing
In contrary to chemical ageing the physical ageing process does not modify the
chemical structure of the polymer. However, due to physical ageing mechanism
significant changes in material properties can be observed.
The processes which carry physical ageing can be [2]:
- alteration in molecular order and crystallisation pattern
- diffusion of gases and fluids (including water) into the polymer
- evaporation of additives such as plasticisers or flame prohibiter.
Most of these phenomena are regarded to be reversible, excluding of course the
evaporation of additives. Thus an electrical insulation, which has been immersed in
water, may regain its original properties after complete drying as long as no
hydrolytic deterioration has occurred. The crystallisation pattern of a semi
crystalline polymer in its new condition is – either by purpose or by chance –
dominated by manufacturing temperatures or thermal treatment during the
production process.
Every thermal storage alters the thermal history of the polymer and thus its
crystallisation pattern. This physical ageing effect may influence the chemical
ageing as well, since active gas particle diffusion is sensitive to the crystallinity of
the polymer [8].
3. EXPERIMENTAL
3.1. Water Storage Setup
The setup for ageing by salt water storage in combination with voltage stress is
shown in Figure 1. Cable specimen with a length of (2500 ± 50) mm were prepared
by removing the insulation of both ends of the cable and closely winding three
complete turns on a mandrel with a diameter of 10 cm. The cables were immersed
by a length l of 2 m in a 3% sodium chloride (NaCl) solution with the ends
protruding approx. 250 mm from the liquid. Grounded guard electrodes made of
copper tape were fixed at a distance from the open ends to prevent surface
currents. One end of the cable was connected to a high precision 500 V DC source
and the complete test setup was stored in a heating cabinet at various
temperatures. The measurement electrode was immersed into the saline solution
and connected to a Keithley pA-meter with 10 fA resolution. The volume resistivity
of the cable insulation can thus be calculated as follows:
3.2. Thermal Storage Setup
Storage of cable specimen at high temperatures was carried out in a furnace
according to ISO 6722. The test samples had a minimum length of 350 mm each.
The test samples were fixed by the conductor to avoid any contact between the
insulation and the supports and were separated by at least 20 mm from each other
and from the inner walls of the oven.
Two groups of specimens were tested at different storage durations and
temperatures. The first group was kept for 240 hours at a temperature of 473 K
(200°C), the second group for 6 hours at 498 K (225°C).
3.3. Simultaneous Thermal Analysis
Apparatus: The apparatus used for thermal analysis is a Linseis STA, a
combination of Differential Scanning Calorimetry (DSC) and a
Thermogravimetrical Analyser (TGA). The system consists of a heating unit which
contains the specimen on a high precision balance. Additionally, the specimen is
placed upon a thermocouple, which detects the temperature of the sample in
comparison to an empty sample carrier. The heating unit can operate at a thermal
range from liquid nitrogen up to 1000 K. The sample weight is logged with 0.5 µg
accuracy, the heat flux with 0.3 µW. The specimen mass was 13 mg for all samples.
The chamber of the heating unit has continuously been flushed with Nitrogen
during the complete measuring procedures.
A two-step heating cycle is performed on all samples (Figure 2). The initial cooling
is followed by the first heating run with 10 K/min from 173 K (-100°C) up to 473 K
(200°C) for PO-X and silicone rubber and 573 K (300°C) for ETFE. A second
cooling period with -5 K/min gives the defined thermal history for the following
second heating run, which goes up to 1000 K (≈ 700°C) by a rate of 10 K/min. In
addition, to exclude influences from the first heating run on the TG results, a
separate TG analysis with another sample of the same material was performed
starting from room temperature up to 1000 K by a rate of 10 K/min.
In general, a DSC analysis consists of two heating runs. The curve of the first
heating run is dominated by the thermal and mechanical history of the tested
material and the curve of the second heating run gives information about material
characteristics. Focused on the detection of ageing effects, physical ageing can be
detected in a DSC by various differences between the measurement curves of new
and aged samples [2]:
The first heating run of the aged sample indicates a higher melting peak
temperature and higher crystallinity than the first heating run of the new sample
In the second heating runs of new and aged sample no difference can be observed
Chemical ageing in turn can be detected in a DSC as follows:
- The first heating runs of new and aged sample indicate differences in
melting peak temperature and crystallinity
- The second heating run of the aged sample indicates reduced crystallinity
and a lower peak temperature
9. SUMBER YANG DIPERLUKAN
Untuk kelancaran proses analisis maka diperlukan data – data yang lengkap dan
benar supaya tidak terjadi kesalahan yang tidak diinginkan. Untuk penelitian ini
yang diperlukan adalah data – data seperti : hasil pengambilan gambar dari kamera
inframerah, electrical circuit diagram dari instalasi listrik yang diambil, hasil
inspeksi temperature dan arus saat operasional, dan software khusus untuk
mengolah dan menganalisa gambar thermacam yang sudah di ambil tersebut.
Penulis juga membutuhkan data berapa unit yang mengalami munculnya hotspot
dalam setahun. Di sini penulis akan mencoba membandingkan dengan data pada
tahun berikutnya. Sehingga akan terlihat suatu perubahan atau tidak.
Data-data mengenai infrastruktur secara kelistrikan juga akan sangat menunjang
kegiatan penulis. Terutama sekali data kabel jenis OKONITE type Tray
Application yang di gunakan pada setiap unit yang akan di amati penulis.
10. JADWAL KEGIATAN
KEGIATAN BULAN 1 BULAN 2 BULAN 3 BULAN 4
Studi Literatur X X
Pengumpulan Data X X
Pengolahan Data X X
Analisa Data X X X
Penulisan X X X X
Penyerahan X
11. RINGKASAN
Tujuan yang ingin dicapai dalam Skripsi ini adalah:
Mendapatkan parameter apa saja yang menyebabkan kenaikan suhu pada terminasi
kabel sehingga pengaruh negatif terhadap isolator kabel bisa di kurangi
Mendapatkan metode pencegahan untuk meminimalisir terjadinya hotspot pada
terminasi kabel.
Hasil yang diperoleh dari skripsi ini diharapkan dapat memberi manfaat sebagai
berikut:
Menjadi referensi dalam operasi kabel listrik
Menjadi bahan pertimbangan teknis untuk mengurangi kerusakan isolator kabel
power 3-phase.
12. DAFTAR PUSTAKA
Wire & Cable – Electrical Manual – Chevron Corporation
Internet
Investigation of Electric Stress of Insulation of a Three-Phase Power Cable with
Respecting its Heating by Passing Currents (2000) - Zdena Benešová, Martin
Škopek, Bohuš Ulrych and Ivo Doležel, Member, IEEE
DETERMINATION OF AGEING OF POLYMERIC INSULATING
MATERIALS BY THERMAL ANALYSIS METHODS (2009) A. Haas1* and
J. Kindersberger1 1 Lehrstuhl für Hochspannungs- und Anlagentechnik, TU
München, Germany